Hi Delta 1100.12 - Globalimageserver.com

advertisement
Models HD101 thru 2342B
CSA certified Low Lead Content
Less Than - .25% Lead
Proudly assembled in U.S.A
Up to
85% thermal efficiency!
Raypak’s Hi Delta
Key Features
Decades of expertise and technological innovations went into
creating the Hi Delta boiler, a product that incorporates features
sought after by engineers, installers and end-users alike.
• Models from 100,000 to 2,340,000 BTUH
• All models indoor/outdoor construction
• Efficiency:
n 84% Boilers- standard
n 85% AFUE HD101-HD301
n 85% Water Heaters- standard
In 1948, Raypak introduced the first straight copper finned tube
boiler designed with reliability and serviceability in mind. The
tradition continues with Raypak’s Hi Delta model. It’s patented burner “security blanket,” an ingenious enhancement that provides a perfected air-gas pathway for complete combustion, makes the
Hi Delta the most adaptable sealed-combustion boiler on the market
today.
While many manufacturers claim simple, convenient heat exchanger
removal, servicing the Hi Delta couldn’t be more straightforward.
Just open the unit from the front and slide it out on built-in runners.
Adding to the Hi Delta’s ease of use is the On-board Diagnostic
Center. In the event of an operating problem, this key enhancement
allows an on-site technician to quickly review the unit’s entire fault
history, in easy to understand “real English”. No cryptic codes to
deal with. Our diagnostic center even offers possible solutions to the
problem at hand.
The Hi Delta product family covers the full spectrum of both indoor
and outdoor applications including space heating, process heating,
pool heating and domestic hot water heating. When installed
indoors, the Hi Delta’s versatility is revealed in smaller vent
diameters, direct-venting and the convenience of stacking without
an increased footprint.
Raypak’s focus on customer satisfaction goes beyond product
design. Like all Raypak boilers, every Hi Delta is factory-fire tested,
assuring reliable start-up upon installation.
For over 60 years, Raypak professionals have earned their reputation
as The Hot Water Management Experts. From system design through
installation and start-up, you can count on your local Raypak
Representative and the backing of the industry’s best sales staff,
applications engineers and service department.
• Patented burner “security blanket” enhances staged
combustion, minimizes installation and start-up issues,
and protects burners from metal fatigue
• 105ºF minimum inlet water temp
• Copper finned tube heat exchanger; Cupro-nickel available
• CSA low lead certified (less than .25%)
• Bronze headers standard on water heaters, optional
on boilers
• Sidewall venting ready; No extractor needed for
most applications
• Ducted combustion air ready; TruSeal® CSA-certified
direct-vent available
• Status display and on-board diagnostic center, real english, no
codes.
• Less than 20ppm NOx
Options
• G-20 – Low Gas Pressure operation (Models 302B-2342B)
CSA-certified for 4” WC supply pressure, natural gas only.
• D-14 – Rear vent option available at time of order
• D-21– TruSeal direct vent air intake system
• A-6 – Right hand water connection
Visit our website at www.raypak.com to find the Raypak representative in your area.
2
3
9
5
8
6
7
4
11
2
1
1. Lightweight Refractory Panels
Multi-piece ceramic fiber panels enhance combustion while minimizing heat retention.
2. Fully-enclosed Headers
Temperature sensors and lead wires/capillaries are
protected from weather, vandalism, and accidental
damage during installation and service.
3. Flue Connection
Top or back outlet flue connections offer greater
installation flexibility.
4. Air Filter
An easily-cleaned combustion air filter protects the
burners from airborne particles including flying
insects.
10
5. On-Board Diagnostic Center
Factory-mounted standard equipment (302-2342).
Gives relevant service feedback as well as possible
solutions to clear the fault. All in plain English, no
cryptic codes to decipher. The control stores up to
16 faults in its history file for the service technician
to review.
6. Status Display Lights
Up to 12 high-intensity LED lights, visible up-front,
indicate the operating status of the boiler.
7. Construction
The cabinet and all internal parts are made from
galvanized, aluminized or stainless steel. The exterior is protected by textured powder-coat paint,
ideally designed for indoor or outdoor installations.
8. Central Point Wiring
Factory-made wire harnesses connect all electrical
components to an easy-to-troubleshoot circuit
board with multi-pin connectors.
9. Heat Exchanger Tubes
Time-proven copper finned tubes and optional
cupro-nickel tubes stand up to even the harshest
water conditions.
10. Burners
Special stainless steel alloy pre-mix burners provide clean, robust combustion and meet all low
NOx regulations.
11. HSI Access Panel
A small panel provides access to both the hot surface igniter and the flame sensor to aid inspection
and service.
On-Board Diagnostic Center
Raypak’s Hi Delta (302B thru 2342B) comes equipped with a microprocessor-controlled diagnostic control center that displays its
information on a 2x20 character LCD display in plain English. This control monitors system safeties, ignition faults and system
status, while storing up to 16 reported faults. Raypaks diagnostic center also monitors the fault outputs of the Fenwal ignition
control. The Fenwal’s flash codes are converted into real English fault codes that anyone can understand. The control is also
equipped with a SPDT dry contact relay output that is switched anytime a safety fault occurs. This can be used for a heater alarm
or a BMS safety interface.
Example Diagnostic Fault Report
Water Flow Sw Fault
Check Boiler Pump, Purge Air, Replace Flow Switch
Diagnostic Information
Safety Faults
• Manual High Limit
• Auto High Limit
• Low Water Cut-off
• Vent Pressure
• High Gas Pressure
• Low Gas Pressure
• Controller Alarm
• Flow Switch
• Blower Switch
• Factory Option
• External Interlock
• Cold Water Run
Ignition Control Faults
• Low Air
• Flame- No CFH
• Ignition Lockout
• Low HSI Current
• Low 24VAC
• Internal Control Fault
3
Sidewall Vent
Vertical Venting
Category III
Category I (Type B)
Options
SureRack® Kit
The perfect solution for today’s most space challenged equipment rooms.
Stacking two Hi Delta 2342 boilers provides over 4.6MMBTU in just over
26 square feet plus clearances. All components (except pumps, flow
switches and PRVs) are contained inside the cabinet, so there won’t be any
standard gas valves or fans hanging off the unit. The units remain fully
serviceable even while racked.
• For models 302B thru 2342B
• No Vent Offset Required*
• Small Footprint
• Fits in Low-Ceiling Room
See Cat. 1000.16 for
complete SureRack Details
•
•
•
•
Heavy-Duty Construction
Easy Assembly
All Hardware Included
Still Allows for Complete Servicing
* Lower unit requires D-14 vent tee option.
Control Options
Raypak’s array of leading edge controllers offer features such as: sequence-control of up to 16 boilers; PID technology; optimized approach to outdoor reset; BMS interfacing; freeze protection and other energy-saving functions. Raypak’s controllers have been specially designed to maximize
the performance of its leading-edge Hi Delta boilers.
B-42 TempTracker Analog
TempTracker Mod+ Hybrid
Outdoor air reset controller for on-off or 2-stage units.
Outdoor reset is based on a user-defined reset ratio.
Includes 5 minute pump-off delay. Standard on
hydronic models 299,000 BTUH or smaller. Also available as an option for model HD401 and all WH models.
Provides functionality for multiple-boiler modulating control for precise load tracking of space heating and hot water supply systems. (See Cat.
5100.22)
TempTracker
B-60 Stage interface is designed to stage a single
boiler of up to four total stages using a proportional DC voltage of milliamp current signal from a
building management system or multi-boiler controller such as our Temp Tracker MOD+ Hybrid. It is
available factory-mounted on stage fired boilers as
well as available as a field installed kit
Designed to sequence multiple boilers up to four total
stages, whether it’s one to four on/off boilers, two twostage boilers, or one boiler with up to four stages. It is
available factory-mounted or loose. (See Cat. 5100.22)
B-60 Stage Interface Card
Flex Gas®
Dual-fuel boilers and
water heaters
• For models 302B thru 2342B
• Changeover takes less than one minute
• No mechanical components to remove
or replace
With its patented, CSA-certified rapid fuel
• Changeover can be accomplished
while firing: simply turn the key!
switchover system, the Hi Delta FlexGas is
an ideal solution for interruptible-fuel appli- • Factory-installed and tested system
cations (natural/propane gas).
• CSA-Certified
(See Cat. #1000.20)
4
Cold Water Start
Cold Water Run
Cold Water Solution Options
Cold Water Start
It is commonly known that prolonged internal condensation will dramatically shorten the life of standard boilers and water heaters. While
Raypak boilers and water heaters can operate without harmful condensation at lower inlet water temperatures than the competition,
there are still applications that require reliable protection against harmful condensation caused by frequent, extended, cold water startups. Raypak’s Cold Water Start protection system is used with closed loop heating systems and utilizes a proportional three-way valve to
bypass water from the boiler outlet to the inlet during start-up, when the system return water temperature is below the minimum acceptable level.
Cold Water Run
For the same reason stated for Cold Water Starts, it is even more important to provide protection against condensation from cold inlet
water on systems where the return water temperature to the boiler will always be below the acceptable minimum. Raypak’s Cold Water
Run system can be used on boilers, water heaters or pool heaters, and utilizes a variable-speed pump to inject just the right amount of
water from the main system loop into the boiler to maintain the optimum inlet temperature. This approach allows the full capacity of the
boiler to be utilized to meet the system load, while at the same time continuously maintaining the optimum inlet water temperature to
prevent condensation.
(See Cat. #1000.19)
Simple Serviceability
Raypak’s easy-to-understand user interface, including on-board diagnostics and LED operating status lights, tells the technician all he
needs to know. All service/repair components are readily accessible from the front for maximum installation flexibility.
1
2
1
2
3
4
5
3
Diagnostic Control Center
Fenwal ignition control
Central point wiring board
Transformer
Pump delay relay
6
7
8
9
Manual reset high limit
Main power disconnect
Standby power switch
Status lights
4
5
9
8
7
6
5
Dimensions (in.)
Type WH
85%
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002Bª
2072B
2342B
85
128
169
213
254
335
252
335
420
546
630
756
832
1058
1285
1512
1679
1739
1966
85
128
169
213
254
339
255
339
425
553
638
765
842
1071
1301
1530
1699
1760
1989
3
84%
2
100
150
199
250
299
399
300
399
500
650
750
900
990
1260
1530
1800
1999
2070
2340
85% AFUE
Type H
1
BOILER
MBTUH Output*
Ref.
Hi Delta MBTUH
Dwg.
Model Input*
pg. 5
A
Width
B
18-9/16
9-1/4
21-7/8
10-7/8
25-1/16 12-1/2
28-5/16 14-1/8
31-9/16 15-3/4
38-1/16
19
36
18
43
21-1/2
50
25
60-1/2
30-1/4
67-1/2
33-3/4
78
39
57-1/8 28-9/16
68-1/2
34-1/4
79-7/8 39-15/16
91-1/8 45-9/16
102-1/2 51-1/4
102-1/2 51-1/4
113-7/8 56-15/16
Operating
Weight Amps‡
(lbs.)
G
NPT
H
NPT
K
Flue Ø
T
Ø
W
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1-1/4
1-1/4
1-1/4
1-1/4
2
2
2
2
2
2
2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
1-1/2
2
2
2
2
2
2
2-1/2
2-1/2
2-1/2
2-1/2
2-1/2
2-1/2
2-1/2
4
4
5
5
5
6
5
6
6
8
8
8
10
12
12
14
14
14
16
4
4
4
4
4
4
6
6
6
6
6
6
10
10
10
10
10
10
10
N/A
N/A
N/A
N/A
N/A
N/A
14-3/4
18-1/2
22
27-1/4
30-3/4
36
16-13/16
20-9/16
24-3/8
28-1/8
31-15/16
31-15/16
35-11/16
150
175
200
225
250
300
380
445
545
590
675
740
900
1010
1225
1350
1450
1450
1520
4.7
4.7
4.7
4.7
4.7
4.7
6
6
6
6
6
7
<12
<12
<12
<12
<12
<12
<12
* Ratings for models HD101-HD401 for natural or propane gas and for elevations up to 2,000 ft. above sea level. For higher elevations, consult the factory.
* Ratings for models 302B-2342B for natural or propane gas and for elevations up to 4,500 ft. above sea level. For higher elevations, consult the factory.
‡ Current draw is for heater only. (Supply breaker must have a delayed trip.)
ª Natural gas only. Not available for propane.
Floor*
Rear
Water side
Other side
Top
Front
Vent
Indoor
Minimum
Service
0”
1”
12”
1”
1”
Open
2”
0”
6”
24”
24”
6”
24”
2”
* Do not install on carpeting.
Water Hardness
Outdoor
Minimum
Hi Delta
Model
Service
0”
0”
12”
24”
36”
36”
36”
36”
Unobstructed Unobstructed
Open
24”
N/A
N/A
PUMP - HOT WATER SUPPLY
CLEARANCES
Boiler
Side
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002B
2072B
2342B
Soft
Medium
HP
Amps
HP
Amps
HP
Amps
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/8
1/2
1/2
1/2
1/2
3/4
3/4
3/4
1
1.1
1.1
1.1
1.1
1.1
1.1
1.3
1.3
1.3
1.3
1.3
7
7
7
7
11
11
11
14
1/8
1/8
1/8
1/8
1/8
1/8
1/4
1/4
1/4
1/4
1/2
1/2
1/2
3/4
1
1
1-1/2
1-1/2
1-1/2
1.3
1.3
1.3
1.3
1.3
1.3
5.7
5.7
5.7
5.7
7
7
7
11
14
14
15
15
15
1/4
1/4
1/4
1/4
1/4
1/4
1/2
1/2
1/2
1/2
3/4
3/4
3/4
1
1
1-1/2
1-1/2
1-1/2
1-1/2
5.7
5.7
5.7
5.7
5.7
5.7
7
7
7
7
11
11
11
14
14
15
15
15
15
Note: Current draw (Amps) is for pump only.
6
Hard
DRAWING 1 - MODELS HD101-HD401
K FLUE CONNECTION DIA.
B
OPTIONAL PUMP
8-7/8
H WATER IN
LOW VOLTAGE CONNECTIONS
T COMBUSTION AIR DIA.
A
G GAS CONNECTION
H WATER OUT
1° SLOPE ON JACKET TOP
POWER
ON
CALL FOR
HEAT
®
BURNER
FIRING
SERVICE
SS
SS
REQUIRED
OFF
P/N 901927 REV 1
26-3/8
19-7/16
1-1/4
18-1/4
16-9/16
4-9/16
8-1/2
19-3/8
22-1/8
23-1/2
26
5-1/16
13-1/2
DRAWING 2 - MODELS 302B-902B
1° SLO
T COMBUSTION AIR
A
K FLUE
CONNECTION DIA.
P
CKET TO
PE ON JA
B
OUTDOOR
VENT TERMINAL
25
INLET DIA.
11-5/8
7-1/8
K OPTIONAL
G GAS CONNECTION
REAR FLUE
CONNECTION DIA.
4-15/16
MANUAL SHUT-OFF
& DIAGNOSTIC LIGHTS
LINE VOLTAGE CONNECTIONS
T OPTIONAL COMBUSTION AIR
ON-BOARD
DIAGNOSTIC
CENTER
INLET DIA.
G OPTIONAL GAS CONNECTION
INLET DIA.
17-3/4
H WATER OUT
H WATER IN
6
28-1/2
POWER
CALL FOR
HEAT
STAGE 1
STAGE 2
ON
FLOW
BLOWER 1
OPTIONAL
PUMP COVER
STANDBY
34-1/8
P/N 901891
31-1/4
VIEW PORT
25-1/2
SAFETY
IGNITION
PROUDLY MADE IN AMERICA
28-1/2
18-5/8
12-1/8
PRV
1-3/4
7-1/2
7
6-1/2
OPTIONAL PUMP
W
3-1/4
T & P GAUGE
2-1/2
MANUAL SHUT-OFF
& DIAGNOSTIC LIGHTS
DRAWING 3 - MODELS 992B-2342B
A
K FLUE
1° SLO
T COMBUSTION AIR
P
CKET TO
PE ON JA
32-5/8
INLET DIA.
9-1/2
K OPTIONAL
10-7/8
B
OUTDOOR
VENT TERMINAL
CONNECTION DIA.
ON-BOARD
DIAGNOSTIC
G GAS CONNECTION CENTER
T OPTIONAL COMBUSTION AIR
INLET DIA.
REAR FLUE
CONNECTION DIA.
G OPTIONAL GAS CONNECTION
INLET DIA.
H WATER OUT
H WATER IN 41-1/4
8-5/8
35-3/4
32-7/8
30-3/8
20-3/8
12-7/8
POWER
CALL FOR
HEAT
STAGE 1
STAGE 2
STAGE 3
17-3/4
SAFETY
IGNITION
ON
FLOW
BLOWER 1
BLOWER 2
OPTIONAL
PUMP COVER
STANDBY
PROUDLY MADE IN AMERICA
32-7/8
VIEW PORT
PRV
6-3/4
2-1/2
8-1/4
13-1/4
T & P GAUGE
3-1/4
W
2-1/2
OPTIONAL PUMP
MANUAL SHUT-OFF
& DIAGNOSTIC LIGHTS
7
Flow Rates
84% EFFICIENCY (TYPE H)
85% AFUE
Hi Delta
Model
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002B
2072B
2342B
Minimum Flow
Pressure Drops
10°F DT
Maximum Flow
GPM
DP Ft
DT °F
GPM
DP Ft
13
13
13
13
13
22
20
20
21
27
32
38
42
53
64
76
84
87
98
<1.0
<1.0
3.4
<1.0
<1.0
2.4
<1.0
<1.0
<1.0
1.1
1.5
2.2
1.3
2.4
4.0
6.0
7.9
8.5
12.1
14
20
27
34
41
30
25
34
40
40
40
40
40
40
40
40
40
40
40
44
44
44
44
44
44
90
90
90
90
90
90
132
132
132
132
132
132
132
8.8
8.8
8.9
9.2
9.4
9.8
9.8
10.0
10.4
10.8
11.3
11.7
13.1
14.8
16.5
18.3
19.0
19.0
21.4
DT °F
4
6
8
10
12
15
6
7
9
12
14
17
13
16
19
23
25
26
30
GPM
17
26
34
43
DP Ft
1.4
3.1
5.4
8.5
Exceeds
Maximum Flow
50
67
84
3.3
5.8
9.1
20°F DT
30°F DT
GPM
DP Ft
13
17
21
25
34
25
34
42
55
63
76
83
106
129
1.0
1.3
2.1
3.1
5.6
<1.0
1.4
2.3
4.1
5.7
8.3
5.2
9.6
15.7
GPM
DP Ft
40°F DT
GPM
DP Ft
Less than Minimum Flow
14
17
22
<1.0
1.4
2.5
13
17
<1.0
1.4
Less than Minimum Flow
22
28
36
42
50
55
71
86
101
112
116
131
Exceeds Maximum Flow
<1.0
1.1
1.8
2.6
3.8
2.3
4.3
7.1
10.7
13.8
14.8
21.1
21
27
32
38
42
53
64
76
84
87
98
<1.0
1.1
1.5
2.2
1.3
2.4
4.0
6.0
7.9
8.5
12.1
Water Hardness
85% EFFICIENCY (TYPE WH)
Hi Delta
Model
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002B
2072B
2342B
Medium
Soft
MTS
Hard
DT °F
GPM
DP Ft
SHL*
DT °F
GPM
DP Ft
SHL*
DT °F
GPM
DP Ft
SHL*
9
13
17
21
25
31
13
17
21
28
30
30
28
30
30
30
30
30
30
20
20
20
20
20
22
40
40
40
40
42
51
60
72
86
102
112
117
132
1.8
1.8
1.9
1.9
1.9
2.4
2.0
2.0
2.1
2.2
2.6
3.9
2.7
4.4
7.1
10.9
13.9
15.1
21.4
3.8
3.8
3.9
3.9
3.9
4.8
5.1
5.1
5.2
5.3
6.0
8.7
5.2
7.9
11.9
17.4
21.6
23.4
31.8
7
10
13
16
20
26
10
13
16
20
17
21
17
19
22
26
26
27
30
26
26
26
26
26
26
52
52
52
55
73
73
98
115
120
120
132
132
132
3.0
3.1
3.2
3.2
3.2
3.3
3.3
3.4
3.5
4.1
7.5
7.8
7.3
11.3
13.7
15.1
19.0
19.0
21.4
6.3
6.3
6.4
6.5
6.5
6.6
8.3
8.4
8.6
9.7
16.9
17.2
13.3
19.4
22.5
23.9
29.5
29.5
31.8
4
6
8
9
11
15
7
9
12
15
14
17
13
16
20
23
26
27
30
45
45
45
45
45
45
74
74
73
72
90
90
132
132
132
132
132
132
132
9.2
9.2
9.4
9.6
9.8
10.3
6.6
6.8
6.9
7.0
11.3
11.7
13.1
14.8
16.5
18.3
19.0
19.0
21.4
18.0
18.1
18.2
18.5
18.7
19.1
16.3
16.4
16.3
16.2
25.1
25.5
23.6
25.3
27.0
28.7
29.5
29.5
31.8
1-1/2”
1-1/2”
1-1/2”
1-1/2”
1-1/2”
1-1/2”
2”
2”
2”
2”
2”
2”
2-1/2”
2-1/2”
2-1/2”
2-1/2”
2-1/2”
2-1/2”
2-1/2”
NOTES: Minimum flow rates in closed systems may be reduced to a flow rate consistent with a 40°F DT.
Maximum flow rates are limited by maximum acceptable velocity through the heat exchanger tubes and may be increased by 10% for closed heating systems. Pressure drop would increase 21%.
*SHL = Calculated at 100 feet effective pipe length.
8
Recovery Rates (GPH)
84% EFFICIENCY (TYPE H)
85% AFUE
Hi Delta MBTUH
Model Input
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002B
2072B
2342B
100
150
199
250
299
399
300
399
500
650
750
900
990
1260
1530
1800
1999
2070
2340
Temperature Rise (°F)
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
1020
1531
2031
2551
3051
4024
3055
4063
5091
6618
7636
9164
10080
12829
15578
18327
20353
21076
23825
510
765
1015
1276
1526
2012
1527
2031
2545
3309
3818
4582
5040
6415
7789
9164
10177
10538
11913
340
510
677
850
1017
1341
1018
1354
1697
2206
2545
3055
3360
4276
5193
6109
6784
7025
7942
255
383
508
638
763
1006
764
1016
1273
1655
1909
2291
2520
3207
3895
4582
5088
5269
5956
204
306
406
510
610
805
611
813
1018
1324
1527
1833
2016
2566
3116
3665
4071
4215
4765
170
255
338
425
509
671
509
677
848
1103
1273
1527
1680
2138
2596
3055
3392
3513
3971
146
219
290
364
436
575
436
580
727
945
1091
1309
1440
1833
2225
2618
2908
3011
3404
128
191
254
319
381
503
382
508
636
827
955
1145
1260
1604
1947
2291
2544
2635
2978
113
170
226
283
339
447
339
451
566
735
848
1018
1120
1425
1731
2036
2261
2342
2647
102
153
203
255
305
402
305
406
509
662
764
916
1008
1283
1558
1833
2035
2108
2383
93
139
185
232
277
366
278
369
463
602
694
833
916
1166
1416
1666
1850
1916
2166
85
128
169
213
254
335
255
339
424
552
636
764
840
1069
1298
1527
1696
1756
1985
78
118
156
196
235
310
235
313
392
509
587
705
775
987
1198
1410
1566
1621
1833
73
109
145
182
218
287
218
290
364
473
545
655
720
916
1113
1309
1454
1505
1702
68
102
135
170
203
268
204
271
339
441
509
611
672
855
1039
1222
1357
1405
1588
Recovery Rates (GPH)
85% EFFICIENCY (TYPE WH)
Hi Delta MBTUH
Model Input
HD101
HD151
HD201
HD251
HD301
HD401
302B
402B
502B
652B
752B
902B
992B
1262B
1532B
1802B
2002B
2072B
2342B
100
150
199
250
299
399
300
399
500
650
750
900
990
1260
1530
1800
1999
2070
2340
Temperature Rise (°F)
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
1020
1531
2031
2551
3051
4071
3091
4111
5152
6697
7727
9273
10200
12982
15764
18545
20596
21327
24109
510
765
1015
1276
1526
2036
1545
2055
2576
3348
3864
4636
5100
6491
7882
9273
10298
10664
12055
340
510
677
850
1017
1357
1030
1370
1717
2232
2576
3091
3400
4327
5255
6182
6865
7109
8036
255
383
508
638
763
1018
773
1028
1288
1674
1932
2318
2550
3245
3941
4636
5149
5332
6027
204
306
406
510
610
814
618
822
1030
1339
1545
1855
2040
2596
3153
3709
4119
4265
4822
170
255
338
425
509
679
515
685
859
1116
1288
1545
1700
2164
2627
3091
3433
3555
4018
146
219
290
364
436
582
442
587
736
957
1104
1325
1457
1855
2252
2649
2942
3047
3444
128
191
254
319
381
509
386
514
644
837
966
1159
1275
1623
1970
2318
2574
2666
3014
113
170
226
283
339
452
343
457
572
744
859
1030
1133
1442
1752
2061
2288
2370
2679
102
153
203
255
305
407
309
411
515
670
773
927
1020
1298
1576
1855
2060
2133
2411
93
139
185
232
277
370
281
374
468
609
702
843
927
1180
1433
1686
1872
1939
2192
85
128
169
213
254
339
258
343
429
558
644
773
850
1082
1314
1545
1716
1777
2009
78
118
156
196
235
313
238
316
396
515
594
713
785
999
1213
1427
1584
1641
1855
73
109
145
182
218
291
221
294
368
478
552
662
729
927
1126
1325
1471
1523
1722
68
102
135
170
203
271
206
274
343
446
515
618
680
865
1051
1236
1373
1422
1607
9
Boilers (Type H)
HEAT EXCHANGER
OPERATING CONTROLS
SAFETIES
GAS TRAIN
992B-2342B
N/A
v
v
V
v
V
V
v
v
V
N/A
v
v
V
v
V
V
v
v
V
N/A
v
v
V
v
V
V
v
v
V
v
v
v
V
V
V
V
V
V
V
V
v
v
N/A
V
V
V
V
V
V
V
V
v
v
v
V
V
V
V
V
V
V
V
v
v
v
V
V
V
V
V
V
V
V
v
V
V
V
v
N/A
v
(1)
V
v
v
V
V
v
v
N/A
v
V
V
v
v
N/A
V
V
v
v
V
V
V
v
v
V
V
V
v
N/A
v
V
V
v
v
V
V
v
v
N/A
v
V
V
v
V
v
N/A
N/A
v
(2)
(3)
N/A
N/A
V
V
V
(4)
(5)
(6)
v
V
N/A
N/A
v
(2)
(3)
N/A
N/A
V
V
V
(4)
(5)
(6)
v
v
v
V
v
V
V
v
V
v
v
v
V
v
V
V
v
V
v
N/A
v
V
V
V
N/A
v
N/A
V
v
N/A
v
V
V
V
(7)
v
V
V
v
N/A
v
V
V
V
V
(8)
V
V
N/A
v
v
V
V
V
N/A
v
N/A
V
N/A
v
v
V
V
V
(7)
v
V
V
N/A
v
v
V
V
V
V
(8)
V
V
H Stamp
HLW Stamp
Copper
Cupro Nickel
Bronze
Cast Iron
30, 45, 75 & 150 PSI Available
60 & 125
v
N/A
v
V
V
v
V
v
v
V
v
N/A
v
V
V
v
V
v
v
V
v
N/A
v
V
V
v
V
v
v
V
120V Power Supply
Pump Time Delay
Diagnostic Display Central
Temperature Controller
With 120V/24V Transformer
Single Phase
16-Event Memory
B-20: On/Off, Mechanical
B-28: On/Off, Digital
B-6: 2-Stage, Mechanical
B-26–B-27: 2-Stage, Digital
B-21–B-23: 4-Stage, Digital
B-60 Stage Interface Card
TempTracker Mod+ Hybrid
B-42 TempTracker Analog
v
v
N/A
V
V
V
V
V
V
V
(9)
v
v
v
V
V
V
V
V
V
V
V
Hot Surface Ignition System
3-try
1-try
v
N/A
V
V
v
v
V
V
V
v
Heat Exchanger Tubes
Headers
Pressure Relief Valve
Temperature & Pressure Gauge
Pump – 120V, Single-Phase
High Gas Pressure Switch
Low Gas Pressure Switch
Blocked Vent and Air Pressure Switches
High Limit Switch
Low Water Cut-Off, 24V
Flow Switch
AIR
302B-902B
302B-902B
ASME, National Board Registered, 160 PSI
Firing Mode
Manual Reset, Fixed
Manual Reset, Adjustable
Automatic Reset, Adjustable
With manual reset and test button
On/Off (H4, WH1)
2-Stage (H3, WH3)
3-Stage (H8, WH8)
4-Stage (H9, WH9)
Natural Gas Only
4” WC Supply Pressure
TruSeal Direct Vent System
Air Filter, Room Air
Air Filter, Ducted Outside Air
Efficiency
OTHER
Water Heaters (Type WH)
992B-2342B HD101-HD401
HD101-HD401
84% (Category I)
85% (Category I)
Combustible Floor Rated
Alarm System
Vent Terminal
Right-Hand Water Connections
CSD-1/GE GAP Control System
Low NOx Compliance
Cold Water Start
Cold Water Run
Outdoor and Through-the-Wall
Less than 20ppm
Cold water protection systems
Cold water protection systems
Notes:
1 Standard on on/off boilers (H4); Optional on all others
2 Standard on Models 302B and 402B; Optional on Models 502B-902B
3 Optional on Models 302B and 402B; Standard on Models 502B-902B
4 Standard on 992B; Optional on 1262B-2342B
5 Not available on Model 992B; Standard on Models 1262B-2342B
v v = Standard
6 Option but not available on Model 2002B
7 Not applicable for Models 302B and 402B; Optional for Models 502B-902B
8 Standard on Models 992B-2002B; Models 2072B and 2342B
require site testing and have different emissions requirements (Consult factory)
9 Standard on HD101-HD301
V V = Optional
Raypak, Inc. • 2151 Eastman Ave., Oxnard, CA 93030 • phone: (805) 278-5300 • fax: (800) 872-9725 • www.raypak.com
Cat. No. 1100.12-N Effective 04-15-16
Replaces: 04-15-15