GROUND VOLTAGE MONITOR SYSTEM Assigned PE# 0462 GVMon from Balfour Beatty Rail continuously scans a realtime analog input that indicates the ground-to-negative rail voltage of the traction system. GVMon allows negative excursions (earth ground more negative than the rail) of any magnitude, but will fire a SCR to connect the rail to earth ground if the earth ground becomes positive with respect to the rail by an amount that equals or exceeds the preset (adjustable) threshold voltage. Features • • • • • Digital meter reads rail voltage and number of operations Adjustable pick-up voltage for ground SCR Adjustable trip time to prevent tripping due to rail drop during train start Sensitive current detection provides detection and lock out on a feeder with a catenary to earth leakage of 50 ohms Built in diagnostics description The unit consists of a voltage detector, a current detector, an eight bit micro controller, output relay board, and an LCD display. The unit is housed in a metal enclosure with two (2) power supplies to convert 125VDC input control power to isolated low voltage (5V) for micro controller power and SCR gate drive. Output contacts are provided for breaker tripping and annunciation display. The display is mounted on the enclosure door and digitally displays negative to ground voltage. A pushbutton converts the display to an operations counter when pressed. Specifications The unit monitors the voltage from negative to ground and displays this voltage on a digital display. When the voltage exceeds the setting level (typically -50 volts) for a short time (typically 50mS), the micro controller triggers an SCR providing a current path from ground to negative. The condition described commonly is the result of a catenary to earth (ground) fault such that the current return path is through earth to rail. A current sensor consisting of a diode with parallel resistors is set for approximately 10 amps. GV Monitor will close the breakers back if the negative to ground voltage disappears in a set time. It will lock out specific breakers which have a constant Negative to Ground voltage. 1205 W. Dewey St., Goldsboro, NC 27530 • Tel: 919.432.1470 • Fax: 919.800.3834 • Web: www.bbiius.com • E-mail: rail@bbiius.com