Edco™ TER Series - Alpine Power Systems

advertisement
Surge Protection
For Business-Critical ContinuityTM
Edco™ TER Series
Single Pair Medium Duty Low Voltage
Zone/Horn/Strobe/Data
The Edco TER surge suppressor directly installs onto electronic circuit wiring
terminal screws. This close proximity preserves Edco TER’s response time, clamping
level and ground reference by eliminating lead lengths. The Edco TER’s miniature
size fits directly inside fire or security panels, CCTV housings and other system
electronic enclosures. These features maximize surge suppression performance
while reducing hardware and labor costs to install.
General Technical Specifications
Operating Voltage
40 VDC
Clamping Voltage
43 VDC
Operating Current
2A
Peak Pulse Current (10 x 1000 µs)
043 = 46.5A
Frequency Range
0 to 20 MHz
Insertion Loss
SPD Technology
Connection Type
<0.1 dB at 20 MHz
Silicon Avalanche Diode (SAD)
Terminal block w/compression lugs
Terminals accept up to 12 AWG
Operating Temperature
Dimensions (Inches)
-40°C to +85°C
1.3H x 0.4W x 2.0L
Weight
Certifications
Warranty
Features
Fits Euro style and barrier strip terminals
Automatic recovery
Single pair protection
High energy silicon avalanche
technology
UL 497B listed
0.6 oz
UL 497B
5 years
Operating current > 2 Amps
Compact size: 1.3" x 0.4" x 2" (HxWxL)
5 year warranty
Ordering Information
Fits in series with circuit wires at the terminal screws
Zone, Buss, Loop, Data, Receive, Bell, Horn, Strobe, Pan/Tilt & CCTV
TER-043 (For 12 VDC, 24 VDC, 25 VAC Systems)
Installation
1. Install zone or loop circuit wires
(1 pair) at the vacant end of the
Edco TER. Torque terminal screws
to 3.5 LB-IN max.
2. Slip the Edco TER’s Rigid
Mounting Prongs into the panels
designated Zone or Loop
terminals and tighten.
3. Using a 16-12 AWG solid wire,
attach all Edco TERs via the center
ground terminal. Run this wire to
your panel’s “single point” AC
power ground or building
approved ground. Torque
terminal screws to 6.0 LB-IN max.
CAUTION
A.Never install data wiring during a lightning storm.
B.Disconnect data line before installing the protection module.
C.These protectors are intended for indoor use on communication loop circuits which have been isolated
from the Public Switch Telephone Network.
D.The communication loop circuits shall not be exposed to accidental contact with the electric light or power
conductors. The protectors shall be installed per the applicable requirements of the National Electric Code,
ANSI/NFPA 70.
Emerson Network Power.
The global leader in enabling
Business-Critical ContinuityTM.
AC Power
Embedded Computing
Outside Plant
Racks and Integrated Cabinets
Connectivity
Embedded Power
Power Switching & Control
Services
DC Power
Infrastructure Management
& Monitoring
Precision Cooling
Surge Protection
Emerson Network Power Contact information
www.emersonnetworkpower.com/surge
Headquarters
Surge Protection
100 Emerson Parkway
Binghamton, New York 13905
T: (607) 721-8840
T: (800) 288-6169
F: (607) 722-8713
E: contactsurge@emerson.com