UL Type MC-HL, Silicone, 600 V, 90°C Dry/75˚C Wet, Cable Tray Use, Fire-Resistant
Sunlight-Resistant, Direct Burial, UL Marine Shipboard Cable, ABS CWCMC
SPEC 9351
September, 2015
Product Construction:
Conductor:
• Tinned annealed copper per ASTM B33
• Class B stranding per ASTM B8
Insulation:
• Ceramifiable silicone insulation per
UL 44, listed RHH
Braid:
• Fiberglass braid over each conductor
• Color-coded per ICEA S-73-532,
Method 7
Shielded Pair/Triad:
• Isolated and individually twisted pairs or triads with Flexfoil ® aluminum/polyester tape shield providing 100% coverage
• Stranded tinned copper drain wire, two sizes smaller than insulated conductors
Cable Assembly:
• Individually shielded pairs or triads are cabled together with a left-hand lay
Overall Shield:
• Flexfoil ® aluminum/polyester tape shield providing 100% coverage
• Stranded tinned copper drain wire, same size as insulated conductors
Inner Jacket:
• Flame-retardant Polyvinyl Chloride
(PVC) per UL Standard 1569, black
• Low temperature performance meets
ASTM D746 brittleness temperature at or below -40°C
• Nylon rip cord to facilitate jacket removal
CCW Armor:
• Impervious, continuously welded and corrugated aluminum alloy sheath per
UL Standards 1569 and 2225
• CCW armor conductivity meets the grounding requirements of NEC
Article 250
Overall Jacket:
• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride
(PVC) per UL Standard 1569, black
• Low temperature performance meets
ASTM D746 brittleness temperature at or below -40°C
Applications:
• Fire-resistant CCW cables are used in critical safety systems where circuit integrity is required in the event of a fire
• CCW armored 600 volt instrumentation cables with individually shielded pairs or triads and an overall shield provide superior protection and reliability against physical damage for use in instrumentation and process control applications where shielding against both external EMI and EMI between groups is required
• For use in Class I remote-control and signal circuits in accordance with NEC
Article 725
• Recognized for use in Class I, II and
III, Divisions 1 and 2; or Class I, Zones
1 and 2 hazardous locations per NEC
Articles 501, 502, 503 and 505
• Installed indoors or outdoors, in wet or dry locations, in a raceway, as aerial cable on a messenger, in cable trays, or for direct burial
• Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American
Petroleum Institute
Features:
• CCW armor provides superior mechanical protection and an impervious barrier to moisture, gas and liquids
• CCW armor provides EMI shielding performance
• Meets cold impact at -40°C
Specifications:
Design Adherence:
• UL 1569 Metal Clad Cables
• UL 2225 Cables and Cable Fittings for
Use in Hazardous Locations
• UL 1309/CSA C22.2 No. 245 Marine
Shipboard Cable
Flame Tests:
• ICEA T-29-520 (210,000 BTU/hr)
• CSA FT4
• IEEE 1202 (70,000 BTU/hr)
• UL 1581 (70,000 BTU/hr)
• IEC 60331-21
Compliances:
• UL Type MC-HL, RHH, SUN RES, CT
USE, DIR BUR, -40°C, UL File # E90496
• UL Listed Marine Shipboard, S100,
UL File # E85994
• Fire-Resistant, 750˚C for 3 Hours,
IEC 60331-21
• American Bureau of Shipping (ABS)
Listed for CWCMC
Phone: 888-593-3355 www.generalcable.com
®
UL Type MC-HL, Silicone, 600 V, 90°C Dry/75˚C Wet, Cable Tray Use, Fire-Resistant
Sunlight-Resistant, Direct Burial, UL Marine Shipboard Cable, ABS CWCMC
SPEC 9351
September, 2015
CATALOG
NUMBER
9351.18020001
9351.18040001
9351.18060001
9351.18080001
9351.18100001
9351.18120001
9351.18160001
9351.18200001
9351.18240001
9351.18360001
9351.18500001
9351.16020001
9351.16040001
9351.16060001
9351.16080001
9351.16100001
9351.16120001
9351.16160001
9351.16200001
9351.16240001
9351.16360001
9351.16500001
16
16
16
16
16
16
16
16
16
16
16
18
18
18
18
18
18
18
18
18
18
18
COND.
SIZE
(AWG)
NO. OF
PAIRS
INSULATION
THICKNESS
INNER JACKET
THICKNESS
NOMINAL
CORE O.D.
NOMINAL
ARMOR O.D.
JACKET
THICKNESS
NOMINAL
OVERALL O.D.
mils mm mils mm INCHES mm INCHES mm mils mm INCHES mm
18 AWG 7W (0.82 mm²) INDIVIDUAL AND OVERALL SHIELDED PAIRS
CROSS-
SECTIONAL
AREA¹
SQ. IN.
LBS/1000 FT kg/1000 m
2 45 1.14
50 1.27 0.635 16.13 0.845 21.46 50 1.27 0.950 24.13
0.71
4 45 1.14
50 1.27 0.745 18.92 0.985 25.02 50 1.27 1.090 27.69
0.93
6 45 1.14
50 1.27 0.895 22.73 1.170 29.72 50 1.27 1.275 32.39
1.28
8 45 1.14
50 1.27 0.980 24.89 1.290 32.77 50 1.27 1.395 35.43
1.53
10 45 1.14
50 1.27 1.160 29.46 1.510 38.35 60 1.52 1.635 41.53
2.10
12 45 1.14
50 1.27 1.195 30.35 1.545 39.24 60 1.52 1.670 42.42
2.19
16 45 1.14
50 1.27 1.340 34.04 1.640 41.66 60 1.52 1.765 44.83
2.45
20 45 1.14
50 1.27 1.500 38.10 1.780 45.21 60 1.52 1.905 48.39
2.85
24 45 1.14
60 1.52 1.700 43.18 1.960 49.78 60 1.52 2.085 52.96
3.41
36 45 1.14
60 1.52 1.965 49.91 2.230 56.64 60 1.52 2.355 59.82
4.36
50 45 1.14
60 1.52 2.330 59.18 2.750 69.85 70 1.78 2.895 73.53
6.58
16 AWG 7W (1.31 mm²) INDIVIDUAL AND OVERALL SHIELDED PAIRS
2 45 1.14
50 1.27 0.680 17.27 0.890 22.61 50 1.27 0.995 25.27
0.78
4 45 1.14
50 1.27 0.795 20.19 1.070 27.18
50 1.27 1.175 29.85
1.08
6 45 1.14
50 1.27 0.960 24.38 1.275 32.39 50 1.27 1.380 35.05
1.50
8 45 1.14
50 1.27 1.085 27.56 1.360 34.54 50 1.27 1.465 37.21
1.69
10 45 1.14
50 1.27 1.245 31.62 1.595 40.51 60 1.52 1.720 43.69
2.32
12 45 1.14
50 1.27 1.285 32.64 1.600 40.64 60 1.52 1.750 44.45
2.41
16 45 1.14
50 1.27 1.440 36.58 1.640 41.66 60 1.52 1.765 44.83
2.45
20 45 1.14
60 1.52 1.635 41.53 1.960 49.78 60 1.52 2.085 52.96
3.41
24 45 1.14
60 1.52 1.830 46.48 2.190 55.63 60 1.52 2.315 58.80
4.21
36 45 1.14
60 1.52 2.115 53.72 2.490 63.25 70 1.78 2.635 66.93
5.45
50 45 1.14
70 1.78 2.535 64.39 3.030 76.96 80 2.03 3.200 81.28
8.04
APPROXIMATE
NET WEIGHT
353
491
616
746
965
1036
1237
1522
1753
2360
3284
387
574
750
846
1090
1220
1416
1814
2125
2981
3994
575
852
1114
1256
1619
1812
2103
2694
3156
4427
5931
524
729
915
1108
1433
1538
1837
2260
2603
3505
4877
CATALOG
NUMBER
9351.18020002
9351.18040002
9351.18080002
9351.18120002
9351.18160002
9351.18240002
9351.18360002
COND.
SIZE
(AWG)
18
18
18
18
18
18
18
NO. OF
TRIADS
INSULATION
THICKNESS
INNER JACKET
THICKNESS
NOMINAL
CORE O.D.
NOMINAL
ARMOR O.D.
JACKET
THICKNESS
NOMINAL
OVERALL O.D.
mils mm mils mm INCHES mm INCHES mm mils mm INCHES mm
18 AWG 7W (0.82 mm²) INDIVIDUAL AND OVERALL SHIELDED TRIADS
CROSS-
SECTIONAL
AREA¹
SQ. IN.
2 45 1.14
50 1.27 0.705 17.91 0.950 24.13
50 1.27 1.055 26.80
0.87
4 45 1.14
50 1.27 0.825 20.96 1.100 27.94 50 1.27 1.205 30.61
1.14
8 45 1.14
50 1.27 1.110 28.19 1.460 37.08 50 1.27 1.565 39.74
1.92
12 45 1.14
50 1.27 1.340 34.04 1.640 41.66 60 1.52 1.765 44.83
2.45
16 45 1.14
50 1.27 1.505 38.23 1.830 46.48 60 1.52 1.955 49.66
3.00
24 45 1.14
60 1.52 1.910 48.51 2.280 57.91
70 1.78 2.425 61.60
4.62
36 45 1.14
60 1.52 2.205 56.01 2.620 66.55 70 1.78 2.765 70.23
6.00
16 AWG 7W (1.31 mm²) INDIVIDUAL AND OVERALL SHIELDED TRIADS
APPROXIMATE
NET WEIGHT
LBS/1000 FT kg/1000 m
447
590
961
1270
1580
2299
3100
664
876
1427
1886
2346
3414
4604
9351.16020002
9351.16040002
9351.16080002
9351.16120002
9351.16160002
9351.16240002
9351.16360002
16
16
16
16
16
16
16
2
4
8
45
45
45
1.14
1.14
1.14
50
50
50
1.27 0.755 19.18 1.000 25.40 50
1.27 0.885 22.48 1.160 29.46 50
1.27 1.175 29.85 1.525 38.74 60
1.27 1.105 28.07
1.27 1.215 30.86
1.52 1.650 41.91
0.96
1.16
2.14
12 45 1.14
50 1.27 1.445 36.70 1.640 41.66 60 1.52 1.765 44.83
2.45
16 45 1.14
60 1.52 1.640 41.66 1.960 49.78 60 1.52 2.085 52.96
3.41
24 45 1.14
60 1.52 2.055 52.20 2.400 60.96 70 1.78 2.545 64.64
5.09
36 45 1.14
70 1.78 2.400 60.96 3.030 76.96 80 2.03 3.200 81.28
8.04
Dimensions and weights are nominal; subject to industry tolerances.
¹ Cross-sectional area for cable tray fill is in accordance with NEC ® Section 392.22.
493
665
1126
1446
1915
2837
3972
732
988
1672
2147
2844
4213
5898
Phone: 888-593-3355 www.generalcable.com