Underground Feeder and Branch Circuit Cable

Underground Feeder Cable
NMWU
Underground
Feeder and Branch
Circuit Cable
APPLICATIONS
For use in underground applications, including direct burial, at conductor temperatures not to
exceed 60° C. May be used in concealed areas or areas exposed to the weather in wet or dry
locations where not exposed to mechanical damage. The minimum installation temperature is
-25°C for 2 conductor cables and -10°C for 3 conductor cables. Cables should be stored above 0°C
for 24 hours prior to installation.
60°C insulation
300 volts
Sunlight-resistant
jacket
CONDUCTORS
Solid conductors: Soft, annealed copper
Stranded conductors: Soft (annealed) copper compressed stranded copper
CONDUCTOR INSULATION
Conductors are insulated with a thick wall of color coded PVC, rated 60° C
BONDING CONDUCTOR
Soft, uncoated copper per ASTM-B3
ASSEMBLY
Two conductor cables have the insulated conductors laid parallel with the bare bonding conductors
laid between the two insulated conductors. Three conductor cables have the insulated conductors
and bare bonding conductor twisted together.
JACKET
black, sunlight-resistant PVC (polyvinyl chloride) is applied directly over and around the assembly
A
of insulated and bare conductors
INDUSTRY STANDARDS*
CSA C 22.2 No. 48, Master Contract 251402
Canadian Electrical Code
RoHS Compliant
SURFACE PRINT
Sample: CERROWIRE-A CSA AWG 14 CU 2 CDRS NMWU (-25C) 300 VOLTS FT1
2012, Cerro Wire LLC
All Rights Reserved
©
*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and
application.
Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563
www.cerrowire.com
REV-04/2013
A Marmon Group/
Berkshire Hathaway Company
Underground Feeder Cable
NMWU
Underground Feeder
and Branch Circuit Cable
Product
Code
W/Ground
Conductors
Thickness mm
With Bonding Conductor
Bonding Conductor
AWG No.
Conds.
PVC/Nylon
Jacket
Size
Strand
Cable Dim.
mm
Approx. *Ampacity
Net Wt. at 30°C
KG/KM Ambient
1382-1402xx
14-2
Solid
1.52
0.76
14
1
12.50 x 6.20
132
15
1382-1403xx
14-3
Solid
1.52
0.76
14
1
11.38
172 15
1382-1602xx
12-2
Solid
1.52
0.76
14
1
13.35 x 6.62
163
20
1382-1603xx 12-3
Solid
1.52
0.76
14
1
12.54
217
20
1382-1802xx 10-2
Solid
1.52
0.76
12
1
14.85 x 7.16
219
30
1382-1803xx 10-3
Solid
1.52
0.76
12
1
13.70
29530
30
1382-4002xx 8-2
Stranded
1.90
1.14
10
1
19.71 x 9.70
377
40
1382-4003xx 8-3
Stranded
1.90
1.14
10
1
18.31
503
40
1382-4202xx
6-2
Stranded
2.28
1.14
10
1
23.06 x 11.38
528
55
1382-4203xx
6-3
Stranded
2.28
1.14
10
1
21.93
724
55
•
•
•
All products are offered in either a 75 meter reel or a 150 meter reel.
xx Packaging add code (9th and 10th Digits): 75 meter reel - GM, 150 meter reel - JM
Allowable ampacities are for general use as specified by the Canadian Electrical Code, 2012, Table 2.
Electrical Distribution Division: 800.523.3869 | FAX 877.877.9563
www.cerrowire.com
REV-04/2013
A Marmon Group/