9.87 WIRING DIAGRAM [251] 1.14 [29] 17.00 S 23.32 [432] / N [592] .41 DIA [10] 3.16 [80] 10.88 [276] .50 BREATHER AND DRAIN HOLE [13] 7.75 .50 [197] [13] 2.03 [52] 2.38 [61] DUAL DIMENSIONS: 2 1/2"-8 NPT HUB TOP AND BOTTOM INCHES MILLIMETERS FIELD INSTALLABLE SOLID NEUTRAL ASSEMBLY NEMA TYPE 7 AND 9 CATALOG NUMBER AMPERE RATING 225SNA 225A WIRE SIZE NUMBER OF CONDUCTORS PER TERMINALS TERMINAL MAX. MIN 2 1 300 KCMIL 1 1 # 4 AWG #14 AWG PKDB-1, BREATHER AND DRAIN KIT INCLUDED FOR OUTDOOR USE. #4 AWG TYPE CU HORSEPOWER RATINGS NOTES: FINISH - ALUMINUM LACQUER ON CAST ALUMINUM. NEUTRAL - INSULATED GROUNDABLE. UL LISTED - FILE E-10673 SUITABLE FOR USE AS SERVICE EQUIPMENT - (NEUTRAL NOT SUPPLIED). CATALOG NUMBER H225XKA SERIES C2 AMPERE RATING 225 VOLTAGE RATINGS 600VAC;250VDC 240VAC - 3Ø 480VAC - 3Ø 600VAC - 3 Ø STD. STD. STD. 60 125 150 AUTOMATIC MOLDED CASE SWITCH, CATALOG NUMBER KHL36000M IS FACTORY INSTALLED. USE 75°C COPPER WIRE ONLY. NOT FOR USE AS A MOTOR CONTROLLER OVER 100 HORSEPOWER. (USE MOTOR STARTER) THIS SWITCH IS SUITABLE FOR USE ON A CIRCUIT CAPABLE OF DELIVERING NOT MORE THEN 10,000 RMS SYMMETRICAL AMPERES, 600 VOLTS MAXIMUM WHEN PROTECTED BY CLASS H OR K FUSES RATED 225 AMPERES MAXIMUM. DECEMBER 2008 HEAVY DUTY SAFETY SWITCHES ENCLOSED MOLDED CASE SWITCH FOR HAZARDOUS LOCATIONS/225 AMPERE/ENCLOSURE-CLASS I, DIVISION 1 OR 2, GROUPS C AND/OR D / CLASS II, DIVISON 1 OR 2, GROUPS E, F AND/OR G / CLASS III, DIVISION 1 OR 2 DWG# 1919 NO. REF DWG #1919