HAWKEYE ETH
THE CLEAN ROOM MONITOR
RH+T+DP INDICATOR, WITH ETHERNET PORT (MODBUS/TCP)
FEATURES
› Microcontroller based
› RH, Temperature & DP measurement
› Software programmable channel ranges, units & input types
› User programmable for 1, 2 or 3 channel measurement
› 3 programmable Alarms with visual annunciation
› 3 programmable Alarms with open collector outputs to operate
external relays
› Real Time Clock with battery back-up
› Software calibration for all 3 channels
› Calibration history / schedule for validation
› MODBUS / TCP & Telnet multidrop communication for PLC, SCADA, etc.
› 20~30 VDC or 85~265 VAC SMPS supply
› Powerful, user-friendly SCADA available
› FDA 21CFR Part11 compliant SCADA version also
› Advanced digital RH+T sensor technology
HAWKEYE ETH
www.radix.co.in
HAWKEYE ETH
THE CLEAN ROOM MONITOR
RH+T+DP INDICATOR, WITH ETHERNET PORT (MODBUS/TCP)
BMS - CLEAN ROOM MONITORING SYSTEM
24 Port
Ethernet switch
LAN
HAWKEYE ETH ETH-01
HAWKEYE ETH ETH-02
192.168.1.1
192.168.1.2
HAWKEYE ETH ETH-24
HAWKEYE ETH ETH-25
HAWKEYE ETH ETH-23
192.168.1.23
8 Port
Ethernet switch
LAN
Server with 21 CFR
SCADA Systems
192.168.1.24
HAWKEYE ETH ETH-47
LAN
LAN
HAWKEYE ETH ETH-46
192.168.1.46
192.168.1.25
HAWKEYE ETH ETH-48
HAWKEYE ETH ETH-69
192.168.1.47
192.168.1.48
192.168.1.69
HAWKEYE ETH ETH-231
HAWKEYE ETH ETH-232
HAWKEYE ETH ETH-250
192.168.1.231
192.168.1.250
192.168.1.232
CLEAN ROOM AREA
HAWKEYE ETH
www.radix.co.in
HAWKEYE ETH
THE CLEAN ROOM MONITOR
RH+T+DP INDICATOR, WITH ETHERNET PORT (MODBUS/TCP)
SPECIFICATIONS
INPUTS
No. of inputs
Input RH
All specifications at ambient of 25 °C, unless specified otherwise
MOC
3 (RH, T, DP)
a) 0-1 V DC b) 0-10 V DC c) 0-20 mA
d) 4~20 mA e) Integral, radix RH+T sensor
Input T
a) 0-1 V DC b) 0-10 V DC c) 0-20 mA
d) 4~20 mA e) Integral, radix RH+T sensor
Input DP
a) 0-1 V DC b) 0-10 V DC c) 0-20 mA
d) 4~20 mA e) Integral, radix DP sensor
20 V nominal, 100 mA max
0~100% RH
-40 ~ 90.0 °C (user selectable)
-199 ~ 900Pa, -19.9 ~ 90.0mmWC
(user selectable)
Transmitter supply (VTX)
Range
%RH
Temperature
DP
Accuracy
For Integral Sensors
%RH
Temperature
DP
For Remote Input
%RH
Temperature
DP
INDICATION
2-ROWS
Process variable 1
Process variable 2
3-ROWS
% RH
Temperature
Differential Pressure
Status indication
± 2% RH
± 0.3 °C
± 1.5% of reading ± 5 Pa,
± 1.5% of reading ± 0.5 mmWC
± 1% RH
± 0.25% of span (min ±0.2 °C)
± 0.25% of span (min ±0.3 mmWC)
Window 1, 3 digit, 7 segment
0.8” (20.3 mm) red LED display
Window 2, 3 digit, 7 segment
0.8” (20.3 mm) red LED display
Window 1, 3 digit, 7 segment
0.8” (20.3 mm) red LED display
Window 2, 3 digit, 7 segment
0.8” (20.3 mm) red LED display
Window 3, 3 digit, 7 segment
0.8” (20.3 mm) red LED display
Faceplate
Body
Dimensions (in mm)
Mounting
Modular panel
Brick wall
Cutout (in mm)
COMMUNICATION
System
CPU
Communication interface
Ethernet
Ethernet Protocol
Com port format
Databit
Parity
Stop bit
Baud rate
Slave ID
Data type
Parameters
Process Variables Read only
Setpoints
Alarm Status
Hysterisis
Alarm Activation Delay
Power On Activation Delay
Input Bias
Input Skip
RTC Synchronzation
PROGRAMMABLE PARAMETERS
Setpoint
% RH
Temperature
DP
CLOCK
Real time clock
Battery backup
a) 50 mm or more b) 100 mm or more
Using accessories grouting box
and SS304 interface plate
(both to be ordered separately)
177(W) x 165(H)
32 bit MCU
10/100 Base-TX, 8-pin RJ-45X1,
(Auto-negotiating, LED indicator)
Telnet, TCP MODBUS
8
None
1
9600 bps
User programmable, 1~247
Integer x 10
Read & write from the host computer
Read only
Read & write from the host computer
Read & write from the host computer
Read & write from the host computer
Read & write from the host computer
Read & write from the host computer
Read & write from the host computer
Provided
Provided
Digital filter
Hysteresis
Alarm logic (Fig 1)
Alarm type
Alarm activation delay
Setpoint lock
0 ~ 100
-40 ~ 90.0 °C
-19.9 ~ 90.0 mmWC
-199 ~ 900 Pa
1 for RH
0.1 for T
0.1 for DP unit mmWC
1 for DP unit Pa
A (minimum) ~ F (maximum)
User selectable
a. Full scale high
b. Full scale low
Self reset
User selectable, 0~240 sec
ON, OFF
a) Integral RH+T in front sensing
b) Integral RH+T sensing at rear
c) RH+T+DP from remote 2-wire
transmitters/Sensors
d) Integral RH+T transmitter,
DP sensing : Any
OTHER
Programming
Supply voltage
Power consumption
Operating ambient temperature
Relative humidity
Through 3 tactile keys
20~30 V DC, 85~265 V AC/DC
4 watts maximum
0~50 °C
Below 90%, non condensing
LEDs for open collector and
visual alarms
Resolution
OUTPUTS
No. of open collector outputs
No. of visual alarms
SS304
MS, powder coated
200(W)x180(H)x30(D) mm
3
6
ENCLOSURE
Construction
HAWKEYE ETH
www.radix.co.in
HAWKEYE ETH
THE CLEAN ROOM MONITOR
RH+T+DP INDICATOR, WITH ETHERNET PORT (MODBUS/TCP)
ALARM LOGIC
ON
HYST
SP
SP
OFF
HYST
Fig1
FULL SCALE HIGH
FULL SCALE LOW
ORDERING INFORMATION
2558
A B C D E F G H I
Product
code
A
2558
RH+T Sensing
Position
B
1
None
1
2
Integral Sensor
2
front
3
Integral Sensor
rear
4
Remote
Transmitter
DP Sensing
Position
None
Remote
Transmitter
J
C
RH Input
D
Temperature
Input
E
DP Input
F
DP Unit
1
None
1
None
1
None
1
None
2
Integral RH+T
sensor
2
Integral RH+T
sensor
2
4~20 mA
2
mmWC
3
4~20 mA
3
4~20 mA
3
0~10 VDC
3
Pa
4
0~10 VDC
4
0~10 VDC
G
No. of
Display Rows
H
Alarms
I
Alarm
Acknowledge
Key
J
1
2-row
1
Not provided
1
Not provided
1
85~265 VAC
2
3-row
2
Provided
2
Provided
2
20~30 VDC
Supply voltage
CAT#520R0/311216/A
ENQUIRIES
Instruments: sales@radix.co.in
Sensors: sensors@radix.co.in
Gauges: gauges@radix.co.in
Automation: automation@radix.co.in
Level: level@radix.co.in
RADIX ELECTROSYSTEMS PVT LTD
B-14, 2nd Floor, Ghanshyam Indl Estate
Veera Desai Road, Andheri (West)
Mumbai - 400 053, India
+ 91 22 42537707 l sales@radix.co.in
www.radix.co.in
Download