flat thin profile centrifugal fan coil unit thin profile centrifugal

advertisement
FLAT
THIN
THIN PROFILE
PROFILE CENTRIFUGAL
CENTRIFUGAL FAN
FAN COIL
COIL UNIT
UNIT
FLAT
Thin profile centrifugal fan coil unit
FLAT series
Simple, attractive design with thin thikness.
30 basic models, differing sizes and versions.
Floor-standing,
suspended,
built-in,
ceiling-
mounted, suspended-ceiling installation, ductable.
With bottom or front air intake and top or front air
outlet.
For 2 or 4-pipe systems, with 3 or 4-row exchangers.
Cased units with airflow direction louvers.
Decorative panels in lacquered wood or painted
sheet metal.
design
157 m
m
360° INDOOR CLIMATE SOLUTIONS
Strutture
Electric fans
In galvanised, insulated sheet metal. Con-
Single-phase asynchronous motor with 6 speed
densate-drain pan in galvanised, insulated
settings (3 connected in the factory) with over-
sheet metal with fittings for condensate drai-
load cutout. Anti-vibration mountings for low-
nage. Knock-outs on side panels for easy
noise operation.
factory or site fitting of accessories. Slots on
Three-dimensional double-inlet centrifugal fans
rear of pane to facilitate wall-mounting.
with aluminium impellers. Statically and dynamically balanced.
All fans are run tested during final on-line test
and inspection procedures.
Heat exchangers
ultrasottile
Consist of Aluminium fins mechanically expanded
onto copper tubes in a continuous block.
Frame in galvanised steel, brass headers with female 3/4” gas fitting. Air vents on both headers.
Standard water connections on left-hand side;
right-hand side on request. Coil can be easily rotated if necessary.
Air filters
Metal frame containing honeycomb polypropylene filter media. Easy to remove and clean.
Standard filters are to EU1 efficiency;other efficiencies available on request.
Cabinet
Hot-galvanised sheet metal pre-coated with a
PVC film to increase resistance to corrosion.
Airflow direction louvres in ABS or nylon.
Colour of housing: white.
Colour of louvres: light grey.
Other RAL colours available on request.
www.eden-clima.com
FLAT
Decorative panels
For vertical wall recessed type and horizontal ceiling concealed type, decorative panels in white
lacquered wood or white PVC-coated galvanised
metal are available.
The panels come complete with air intake and outlet grilles and filter.
Accessories
• Electric heaters
• 2 or 3- way valves
• On-off and balancing valves
• External air intake dampers
(manual or motor-operated)
• Inlet and discharge plenums
• Auxiliary coils
• Condensate drain pans
• Telescopic extensions
• Plinths
• Decorative panels
• Condensate drain pump
• etc.
Controls
Terminal strip applied to the side of the fan coil
for connection to the wall-mounted controller.
Manual, semi-automatic and automatic controls, with display and infrared remote control on
request.
360° INDOOR
R CLIMATE SOLUTIONS
000
001
002
n°
2
2
2
Ø
1/2”
1/2”
1/2”
kg
16
19
21,5
Ø
1/2”
1/2”
1/2”
kg
17
20
23
L
mm
960
1160
1360
M
mm
742
942
1142
C
mm
712
912
1112
Fans
2 rows coil
Fittings
Net weight (2 rows)
3 rows coil
Fittings
Net weight (3 ranghi)
External dimensions
GENERAL DIMENSIONS
233
460
25
Ø 20
130
120
L
M
C
480
25
152
157
www.eden-clima.com
FLAT
000
001
002
2 pipe system (3R coil) - The values marked with min, med and max refer to the 3 standard speeds set in the factory
Total cooling capacity
W
max
1890
2270
2660
W
med
1510
2020
2190
W
min
1160
1470
1730
W
max
1460
1750
2020
Sensible cooling capacity
W
med
1140
1540
1640
W
min
866
1100
1290
Water flow
l/h
max
326
391
458
Water pressure drop
kPa
max
13,3
7,24
11,3
W
max
2410
2930
3350
W
med
1900
2570
2720
W
min
1430
1820
2120
l/h
max
4100
4940
5680
kPa
max
3220
4360
4590
W
max
2410
3080
3560
W
med
343
407
453
W
min
254
347
353
Water flow
l/h
max
182
232
265
Water pressure drop
kPa
max
51,6
51,8
54,3
m3/h
max
43,1
45,5
48,8
m3/h med
35,5
37,8
40,6
Heating capacity
Water flow
Water pressure drop
Heating capacity
Air flow
40
38
64
db(A) max
0,18
0,17
0,32
db(A) med
41
41
61
db(A) min
33
37
53
m /h
3
Sound power level
-
min
Power input
W
max
30
30
273
Absorbet current
A
max
018
025
125
Standard unit with free outlet: external static pressure = 0 Pa
Sound power level: ISO 23741
Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec.
Supported power supply: ~230V±10% / 1ph / 50-60Hz
COOLING
Inlet water temp.: 7°C
Outlet water temp.: 12°C
Inlet air temp.: 27°C d.b. - 19°C w.b.
360° INDOOR CLIMATE SOLUTIONS
HEATING
Air temp.: 20°C
Inlet water temp.: 50°C
HEATING
Air temp.: 20°C
Inlet water temp.: 70/60°C
000
001
002
2 pipe system (2R coil) - The values marked with min, med and max refer to the 3 standard speeds set in the factory
Total cooling capacity
W
max
1450
1850
2240
W
med
1200
1600
1920
W
min
959
1270
1500
W
max
1180
1460
1740
Sensible cooling capacity
W
med
956
1250
1470
W
min
751
972
1130
Water flow
l/h
max
249
319
386
Water pressure drop
kPa
max
5,45
10,3
17,1
W
max
1960
2430
2910
Heating capacity
W
med
1610
2090
2450
W
min
1250
1610
1870
Water flow
l/h
max
3380
4,15
4960
Water pressure drop
kPa
max
2770
3570
4170
W
max
2150
2750
3170
W
med
351
415
477
W
min
264
335
382
Water flow
l/h
max
192
241
272
Water pressure drop
kPa
max
54,9
53,6
55
m /h
max
48,3
47,4
49,3
m3/h med
41,8
38
37,6
40
38
64
db(A) max
0,18
0,17
0,32
db(A) med
41
41
61
db(A) min
Heating capacity
3
Air flow
m /h
3
Sound power level
-
min
33
37
53
Power input
W
max
30
30
273
Absorbet current
A
max
018
025
125
Standard unit with free outlet: external static pressure = 0 Pa
Sound power level: ISO 23741
Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec.
Supported power supply: ~230V±10% / 1ph / 50-60Hz
000
001
002
4 pipe system (1R coil data) - The values marked with min, med and max refer to the 3 standard speeds set in the factory
W
max
2470
2620
3530
W
med
1990
2350
2940
W
min
1560
1780
2370
Water flow
l/h
max
343
407
453
Water pressure drop
kPa
max
254
347
353
m /h
max
182
232
265
m /h med
51,6
51,8
54,3
m3/h
min
43,1
45,5
48,8
db(A) max
35,5
37,8
40,6
db(A) med
41
41
61
db(A) min
33
37
53
Heating capacity
3
Air flow
Sound power level
-
3
Standard unit with free outlet: external static pressure = 0 Pa
Sound power level: ISO 23741
Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec.
Supported power supply: ~230V±10% / 1ph / 50-60Hz
COOLING
Inlet water temp.: 7°C
Outlet water temp.: 12°C
Inlet air temp.: 27°C d.b. - 19°C w.b.
HEATING
Air temp.: 20°C
Inlet water temp.: 50°C
HEATING
Air temp.: 20°C
Inlet water temp.: 70/60°C
www.eden-clima.com
DP FLAT 2013-0 GB
A GROUP S.p.A. - Via Montegrappa, 67 - 31020 San Zenone degli Ezzelini (Treviso) - Italy
Tel. +39 0423 567774 - Fax +39 0423 567985 - www.aliseogroup.com - info@agroup-it.com
Download