Rule 1 covers multiple fixture branch lines which do not exceed 20 feet length. Sizing and Placement Series 15M2 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). Water Hammer Arrestor For Commercial/Residential Systems Riser Up to 20' Rule 1 Typical Branch Line As shown above, it has been established that the preferred location for the water hammer arrestor is at the end of the branch line between the last two fixtures served. The location of the water hammer arrestor shown above applies to branch lines that do not exceed 20 feet in length, from the start of the horizontal branch line to the last fixture supply on this branch line. When the branch line exceeds the 20 foot length, an additional water hammer arrestor should be used. This practice is best defined by two rules which have been established to cover the placement of water hammer arrestors. Features • NPT solid hex brass adapter or solder end connection for easy installation • Approved for installation with no access panel required • May be installed in new or existing plumbing systems with a standard pipe tee vertically, horizontally or at any angle • PDI Listed (PDI WH201) • Maintenance free – unit piston is the only moving part • Air pre-load is 60 psi (4.2 bar) • Factory air charged and permanently sealed 15M2 Pre-charged Air Chamber Permanently Sealed from Water System Operating Pressure: Designed to operate on all domestic and commercial lines @150psi (10.6 bar) working pressure. B Materials Bodies: Copper tubing Pistons: Polypropylene O-Ring: EPDM Adapter: Brass NPT Brass Adapter for Easy Installation Standards Listed by IAPMO, ASSE 1010 approved, ANSI A112.261M approved, PDI WH201 approved and certified. A Dimensions — Weight DIMENSIONS WEIGHT (lbs.) A Selection for Long Piping Runs Sizing Table The majority of sizing and selection applications will involve single and multiple fixture branch lines. These are easily handled with the sizing and selection table. The remainder of the applications involve individual runs of piping to a remote item of equipment. The properly sized water hammer arrestor for such applications can be determined by the tables below. For Water Pressures up to 65psi All sizing data in this section is based on flow velocities of 10 fps or less. The certification testing was conducted with a velocity of 10 fps to offer assurance that PDI approved units were capable of handling shock of maximum intensity that may be encountered. ⁄2" ⁄4" 1" 1" 1" 1" 3 25' 50' 75' 100' 125' 150' mm in. 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F 11⁄8 13⁄8 15⁄8 21⁄8 21⁄8 25⁄8 28.5 34.9 41.3 54.0 54.0 66.7 515⁄16 89⁄16 813⁄16 915⁄16 1211⁄16 115⁄32 150.9 218.0 223.5 252.5 322.5 283.5 0.5 0.9 1.3 2.0 2.3 2.7 0.2 0.4 0.6 0.9 1.1 1.2 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS 11⁄8 11⁄8 13⁄8 21⁄8 21⁄8 21⁄8 210.0 254.0 317.5 280.0 343.0 406.5 81⁄4 10 121⁄2 11 131⁄2 16 28.5 28.5 34.9 54.0 54.0 54.0 0.44 0.54 0.92 1.63 1.98 2.32 0.2 0.2 0.4 0.7 0.9 1.1 mm Water Hammer Arrestor 5 ⁄2" A A B C C D 3 ⁄4" 1" 11⁄4" 11⁄2" 2" A B C D D E B C D E F F C D AE F AF DF D E F CF EF FF E F EF FF EFF FFF Water Hammer Arrestors Over 65 psi and up to 85psi LENGTH OF PIPE (ft) NOMINAL PIPE DIAMETER - IN. 1 of Pipe 25' 50' 75' 100' 125' 150' B in. NOMINAL PIPE DIAMETER - IN. 1 ⁄2" B B C D D E 3 ⁄4" 1" 11⁄4" 11⁄2" 2" B C D E E F C D E F CF CF D E F CF DF FF E F CF EF FF DFF F CF FF EFF BFFF FFFF Sizing and Selection Table Shock SIZE (DN) Quick Closure Valve in. Long Run of Piping 1 Outlet Solder 1 LENGTH OF PIPE (ft) When long runs of piping are employed to serve a remote item of equipment, the water hammer arrestor should be located as close as possible to the point of quick closure. At this location, the water hammer arrestor will control the developed energy and prevent the shock wave from surging through the piping system. A typical example of placement is as shown. (kgs.) Threaded ⁄2" 3 ⁄4" 1" 1" 1" 1" Over 20' Rule 2 Ideally, the flow pressure in branch lines serving fixtures should never exceed 55psi. Pressure reducing valves should be installed to maintain proper pressure. When flow pressures are 65 to 85psi the next size water hammer arrestor should be selected. Refer to sizing table for water pressure over 65psi. Temperature Range: 33°F to 180°F (0.5°C to 82°C). 1 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). The sum of the fixture unit rating of units X and Y shall be equal to or greater than the demand of the branches. 15M2S Pressure — Temperature SIZE (DN) Rule 2 covers multiple fixture branch lines which exceed 20 feet in length. A Watts Water Technologies Company F-WHA 1050 /2" /4" 1" 1" 1" 1" 3 MODEL mm Threaded 15 20 25 25 25 25 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F ORDER CODE MODEL ORDER CODE CROSS FIXTURE UNITS REF. PDI STANDARD 0750150 0750151 0750152 0750153 0750154 0750155 1-11 12-32 33-60 61-113 114-154 155-330 A B C D E F Solder 0750140 0750141 0750142 0750143 0750144 0750145 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com Canada: Burlington, ONT. • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca © 2010 Watts watts.com What is Water Hammer? Series 05 Series 150A For Light Commercial/Residential Systems For Residential Systems Only Model 05H-M1 ⁄4" (20mm) Hose Type specially designed for in-line use with washing machines 3 3 ⁄4" 05-QC Dishwashers, clothes washers, fast closing positive shutoff valves incorporated in the system, all contribute to creating water shock which is not only annoying but damaging to pipes and appliances. Watts Water Hammer Arrestors incorporate a permanent pre-charged sealed air chamber to absorb the shock. The sealed chamber prevents the loss of air to the water and ensures long and trouble-free life. All potential leak points are permanently sealed. he noise from banging pipes is caused by shocks of high speed water flowing in the piping system when a fixture is suddenly closed. Sudden stoppage of the water (a non-compressible liquid) flowing at a given pressure and velocity causes a surge or spike of pressure and is called water hammer. When this occurs a pressure wave travels back through the piping until it finds a point of relief. T Features Features 5 ⁄8" 05-C • Economical and effective single fixture protection against water pressure shock • Pre-charged air chamber • May be installed in concealed locations without access panels • Rechargeable • Sealed in diaphragm • Stainless steel chamber construction • Factory air charged and not rechargeable • May be installed in new or existing plumbing systems vertically, horizontally or at any angle 5 Sizing and Placement The fixture unit valve shown in the cold and hot water columns of Table A below are utilized in the sizing of water hammer arrestors. Once the total number of fixture units has been calculated for the hot and cold water branch lines serving a group of fixtures, this number can be applied to the sizing and selection Table B below to determine the appropriate size water hammer arrestor for the hot and cold branch lines. Table B — Series 15M2 Sizing and Selection Table A — Fixture Units Sizing Information SIZE (DN) WEIGHT IN FIXTURE-UNITS TYPE OF SUPPLY FIXTURE Water Closet 1.66 PF Water Closet 1.66 PF Pedestal Urinal 1.06 PF Stall or Wall Urinal Stall or Wall Urinal Lavatory Bathtub Shower Head Bathroom Group Bathroom Group Separate Shower Service Sink Laundry Tubs (1-3) Combination Fixture CONTROL Flush Valve Flush Tank Flush Valve Flush Valve 1.06 PF Flush Tank 1.06 PF Faucet Faucet Mixing Valve Flush Valve Closet Flush Tank Closet Mixing Valve Faucet Faucet Faucet PUBLIC TOTAL C.W. 8 5 4 4 2 2 4 4 – – – 3 – – 8 5 4 4 2 11⁄2 2 2 – – – 3 – – PRIVATE H.W. – – – – – 11⁄2 3 3 – – – 3 – – TOTAL C.W. 5 2.5 – – – 1 2 2 8 6 2 – 3 3 5 2.5 – – – 1 11⁄2 1 8 6 1 – 3 3 H.W. – – – – – 1 11⁄2 2 3 3 2 – 3 3 CROSS FIXTURE UNITS In. mm 1 15 20 25 32 40 50 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 1-11 12-32 33-60 61-113 114-154 155-330 REF. PDI STANDARD A B C D E F ⁄8" 05-CXT Pressure & Temperature Operating Pressure: Designed especially for use in light commercial or residential applications on lines up to 150psi (10.6 bar) working pressure. ⁄8" 05-PEX-T Temperature Range: 33°F to 180°F (0.5°C-82°C) 05-C For compression installation on ⁄2" CTS new or retrofit Temperature Range: 33°F to 180°F (0.5°C - 82°C) 05-QC Arrestor offered with Quick-Connect Tee Air Preload: 60psi (4.2 bar) 05H-M1 For inline use with washing machines Standards 05-C-T For either 1⁄4" icemaker or 3⁄8" lav supply tube installation Dimensions - Weight in 05 05 05-CPVC 05-H 05H-M1 05-S 05-S 05-C 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 3 ⁄4 1 ⁄2 3 ⁄4 5 ⁄8 MODEL 1 05-PEX-T For either ⁄8" or ⁄2" inline PEX installation For complete list of models, send for ES-05. Straight Models SIZE (DN) Models 05-CXT For direct installation on supply stop either between stub out and stop or between stop and supply tube 3 MODEL Maximum Shock Pressure: 200psi (13.8 bar) 1 Certified to ASSE 1010 and listed by IAPMO. CONNECTION TYPE DIMENSION mm in. 10 15 15 20 20 15 20 16 1 NPT NPT CPVC Hose Hose Sweat Sweat OD Comp. 1 ⁄4 11⁄4 11⁄8 2 33⁄16 1 1 11⁄4 MODEL SIZE (DN) CONNECTION TYPE IPC-International Plumbing Code 609.10 Water Hammer. All building water supply systems in which quick-acting valves are installed shall be provided with devices to absorb the hammer caused by high pressures resulting from the quick closing of these valves. These pressure-absorbing devices shall be approved mechanical devices. Water pressure-absorbing devices shall be installed as close as possible to quick-acting valves. 604.9 Water Hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water hammer arrestor shall be installed where quick-closing valves are utilized. Water hammer arrestors shall be installed in accordance with the manufacturer's specifications. Water hammer arrestors shall conform to ASSE 1010. 2 05-C-T 05-C-T 05-CXT 05-CXT 05-PEX-T 05-PEX-T 05-QC 05-QC in mm 1 8 10 10 16 10 15 15 20 ⁄4 3 ⁄8 3 ⁄8 5 ⁄8 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 OD Comp. OD Comp. OD Comp. x Reverse Comp. Nut OD Comp. x Reverse Comp. Nut PEX PEX Quick-Connect Quick-Connect SIZE in. 150A Water Hammer Arrestor Only 150A-HA Water Hammer Arrestor and Fitting 150HA Fitting Only 1 ⁄2" ⁄4" 3 ⁄4" 3 CONNECTION TYPE mm 15 20 20 NPT Hose Hose WEIGHT mm in. mm lbs. kgs. 32 32 29 50 81 25 25 32 1 133 140 118 162 170 140 124 143 0.34 0.36 0.10 0.48 0.60 0.30 0.08 0.40 0.15 0.16 0.05 0.20 0.27 0.14 0.04 0.18 5 ⁄4 51⁄2 411⁄16 63⁄8 611⁄16 51⁄2 47⁄8 55⁄8 DIMENSION A UPC-Uniform Plumbing Code DESCRIPTION B Dimensions NOMINAL A Pipe Size in. mm WEIGHT 1 15 3 ⁄4 20 1 25 11⁄4 32 ⁄2 B in. mm in. mm lbs. kgs. 23⁄4 3 213⁄16 31⁄16 21⁄4 21⁄4 35⁄8 33⁄32 70 77 72 78 58 58 93 104 413⁄16 413⁄16 413⁄16 413⁄16 411⁄16 411⁄16 73⁄8 93⁄4 122 122 122 122 119 119 187 247 0.17 0.17 0.17 0.18 0.12 0.12 0.4 0.57 0.07 0.07 0.07 0.08 0.05 0.05 0.18 0.26 3 150A-HA B Tee Models 2006 Plumbing Code Requirements 150A Maximum Velocity: 10 fps (.93 mps) 05 For NPT threaded applications A For additional information, send for ES-15M2. 3 Models Operating Pressure: Designed for residential/domestic water systems on lines up to 150psi (10.6 bar) working pressure. B A LENGTH Pipe Up to ft. m 50 75 100 25 50 75 25 50 75 25 15.2 22.9 30.5 7.6 15.2 22.9 7.6 15.2 22.9 7.6 FLOW PRESSURE - PSI psi 30 bar 2.11 150A 150A 150A 150A 150A 150A 150A 2-150A 2-150A 2-150A psi 40 bar 2.81 › › › › › › › › — › psi 50 bar 3.52 › › 2-150A › 2-150A › › › — › For additional information, send for ES-150A. 4 and Number of 150A valves to install psi bar psi bar 60 4.22 70 4.92 › › › › › › › › — › › 2-150A › › › — 2-150A — — › psi 80 bar 5.62 › › › › › — › — — — psi 90 bar 6.33 2-150A › — 2-150A — — › — — — psi bar 100 7.03 › — — ›✟ — — — — — — What is Water Hammer? Series 05 Series 150A For Light Commercial/Residential Systems For Residential Systems Only Model 05H-M1 ⁄4" (20mm) Hose Type specially designed for in-line use with washing machines 3 3 ⁄4" 05-QC Dishwashers, clothes washers, fast closing positive shutoff valves incorporated in the system, all contribute to creating water shock which is not only annoying but damaging to pipes and appliances. Watts Water Hammer Arrestors incorporate a permanent pre-charged sealed air chamber to absorb the shock. The sealed chamber prevents the loss of air to the water and ensures long and trouble-free life. All potential leak points are permanently sealed. he noise from banging pipes is caused by shocks of high speed water flowing in the piping system when a fixture is suddenly closed. Sudden stoppage of the water (a non-compressible liquid) flowing at a given pressure and velocity causes a surge or spike of pressure and is called water hammer. When this occurs a pressure wave travels back through the piping until it finds a point of relief. T Features Features 5 ⁄8" 05-C • Economical and effective single fixture protection against water pressure shock • Pre-charged air chamber • May be installed in concealed locations without access panels • Rechargeable • Sealed in diaphragm • Stainless steel chamber construction • Factory air charged and not rechargeable • May be installed in new or existing plumbing systems vertically, horizontally or at any angle 5 Sizing and Placement The fixture unit valve shown in the cold and hot water columns of Table A below are utilized in the sizing of water hammer arrestors. Once the total number of fixture units has been calculated for the hot and cold water branch lines serving a group of fixtures, this number can be applied to the sizing and selection Table B below to determine the appropriate size water hammer arrestor for the hot and cold branch lines. Table B — Series 15M2 Sizing and Selection Table A — Fixture Units Sizing Information SIZE (DN) WEIGHT IN FIXTURE-UNITS TYPE OF SUPPLY FIXTURE Water Closet 1.66 PF Water Closet 1.66 PF Pedestal Urinal 1.06 PF Stall or Wall Urinal Stall or Wall Urinal Lavatory Bathtub Shower Head Bathroom Group Bathroom Group Separate Shower Service Sink Laundry Tubs (1-3) Combination Fixture CONTROL Flush Valve Flush Tank Flush Valve Flush Valve 1.06 PF Flush Tank 1.06 PF Faucet Faucet Mixing Valve Flush Valve Closet Flush Tank Closet Mixing Valve Faucet Faucet Faucet PUBLIC TOTAL C.W. 8 5 4 4 2 2 4 4 – – – 3 – – 8 5 4 4 2 11⁄2 2 2 – – – 3 – – PRIVATE H.W. – – – – – 11⁄2 3 3 – – – 3 – – TOTAL C.W. 5 2.5 – – – 1 2 2 8 6 2 – 3 3 5 2.5 – – – 1 11⁄2 1 8 6 1 – 3 3 H.W. – – – – – 1 11⁄2 2 3 3 2 – 3 3 CROSS FIXTURE UNITS In. mm 1 15 20 25 32 40 50 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 1-11 12-32 33-60 61-113 114-154 155-330 REF. PDI STANDARD A B C D E F ⁄8" 05-CXT Pressure & Temperature Operating Pressure: Designed especially for use in light commercial or residential applications on lines up to 150psi (10.6 bar) working pressure. ⁄8" 05-PEX-T Temperature Range: 33°F to 180°F (0.5°C-82°C) 05-C For compression installation on ⁄2" CTS new or retrofit Temperature Range: 33°F to 180°F (0.5°C - 82°C) 05-QC Arrestor offered with Quick-Connect Tee Air Preload: 60psi (4.2 bar) 05H-M1 For inline use with washing machines Standards 05-C-T For either 1⁄4" icemaker or 3⁄8" lav supply tube installation Dimensions - Weight in 05 05 05-CPVC 05-H 05H-M1 05-S 05-S 05-C 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 3 ⁄4 1 ⁄2 3 ⁄4 5 ⁄8 MODEL 1 05-PEX-T For either ⁄8" or ⁄2" inline PEX installation For complete list of models, send for ES-05. Straight Models SIZE (DN) Models 05-CXT For direct installation on supply stop either between stub out and stop or between stop and supply tube 3 MODEL Maximum Shock Pressure: 200psi (13.8 bar) 1 Certified to ASSE 1010 and listed by IAPMO. CONNECTION TYPE DIMENSION mm in. 10 15 15 20 20 15 20 16 1 NPT NPT CPVC Hose Hose Sweat Sweat OD Comp. 1 ⁄4 11⁄4 11⁄8 2 33⁄16 1 1 11⁄4 MODEL SIZE (DN) CONNECTION TYPE IPC-International Plumbing Code 609.10 Water Hammer. All building water supply systems in which quick-acting valves are installed shall be provided with devices to absorb the hammer caused by high pressures resulting from the quick closing of these valves. These pressure-absorbing devices shall be approved mechanical devices. Water pressure-absorbing devices shall be installed as close as possible to quick-acting valves. 604.9 Water Hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water hammer arrestor shall be installed where quick-closing valves are utilized. Water hammer arrestors shall be installed in accordance with the manufacturer's specifications. Water hammer arrestors shall conform to ASSE 1010. 2 05-C-T 05-C-T 05-CXT 05-CXT 05-PEX-T 05-PEX-T 05-QC 05-QC in mm 1 8 10 10 16 10 15 15 20 ⁄4 3 ⁄8 3 ⁄8 5 ⁄8 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 OD Comp. OD Comp. OD Comp. x Reverse Comp. Nut OD Comp. x Reverse Comp. Nut PEX PEX Quick-Connect Quick-Connect SIZE in. 150A Water Hammer Arrestor Only 150A-HA Water Hammer Arrestor and Fitting 150HA Fitting Only 1 ⁄2" ⁄4" 3 ⁄4" 3 CONNECTION TYPE mm 15 20 20 NPT Hose Hose WEIGHT mm in. mm lbs. kgs. 32 32 29 50 81 25 25 32 1 133 140 118 162 170 140 124 143 0.34 0.36 0.10 0.48 0.60 0.30 0.08 0.40 0.15 0.16 0.05 0.20 0.27 0.14 0.04 0.18 5 ⁄4 51⁄2 411⁄16 63⁄8 611⁄16 51⁄2 47⁄8 55⁄8 DIMENSION A UPC-Uniform Plumbing Code DESCRIPTION B Dimensions NOMINAL A Pipe Size in. mm WEIGHT 1 15 3 ⁄4 20 1 25 11⁄4 32 ⁄2 B in. mm in. mm lbs. kgs. 23⁄4 3 213⁄16 31⁄16 21⁄4 21⁄4 35⁄8 33⁄32 70 77 72 78 58 58 93 104 413⁄16 413⁄16 413⁄16 413⁄16 411⁄16 411⁄16 73⁄8 93⁄4 122 122 122 122 119 119 187 247 0.17 0.17 0.17 0.18 0.12 0.12 0.4 0.57 0.07 0.07 0.07 0.08 0.05 0.05 0.18 0.26 3 150A-HA B Tee Models 2006 Plumbing Code Requirements 150A Maximum Velocity: 10 fps (.93 mps) 05 For NPT threaded applications A For additional information, send for ES-15M2. 3 Models Operating Pressure: Designed for residential/domestic water systems on lines up to 150psi (10.6 bar) working pressure. B A LENGTH Pipe Up to ft. m 50 75 100 25 50 75 25 50 75 25 15.2 22.9 30.5 7.6 15.2 22.9 7.6 15.2 22.9 7.6 FLOW PRESSURE - PSI psi 30 bar 2.11 150A 150A 150A 150A 150A 150A 150A 2-150A 2-150A 2-150A psi 40 bar 2.81 › › › › › › › › — › psi 50 bar 3.52 › › 2-150A › 2-150A › › › — › For additional information, send for ES-150A. 4 and Number of 150A valves to install psi bar psi bar 60 4.22 70 4.92 › › › › › › › › — › › 2-150A › › › — 2-150A — — › psi 80 bar 5.62 › › › › › — › — — — psi 90 bar 6.33 2-150A › — 2-150A — — › — — — psi bar 100 7.03 › — — ›✟ — — — — — — What is Water Hammer? Series 05 Series 150A For Light Commercial/Residential Systems For Residential Systems Only Model 05H-M1 ⁄4" (20mm) Hose Type specially designed for in-line use with washing machines 3 3 ⁄4" 05-QC Dishwashers, clothes washers, fast closing positive shutoff valves incorporated in the system, all contribute to creating water shock which is not only annoying but damaging to pipes and appliances. Watts Water Hammer Arrestors incorporate a permanent pre-charged sealed air chamber to absorb the shock. The sealed chamber prevents the loss of air to the water and ensures long and trouble-free life. All potential leak points are permanently sealed. he noise from banging pipes is caused by shocks of high speed water flowing in the piping system when a fixture is suddenly closed. Sudden stoppage of the water (a non-compressible liquid) flowing at a given pressure and velocity causes a surge or spike of pressure and is called water hammer. When this occurs a pressure wave travels back through the piping until it finds a point of relief. T Features Features 5 ⁄8" 05-C • Economical and effective single fixture protection against water pressure shock • Pre-charged air chamber • May be installed in concealed locations without access panels • Rechargeable • Sealed in diaphragm • Stainless steel chamber construction • Factory air charged and not rechargeable • May be installed in new or existing plumbing systems vertically, horizontally or at any angle 5 Sizing and Placement The fixture unit valve shown in the cold and hot water columns of Table A below are utilized in the sizing of water hammer arrestors. Once the total number of fixture units has been calculated for the hot and cold water branch lines serving a group of fixtures, this number can be applied to the sizing and selection Table B below to determine the appropriate size water hammer arrestor for the hot and cold branch lines. Table B — Series 15M2 Sizing and Selection Table A — Fixture Units Sizing Information SIZE (DN) WEIGHT IN FIXTURE-UNITS TYPE OF SUPPLY FIXTURE Water Closet 1.66 PF Water Closet 1.66 PF Pedestal Urinal 1.06 PF Stall or Wall Urinal Stall or Wall Urinal Lavatory Bathtub Shower Head Bathroom Group Bathroom Group Separate Shower Service Sink Laundry Tubs (1-3) Combination Fixture CONTROL Flush Valve Flush Tank Flush Valve Flush Valve 1.06 PF Flush Tank 1.06 PF Faucet Faucet Mixing Valve Flush Valve Closet Flush Tank Closet Mixing Valve Faucet Faucet Faucet PUBLIC TOTAL C.W. 8 5 4 4 2 2 4 4 – – – 3 – – 8 5 4 4 2 11⁄2 2 2 – – – 3 – – PRIVATE H.W. – – – – – 11⁄2 3 3 – – – 3 – – TOTAL C.W. 5 2.5 – – – 1 2 2 8 6 2 – 3 3 5 2.5 – – – 1 11⁄2 1 8 6 1 – 3 3 H.W. – – – – – 1 11⁄2 2 3 3 2 – 3 3 CROSS FIXTURE UNITS In. mm 1 15 20 25 32 40 50 ⁄2 3 ⁄4 1 11⁄4 11⁄2 2 1-11 12-32 33-60 61-113 114-154 155-330 REF. PDI STANDARD A B C D E F ⁄8" 05-CXT Pressure & Temperature Operating Pressure: Designed especially for use in light commercial or residential applications on lines up to 150psi (10.6 bar) working pressure. ⁄8" 05-PEX-T Temperature Range: 33°F to 180°F (0.5°C-82°C) 05-C For compression installation on ⁄2" CTS new or retrofit Temperature Range: 33°F to 180°F (0.5°C - 82°C) 05-QC Arrestor offered with Quick-Connect Tee Air Preload: 60psi (4.2 bar) 05H-M1 For inline use with washing machines Standards 05-C-T For either 1⁄4" icemaker or 3⁄8" lav supply tube installation Dimensions - Weight in 05 05 05-CPVC 05-H 05H-M1 05-S 05-S 05-C 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 3 ⁄4 1 ⁄2 3 ⁄4 5 ⁄8 MODEL 1 05-PEX-T For either ⁄8" or ⁄2" inline PEX installation For complete list of models, send for ES-05. Straight Models SIZE (DN) Models 05-CXT For direct installation on supply stop either between stub out and stop or between stop and supply tube 3 MODEL Maximum Shock Pressure: 200psi (13.8 bar) 1 Certified to ASSE 1010 and listed by IAPMO. CONNECTION TYPE DIMENSION mm in. 10 15 15 20 20 15 20 16 1 NPT NPT CPVC Hose Hose Sweat Sweat OD Comp. 1 ⁄4 11⁄4 11⁄8 2 33⁄16 1 1 11⁄4 MODEL SIZE (DN) CONNECTION TYPE IPC-International Plumbing Code 609.10 Water Hammer. All building water supply systems in which quick-acting valves are installed shall be provided with devices to absorb the hammer caused by high pressures resulting from the quick closing of these valves. These pressure-absorbing devices shall be approved mechanical devices. Water pressure-absorbing devices shall be installed as close as possible to quick-acting valves. 604.9 Water Hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water hammer arrestor shall be installed where quick-closing valves are utilized. Water hammer arrestors shall be installed in accordance with the manufacturer's specifications. Water hammer arrestors shall conform to ASSE 1010. 2 05-C-T 05-C-T 05-CXT 05-CXT 05-PEX-T 05-PEX-T 05-QC 05-QC in mm 1 8 10 10 16 10 15 15 20 ⁄4 3 ⁄8 3 ⁄8 5 ⁄8 3 ⁄8 1 ⁄2 1 ⁄2 3 ⁄4 OD Comp. OD Comp. OD Comp. x Reverse Comp. Nut OD Comp. x Reverse Comp. Nut PEX PEX Quick-Connect Quick-Connect SIZE in. 150A Water Hammer Arrestor Only 150A-HA Water Hammer Arrestor and Fitting 150HA Fitting Only 1 ⁄2" ⁄4" 3 ⁄4" 3 CONNECTION TYPE mm 15 20 20 NPT Hose Hose WEIGHT mm in. mm lbs. kgs. 32 32 29 50 81 25 25 32 1 133 140 118 162 170 140 124 143 0.34 0.36 0.10 0.48 0.60 0.30 0.08 0.40 0.15 0.16 0.05 0.20 0.27 0.14 0.04 0.18 5 ⁄4 51⁄2 411⁄16 63⁄8 611⁄16 51⁄2 47⁄8 55⁄8 DIMENSION A UPC-Uniform Plumbing Code DESCRIPTION B Dimensions NOMINAL A Pipe Size in. mm WEIGHT 1 15 3 ⁄4 20 1 25 11⁄4 32 ⁄2 B in. mm in. mm lbs. kgs. 23⁄4 3 213⁄16 31⁄16 21⁄4 21⁄4 35⁄8 33⁄32 70 77 72 78 58 58 93 104 413⁄16 413⁄16 413⁄16 413⁄16 411⁄16 411⁄16 73⁄8 93⁄4 122 122 122 122 119 119 187 247 0.17 0.17 0.17 0.18 0.12 0.12 0.4 0.57 0.07 0.07 0.07 0.08 0.05 0.05 0.18 0.26 3 150A-HA B Tee Models 2006 Plumbing Code Requirements 150A Maximum Velocity: 10 fps (.93 mps) 05 For NPT threaded applications A For additional information, send for ES-15M2. 3 Models Operating Pressure: Designed for residential/domestic water systems on lines up to 150psi (10.6 bar) working pressure. B A LENGTH Pipe Up to ft. m 50 75 100 25 50 75 25 50 75 25 15.2 22.9 30.5 7.6 15.2 22.9 7.6 15.2 22.9 7.6 FLOW PRESSURE - PSI psi 30 bar 2.11 150A 150A 150A 150A 150A 150A 150A 2-150A 2-150A 2-150A psi 40 bar 2.81 › › › › › › › › — › psi 50 bar 3.52 › › 2-150A › 2-150A › › › — › For additional information, send for ES-150A. 4 and Number of 150A valves to install psi bar psi bar 60 4.22 70 4.92 › › › › › › › › — › › 2-150A › › › — 2-150A — — › psi 80 bar 5.62 › › › › › — › — — — psi 90 bar 6.33 2-150A › — 2-150A — — › — — — psi bar 100 7.03 › — — ›✟ — — — — — — Rule 1 covers multiple fixture branch lines which do not exceed 20 feet length. Sizing and Placement Series 15M2 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). Water Hammer Arrestor For Commercial/Residential Systems Riser Up to 20' Rule 1 Typical Branch Line As shown above, it has been established that the preferred location for the water hammer arrestor is at the end of the branch line between the last two fixtures served. The location of the water hammer arrestor shown above applies to branch lines that do not exceed 20 feet in length, from the start of the horizontal branch line to the last fixture supply on this branch line. When the branch line exceeds the 20 foot length, an additional water hammer arrestor should be used. This practice is best defined by two rules which have been established to cover the placement of water hammer arrestors. Features • NPT solid hex brass adapter or solder end connection for easy installation • Approved for installation with no access panel required • May be installed in new or existing plumbing systems with a standard pipe tee vertically, horizontally or at any angle • PDI Listed (PDI WH201) • Maintenance free – unit piston is the only moving part • Air pre-load is 60 psi (4.2 bar) • Factory air charged and permanently sealed 15M2 Pre-charged Air Chamber Permanently Sealed from Water System Operating Pressure: Designed to operate on all domestic and commercial lines @150psi (10.6 bar) working pressure. B Materials Bodies: Copper tubing Pistons: Polypropylene O-Ring: EPDM Adapter: Brass NPT Brass Adapter for Easy Installation Standards Listed by IAPMO, ASSE 1010 approved, ANSI A112.261M approved, PDI WH201 approved and certified. A Dimensions — Weight DIMENSIONS WEIGHT (lbs.) A Selection for Long Piping Runs Sizing Table The majority of sizing and selection applications will involve single and multiple fixture branch lines. These are easily handled with the sizing and selection table. The remainder of the applications involve individual runs of piping to a remote item of equipment. The properly sized water hammer arrestor for such applications can be determined by the tables below. For Water Pressures up to 65psi All sizing data in this section is based on flow velocities of 10 fps or less. The certification testing was conducted with a velocity of 10 fps to offer assurance that PDI approved units were capable of handling shock of maximum intensity that may be encountered. ⁄2" ⁄4" 1" 1" 1" 1" 3 25' 50' 75' 100' 125' 150' mm in. 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F 11⁄8 13⁄8 15⁄8 21⁄8 21⁄8 25⁄8 28.5 34.9 41.3 54.0 54.0 66.7 515⁄16 89⁄16 813⁄16 915⁄16 1211⁄16 115⁄32 150.9 218.0 223.5 252.5 322.5 283.5 0.5 0.9 1.3 2.0 2.3 2.7 0.2 0.4 0.6 0.9 1.1 1.2 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS 11⁄8 11⁄8 13⁄8 21⁄8 21⁄8 21⁄8 210.0 254.0 317.5 280.0 343.0 406.5 81⁄4 10 121⁄2 11 131⁄2 16 28.5 28.5 34.9 54.0 54.0 54.0 0.44 0.54 0.92 1.63 1.98 2.32 0.2 0.2 0.4 0.7 0.9 1.1 mm Water Hammer Arrestor 5 ⁄2" A A B C C D 3 ⁄4" 1" 11⁄4" 11⁄2" 2" A B C D D E B C D E F F C D AE F AF DF D E F CF EF FF E F EF FF EFF FFF Water Hammer Arrestors Over 65 psi and up to 85psi LENGTH OF PIPE (ft) NOMINAL PIPE DIAMETER - IN. 1 of Pipe 25' 50' 75' 100' 125' 150' B in. NOMINAL PIPE DIAMETER - IN. 1 ⁄2" B B C D D E 3 ⁄4" 1" 11⁄4" 11⁄2" 2" B C D E E F C D E F CF CF D E F CF DF FF E F CF EF FF DFF F CF FF EFF BFFF FFFF Sizing and Selection Table Shock SIZE (DN) Quick Closure Valve in. Long Run of Piping 1 Outlet Solder 1 LENGTH OF PIPE (ft) When long runs of piping are employed to serve a remote item of equipment, the water hammer arrestor should be located as close as possible to the point of quick closure. At this location, the water hammer arrestor will control the developed energy and prevent the shock wave from surging through the piping system. A typical example of placement is as shown. (kgs.) Threaded ⁄2" 3 ⁄4" 1" 1" 1" 1" Over 20' Rule 2 Ideally, the flow pressure in branch lines serving fixtures should never exceed 55psi. Pressure reducing valves should be installed to maintain proper pressure. When flow pressures are 65 to 85psi the next size water hammer arrestor should be selected. Refer to sizing table for water pressure over 65psi. Temperature Range: 33°F to 180°F (0.5°C to 82°C). 1 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). The sum of the fixture unit rating of units X and Y shall be equal to or greater than the demand of the branches. 15M2S Pressure — Temperature SIZE (DN) Rule 2 covers multiple fixture branch lines which exceed 20 feet in length. A Watts Water Technologies Company F-WHA 1050 /2" /4" 1" 1" 1" 1" 3 MODEL mm Threaded 15 20 25 25 25 25 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F ORDER CODE MODEL ORDER CODE CROSS FIXTURE UNITS REF. PDI STANDARD 0750150 0750151 0750152 0750153 0750154 0750155 1-11 12-32 33-60 61-113 114-154 155-330 A B C D E F Solder 0750140 0750141 0750142 0750143 0750144 0750145 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com Canada: Burlington, ONT. • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca © 2010 Watts watts.com Rule 1 covers multiple fixture branch lines which do not exceed 20 feet length. Sizing and Placement Series 15M2 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). Water Hammer Arrestor For Commercial/Residential Systems Riser Up to 20' Rule 1 Typical Branch Line As shown above, it has been established that the preferred location for the water hammer arrestor is at the end of the branch line between the last two fixtures served. The location of the water hammer arrestor shown above applies to branch lines that do not exceed 20 feet in length, from the start of the horizontal branch line to the last fixture supply on this branch line. When the branch line exceeds the 20 foot length, an additional water hammer arrestor should be used. This practice is best defined by two rules which have been established to cover the placement of water hammer arrestors. Features • NPT solid hex brass adapter or solder end connection for easy installation • Approved for installation with no access panel required • May be installed in new or existing plumbing systems with a standard pipe tee vertically, horizontally or at any angle • PDI Listed (PDI WH201) • Maintenance free – unit piston is the only moving part • Air pre-load is 60 psi (4.2 bar) • Factory air charged and permanently sealed 15M2 Pre-charged Air Chamber Permanently Sealed from Water System Operating Pressure: Designed to operate on all domestic and commercial lines @150psi (10.6 bar) working pressure. B Materials Bodies: Copper tubing Pistons: Polypropylene O-Ring: EPDM Adapter: Brass NPT Brass Adapter for Easy Installation Standards Listed by IAPMO, ASSE 1010 approved, ANSI A112.261M approved, PDI WH201 approved and certified. A Dimensions — Weight DIMENSIONS WEIGHT (lbs.) A Selection for Long Piping Runs Sizing Table The majority of sizing and selection applications will involve single and multiple fixture branch lines. These are easily handled with the sizing and selection table. The remainder of the applications involve individual runs of piping to a remote item of equipment. The properly sized water hammer arrestor for such applications can be determined by the tables below. For Water Pressures up to 65psi All sizing data in this section is based on flow velocities of 10 fps or less. The certification testing was conducted with a velocity of 10 fps to offer assurance that PDI approved units were capable of handling shock of maximum intensity that may be encountered. ⁄2" ⁄4" 1" 1" 1" 1" 3 25' 50' 75' 100' 125' 150' mm in. 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F 11⁄8 13⁄8 15⁄8 21⁄8 21⁄8 25⁄8 28.5 34.9 41.3 54.0 54.0 66.7 515⁄16 89⁄16 813⁄16 915⁄16 1211⁄16 115⁄32 150.9 218.0 223.5 252.5 322.5 283.5 0.5 0.9 1.3 2.0 2.3 2.7 0.2 0.4 0.6 0.9 1.1 1.2 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS 11⁄8 11⁄8 13⁄8 21⁄8 21⁄8 21⁄8 210.0 254.0 317.5 280.0 343.0 406.5 81⁄4 10 121⁄2 11 131⁄2 16 28.5 28.5 34.9 54.0 54.0 54.0 0.44 0.54 0.92 1.63 1.98 2.32 0.2 0.2 0.4 0.7 0.9 1.1 mm Water Hammer Arrestor 5 ⁄2" A A B C C D 3 ⁄4" 1" 11⁄4" 11⁄2" 2" A B C D D E B C D E F F C D AE F AF DF D E F CF EF FF E F EF FF EFF FFF Water Hammer Arrestors Over 65 psi and up to 85psi LENGTH OF PIPE (ft) NOMINAL PIPE DIAMETER - IN. 1 of Pipe 25' 50' 75' 100' 125' 150' B in. NOMINAL PIPE DIAMETER - IN. 1 ⁄2" B B C D D E 3 ⁄4" 1" 11⁄4" 11⁄2" 2" B C D E E F C D E F CF CF D E F CF DF FF E F CF EF FF DFF F CF FF EFF BFFF FFFF Sizing and Selection Table Shock SIZE (DN) Quick Closure Valve in. Long Run of Piping 1 Outlet Solder 1 LENGTH OF PIPE (ft) When long runs of piping are employed to serve a remote item of equipment, the water hammer arrestor should be located as close as possible to the point of quick closure. At this location, the water hammer arrestor will control the developed energy and prevent the shock wave from surging through the piping system. A typical example of placement is as shown. (kgs.) Threaded ⁄2" 3 ⁄4" 1" 1" 1" 1" Over 20' Rule 2 Ideally, the flow pressure in branch lines serving fixtures should never exceed 55psi. Pressure reducing valves should be installed to maintain proper pressure. When flow pressures are 65 to 85psi the next size water hammer arrestor should be selected. Refer to sizing table for water pressure over 65psi. Temperature Range: 33°F to 180°F (0.5°C to 82°C). 1 Explanation - Fixture unit sizing and selection table is used to select the required PDI unit (water hammer arrestor). The sum of the fixture unit rating of units X and Y shall be equal to or greater than the demand of the branches. 15M2S Pressure — Temperature SIZE (DN) Rule 2 covers multiple fixture branch lines which exceed 20 feet in length. A Watts Water Technologies Company F-WHA 1050 /2" /4" 1" 1" 1" 1" 3 MODEL mm Threaded 15 20 25 25 25 25 15M2-A 15M2-B 15M2-C 15M2-D 15M2-E 15M2-F ORDER CODE MODEL ORDER CODE CROSS FIXTURE UNITS REF. PDI STANDARD 0750150 0750151 0750152 0750153 0750154 0750155 1-11 12-32 33-60 61-113 114-154 155-330 A B C D E F Solder 0750140 0750141 0750142 0750143 0750144 0750145 15M2-AS 15M2-BS 15M2-CS 15M2-DS 15M2-ES 15M2-FS USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com Canada: Burlington, ONT. • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca © 2010 Watts watts.com