Model EHRE
heating water
100 - 600 kW
High Capacity
Water Heater EH
®
ECOTHERM
Model EHRE, 100 - 600 kW
®
Heat Transfer Technology
Model EHRE: High capacity water heater 100 - 600 kW
 Stainless steel AISI-316Ti for lifelong service
 Freshly made, hygienic hot water
 Legionella decontamination cycle, 'Anti-Legio' design
 Anti-fouling cycle
 Microprocessor control with optional remote control via
PC
Description
High capacity water heater for water/water operation. External heat exchanger
with free floating turbulator rods for increased efficiency and self cleaning effect.
Insulated hot water storage tank, upright standing. All parts in contact with
water are made entirely of stainless steel AISI-316Ti. 'Anti-Legio' design fully
compliant with European anti-legionella recommendations. Primary & secondary
circulating pumps, motorised control valve on primary circuit, 4 temperature
sensors for preheat start-up, heating cycle start, heating cycle stop and antifouling cooling cycle. Microprocessor control unit with volt free output signals
for boiler request and alarm. Input signal for remote operation. All components
are pre-assembled and wired. Simple on-site assembly.
Output performance
 Output rating: 100 - 600 kW
 Storage capacity: 540, 1000, 2000 litres, or larger
 Peak hot water output: 3030 - 18440 litres/hr at 45°C
(Higher output and storage capacities available on request)
Pressure ratings
Tank <= 1000 litres
Safety valve setting 10 bar
Testing pressure
13 bar
Tank > 1000 litres
6 bar*
10 bar*
*) Higher pressures available on request
Microprocessor control unit
User friendly menus for customised installation. Exact control of programmed hot
water temperature. Anti-fouling cycle and permanent monitoring of secondary
circuit differential pressure loss with fouling alarm, uploadable to BMS. Legionella
decontamination cycle. Continuous status monitoring and memory storage of
output values.
Storage tank insulation
CFC-free hard polyurethane foam (fire protection class B2 DIN 4102)
Grey aluminium casing, removable.
70mm thickness for tank sizes below 800 litres
90mm thickness for tank sizes from 800 litres
Accessories optional
 Violet aluminium front cover
 External cooling for anti-fouling
 Heat exchanger sludge flushing kits
 T5 strap-on temperature sensor for district heating
 Remote control and monitor via PC or BMS using TCP/IP
network, internet or telephone.
Differential pressure sensor ensures operational safety by
permenantly monitoring for possible heat exchanger fouling. Fitted as
standard.
High capacity Water Heaters models EH..
ECOTHERM
®
Model EHRE, 100 - 600 kW
Heat Transfer Technology
Typ EHRE Funktionsschema
Heating circle conduit - return to boiler
Heating circle conduit - heating water from boiler
HW Vorl
HW Rückl.
- Heating water from Boiler -Heating water return to boiler
FS
11
9
9
7
9
Air vent
Pp
WT Rückl.
- Heat exchanger
return
T3
9 17
WW - Hot water
T5
M
Datum 14.01.04 09:56
Anlage
Ein
Anlage
Normal
T1 Sp.oben
64.5
4
SV
8
on/off
High Ca pacity Water H eaters & Boiler s
ECOTHERM
Heat Transfer Technology
®
ELC-10.0
6
18
T4
11
9
10
14
9
Z - Circulation
Z
11
9
9
12
2
16
15
KW - Cold water
5
Ps
T1
T2
T2
17
14
1
6
8
9
MS
MS
10
P1
3
17
P
p
P
s
P
z
V+
VB
A
A
N
S
S
1
S
S
S
S
S
6
S
S
8
V
1
V
V
Heating on
19
P2
Heating off
6
WT Vorl.
- Heat exchanger feed
13
Drain
Scope of delivery
Type EHRE heating water
Heat exchanger piping connections to
the boiler circuit (primary), and to the
domestic hot water circuit (secondary)
1*....
2*....
3*....
4*....
5*....
6*....
7*....
8*....
9 ....
10...
11 ...
12 ...
13 ...
14 ...
15 ...
16 ...
17 ...
18*...
19*...
T1*...
T2*...
T3*...
T4*...
T5 ...
SV*...
Warm water tank
Flange øi 190 mm
Heat exchanger
Primary pump (Pp)
Domestic water pump (Ps)
Shut-off-valves
Modulating control valve
Microprocessor control unit
Shut-off-valves
Circulating pump
Fine filter
Test valve
Pressure reducer
Non-return-valve
Pressure gauge connection
Safety valve
Galvanic isolation union
Non-return-valve
Differential pressure sensor, Huba 692
Temperature sensor Charge “ON”
Temperature sensor Charge “OFF”
Temp. sensor, warm water charging temperature
Temp. sensor, primay circuit delivery
Temp. sensor, primay circuit return (option)
Pressure relief valve
* = Included in the scope of delivery
WW...
Hot water connection
KW....
Cold water connection gem. per
DIN 1988 part 2 and
DIN 4753 part 1 Z...
Circulation
WTVorl... Cold water - feed from boiler
WTRück... Warm water - output from boiler
HWVorl... Hot water feed from boiler
HWRückl... Hot water return to boiler
High capacity Water Heaters models EH..
ECOTHERM
Model EHRE, 100 - 600 kW
®
Heat Transfer Technology
Performance Data Type EHRE
Tank capacity 300 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Model
Nominal
rating
Continous hot
water output
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-300
EHRE-120-7555-1260-300
EHRE-140-7555-1260-300
EHRE-160-7555-1260-300
EHRE-180-7555-1260-300
EHRE-200-7555-1260-300
EHRE-220-7555-1260-300
EHRE-225-7555-1260-300
EHRE-240-7555-1260-300
EHRE-250-7555-1260-300
EHRE-260-7555-1260-300
EHRE-275-7555-1260-300
EHRE-280-7555-1260-300
EHRE-300-7555-1260-300
100
120
140
160
180
200
220
225
240
250
260
275
280
300
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
590
650
710
770
830
890
950
950
1010
1030
1070
1100
1130
1180
Liter in
1 Stunde
2080
2440
2800
3160
3520
3880
4240
4320
4590
4770
4950
5220
5310
5670
Liter in
10 Min.
850
940
1030
1120
1190
1280
1370
1390
1460
1500
1540
1610
1630
1720
Liter in
1 Stunde
3030
3550
4070
4600
5120
5640
6160
6290
6690
6940
7210
7590
7730
8250
Living Hotel
units** units**
20
24
28
34
39
43
54
5
55
6
57
8
60
9
63
10
67
11
69
12
74
15
Tank capacity 540 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Model
Nominal
rating
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-540
EHRE-120-7555-1260-540
EHRE-140-7555-1260-540
EHRE-160-7555-1260-540
EHRE-180-7555-1260-540
EHRE-200-7555-1260-540
EHRE-220-7555-1260-540
EHRE-225-7555-1260-540
EHRE-240-7555-1260-540
EHRE-250-7555-1260-540
EHRE-260-7555-1260-540
EHRE-275-7555-1260-540
EHRE-280-7555-1260-540
EHRE-300-7555-1260-540
100
120
140
160
180
200
220
225
240
250
260
275
280
300
Continous hot
water output
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
820
880
940
1000
1060
1120
1180
1200
1240
1270
1300
1350
1360
1420
Liter in
1 Stunde
2310
2670
3030
3390
3750
4110
4470
4560
4830
5010
5180
5460
5540
5900
Liter in
10 Min.
1190
1270
1360
1450
1530
1620
1710
1730
1800
1840
1880
1950
1970
2060
Liter in
1 Stunde
3360
3880
4410
4930
5450
5970
6490
6630
7020
7280
7540
7930
8060
8580
Living Hotel
units** units**
33
40
47
55
61
63
74
10
75
12
77
15
80
18
83
20
87
23
89
25
94
30
High capacity Water Heaters models EH..
ECOTHERM
®
Model EHRE, 100 - 600 kW
Heat Transfer Technology
Tank capacity 750 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Nominal
rating
Model
Continous hot
water output
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-750
EHRE-120-7555-1260-750
EHRE-140-7555-1260-750
EHRE-160-7555-1260-750
EHRE-180-7555-1260-750
EHRE-200-7555-1260-750
EHRE-220-7555-1260-750
EHRE-225-7555-1260-750
EHRE-240-7555-1260-750
EHRE-250-7555-1260-750
EHRE-260-7555-1260-750
EHRE-275-7555-1260-750
EHRE-280-7555-1260-750
EHRE-300-7555-1260-750
EHRE-325-7555-1260-750
EHRE-350-7555-1260-750
EHRE-375-7555-1260-750
EHRE-400-7555-1260-750
EHRE-425-7555-1260-750
EHRE-450-7555-1260-750
EHRE-475-7555-1260-750
EHRE-500-7555-1260-750
EHRE-550-7555-1260-750
EHRE-600-7555-1260-750
100
120
140
160
180
200
220
225
240
250
260
275
280
300
325
350
375
400
425
450
475
500
550
600
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
5840
6290
6740
7180
7630
8080
8530
8980
9870
10770
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
8490
9140
9790
10450
11100
11750
12400
13060
14360
15670
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
1020
1080
1140
1200
1260
1320
1380
1400
1440
1470
1500
1550
1560
1610
1690
1760
1840
1910
1990
2060
2140
2210
2370
2520
Liter in
1 Stunde
2510
2870
3230
3590
3950
4310
4670
4760
5020
5210
5380
5660
5740
6100
6550
7000
7450
7900
8340
8790
9240
9690
10590
11490
Liter in
10 Min.
1480
1560
1650
1740
1820
1910
2000
2020
2090
2130
2170
2240
2260
2350
2460
2560
2670
2780
2890
3000
2110
3220
3440
3650
Liter in
1 Stunde
3650
4170
4700
5220
5740
6260
6780
6920
7310
7570
7830
8220
8350
8870
9530
10180
10830
11480
12140
12790
13440
14090
15400
16710
Living Hotel
units** units**
41
10
48
15
55
20
63
25
70
30
74
35
78
40
79
41
82
45
85
47
88
50
92
53
94
55
112
60
133
65
142
70
152
75
161
80
171
85
180
90
190
95
200
100
220
110
240
120
.....continous next page
Key to model number
Opt
_Type
_ _ _ – _ kW
_ _ _ – _ _t1_ _ – _ _t2_ _ – _ Vol
___–_
_
8
}
7
}
6
}
5
}
1 2 3 4
9
10
Type
1stdigit: E = ECOTHERM high capacity water heater
2nddigit: H = Heating water type boiler
3rddigit: R = Shell and tube heat exchanger
4thdigit: E = Electronic control
kW
5thdigit: Heat exchanger performance rating in Kilowatt
t1
6thdigit: Feed temperature from boiler in °C
7thdigit: Return temperature to boiler in °C
High capacity Water Heaters models EH..
11
t2
8thdigit: Domestic cold water inlet temperaure in °C
9thdigit: Domestic hot water output temperature in °C
Vol
10th digit: Tank capacity in Litres
Opt - Options
11th digit: F = Violet front cover, D = Double tank,
N = Network remote control, M = Modem remote control,
A = Electric anode, T5 = Sensor for district heating, E = External antifouling cooling, S = Heat exchanger sludge flushing kit
ECOTHERM
Model EHRE, 100 - 600 kW
®
Heat Transfer Technology
Performance Data ...continous
Tank capacity 1000 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Model
Nominal
rating
Continous hot
water output
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-1000
EHRE-120-7555-1260-1000
EHRE-140-7555-1260-1000
EHRE-160-7555-1260-1000
EHRE-180-7555-1260-1000
EHRE-200-7555-1260-1000
EHRE-220-7555-1260-1000
EHRE-225-7555-1260-1000
EHRE-240-7555-1260-1000
EHRE-250-7555-1260-1000
EHRE-260-7555-1260-1000
EHRE-275-7555-1260-1000
EHRE-280-7555-1260-1000
EHRE-300-7555-1260-1000
EHRE-325-7555-1260-1000
EHRE-350-7555-1260-1000
EHRE-375-7555-1260-1000
EHRE-400-7555-1260-1000
EHRE-425-7555-1260-1000
EHRE-450-7555-1260-1000
EHRE-475-7555-1260-1000
EHRE-500-7555-1260-1000
EHRE-550-7555-1260-1000
EHRE-600-7555-1260-1000
100
120
140
160
180
200
220
225
240
250
260
275
280
300
325
350
375
400
425
450
475
500
550
600
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
5840
6290
6740
7180
7630
8080
8530
8980
9870
10770
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
8490
9140
9790
10450
11100
11750
12400
13060
14360
15670
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
1250
1310
1370
1430
1490
1550
1610
1630
1670
1700
1730
1780
1790
1850
1930
2000
2080
2150
2230
2300
2380
2450
2595
2745
Liter in
1 Stunde
2750
3110
3470
3830
4190
4540
4900
4990
5260
5440
5620
5890
5980
6340
6790
7240
7690
8130
8580
9030
9480
9930
10820
11720
Liter in
10 Min.
1820
1910
2000
2080
2170
2260
2340
2360
2430
2470
2520
2580
2610
2690
2800
2910
3020
3130
3240
3340
3450
3560
3780
4000
Liter in
1 Stunde
4000
4520
5040
5560
6090
6610
7130
7260
7650
7910
8170
8560
8700
9220
9870
10520
11180
11830
12480
13130
13790
14440
15740
17047
Living Hotel
units** units**
53
15
57
20
61
25
71
30
74
35
78
40
83
45
85
47
88
50
91
53
94
55
108
58
112
60
133
65
148
70
156
75
173
80
182
85
190
90
197
95
207
100
224
105
254
110
285
115
Tank capacity 1500 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Model
Nominal
rating
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-1500
EHRE-120-7555-1260-1500
EHRE-140-7555-1260-1500
EHRE-160-7555-1260-1500
EHRE-180-7555-1260-1500
EHRE-200-7555-1260-1500
EHRE-220-7555-1260-1500
EHRE-225-7555-1260-1500
EHRE-240-7555-1260-1500
EHRE-250-7555-1260-1500
EHRE-260-7555-1260-1500
EHRE-275-7555-1260-1500
EHRE-280-7555-1260-1500
EHRE-300-7555-1260-1500
EHRE-325-7555-1260-1500
EHRE-350-7555-1260-1500
EHRE-375-7555-1260-1500
EHRE-400-7555-1260-1500
EHRE-425-7555-1260-1500
EHRE-450-7555-1260-1500
EHRE-475-7555-1260-1500
EHRE-500-7555-1260-1500
EHRE-550-7555-1260-1500
EHRE-600-7555-1260-1500
100
120
140
160
180
200
220
225
240
250
260
275
280
300
325
350
375
400
425
450
475
500
550
600
Continous hot
water output
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
5840
6290
6740
7180
7630
8080
8530
8980
9870
10770
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
8490
9140
9790
10450
11100
11750
12400
13060
14360
15670
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
1730
1790
1850
1910
1970
2030
2090
2110
2150
2180
2210
2260
2270
2330
2400
2480
2550
2630
2700
2780
2850
2930
3080
3230
Liter in
1 Stunde
3220
3580
3940
4300
4660
5020
5380
5470
5740
5920
6100
6370
6460
6810
7260
7710
8160
8610
9060
9510
9950
10400
11300
12200
Liter in
10 Min.
2510
2600
2690
2770
2860
2950
3030
3050
3120
3160
3210
3270
3300
3380
3490
3600
3710
3820
3930
4040
4140
4250
4470
4690
Liter in
1 Stunde
4690
5210
5730
6250
6780
7300
7820
7950
8340
8600
8860
9250
9390
9910
10560
11210
11870
12520
13170
13820
14480
15130
16430
17740
Living Hotel
units** units**
61
22
64
30
67
38
78
43
83
50
89
58
97
63
102
65
114
68
118
70
122
73
127
76
131
78
148
83
167
85
173
88
186
90
196
93
209
95
225
100
242
105
273
110
301
120
332
130
High capacity Water Heaters models EH..
ECOTHERM
®
Model EHRE, 100 - 600 kW
Heat Transfer Technology
Tank capacity 2000 litres, boiler water 75°55°C, domestic water 12°60°C (or 45°C after mixing with cold water)
Model
Nominal
rating
Continous hot
water output
75°C55°C 12°C60°C 12°C45°C
Type - kW - t1 - t2 - Vol
kW
EHRE-100-7555-1260-2000
EHRE-120-7555-1260-2000
EHRE-140-7555-1260-2000
EHRE-160-7555-1260-2000
EHRE-180-7555-1260-2000
EHRE-200-7555-1260-2000
EHRE-220-7555-1260-2000
EHRE-225-7555-1260-2000
EHRE-240-7555-1260-2000
EHRE-250-7555-1260-2000
EHRE-260-7555-1260-2000
EHRE-275-7555-1260-2000
EHRE-280-7555-1260-2000
EHRE-300-7555-1260-2000
EHRE-325-7555-1260-2000
EHRE-350-7555-1260-2000
EHRE-375-7555-1260-2000
EHRE-400-7555-1260-2000
EHRE-425-7555-1260-2000
EHRE-450-7555-1260-2000
EHRE-475-7555-1260-2000
EHRE-500-7555-1260-2000
EHRE-550-7555-1260-2000
EHRE-600-7555-1260-2000
100
120
140
160
180
200
220
225
240
250
260
275
280
300
325
350
375
400
425
450
475
500
550
600
Litres per
hour
1800
2160
2520
2880
3240
3590
3950
4040
4310
4490
4670
4940
5030
5390
5840
6290
6740
7180
7630
8080
8530
8980
9870
10770
Litres per
hour
2620
3140
3660
4180
4700
5230
5750
5880
6270
6530
6790
7180
7310
7840
8490
9140
9790
10450
11100
11750
12400
13060
14360
15670
Peak hot water
output***
Peak hot water
output***
Norm output*
12°C60°C
12°C45°C
DIN 4708
Liter in
10 Min.
2200
2260
2320
2380
2440
2500
2560
2580
2620
2650
2680
2730
2740
2800
2880
2950
3030
3100
3180
3250
3330
3400
3550
3700
Liter in
1 Stunde
3700
4060
4420
4780
5140
5490
5850
5940
6210
6390
6570
5130
6930
7290
7740
8190
8640
9080
9530
9980
10430
10880
11770
12670
Liter in
10 Min.
3200
3290
3380
3460
3550
3640
3730
3750
3810
3860
3900
3970
3990
4070
4180
4290
4400
4510
4620
4730
4840
4940
5170
5380
Liter in
1 Stunde
5380
5900
6420
6950
7470
7990
8510
8650
9030
9300
9560
9950
10080
10600
11250
11910
12560
13210
13860
14520
15170
15820
17130
18440
Living Hotel
units** units**
66
26
70
35
74
44
85
49
92
58
100
66
111
71
117
73
125
76
131
79
136
81
145
84
151
86
163
91
186
93
190
94
198
95
211
96
228
98
254
103
277
108
322
113
360
123
410
133
Heating water temperature 75°55°C, Domestic water temperature boiler 12°C60°C.
To produce hygienic hot water at 45°C ECOTHERM recommends running the ECOTHERM High Capacity Water Heater at 60°C for optimum safety
against legionella infection, and then using a mixing unit (available from ECOTHERM on request) to mix down to 45°C for hot water distribution.
*) Nominal output according to DIN 4708, T1 and T3.
**) Living units: Nominal output type NL1 for living quarters,
Hotel units: Nominal output type NL2 for hotels, hospitals and restaurants
***)Peak hot water output = Continuous hot water output + approx. 95% of tank capacity at 60°C
For more information visit our homepage:
www.ecotherm.com.
High capacity Water Heaters models EH..
20070426 EH_Fly
Ecotherm English
Distribution & Service:
© Copyright Ecotherm Austria GmbH, all rights reserved. Subject to change without notice.
High Capacity Water Heaters & Boilers
ECOTHERM
®
Heat Transfer Technology
www.ecotherm.com
ECOTHERM Austria GmbH,Karlinger Str. 8, A-4081 Hartkirchen, Europe
email:office@ecotherm.at Tel.:+43-7273-6030 Fax:+43-7273-6030-15