Commonwealth of Pennsylvania Department of Transportation PA Test Method No. 429 October 2013 7 Pages LABORATORY TESTING SECTION Method of Test for HIGH STRENGTH BOLT INSPECTION TESTING 1. SCOPE 1.1 This method of test is in accordance with AASHTO M-164 (ASTM A 325), and AASHTO M-253 (ASTM A-490). Additional requirements of the 1996 supplement AASHTO Division II, Section 11.5.6.4.9, cover the procedures for final field inspection or shop testing of black or galvanized bolt, nut and washer assemblies. 1.2 Perform calibration at least once each inspection day (torque/tension relationship). 1.3 Washers or steel spacers are required behind nuts for all tests, even if not required on the plan (prevents face plate wear of the testing device). 1.4 Determine a job inspection torque for all representative combinations, (grade/size/condition) of Bolt/Nut/Washer assemblies as those under inspection. Do not reuse assemblies that have been tested in the installation process. 2. 1.5 Assign an inspection lot number that coincides with each assembly in the section. 1.6 Test a minimum of three assemblies per inspection lot. EQUIPMENT REQUIRED 2.1 Use a Skidmore- Wilhelm Calibrator (Skidmore) or an acceptable equivalent device with proof of calibration within the last year. For bolts that cannot be assembled in the Skidmore test device, see Section 4 for the proper procedure. 2.2 Use a calibrated manual dial torque wrench with a 1355 N∙m (1000 Ft.-lb.) capacity or a torque multiplication device with proof of calibration within the last year. 2.3 Use steel spacers and/or washers with a hole diameter a maximum 1.59 mm (1/16") greater than the diameter of bolt to be tested. 2.4 Use a rigid steel section upon which to mount the Skidmore test device. The flange of girders or cross frames, accessible from the ground, is satisfactory. 2.5 Use bolts, nuts, and washers (if used) having lubrication characteristics similar to the installed bolts. PTM No. 429 October 2013 Page 2 3. PROCEDURE FOR LONG BOLTS IN THE SKIDMORE 3.1 Test three bolt, nut, and washer assemblies from each inspection lot. Install the nut on the bolt. Measure the length of bolt remaining when 3 to 5 full threads of the bolt are located between the bearing face of the nut and the bolt head. Measure the effective bolt length, (the distance from the end of the threaded shank to underside of the bolt head). 3.2 Place the bolt in the Skidmore. Use steel shims or washers to take up any space, if necessary to produce the same length measured in Section 3.1 above. Tighten each bolt by any convenient means to the specified tension (see Table 2 for values). 3.3 Apply an inspection wrench to the tightened bolt to determine the torque required to turn the nut head 5 degrees (approximately 25.4 mm (1") at a 304.8 mm (12") radius) in the tightening direction. 3.4 The average of the torques required for all three bolts shall be taken as the jobinspection torque. 3.5 Select ten percent (at least two per connection) of the tightened bolts on the structure represented by the test bolts in each connection. 3.6 Apply job-inspection torque in the tightening direction to each of the selected bolts using the inspection wrench. 3.7 If none of the selected bolt nuts or heads turn under the job-inspection torque, consider the bolts in the connection to be properly tightened. 3.8 If the application of the job-inspection torque turns one or more bolt heads or nuts, apply the job-inspection torque to all bolts in the connection. Tighten and reinspect bolts whose head or nut turns under the job-inspection torque. The Contractor may, however, retighten all the bolts in the connection and resubmit it for inspection, under Sections 3.5 to 3.8, so long as bolts are not overtightened or damaged by this action. 3.9 4. Record all test results on Attachment 1 of this procedure. PROCEDURE FOR BOLTS THAT CANNOT BE ASSEMBLED IN THE SKIDMORE Note 1 - Bolt assemblies that cannot be assembled in the Skidmore may be tested in a steel section with the hole diameter in the plate being a maximum 1.59 mm (1/16 in.) greater than the bolt diameter. The turn Test Tension requirement of Table 2 does not apply. 4.1 Test three bolt, nut, and washer assemblies from each inspection lot. Install the nut on the bolt and measure the length of bolt when 3 to 5 full threads of bolt are located between the bearing face of the nut and the bolt head. PTM No. 429 October 2013 Page 3 4.2 Choose a steel section with the proper size hole to install the bolt. Any available splice hole can be used with a plate thickness that will provide the required number of threads under the nut. 4.3 Install the bolt and use appropriate shims to produce the thread stick out measured in Section 4.1. 4.4 Install the nut and washer using a second wrench to prevent the bolt head from turning at all times. 4.5 Tighten the nut snug tight (approximately 75-100 ft-lb). Mark reference points on the socket, nut, bolt, and steel plate and turn the nut using a torque wrench to the minimum rotation required for turn of the nut installation in Table 1. Apply the inspection wrench in the tightening direction to the tightened bolt to determine the torque required to turn the nut head 5 degrees (approximately 25.4 mm (1") at a 304.8 mm (12") radius). Torque must be measured with the nut in motion. Record the torque. Table 1 4.6 through 3.8. 4.7 Bolt Length (measured in Section 4.1) ≤ 4 x Bolt Diameter >4 ≤ 8xBolt Diameter Required Rotation 1/3 1/2 Continue inspection by following the procedures as described in Sections 3.4 Record all test results on Attachment 1 of this procedure. PTM No. 429 October 2013 Page 4 TABLE 2 REQUIRED FASTENER TENSION MINIMUM BOLT TENSION IN KN (POUNDS) Bolt Size mm (inches) 12.7 (½) 15.9 (⅝) 19.1 (¾) 22.2 (⅞) 25.4 (1) 28.6 (1⅛) 31.8 (1¼) 34.9 (1⅜) 38.1 (1½) AASHTO M-164 ASTM A 325 53.4 (12,000) 84.5 (19,000) 124.5 (28,000) 173.5 (39,000) 226.8 (51,000) 249.1 (56,000) 315.8 (71,000) 378.1 (85,000) 458.1 (103,000) AASHTO M-253 ASTM A 490 66.7 (15,000) 106.7 (24,000) 155.7 (35,000) 218.0 (49,000) 284.7 (64,000) 355.8 (80,000) 453.7 (102,000) 538.2 (121,000) PTM No. 429 October 2013 Page 5 ATTACHMENT 1 COUNTY ___________ S.R.___________ SECTION __________DATE ___________ Structure No. S-____________ ================================================================ Has the pre-installation process been verified?_____________________________________ What installation process was used?__________________________________________ Was it done correctly and documented?_______________________________________ ================================================================ High Strength Bolts Inspection Testing 1. Bolt: _____A 325 _____A 490 Inspection Lot # __________ Galvanized: _____Yes _____No Condition: _______________ 2. Manufacturer: Bolt _______________ Length _____in. Diameter _____in. Nut _______________ Washer _______________ 3. Specified Tension (Table 2- Typical) __________ kips Note: Specified tension N/A for short bolts. Rotation in accordance with Table 1. Sample 1 Sample 2 Sample 3 4. Measured Torque __________ ft-lbs __________ ft-lbs __________ ft-lbs (Torque measured with a required nut turn of 5 degrees in the tightening direction.)_____Yes 5. Average Torque (Job Inspection Torque) Note: See Field Book # __________ Page _____ Connection Description: 6. __________ ft-lbs Ten percent (at least two) bolts per connection verified with the inspection torque wrench? _____ Yes _____ No 7. Did any selected bolt or nut head assemblies turn in the connection under the job-inspection torque? _____Yes _____No (If no, consider the connection to be properly tightened. If yes go to question 8 or 9). PTM No. 429 October 2013 Page 6 8. Was the job-inspection torque applied to all bolts or nuts in the affected connections? _____ Yes ____ No ____N/A 8A. Were all bolts that turned retightened? _____ Yes ____ No ____N/A 8B. Were all bolts re-inspected and found not to turn? _____ Yes ____ No ____N/A ( If all of the questions in # 8 are answered yes, consider the connection to be properly tightened). or 9. At the option of the Contractor were all of the bolt assemblies in the connection retightened that were found to turn.? _____ Yes _____No _____N/A 9A. Were all bolts that turned retightened? _____Yes _____No _____N/A 9B. Were all bolts re-inspected and found not to turn? _____Yes _____No _____N/A (If all of the questions in #9 are answered yes, consider the connection to be properly tightened). Tested by:_________________________________________ Witnessed by:______________________________________ PTM No. 429 October 2013 Page 7 This page left intentionally blank