SPECTRA - Moulded case circuit breakers

advertisement
SPECTRA - Moulded case circuit breakers
Contents
B.2
General characteristics
B.6
Technical data
B.8
Functions
B.10 Operating curves
B.11 Limiter circuit breakers
B.12 Earth leakage protection circuit breakers
B.13 SHR Residual current earth
leakage devices
B.14 MTS Earth leakage protection units with separate
magnetic cores
B.15 Electrical auxiliaries AS, BA, ST, UV
B.18 Electrical control
B.20 Manual rotary control
B.22 Visible isolation circuit breakers
B.24 Catalogue numbers
B.48 Overall dimensions
B.68 Connections
B.74 Drilling diagrams
B.77 Weights
B
1
SPECTRA - Moulded case circuit breakers
Description
General chracteristics
Spectra "Moulded case" circuit-breakers with electronic protection are
available in three and four pole versions, in fixed or withdrawable formats.
The Spectra circuit-breakers have individual rating plugs and enable
protected distribution of electricity within a current range of 20 and 1250 A.
Suitability for visible isolation
Spectra circuit-breakers are ideal for fully visible isolation selection:
With the handle free, the indication "open" (green display) is only possible
when the main contacts are separated by a distance of > 20 mm.
Spectra circuit-breakers conform to standards: IEC 947-3,
NF C 79-130 and CNOMO recommendations (protection of machine tools).
B
2
Double, forward-facing insulation
Spectra circuit-breakers are provided with forward-facing sockets designed
for insertion of internal electrical auxilliaries in situ without the need to
interrupt the power supply.
The sockets are completely insulated from the power circuit.
Seal
For extra safety, access to connection terminals and to controls can be
locked off while at the same time retaining visibility.
Degree of protection
Use
Spectra circuit-breakers provide a solution for three performance levels:
- normal breaking capacity, type EN
- High breaking capacity, type EH
- Limiter circuit-breaker, type EL
By adding or replacing elements, it is possible to perform the following
functions:
- earth leakage protection,
- visible breaking isolation.
In front, in accordance with the NF C 20-010 standard:
- basic circuit-breaker:
IP 2X (E 160)
IP 3X (E 250 to E 1250)
- fixed or withdrawable circuit-breaker, with terminal covers:
IP 3X
Note: the addition of electrical control units, rotary control handle, earthleakage units or the use of withdrawable devices does not affect the
protection offered by the circuit-breaker
Temperature derating
The maximum normal current for a circuit-breaker depends on the ambient
temperature in which it is placed.
This is concerned with the temperature around the circuit-breaker:
- either the ambient temperature when the circuit-breaker is installed in the
open air
- or the air inside the box or casing which the circuit-breaker is encased.
The reference (test) temperature for all Spectra circuit-breakers is 400C.
Breaking capacity (according to IEC 947-2 at 415V)
Icu (kA)
100
EL
160
EL
250
EL
400
EL
630
Derating is not automatic, the rating plug must be selected according to the
ambient temperature around the circuit-breaker.
Withdrawable appliance
Fixed appliance
65
EH
160
EH
250
EH
400
EH
630
EH
800
EN
250
EN
400
EN
630
EN
800
40 C
0
50 C
0
60 C
0
70 C
40 C
500 C
600 C
700 C
160 A
250 A
160 A
235 A
160 A
215 A
145 A
185 A
160 A
230 A
160 A 160 A
210 A 195 A
145 A
170 A
E 400 400 A 400 A
E 630 630 A 630 A
400 A
590 A
400 A
550 A
400 A
580 A
400 A 400 A
570 A 530 A
400 A
500 A
E 160
E 250
EH
1250
35
EN
160
0
0
E 800 800 A 800 A 800 A 800 A 800 A 800 A 800 A 800 A
E 1250 1250 A 1250 A 1250 A 1110 A 1125 A 1125 A 1125 A 1000 A
EN
1250
Resistance/pole
0
To enable calculation of the power dissipated by the fixed circuit-breaker
during normal operation.
160
250
400
630
800
1250
Ith (A)
Breaker
E 160
E 250
E 400
E 630
E 800
E 1250
Resistance(1)
0.25
0.20
0.10
0.10
0.03
0.03
(1) Value in milli-ohms.
SPECTRA - Moulded case circuit breakers
Internal electrical auxiliaries
The BA bell alarm, AS auxilliary "ON/OFF" switch, ST voltmetric shunt
release, and UV undervoltage releases are common to the whole Spectra
range.
These are placed face up on the appliance installed, without the need to
interrupt the power supply.
Orientation
A fixed circuit breaker can be mounted as follows:
vertical
horizontal
UPLINE
900
UPLINE
O
I
Spectra circuit-breakers can be mounted on all boards for industrial and
tertiary use.
In particular, adapter accessories (plates, racks, ...) have been designed for
integration within our Modula 400 boxes and Modula 4000 switchboards.
O
I
DOWNLINE
Installation
900
DOWNLINE
3
Circuit breaker models
Fixture
Spectra circuit-breakers, in the fixed or withdrawable versions, can be fixed
on panels, girders or stanchions.
Mounting behind or against a door or panel requires no special effort. The
cut-out in the door or panel enables the control handle alone or all the
displays and controls to be visible, as required.
Fixed
160 / 1250
Withdrawable
125 / 630
Withdrawable type V
160 /1250
•
•
•
•
•
•
Safety perimeter
Power source
The power source can be connected either upline or downline of the Spectra
circuit-breaker, and up to the maximum voltage for use (690V).
During breaking, all circuit breakers produce external agents (fragments,
gases, . . . ); in order to guarantee security during this phase, it is necessary
to respect the safety distances indicated below.
UPLINE
⇒
100
25
70
0
0 (1)
⇒
Note: forward
facing
safety distance = 0
I
I
O
O
(1) 10 mm for:
- E 160 types H, L, EM
- E 400/630/800/1250 with
extensions or PAR
painted or insulated metal
DOWNLINE
0
B
10
metal
Accreditation/certification
IEC 947-2, EN 60 947.2, NF C 63 120,
UL 489, JIS, CSA, Bureau Véritas, Germanischer Lloyd,
Lloyd's Register of Shipping, RINA
SPECTRA - Moulded case circuit breakers
Spectra electronics
High performance electronic protection.
Spectra's secret in finding the correct protection lies in the combination of a
very sensitive current sensor, a fast AD Converter unit and a
microprocessor specially designed for protection.
N L1 L2 L3
Sampler
B
4
AD Converter
Activator
Processing
unit
LT setting
Traditional electronic protection devices are based on the measurement of
the peak value of the current and the deduction of the RMS value.
This method is accurate on condition that:
- the power source is sinusoidal and alternating at a constant frequency,
- the load is a passive one (R, L, C).
Modern electrical installations are no longer of this type.
Modern installations without a static converter or other electronic equipment
generating harmonics are rare,
- power networks are subject to interference, both with respect to
voltage and frequency,
- loads are increasingly active.
Under these conditions, traditional electronic breakers are completely
unsuitable. According to the network/load couple, it will create an "overprotection" or an "underprotection".
ST and I setting
The current sensor output signal
for each phase is sampled more
than 30 times per cycle in order to
establish the true RMS value,
independent of the network, the
nature of the load and the
environment of the installation.
In this way Spectra guarantees
"correct protection".
Spectra samples more than 30 times per cycle.
Spectra: multi-protector or multi-protection
Curve 1: "over-protection"
Curve 1 shows a current with a
distortion of 10% due to
harmonic 5:
- peak value: Ic = 110 A
- deducted RMS value:
I eff. = 110/√2= 78 A
- true RMS value Irms = 71 A
A traditional circuit breaker
would trip prematurely, resulting
in a disruption of operations.
Curve 2: "under-protection"
Curve 2 shows a current with a
20% distortion due to harmonic 3:
- peak value Ic = 85 A
- deducted RMS value:
I eff. = 85/√2= 60 A
- true RMS value: Irms = 71 A
A traditional electronic circuit
breaker would not trip for this
overload condition, resulting in
the risk of the cable or the load
being destroyed.
The Spectra electronic circuit breaker may receive two types of instructions:
- The rating plug, adjustable from 0.8 to 1 enables the adjustment of
protection againt overcurrent according to the maximum current
supported by the cable (Iz) and the operating current(Ie).
- Short-term (ST) and instantaneous (I) trip setting enables protection of
cables against overloads and the protection of people against indirect
contact, while taking into account the nature of the source.
The same circuit breaker enables protection of lower power sources from
short-circuits (alternator) or the protection of a load from a high inrush
current (transformer).
One version, without the LT function, is intended for the protection of motors
(EM circuit-breaker).
The fine tuning and precision of the ST setting enables discrimination
between circuit breakers with LT settings close to each other.
In order to guarantee total protection of the installation, the two settings of
the circuit breaker are linked. Selection of LT protection automatically
defines the ST and instantaneous (I) setting ranges. This link precludes all
risk of "under-protection" in ST mode.
SPECTRA - Moulded case circuit breakers
Protection selection
In order to define the desired characteristics:
B
5
EN - EH - EL
EN - EH - EL -EM
LT setting
defined by the rating pug
Circuit breaker curve
EM type
Zone that is automatically generated
as soon as the
Ir and Iinst. selection is made
Instantaneous setting
defined by I >
Ir
3 or 4 pole
circuit
breaker
160/32
160/63
160/160
250
400
630
800
1250
Rating plug
(designation)
E 3A 160/32
E 4A 160/32
E 3A 160/63
E 4A 160/63
E 3A 160/160
E 4A 160/160
E 3A 250
E 4A 250
E 3A 400
E 4A 400
E 3A 630
E 4A 630
E 3A 800
E 4A 800
E 3A 1250
E 4A 1250
Iinst
MIN.
2.9
3.0
Instantaneous setting points
in x Ir
•
•
•
•
•
5.9
4.7
7.7
10.1
3.7
6.0
7.9
10.5
5.9
4.7
7.7
10.0
3.7
2.9
3.0
3.0
3.7
3.8
3.8
4.7
5.9
4.8
6.0
MIN.
3.0
•
3.7
•
4.7
3.0
3.8
3.0
In (A)
adj. 0.8 to 1
25
32
50
63
80
100
125
160
80 - 100 - 125
160 - 200 - 250
160 - 200 - 250
320 - 400
250 - 320 - 400
500 - 630
320 - 400 - 500
630
800
630 - 800
1000 - 1250
x Ir
0.63 Iinst
•
5.9
7.7
7.8
7.8
7.9
•
7.7
9.9
10.0
10.1
10.2
MAX.
10
4.8
6.1
7.9
10.2
3.8
4.8
6.1
7.8
10.1
3.0
3.8
4.8
6.1
7.9
3.0
3.8
4.8
6.1
8.0
7.9
10.0
10.3
10.8
10.2
Without rating plug, the circuit breaker is auto-protected between 15 and 25 % Iu
MAX.
13.3
13.8
12.8
13.0
12.5
12.8
13.1
13.3
SPECTRA - Moulded case circuit breakers
Technical data
E 160
E 250
E400
B
6
Circuit breakers
Rated current
(A)
Ith 400C
Ith 500C
(A)
Ith 600C
(A)
Rated operating voltage Ue
AC 50/60Hz
(V)
Rated insulation voltage Ui
(V)
Ultimate short-circuit breaking capacity Icu
AC 50/60Hz
220/240V
(kA)
380/415V
(kA)
500V
(kA)
660/690V
(kA)
Service short-circuit breaking capacity Ics
AC 50/60Hz
220/240V
(% Icu)
380/415V
(% Icu)
500V
(% Icu)
660/690V
(% Icu)
Rated short-circuit making capacity Icm
220/240V (kA peak)
380/415V (kA peak)
Single pole IT system breaking capacity Ice
220/240V
(% Icu)
380/415V
(% Icu)
Rated impulse voltage Uimp
(kV)
Operational category
Number of poles
Endurance
Mechanical
ops.
Electrical
ops.
Total fault elimination time
(ms)
Degree of pollution
EM circuit breakers
Rating plugs supplied with the appliance (nonadjustable)
EM 160/32 to 630: Breaking capacities are
identical to those for the EL range
EM 800 to 1250: Breaking capacities are identical
to those for the EH range
Rating plugs
EN 160 EH 160 EL 160 EN 250 EH 250 EL 250 EN400 EH400 EL400
160
160
160
160
160
160
160
160
160
250
235
215
250
235
215
250
235
215
400
400
400
400
400
400
400
400
400
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
690
65
35
25
8
130
65
40
8
200
100
50
10
65
35
25
10
130
65
40
10
200
100
50
12
65
35
25
10
130
65
40
10
200
100
50
16
75
75
50
50
50
50
50
50
50
50
50
50
75
75
50
50
50
50
50
75
50
50
50
75
75
75
50
50
50
50
50
50
50
50
50
50
145
75
290
145
440
220
145
75
290
145
440
220
145
75
290
145
440
220
50
30
8
A
3-4
50
25
8
A
3-4
50
15
8
A
3-4
50
30
8
A
3-4
50
25
8
A
3-4
50
25
8
A
3-4
50
30
8
A
3-4
50
25
8
A
3-4
50
15
8
A
3-4
15 000
4 000
10
3
15 000
4 000
8
3
15 000
4 000
4
3
15 000
4 000
10
3
15 000
4 000
8
3
15 000
4 000
5
3
10 000
3 000
12
3
10 000
3 000
10
3
10 000
3 000
6
3
Motor protection
EM 160/32 EM 160/63 EM 160/160
Setting range: 0.8 to 1 x In
25A
32A
50A
63A
80A
100A
125A
160A
EM 250
80A
100A
125A
160A
200A
250A
EM 400
160A
200A
250A
320A
400A
SPECTRA - Moulded case circuit breakers
E 630
E 800
E 1250
B
7
EN 630
EH 630
EL 630
EN 800
EH 800
EN 1250
EH 1250
630
630
630
630
630
630
630
630
630
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
690
690
690
690
690
690
690
690
690
690
690
690
690
690
65
35
25
10
130
65
40
16
200
100
50
18
65
35
25
10
100
65
50
18
65
35
25
10
100
65
50
18
75
75
50
50
50
50
50
50
50
50
50
50
75
75
75
100
50
75
50
100
75
75
75
100
50
75
50
100
145
75
290
145
440
220
145
75
220
145
145
75
220
145
50
30
8
A
3-4
50
25
8
A
3-4
50
15
8
A
3-4
50
30
8
A
3-4
65
25
8
A
3-4
50
30
8
A
3-4
65
25
8
A
3-4
10 000
3 000
12
3
10 000
3 000
10
3
10 000
3 000
6
3
5 000
1 000
20
3
5 000
1 000
12
3
5 000
1 000
20
3
5 000
1 000
12
3
EM 630
250A
320A
400A
500A
630A
EM 800
320A
400A
500A
630A
800A
EM 1250
630A
800A
1000A
1250A
SPECTRA - Moulded case circuit breakers
Functions
B
8
Circuit breakers
EN 160
EH 160
EL 160
EN 250
EH 250
EL 250
Differential (adaptable casing)
According to selection of visible isolation(2)
(withdrawable & type V)
Motor protection (ST and I only)
•(1)
•
•(1)
•
•(1)
•(1)
•(1)
•(1)
•
•
•
•
EM32/63/160
EM32/63/160
EM 250
EM 250
EM 250
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
EM32/63/160
Internal electrical auxiliaries
BA bell alarm
AS auxiliary "ON/OFF" switch
ST voltmetric shunt release
UV undervoltage release
Control accessories
Manual rotary
Electrical
Safety accessories
Terminal cover
Locking off
by padlock
by lock
Installation /Connection
Fixed
appliance
Withdrawable
appliance
front connections
rear connections
front connections
rear connections
(1) Separate core unit
(2) All Spectra circuit breakers meet the
selection function standard (IEC 947-3)
FAV
FAR
DAV
DAR
SPECTRA - Moulded case circuit breakers
EN 400
EH 400
EL 400
EN 630
EH 630
EL 630
EN 800
EH 800
EN 1250
•(1)
•
•(1)
•
•(1)
•(1)
•(1)
•(1)
(1)
(1)
(1)
EH 1250
(1)
•
•
•
•
•(type V)
•(type V)
•(type V)
•(type V)
EM 400
EM 400
EM 400
EM 630
EM 630
EM 630
EM 800
EM 800
EM 1250
EM 1250
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
B
9
SPECTRA - Moulded case circuit breakers
Operating curves
E 250 to E1250 circuit breakers
E 160 circuit breaker
10000
10000
1000
1000
100
100
7
5
4
3
2
7
5
4
3
2
B
7
5
4
3
2
7
5
4
3
2
7
5
4
3
2
Operating time in seconds
Operating time in seconds
10
MIN
10
7
5
4
3
2
MAX
1
7
5
4
3
2
7
5
4
3
2
MIN
10
7
5
4
3
2
MAX
1
7
5
4
3
2
MIN
0.1
0.1
MAX
7
5
4
3
2
MIN
MAX
7
5
4
3
2
0.01
0.01
1
2
3
4
5 6 7 8 910
multiples of the setting current
2
3
1
2
3
4
5 6 7 8 910
multiples of the setting current
2
3
SPECTRA - Moulded case circuit breakers
Limiter circuit breakers
General
Curves
(derived from tests according to IEC 947-2)
Network voltage 380/415 V
Limited peak intensity as a function of the actual intensity of the
short-circuit current.
KA peak
120
1
0.2
80
70
j
N
60
E400/630
L
H
N
40
2
11
ϕ=
90
50
This characteristic is expressed by
limiting curves.
H
Ma
xim
um
ass
um
ed
am
plit
ude
100
The limiting capacity of a circuit
breaker is the expression of the
breaker's capacity, in the event of a
short-circuit, to let no current
through that is greater than the
assumed fault current.
B
E800/1250
110
E250
L
E160
H
30
N
20
N
H
10
kA eff.
1: Icc unlimited peak
2: Icc limited peak (actual)
The great limiting capacity of Spectra circuit berakers is a result of the
optimal combination of:
- a light moving part, reducing inertia,
- a strong current loop, to generate maximum force of repulsion,
- a slot motor with strong electro-magnetic field to accelerate the opening of
the contacts
- contact materials combining good conductivity and high durability,
- an arc chamber combining a high energy absorbtion capacity, speed of the
breaking of the arc and the cooling of the gasses.
This combination has enabled an exceptional breaking capacity /volume
ratio.
The use of Spectra limiter circuit-breakers enables a great reduction in
stresses that normally develop during a short-circuit:
- Reduction in thermal constraints in conductors, increasing their life.
- Reduction in mechanical constraints due to the reduction of the
electrodynamic forces of repulsion between conductors, which reduces
the risk of deformation or rupture of the wiring
- Reduction in electro-magnetic effects.
The electro-magnetic field reduces and causes less damage to
neighbouring devices and sensors.
Rationalisation
Spectra limiter circuit breakers offer multiple advantages:
- reduction in the volume of boxes and cabinets,
- reduction in logistic costs because of the smaller volume,
- possibility of connecting circuit breakers with smaller capacity downline.
0
10
20
30
40
50
60
70
80
90
100
Thermal constraints limited as a function of the actual intensity of the
short-circuit
A² s
E800/1250
H
N
E400/630
L
H
107
N
H
N
106
H
N
E250
L
E160
105
kA eff.
104
1
10
30
50
70 100
SPECTRA - Moulded case circuit breakers
Earth leakage protection circuit breakers
Differential protection
Remote control
It is possible to control the opening of the circuit breaker using two isolated
terminals, at the rear of the earth leakage protection unit.
Operating voltage: 220 to 415 V AC or DC: no defined polarity.
Test circuit
The "test" button enables simulation of a 30 mA insulation fault;
The circuit simultaneously tests:
- the sensor (core)
- the processing circuit
- the warning light (V)
- the voltmetric shunt release (ST)
B
12
Presentation
Front facing:
- "test" button.
- fault indicator light
- the RZ reset button
- adjusting switch ∆ I
- adjusting switch ∆ t
- ST terminals (under the shutter)
Rear:
- two terminals for remote control
Diagram
The protection of people and property provided by differential circuit
breakers with residual intensity measurement, is obtained by combining a
Spectra circuit breaker equipped with an ST voltmetric shunt release and a
differential block (MIR).
The MIR block can be adapted in situ, to the E 160, E 250, E 400 and 630
circuit breakers.
The electronic board is powered from three phases: protection is
ensured even if one phase is lost .
N L1 L2 L3
The MIR differential units are:
- protected against untimely tripping (no tripping by the 250A
8/20 micro-second wave, defined by IEC 947.2 app.. B)
- adapted to continual bi-directional and uni-directional pulsed
components (class A).
ST
V
Differential protection devices ensure the following functions:
- protection of people against direct contact in TT systems
- additional protection for people against contact in IT or TNS systems
- protection of property against destruction or fire in the event of faulty
insulation.
Differential protection is also achievable on all Spectra circuit breakers
through the combination of a circuit breaker fitted with voltmetric release and
a differential unit with separate magnetic core (SHR, MTS).
Functioning
Measuring the fault
The sensor consists of a detection magnetic core. The core is made from a
high permability magnetic alloy meeting the requirements of IEC 947.2,
app. B
Processing the measurement
The processing circuit comprises:
- a filter F
- a comparator C
- a timer T
In the event of a fault, the contact I closes.
The rectifier simultaneously powers the voltmetric release ST and the
warning light V:
- the warning light changes
- the voltmetric shunt release opens the circuit breaker (the open command
can be made permanent).
The warning light V cannot be reset (using the RZ button) until the fault has
been rectified and the circuit breaker closed.
C
+
-
F
RZ
I
T
RC
RS
TEST
RS: adjusting switch ∆ I
RT: adjusting switch ∆ t
RT
RZ: reset button
RC: terminals for remote control
Characteristics
Operating voltage
Switchable version
instantaneous fixed threshold
threshold: Mult. position
time delay
Standards
The differential MIR units comply with:
- IEC 947-2
- NF C 60-130
- NF C 61-141 (additional clause)
- NF C 62-411
(V)
(A)
(A)
(ms)
220 to 415
50/60 Hz
0.03
0.3 - 1-3
0 - 100 - 300 - 500
SPECTRA - Moulded case circuit breakers
SHR 1100 and SHR 1110
Residual current earth leakage devices
Residual current earth leakage protection devices
with separate core, which, via a Spectra circuit
breaker provide circuit opening in the event of an
isolation fault.
Specially designed for industrial networks.
Presentation
Characteristics
–
–
–
–
–
Controlled network
alternative L.V.
frequency
Detection principle
Modular box 4 modules - DIN 43880
Mounting on symmetrical rail (surface or flush)
Screw terminals for 2.5 mm2 wires
Front face setting
Sealable transparent cover
Functions
Isolation fault
Pre-alarm 50%
positive security
relay
Fault reset
System failure
Core failure
LED indication
two changeover switches
LED indication
one changeover switch
by push-button
(optional bistable relay)
manual integrated test
external test
signal 'error' and tripping
Performances
Supply voltage
version 1
version 2
version 3
Contacts
output
breaking capacity
insulation
Protection degree
V1
V2
24V~
48V~
110/127V~ 440/480V~
220/240V~ 380/415V~
dry contacts
2 changeover + 1 NO
6A 250V, 1500VA max.
4kV eff.
IP20 surface
IP42 flush
Remarks
1. Ensure cover conductors are centered
2. If the neutral is not out, enclose the 3 phases
3. Never allow the core to enclose the protection
conductor
4. Armoured cable obligatory for cable lengths
(SHR / core) ⊕ 5 m or for sensitive
settings ⊕ 1A
AC
< 1000V
40 to 70Hz - 400Hz N.C.
measurement residual
current
core ratio
600/1 (optional 470/1)
maximum current 500A - 1 s.
nominal impedance 100Ω
Current measurement
threshold
30mA at 3.4A
pre-alarm
50% of the threshold
(not adjustable)
threshold adjustm. 64 steps
indicators
4 LEDs
Power supply
frequency
40 to 400Hz
standard voltage 24 to 480V~ in 3 ranges
consumption
4VA
Operating time
adjustable on SHR 1110
adjustments
0.1 to 1.5 s. in 16 steps
instantaneous
15 ms
bypass if 30mA threshold
B
13
Connection diagram
Cores CITO - CITF
Alarm 50%
Core failure
System failure
– Ratio: 600/1
– Connection by box type terminals for wires of
2.5 mm2
– Connection to earth leakage protection relays
using armoured cable with two insulated
conductors and the shortest possible cabling
(resistance < 30Ω)
Tripping
CT
V1
V2
TEST
SPECTRA - Moulded case circuit breakers
MTS earth leakage protection units with separate magnetic
core
Function and use
Maximum current earth leakage protection relay with separate magnetic core which uses a circuit breaker
Spectra release to open a circuit in the event of an isolation fault.
Specially designed for industrial networks.
Characteristics
B
14
MTS
•
50 to 175Hz
fixed 0.03A
adjustable 0.1 to 1A
0 to 500 ms (for 0.1 to 1A)
2 changeover contacts
(2A/250V cos ϕ 0.3)
•
•
•
Detection core
Passing diameter: 34, 55, 70, 100 mm
(shipped with MTS)
detection core ratio:
- signal:
34: 230/1
55: 200/1
70: 200/1
100: 280/1
- test:
34, 55, 70, 100: 200/1
Alternating earth neutral network protected
Frequency
Setting values
Time delay
Out-going contacts
Display
Test button
Reset button
Power
Frequency 50/60 Hz
AC 220/240V or 380/415V
Mounting
recessible into the bottom of the housing
Detection core mounting
On armoured cable
End box electrically
isolated from its support
sensors
Flexible connection
common to cable's ring and
fuse at the cable end box
For junction boxes
Junction box
electrically isolated
from its support
input
output 2
sensor
Connection diagram
sensors
output 1
220/240V 50/60Hz
380/415V 50/60Hz
3 4 6
0.5/1.5 mm2
1
~
2
12 11 14
22 21 24 3
4
5
6
Notes
1. Ensure conductors are centred in the core.
2. If the neutral is not out, enclose the 3 phases.
3. Never allow the protection conductor to be
enclosed by the core.
SPECTRA - Moulded case circuit breakers
Electrical auxiliaries
General
BA bell alarms, AS auxiliary "ON/OFF" switches, ST voltmetric shunt
releases and UV undervoltage releases are common to all Spectra circuit
breakers,
e.g.: an AS auxiliary "ON/OFF" switch can be installed equally well on an E
160 or E 1250 circuit breaker.
Thus it is not necessary to specify the type of circuit-breaker. Only the
release voltage and the type of contact (standard or low level) has to be
indicated with the order.
B
Assembly
15
Left-hand compartment
Option of connecting UV or ST
releases plus 3-pole BA .
1 or 2 additional AS contacts can be
connected to the 4-pole E 400 to
E 1250 circuit breakers (an extra
socket is provided for this).
Right-hand compartment
Option of connecting 1 or 2 AS
auxilliary switches.
On each circuit breaker, ducts for the wiring are provided enabling the
passage of the cables to the right, left, or to the rear side of the device,
without increasing its original dimensions.
Maximum possibilities for auxilliaries
circuit breaker
AS
BA
ST or UV
3P
160
to 1250
2
1
1
4P
160
to 250
2
1
1
400
to 1250
2+2
1
1
Withdrawable circuit breakers
- option of connecting 8 wires to one 8-contact block
- option of connecting 16 wires to two 8-contact blocks (max.)
As this is intended for installation in compartments that are accesssible from
the front, it is not necessary to take off the cover of the circuit breaker.
SPECTRA - Moulded case circuit breakers
Electrical auxiliaries
Auxiliary AS "ON/OFF" switches
BA bell alarm contacts
Description
Description
Indicates the "open" or "closed" position of the circuit breaker to other
auxiliaries such as logic circuits, relays, diplays, etc. ... for control, locking, or
remote indicator functions...
Changeover contacts signalling the "tripped" status of the circuit breaker
caused by a fault or opening by voltmetric ST or UV trip devices, or by an
earth leakage.
The contact returns to the "normal" position following resetting of the circuit
breaker.
B
16
Low level AS contacts
For communications between the circuit breaker and automatic or logic
circuits.
These (gold plated) contacts are suitable for voltages of
5 to 30 V AC/DC.
Diagrams show switches in the "OFF" position
open closed
12
14
11
common
open closed
22
12
24
14
21
11
Wiring colour code
12: BNWH (brown & white)
14: RD (red)
11: WH (white)
22: OGWH (orange-white)
24: OG (orange)
21: GY (grey)
The BA contact is not activated with a normal closing or opening of the
circuit breaker.
Low level BA contacts
For communications between the circuit breaker and automatic or logic
circuits.
These (gold plated) contacts are suitable for voltages of
5 to 30 V AC/DC.
normal default
96
common
Characteristics
95
Changeover contacts activated at the same time as main poles.
2 versions: 1 NO/NC or 2 NO/NC (in the same volume)
common
Characteristics
Standard contacts
Operating voltage
Load
Uninterrupted current
Breaking capacity
Closing capacity
Wiring colour code
96: GN (green)
98: BN (brown)
95: YE (yellow)
98
(V)
(A)
(A)
(A)
E 160 to E 1250
AC 50-60 Hz DC
120 to 240 48 to 125
resistive
5
0.5
5
0.5
5
0.5
Standard contacts
inductive
0.25
0.25
0.25
Operating voltage
(V)
Load
Uninterrupted current
Breaking capacity
Closing capacity
(A)
(A)
(A)
E 160 to E 1250
AC 50-60 Hz DC
120 to 240 48 to 125
resistive
5
0.5
5
0.5
5
0.5
inductive
0.25
0.25
0.25
E 160 to E 1250
AC 50-60 Hz DC
5 to 30
5 to 30
resistive
1
1
1
1
1
1
inductive
0.5
0.5
0.5
Low level contacts
Operating voltage
Load
Uninterrupted current
Breaking capacity
Closing capacity
(V)
(A)
(A)
(A)
E 160 to E 1250
AC 50-60 Hz DC
5 to 30
5 to 30
resistive
1
1
1
1
1
1
Low level contacts
inductive
0.5
0.5
0.5
Operating voltage
(V)
Load
Uninterrupted current
Breaking capacity
Closing capacity
(A)
(A)
(A)
SPECTRA - Moulded case circuit breakers
Undervoltage release UV
Shunt release ST
B
17
Description
Description
C1
U>
C2
Causes the remote opening of the circuit breaker as
soon as it receives power (power can be permanent).
Operation is guaranteed from 55% of Un with
alternating current and from 70% of Un with direct
current
D1
U<
Causes opening of the circuit breaker in the event of a
drop in voltage (35% to 70 % of Un)
Guaranteed closure of the circuit breaker if
Un > 85%.
Operating range:
0.85 < Uc < 1.1 Un.
D2
Wiring colour code
D1 - D2: Blue (BL)
Wiring colour code:
C1 - C2: Black(BK)
When the release does not receive power, or voltage is too low, the circuit
breaker cannot be reclosed; the contacts do not touch.
Characteristics
E 160 to E 1250
(V) AC 50-60 Hz
DC
24
48
Max. ringing current
(mA) 300
300
Average current
(mA) 10
10
Release breaking time
(ms)
min.
(100 % Un) 15
12
max.*
45
30
Operating voltage
* 55 % of Un for AC - 70 % of Un for DC
AC
50-60Hz
110/127 220/250 380/415
500
400
400
6
5
6
10
35
15
50
15
50
Characteristics
Operating voltage
(V)
Max. calling current
(mA)
Average current
(mA)
Release breaking time
(ms)
mini
(100 % Un)
maxi (1)
E 160 to E 1250
AC 50-60 Hz/DC
24
48
110/127 220/250(2)
100
100
200
200
80
45
45
45
3
85
45
120
(1) 55 % of Un for AC - 70 % of Un for DC.
(2) Time release MVR retarder (250, 500, 800, 1000 ms.)
at 220V AC 50 Hz.
Avoids untimely tripping with sudden loss of voltage.
75
250
75
250
SPECTRA - Moulded case circuit breakers
Electrical control for
E 160 - E 250 circuit breakers
B
18
Characteristics
Nominal voltages:
- alternating current 50/60Hz: 24 - 48 - 110/127 - 220/240 - 380/415V
- direct current: 24 - 48 - 110/125 - 220/250V
Operating voltage: 0.85 to 1.1 Un.
Apparent consumption:
- alternating current (average) 450VA/(max.) 500VA
- direct current: (average) 550W/(max.) 600W
Response time:
- opening/closing: 0.1 s.
Maximum rate of operation:
- 5 cycles /mn.
Interval between two successive operations:
- 0.5 seconds
cycle
closing
rest
0
0.7
0.6
t (s)
rest
1.2
0.1
opening
Description
Diagram
The electrical control is attached to the front of the breaker. It enables the
opening and closing of the circuit breaker by either remote or local control.
Opening and closing by means of a universal motor with two rotational
directions with automatic stop at the end of operation.
Local emergency level control.
Display showing:
- red: circuit breaker "closed"
- white: circuit breaker "open" due to a fault or voltmetric release tripping
- green: circuit breaker "open " and "reset"
Opening through ST, UV release, overload, short-circuit or "TEST" button
with resetting required by depressing the "BPA" button or locally by the
emergency control.
Any release of the reset circuit breaker requires resetting of the electrical
control.
BPA
BPM
3
4
1
YE
BL
GNYE
IND
GN
5
2
OG
FC
Connection of wiring by means of connecting terminals.
Locking in the"open" position:
- using 3 padlocks → 8 (not supplied)
- using Ronis locks (supplied), type 1104, opening to the right.
CS
IND
RD
6
R
1
2
3
4
5
6
BPA
: GN (green)
: BL (blue)
: GNYE (green/yellow)
: YE (yellow)
: OG (orange)
: RD (red)
: "reset/stop"
push-button
BPM
FC
CS
IND
R
: "ON" push-button
: limit switch
: safety contact on lever
: coil/induced
: resistor for U > 240V
: connection terminals
SPECTRA - Moulded case circuit breakers
Electrical control for
E 400 - E 630 - E 800 - E 1250 circuit breakers
Operation
The accumulation of energy (compression of the spring), requires rapid
closure of the circuit breaker, and is performed automatically with the
opening of the electrical control unit.
- closing: depressing the "ON" button (BPM) powers the closing electronics
EF, releasing the spring and closing the circuit breaker.
- opening: depressing the stop/reset (BPA) button powers the motor which
opens the circuit breaker and resets the spring.
Power is cut at the limit of the movement by the limit swicth (FC) contact ;
the circuit breaker is thus ready for a new closure.
- opening by an ST or UV release, overload or short-circuit or
"TEST" button with resetting required by depressing the BPA button or if
necessary by means of local emergency controls.
Any tripping of a circuit breaker requires closing or resetting of the electrical
control.
- use of a specific system for automation: call us.
Insertion of a BA fault contact in the "rearming" circuit makes local manual
resetting obligatory.
If closing is permanent (relay or selector switch), do not connect terminal 2
to avoid hunting.
Diagram
Description
The electrical control is attached to the front of the breaker without removing
the cover. It enables the opening and closing of the circuit breaker by either
remote or local control.
Energy accumulation type: a universal motor "arms" a spring in which the
potential energy needed for its closing is stored.
Local control via a push-button.
Indicator showing:
- red: "closed" or "open" due to a fault or voltmetric release (electrical control
not reset)
- green: "open" and "reset".
Wiring connection by means of connecting terminals.
Locking in "open" position:
- using three Ø 8 padlocks (not supplied)
- using Ronis locks (supplied), type 1104, opening to the right.
BPA
installation of a
fault contact
(local reset
obligatory)
BPM
BP
2
1
LD
3
1 3
GN
1 3
*do not connect 2
EF
OG
BN
FC
M
RD
GNYE
5
4
4
96
95
Characteristics
R
Nominal voltage:
- alternating current 50/60 Hz: 24 - 48 - 110/127 - 220/240 - 380/415 V
- direct current: 24 - 48 - 110/125 - 220/250 V
Operating voltage: 0.85 to 1.1 Un.
Apparent consumption:
- alternating current: (average) 250 VA/(max.) 650 VA
- direct current: (average)175 W/(max.) 600 W
Response time:
- opening: 2.5 s./ closing: 0.05 s.
• with pulse control:
- minimum interval between pulse of 1 second with opening
• maximum rate of operation: 2 cycles/mn
cycle
closing
rest
0
relay
control*
push-button control
selector
switch
control*
0.50
3.0
0.05
opening
rest
8.05
t (s)
1
2
3
4
5
R
LD
BA
BPA
: BN (brown)
: OG (orange)
: GN (green)
: RD (red)
: GNYE (green/yellow)
: resistance > 240V
: fault display
: Bell alarm
: "stop/reset"
push-button
98
BA
R
BPM
EF
M
FC
: "ON" push-button
: electrical closing
: motor
: Limit switch
: manual emergency
opening control
: connection terminals
: manual closing button
B
19
SPECTRA - Moulded case circuit breakers
Manual rotary control
Basic elements for all installations
Handle
Colour:
- grey as standard
- red for safety circuit breakers in accordance with the standard VDE 0113
Locking in the "open" position:
1 - the handle is fitted with a retractable flap giving access to three
→ 8 padlocks only when the unit is in the "open" position.
2 - lock is easily snapped into place, and locking and removal of the key are
only possible in the "open" position.
B
20
CACR display contacts (optional)
General
The rotary control is attached to the front of the circuit breaker
it is equally suited to the following applications:
- fixed
- withdrawable
or installed:
- direct on breaker
- behind a screwed-on panel or a hinged door.
Description
The handle precisely indicates the main contact positions:
- red: device "closed"
- white: device "tripped" by voltmetric release or "test" button
- green: device "open"
The rotary control guarantees opening or isolation function being clearly
visible (IEC 947-3):
the handle comes into the position facing the green indicator when the main
contacts are separated by a distance greater than 20 mm.
Locking off is not possible unless main contacts are fully open.
A seal is available providing enhanced protection in the event of direct
installation on a door.
Two max. NO/NC contacts.
These are integrated into the converters to indicate the opening and/or
pre-closing of the circuit breaker.
Basic converter
Can be fitted to the front of the circuit
breaker to transform the sideways
movement of the control handle into
a rotary movement.
The handle can be snap-on mounted
on the converter.
The handle can be removed in the
"tripped" position by a by-pass.
Locking converter for direct mounting through a door or
panel
Offers the same functions as the
basic converter, plus:
1 - locking, preventing opening of the
door or panel if the circuit breaker
is not "open".
2 - memorises the opening position
and preventing movement of the
handle if the door is open.
3 - by-pass allowing opening of the
door or panel with the circuit
breaker "closed".
SPECTRA - Moulded case circuit breakers
Types
Direct on unit
Direct through door or panel
(IP30)
Behind door or panel
(IP55)
B
21
Components
Grey or red
+
(lock: optional)
Handle
Grey or red
+
(lock: optional)
Grey or red
+
(lock: optional)
Basic converter
+
(1 or 2 CACR, optional)
Converter
Converter with lock
+
(1 or 2 CACR, optional)
Basic converter
+
(1 or 2 CACR, optional)
External operator
Door-mounted operator:
- prevents opening of the door if
the circuit breaker is not "open"
- memorises the opening position
- prevents handle movement with
door open.
Funnel (optional)
This part eliminates the
problem of tolerances and
facilitates the coupling
between the external operator
and the extension bar.
SPECTRA - Moulded case circuit breakers
Visible isolation circuit breakers
General
B
22
Spectra visible isolation circuit breakers can be used:
- in general low voltage protection of low voltage metering, high/low voltage
subscriber stations.
- wherever personnel safety implies the visually clear and physical
separation of the source from the loads.
They meet the standards: NF C 13-100 and NF C 15-100, and the decree of
14/11/1988.
They are constructed based on the standard withdrawable circuit breakers
and may be fitted with the auxiliaries and accessories intended for these
devices.
In additon the Spectra circuit breakers with visible isolation were designed to
enable:
- rapid removal,
- easy replacement without any risk of contact with live parts,
- provision of reserve bases for future extensions.
Structure
Withdrawable and type V circuit breakers comprise a standard circuit
breaker(N, H or L) and a withdrawable unit.
The withdrawable unit comprises:
- a fixed three- or four-pole part equipped with front or rear connection
terminals,
- a moving part that fits onto the circuit breaker,
- a withdrawable safety device, that trips the circuit breaker as soon as
withdrawal starts,
- optional: isolation of the wiring of the internal electrical auxiliaries and the
control accessories.
Withdrawable circuit breakers (plug-in IEC 947-2 type)
For E 160 to E 630 circuit
breakers
- three sizes of plug-in units:
160 - 250 - 400/630,
- two positions:
- plugged in,
- removed.
- connection:
front or rear.
- level of protection:
- plugged in: IP3x
- removed: IP2x
Optional extras
- wiring isolation:
- one 8-contact block
(2 blocks max.).
Visible isolation circuit breakers, type V
(can be isolated according to IEC 947-2)
For E 160 to E 1250 circuit breakers
- four sizes of withdrawable units, type V:
160 - 250 - 400/630 - 800/1250
- two stable positions indicated by front-facing display:
- red: plugged in,
- green: withdrawn.
- connection:
front or rear.
- padlocking:
three → 8 padlocks(not supplied)
Optional extras
- wiring isolation:
one 8-contact block (2 blocks max.).
- locking in withdrawn position by:
Ronis 1104 lock, supplied with adapter kit
- status display contacts (2 contacts: NO + NC):
- plugged in,
- withdrawn.
SPECTRA - Moulded case circuit breakers
Notes
B
23
SPECTRA - Catalogue numbers
Rating plugs
Circuit breakers
B
24
In
160/32
Nº of EN
poles 35kA
3
4
160/63
3
4
160/100
3
4
160/160
3
4
250
3
4
EH
65kA
763032 763035
763083(1)
763042 763045
763084(1)
EL
100kA
763038
763048
763031 763034
763073(1)
763041 763044
763074(1)
763037
763013 763014
763063(1)
763016 763017
763064(1)
763015
763030 763033
763053(1)
763040 763043
763054(1)
764053 764031
764030(1)
764054 764041
764040(1)
763047
763018
763036
763046
764032
764042
80
100
PPP
PPPP
N 0% PPP
N 50% PPP
763081
763091
763093
-
763080
763090
763092
763094
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
PPP N 50%
763113
763123
763133
-
763112
763122
763132
763142
-
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
764115
764125
764135
-
764114
764124
764134
-
PPP
PPPP
N 0% PPP
N 50% PPP
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
400
3
4
765030 765031
765040 765041
765032
765042
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
630
3
4
766030 766031
766040 766041
766032
766042
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
800
3
4
767030 767031
767040 767041
-
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
1250
3
4
768030 768031
768040 768041
-
PPP
PPPP
N 0% PPP
N 50% PPP
PPP N 0%
(1) Connection by non-isolated copper bars.
25
32
763117
763127
763137
-
763116
763126
763136
-
50
63
763115
763125
763135
-
763114
763124
763134
763144
763154
SPECTRA - Catalogue numbers
Circuit breaker features: page B.6
Rating plug features: page B.5
Auxiliary features: page B.11
Dimensions: page B.48
Connections: page B.68
125
160
200
250
763111
763121
763131
763141
763151
-
763110
763120
763130
763140
763150
763160
764113
764123
764133
-
320
400
500
630
764112
764122
764132
764152
764111
764121
764131
764141
764151
764110
764120
764130
764140
764150
765114
765124
765134
-
765113
765123
765133
-
765112
765122
765132
765152
765111
765121
765131
765141
765151
765110
765120
765130
765140
765150
766114
766124
766134
-
766113
766123
766133
767114
767124
767134
-
800
766112
766122
766132
766152
766111
766121
766131
766141
766151
766110
766120
766130
766140
766150
767113
767123
767133
-
767112
767122
767132
-
767111
767121
767131
767141
767151
767110
767120
767130
767140
767150
768113
768123
768133
768153
768112
768122
768132
768152
B
1000
1250
768111
768121
768131
768141
768151
768110
768120
768130
768140
768150
25
SPECTRA - E160 to E1250
EM "motor protection" circuit breakers
MIR - Personnel protection
(including rating plug)
(ST supplied)
3P
4P
763026
-
EM 32
763023
-
EM 63
B
763003
763004
EM 160
26
764003
764004
EM 250
765003
765004
EM 400
766003
766004
EM 630
767003
767004
EM 800
768003
768004
EM 1250
E 160
769323
769324
MIR E 160 3P
MIR E 160 4P
E 250
769423
769424
MIR E 250 3P
MIR E 250 4P
E 400/630
769524
769525
Circuit breaker features: page B.6
Auxiliary features: page B.11
Dimensions: page B.48
Connections: page B.68
MIR E 400/630 3P
MIR E 400/630 4P
SPECTRA - E160
Plug-in circuit breakers, front connections
Plug in circuit breakers - type V, front connections
Complete plug-in unit (without circuit breaker)
Complete plug in unit (without circuit breaker)
769333
769334
EDAV 3P E 160
EDAV 4P E 160
769353
EDVAV 3P E 160
769354
Plug in sub-assembly
(without circuit breaker)
a) moving part
769340
769341
PMED 3P E 160
PMED 4P E 160
EDVAV 4P E 160
Plug in sub-assembly
(without circuit
breaker)
a) moving part
769363
b) fixed part
PMEDV 3P E 160
769343
769344
PFEDAV 3P E 160
PFEDAV 4P E 160
769364
PMEDV 4P E 160
b) fixed part
Plug in circuit breaker, rear connections
769365
PFEDVAV 3P E 160
Complete plug in unit (without circuit breaker)
769366
PFEDVAV 4P E 160
769336
769337
EDAR 3P E 160
EDAR 4P E 160
Removable circuit breakers - type V,
rear connections
Complete plug in unit (without circuit breaker)
Plug-in sub-assembly
(without circuit breaker)
a) moving part
769340
769341
769356
EDVAR 3P E 160
PMED 3P E 160
PMED 4P E 160
769357
EDVAR 4P E 160
b) fixed part
769346
769347
PFEDAR 3P E 160
PFEDAR 4P E 160
Plug in sub-assembly
(without circuit breaker)
a) moving part
769363
Wiring isolation
8-contact block (2 blocks max.).
769085
SECT FIL E 160
PMEDV 3P E 160
769364
PMEDV 4P E 160
b) fixed part
769367
PFEDVAR 3P E 160
769368
PFEDVAR 4P E 160
Wiring isolation 8-contact block (2 blocks max.).
769085
SECT FIL E 160
"Plugged in - removed" display contacts
769298
Dimensions: page B.48
Connections: page B.68
E 160 (2 blocks)
Locking off with Ronis 1104 lock
769309
VERED E 160
B
27
SPECTRA - E160
Electrical auxiliaries
Electrical controls
AS auxiliary contacts
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
B
769070
769071
1 NO/NC
2 NO/NC
28
BA bell alarm
769311
769312
769313
769314
24 V
48 V
110/125 V
220/250 V
AC 50, 60 Hz
769316
769317
769318
769319
769315
24V
48V
110/127V
220/240V
380/415 V
Sandard contacts
769068
1 NO/NC
Locking off in "OFF" position with Ronis 1104 lock
opening to the right (supplied)
Low level contacts
769078
1 NO/NC
ST voltmetric shunt release
AC 50, 60 Hz - DC
769001
769002
769003
769004
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay AC 50 Hz
769054
220 V
Auxiliary features page B.15
769350
VERCE E160
SPECTRA - E160
Rotary controls
Accessories for rotary controls
Direct on the unit
Lock Ronis 1104
769300
769301
Handle
CRDG grey
CRDR red
769080
Opening to the right
Funnel
769090
B
29
Direct through a door or panel
769302
769303
Handle
CRAPG grey
CRAPR red
Display switches
769299
CACR E 160/250
12
14
11
Door joint
769308
Behind door or panel
769384
769385
Handle
CRDPG grey
CRDPR red
E 160/250
Replacement part for rotary control for
direct installation through door or panel.
SPECTRA - E160
Safety accessories
Seals for control settings
769310
PLREG 3/4P E160
B
30
Sealable terminal covers
769377
769378
1 SET
3P E160
4P E160
1 set includes 2 pieces
(up- and downline)
Padlocking the control handle in the "OFF" position
769306
VER MAN E160
Connections
Box type terminals for bare cable
769371
769372
1 SET *
3RCFAV E160
4RCFAV E160
* replacement part
Rear connections for bar or cable with crimp lug
+ and terminal covers
769375
769376
1 SET
3RBFAR + CB E160
4RBFAR + CB E160
Extender
769451
1 set of 4 pieces
SPECTRA - E250
Plug in circuit breakers, front connections
Plug in circuit breakers- type V, front connections
complete withdrawable unit (without circuit breaker)
Complete withdrawable unit (without circuit breaker)
769433
769434
EDAV 3P E250
EDAV 4P E250
769449
EDVAV 3P E250
769450
EDVAV 4P E250
Withdrawable sub-assembly
(without circuit breaker)
Withdrawable subassembly (without circuit
breaker)
a) moving part
a) moving part
769456
769440
769441
PMED 3P E250
PMED 4P E250
b) fixed part
769443
769444
PMEDV 3P E250
769457
PMEDV 4P E250
b) fixed part
PFEDAV 3P E250
PFEDAV 4P E250
Withdrawable circuit breaker, front connections
Complete withdrawable unit (without circuit breaker)
769458
PFEDVAV 3P E250
769459
PFEDVAV 4P E250
Withdrawable circuit breakers - type V,
rear connections
Complete withdrawable unit (without circuit breaker)
769436
769437
EDAR 3P E250
EDAR 4P E250
769452
EDVAR 3P E250
769453
EDVAR 4P E250
Withdrawable sub-assembly
(without circuit breaker)
Withdrawable subassembly (without
circuit breaker)
a) moving part
a) moving part
769440
769441
PMED 3P E250
PMED 4P E250
PMEDV 3P E250
769457
b) fixed part
769446
769447
769456
PFEDAR 3P E250
PFEDAR 4P E250
PMEDV 4P E250
b) fixed part
769460
PFEDVAR 3P E250
769461
PFEDVAR 4P E250
Wiring isoloation
Wiring isolation
8-contact block (2 blocks max.).
8-contact block (2 blocks max.)
769085
SECT FIL E250
769085
SECT FIL E250
Display contacts "plugged in - removed"
769298
Dimensions: page B.49
Connections: page B.69
E250 (2 blocks)
Locking off using a Ronis 1104 lock
769309
VERED E250
B
31
SPECTRA - E250
Electrical auxiliaries
Electrical controls
AS auxiliary contacts
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
B
32
769070
769071
1 NO/NC
2 NO/NC
BA bell alarm
769311
769312
769313
769314
24 V
48 V
110/125 V
220/250 V
AC 50, 60 Hz
769316
769317
769318
769319
769315
24 V
48 V
110/127 V
220/240 V
380/415 V
Standard contact
769068
1 NO/NC
Low level contact
769078
1 NO/NC
Voltmetric ST shunt release
AC 50, 60 Hz - DC
769001
769002
769003
769004
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay unit AC 50 Hz
769054
220 V
Auxiliary features: page B.15
Dimensions: page B.49
Connections: page B.69
Locking of the electrical control in the "OFF" position
with a Ronis 1104 lock opening to the right (supplied)
769350
VERCE E250
SPECTRA - E250
Rotary controls
Accessories for rotary controls
Direct on the unit
Lock (Ronis 1104)
769300
769301
Handle
CRDG grey
CRDR red
769080
Funnel
769090
B
33
Direct through a door or panel
769302
769303
Handle
CRAPG grey
CRAPR red
Display contacts
769299
CACR E250
12
14
11
Door joint
769308
Behind door or panel
769384
769385
Handle
CRDPG grey
CRDPR red
Replacement part for rotary control
mounted direct through door or panel.
SPECTRA - E250
Safety accessories
Lead seals for control settings
769310
PLREG 3/4P E250
B
Sealable terminal covers
1 SET
34
769468
769469
3P E250
4P E250
One set includes 2 pieces
(up- and downline)
Padlocking the control handle in the "OFF" position
769306
VER MAN E250
Connections
Box type terminals for bare cables
769462
769463
1 SET*
3RCFAV E250
4RCFAV E250
* replacement for EH/EL 250
Rear connection for bar or cable with crimp lug + terminal
covers
769466
769467
1 SET
3RBFAR + CB E250
4RBFAR + CB E250
SPECTRA - E400
Withdrawable circuit breakers, front connections
Complete withdrawable unit (without circuit breaker)
Withdrawable circuit breakers-type V, front
connections
Complete withdrawable unit (without circuit breaker)
769533
EDAV 3P E400
769534
EDAV 4P E400
Withdrawable sub-assembly
(without circuit breaker)
769553
EDVAV 3P E400
769554
EDVAV 4P E400
a) moving part
769540
PMED 3P E400
769541
PMED 4P E400
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
b) fixed part
769543
PFEDAV 3P E400
769544
PFEDAV 4P E400
769563
PMEDV 3P E400
769564
PMEDV 4P E400
b) fixed part
Withdrawable circuit breakers, rear connections
Complete withdrawable unit (without circuit breaker)
769536
EDAR 3P E400
769537
EDAR 4P E400
Withdrawable sub-assembly
(without circuit breaker)
a) moving part
769565
PFEDVAV 3P E400
769566
PFEDVAV 4P E400
Withdrawable circuit breakers - type V,
rear connections
Complete withdrawable unit (without circuit breaker)
769556
EDVAR 3P E400
769540
PMED 3P E400
769541
PMED 4P E400
769557
EDVAR 4P E400
b) fixed part
769546
PFEDAR 3P E400
769547
PFEDAR 4P E400
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
769563
Wiring isolation
PMEDV 3P E400
8-contact block (2 blocks max.).
769085
SECT FIL E400
769564
PMEDV 4P E400
b) fixed part
769567
PFEDVAR 3P E400
769568
PFEDVAR 4P E400
Wiring isolation
8-contact block (2 blocks max.)
769085
SECT FIL E400
Display contacts: "plugged in - removed"
769298
Dimensions: page B.50
Connections: page B.70
(2 blocks)
Locking off with a Ronis 1104 lock
769509
VERED E400
B
35
SPECTRA - E400
Electrical auxiliaries
Electrical controls
AS auxiliary switches
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
B
36
769070
769071
1 NO/NC
2 NO/NC
BA bell alarm
Standard contact
769068
AC 50, 60 Hz
769511
769512
769513
769514
769515
769516
1 NO/NC
ST voltmetric shunt release
AC 50, 60 Hz - DC
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay unit AC 50 Hz
769054
24 V
48 V
110/127 V
220/250 V
380 V
415 V
Locking off the electrical control in the "OFF" position
using Ronis 1104 lock opening to the right (supplied)
769521
769001
769002
769003
769004
24 V
48 V
110 V
220 V
1 NO/NC
Low level contact
769078
769517
769518
769519
769520
220 V
Auxiliary characteristics: page B.15
VERCE E400
SPECTRA - E400
Rotary controls
Accessories for rotary controls
Direct on the unit
Lock (Ronis 1104)
769500
769501
Handle
CRDG grey
CRDR red
769080
Funnel
B
769090
37
Direct through door or panel
769502
769503
Handle
CRAPG grey
CRAPR red
Display contacts
769499
CACR E400
12
14
11
Door joint
769508
Behind door or panel
769584
769585
Handle
CRDPG grey
CRDPR red
Replacement part for rotary control
mounted direct through door or panel.
Connections
Box type terminals for bare cables
769571
769572
3RCFAV E400
4RCFAV E400
Safety accessories
Lead seals for settings controls
769510
Rear connection for bar or cables with crimp lug
+ terminal covers
PLREG 3/4P E400
769575
769576
Padlocking the control arm in
the "OFF" position
Extension arms for bar or cable with crimp lug
769506
VER MAN E400
1 SET
3RBFAR + CB E400
4RBFAR + CB E400
769573
769574
1 SET
3RPBFAV E400
4RPBFAV E400
One set includes 3 or 4 pieces
(up- or downline)
SPECTRA - E630
Withdrawable circuit breakers, front connections
Withdrawable circuit breakers-type V, front connections
Complete withdrawable unit (without circuit breaker)
Complete withdrawable unit (without circuit breaker)
769533
769534
EDAV 3P E630
EDAV 4P E630
Withdrawable sub-assembly
(without circuit breaker)
B
38
a) moving part
769540
769541
PMED 3P E630
PMED 4P E630
769553
EDVAV 3P E630
769554
EDVAV 4P E630
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
b) fixed part
769563
769543
769544
PFEDAV 3P E630
PFEDAV 4P E630
PMEDV 3P E630
769564
PMEDV 4P E630
b) fixed part
Withdrawable circuit breakers, rear connections
Complete withdrawable unit (without circuit breaker)
769536
769537
EDAR 3P E630
EDAR 4P E630
Withdrawable sub-assembly
(without circuit breaker)
a) moving part
769540
769541
PMED 3P E630
PMED 4P E630
PFEDVAV 3P E630
769566
PFEDVAV 4P E630
Withdrawable circuit breakers - type V,
rear connections
Complete withdrawable unit (without circuit breaker)
769556
EDVAR 3P E630
769557
b) fixed part
769546
769547
769565
PFEDAR 3P E630
PFEDAR 4P E630
EDVAR 4P E630
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
Wiring isolation
8-contact block (2 blocks max.)
769085
SECT FIL E630
769563
769564
PMEDV 3P E630
PMEDV 4P E630
b) fixed part
769567
769568
PFEDVAR 3P E630
PFEDVAR 4P E630
Wiring isolation
8-contact block (2 blocks max.)
769085
SECT FIL E630
Display contacts: "plugged in - removed"
769298
Dimensions: page B.50
Connections: page B.71
(2 blocks)
Locking off with the Ronis 1104 lock
769509
VERED E630
SPECTRA - E630
Electrical auxiliaries
Electrical controls
AS auxiliary switches
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
769070
769071
1 NO/NC
2 NO/NC
BA bell alarm
Standard contact
769068
AC 50, 60 Hz
769511
769512
769513
769514
769515
769516
1 NO/NC
ST voltmetric shunt release
AC 50, 60 Hz - DC
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay unit AC 50 Hz
769054
24 V
48 V
110/127 V
220/250 V
380 V
415 V
Locking off the electrical control in the
"OFF" position with a Ronis lock (supplied)
769521
769001
769002
769003
769004
24 V
48 V
110 V
220 V
1 NO/NC
Low level contact
769078
769517
769518
769519
769520
220 V
Auxiliary characteristics: page B.15
VERCE E630
B
39
SPECTRA - E630
Rotary controls
Rotary controls accessories
Direct on the unit
Lock (Ronis 1104)
769500
769501
Handle
CRDG grey
CRDR red
769080
Funnel
B
769090
40
Direct through door or panel
769502
769503
Handle
CRAPG grey
CRAPR red
Display contacts
769499
CACR E630
12
14
11
Door joint
769508
Behind door or panel
769584
769585
Handle
CRDPG grey
CRDPR red
Replacement part for rotary control
mounted direct through door or panel.
Connections
Box type terminals for bare cables
769571
769572
1 SET
3RCFAV E630
4RCFAV E630
Safety accessories
Lead seals for control settings
769510
Rear connection bar or cable with crimp lug
+ terminal covers
PLREG 3/4P E630
769575
769576
1 SET
3RBFAR + CB E630
4RBFAR + CB E630
Locking off the control handle in the "OFF" position
769506
VER MAN E630
Extension arms for bar or cable with crimp lug
769573
769574
1 SET
3RPBFAV E630
4RPBFAV E630
One set includes 3 or 4 pieces
(up- or downline)
SPECTRA - E800
Withdrawable circuit breakers - type V,
front connections
Withdrawable circuit breakers - type V,
rear connections
Complete withdrawable unit (without circuit breaker)
Complete withdrawable unit (without circuit breaker)
769733
769736
EDVAV 3P E800
EDVAR 3P E800
769734
769737
EDVAV 4P E800
EDVAR 4P E800
Withdrawable
sub-assembly (without
circuit breaker)
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
a) moving part
769740
769740
PMEDV 3P E800
PMEDV 3P E800
769741
769741
PMEDV 4P E800
PMEDV 4P E800
b) fixed part
b) fixed part
769743
769744
PFEDVAV 3P E800
PFEDVAV 4P E800
769746
769747
B
PFEDVAR 3P E800
PFEDVAR 4P E800
Wiring isolation
Wiring isolation
8-contact block (2 blocks max.)
8-contact block (2 blocks max.)
769085
SECT FIL E800
Display contacts: "plugged in - removed"
769698
(2 blocks)
Locking off with a Ronis 1104 lock
769509
VERED E800
Dimensions: page B.56
Connections: page B.72
769085
SECT FIL E800
Display contacts: "plugged in - removed"
769698
(2 blocks)
Locking off with a Ronis 1104 lock
769509
VERED E800
41
SPECTRA - E800
Electrical auxiliaries
Electrical controls
AS auxiliary switches
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
B
42
769070
769071
1 NO/NC
2 NO/NC
BA bell alarm
Standard contact
769068
AC 50, 60 Hz
769711
769712
769713
769714
769715
769716
1 NO/NC
ST voltmetric shunt release
AC 50, 60 Hz - DC
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay unit AC 50 Hz
769054
24 V
48 V
110/127 V
220/250 V
380 V
415 V
Locking off of the electrical control
in the "OFF" position using Ronis lock (supplied)
769521
769001
769002
769003
769004
24 V
48 V
110 V
220 V
1 NO/NC
Low level contact
769078
769717
769718
769719
769720
220 V
Auxiliary characteristics: page B.15
VERCE E800
SPECTRA - E800
Rotary controls
Accessories for rotary controls
Direct on the unit
Lock (Ronis 1104)
769700
769701
Handle
CRDG grey
CRDR red
769080
Funnel
B
769090
43
Direct through door or panel
769702
769703
Handle
CRAPG grey
CRAPR red
Display contacts
769499
CACR E800
12
14
11
Door joint
769708
Behind door or panel
769784
769785
Handle
CRDPG grey
CRDPR red
Replacement part for rotary control
mounted direct through door or panel.
Connections
Box type terminals for bare cables
769771
769772
1 SET
3RCFAV E800
4RCFAV E800
Safety accessories
Lead seals for controls settings
769510
Rear connection for bar or cable with crimp lug
+ terminal covers
PLREG 3/4P E800
769728
769729
1 SET
3RBFAR + CB E800
4RBFAR + CB E800
Padlocking the control handle in the "OFF" position
769706
Extension arms for bar or cable with crimp lug
VER MAN E800
769724
769725
1 SET
3RPBFAV E800
4RPBFAV E800
One set includes 3 or 4 pieces
(up- or downline)
SPECTRA - E1250
B
44
Withdrawable circuit breakers - type V,
front connections
Withdrawable circuit breakers - type V,
rear connections
Complete withdrawable unit (without circuit breaker)
Complete withdrawable unit (without circuit breaker)
769733
769736
EDVAV 3P E1250
EDVAR 3P E1250
769734
769737
EDVAV 4P E1250
EDVAR 4P E1250
Withdrawable
sub-assembly
(without circuit breaker)
Withdrawable
sub-assembly
(without circuit breaker)
a) moving part
a) moving part
769740
769740
PMEDV 3P E1250
PMEDV 3P E1250
769741
769741
PMEDV 4P E1250
PMEDV 4P E1250
b) fixed part
b) fixed part
769743
769744
PFEDVAV 3P E1250
PFEDVAV 4P E1250
769746
769747
PFEDVAR 3P E1250
PFEDVAR 4P E1250
Wiring isolation
Wiring isolation
8-contact block (2 blocks max.)
8-contact block (2 blocks max.)
769085
SECT FIL E1250
Contacts of signalisation
769698
(2 blocks)
Locking with Ronis 1104 lock
769509
VERED E1250
Dimensions: page B.56
Connections: page B.73
769085
SECT FIL E1250
Contacts of signalisation
769698
(2 blocks)
Locking with Ronis 1104 lock
769509
VERED E1250
SPECTRA - E1250
Electrical auxiliaries
Electrical controls
AS auxiliary switches
DC
Standard contacts
769060
769061
1 NO/NC
2 NO/NC
Low level contacts
769070
769071
1 NO/NC
2 NO/NC
BA bell alarm
Standard contact
769068
AC 50, 60 Hz
769711
769712
769713
769714
769715
769716
1 NO/NC
ST voltmetric shunt release
AC 50, 60 Hz - DC
24 V
48 V
110/127 V
220/250 V
AC 50, 60 Hz
769005
380/415 V
UV undervoltage release
AC 50, 60 Hz - DC
769031
769032
769033
769034
24 V
48 V
110/127 V
220/250 V
UV + time delay unit AC 50 Hz
769054
24 V
48 V
110/127 V
220/250 V
380 V
415 V
Locking off the electrical control in the
"OFF" position using a Ronis lock (supplied)
769521
769001
769002
769003
769004
24 V
48 V
110 V
220 V
1 NO/NC
Low level contact
769078
769717
769718
769719
769720
220 V
Auxiliary characteristics: page B.15
VERCE E1250
B
45
SPECTRA - E1250
Rotary controls
Accessories for rotary controls
Direct on the unit
Lock (Ronis 1104)
769700
769701
Handle
CRDG grey
CRDR red
769080
Funnel
769090
B
46
Direct through door or panel
769702
769703
Handle
CRAPG grey
CRAPR red
Display contacts
769499
CACR E1250
12
14
11
Door joint
769708
Behind door or panel
769784
769785
Handle
CRDPG grey
CRDPR red
Replacement part for rotary control
mounted direct through door or panel.
Connections
Box type terminals for bare cable
769871
769872
Safety accessories
Lead seals for control settings
Rear connections for bar or cable with crimp lug
+ terminal covers
769510
PLREG 3/4P E1250
1 SET
3RCFAV E1250
4RCFAV E1250
769728
769729
1 SET
3RBFAR + CB E1250
4RBFAR + CB E1250
Locking off the control handle in the "OFF" position
Extension arms for bar or cable with crimp lug
769706
VER MAN E1250
769724
769725
1 SET
3RPBFAV E1250
4RPBFAV E1250
One set includes 3 or 4 pieces
(up- or downline)
SPECTRA - Earth leakage protection
Residual current earth leakage devices
SHR 1100 - SHR 1110
MTS earth leakage protection unit with separate
core
B
47
SHR 1100 (instantaneous)
797070
797071
797072
24-48V AC
110-480V AC
220/415V AC
SHR 1110 (time delayed)
797073
797074
797075
24-48V AC
110-480V AC
220/415V AC
Installation kit
797106
Detection cores
Closed core CITF
797060
CITF Ø 35
797061
CITF Ø 80
797062
CITF Ø 110
797063
CITF Ø 140
797064
CITF Ø 210
Open core CITO
797065
797066
CITO Ø 65
CITO Ø 104
Characteristics: pages B.13-14
Connecting diagram: pages B.13-14
Dimensions: page B.144
220/240V
380/415V
742010
742011
742012
742013
742110
742111
742112
742113
Inner core diameter
34Ø
55Ø
70Ø
100Ø
SPECTRA - Overall dimensions
Circuit breakers E160
3 poles
4 poles
B
48
Circuit breakers E160 + MIR
3 poles
fixation points
connection centres
4 poles
SPECTRA - Overall dimensions
Circuit breakers E250
3 poles
4 poles
B
49
Circuit breakers E250 + MIR
3 poles
fixation points
connection centres
4 poles
SPECTRA - Overall dimensions
Circuit breakers E400/630
3 poles
4 poles
B
50
Circuit breakers E400/630 + MIR
3 poles
A
4 poles
B
C
D
E
front connections 346
482.5
63.5
74.5
83
rear connections 267
403.5
24
35
43.5
fixation points
connection centres
SPECTRA - Overall dimensions
Circuit breakers E800/1250 (front connections)
3 poles
4 poles
B
51
Circuit breakers E800/1250 (rear connections)
3 poles
fixation points
connection centres
4 poles
SPECTRA - Overall dimensions
Three-pole plug-in circuit breakers E160 to E630,
front connections.
B
52
A
A1
B
C
C1
D
E
G
H
J
J1
J2
K
E 160
28.75
28.75
360.5
37.5
37.5
66.75
116.25
7
6
81
126.5
138
150
Drilling diagrams: see B.73
fixation points for fixed part
E 250
31.5
26
399
51
48
85.75
135.5
7
6
97
144
157
169
E 400/630
510
60
60
104.5
172.5
5
97
180
202
222
M
N
P
P1
P2
R
S
T
V
W
X
Y
E 160
66
23.5
29.6
72.3
38.15
32
35
70
35
105
105
112
E 250
66
23.5
29.6
72.3
40.15
32
35
70
35
105
105
112
E 400/630
108
18.5
46
96.8
48.9
43
57.5
115
46
140
150
158
SPECTRA - Overall dimensions
Four-pole plug-in circuit breakers E160 to E630,
front connections.
B
53
A
A1
B
C
C1
D
E
G
H
J
J1
J2
K
E 160
28.75
28.75
360.5
37.5
37.5
66.75
116.25
7
6
81
126.5
138
150
Drilling diagrams: see B.73
fixation points for fixed part
E 250
31.5
26
399
51
48
85.75
135.5
7
6
97
144
157
169
E 400/630
510
60
60
104.5
172.5
5
97
180
202
222
M
N
P
P1
P2
R
S
T
V
W
X
Y
E 160
66
23.5
29.6
72.3
38.15
32
35
105
35
140
140
147
E 250
66
23.5
29.6
72.3
40.15
32
35
105
35
140
140
147
E 400/630
108
18.5
46
96.8
48.9
43
57
160
46
186
196
204
SPECTRA - Overall dimensions
Three-pole plug-in circuit breakers E160 to E630,
rear connections.
B
54
A
A1
B
C
C1
D
E
F
G
H
J
J1
J2
E 160
28.75
28.75
43
37.5
37.5
66.75
219.5
203.5
7
6
81
126.5
138
Drilling diagrams: see B.73
fixation points for fixed part
E 250
31.5
26
43
51
48
85.75
257.5
241.5
7
6
97
144
157
E 400/630
43
60
60
104.5
295
324
5
97
180
202
K
M
N
P
P1
P2
R
S
T
V
W
X
Y
E 160
150
82
15
29.6
72.3
38.15
32
35
70
35
105
105
112
E 250
169
82
15
29.6
72.3
40.15
32
35
70
35
105
105
112
E 400/630
222
77
10
46
96.8
48.9
43
57.5
115
46
140
150
158
SPECTRA - Overall dimensions
Four-pole plug-in circuit breakers E160 to E630,
rear connections.
B
55
A
A1
B
C
C1
D
E
F
G
H
J
J1
J2
E 160
28.75
28.75
43
37.5
37.5
66.75
219.5
203.5
7
6
81
126.5
138
Drilling diagrams: see B.73
fixation points for fixed part
E 250
31.5
26
43
51
48
85.75
257.5
241.5
7
6
97
144
157
E 400/630
43
60
60
104.5
295
324
5
97
180
202
K
M
N
P
P1
P2
R
S
T
V
W
X
Y
E 160
150
82
15
29.6
72.3
38.15
32
35
105
35
140
140
147
E 250
169
82
15
29.6
72.3
40.15
32
35
105
35
140
140
147
E 400/630
222
77
10
46
96.8
48.9
43
57
160
46
186
196
204
SPECTRA - Overall dimensions
Three-pole withdrawable type V circuit breakers E160 to E1250,
front connections.
B
56
A
A1
B
C
C1
D
E
G
H
J
J1
J2
K
K1
E 160
28.75
28.75
360.5
37.5
37.5
66.75
116.25
7
6
81
126.5
138
150
178
E 250
31.5
26
399
51
48
85.75
135.5
7
6
97
144
157
169
197
Drilling diagrams: see B.73
fixation points for fixed part
E 400/630
510
60
60
104.5
172.5
5
97
180
202
222
250
E 800/1250
674
80
80
147.5
225.5
5
140
268
285
395
425
L
M
N
P
P1
P2
R
S
T
U
V
W
X
Y
E 160
350
66
23.5
29.6
72.3
38.15
32
35
70
17
35
105
132
182
E 250
350
66
23.5
29.6
72.3
40.15
32
35
70
17
35
105
132
182
E 400/630
445
108
18.5
46
96.8
48.9
43
57.5
115
15.5
46
140
172
225
E 800/1250
520
166
18.5
84.5
158
63.8
58.5
90
180
15
70
210
252
310
SPECTRA - Overall dimensions
Four-pole withdrawable type V circuit breakers E160 to E1250,
front connections.
B
57
A
A1
B
C
C1
D
E
G
H
J
J1
J2
K
K1
E 160
28.75
28.75
360.5
37.5
37.5
66.75
116.25
7
6
81
126.5
138
150
178
E 250
31.5
26
399
51
48
85.75
135.5
7
6
97
144
157
169
197
Drilling diagrams: see B.73
fixation points for fixed part
E 400/630
510
60
60
104.5
172.5
5
97
180
202
222
250
E 800/1250
674
80
80
147.5
225.5
5
140
268
285
395
425
L
M
N
P
P1
P2
R
S
T
U
V
W
X
Y
E 160
350
66
23.5
29.6
72.3
38.15
32
35
105
17
35
140
167
217
E 250
350
66
23.5
29.6
72.3
40.15
32
35
105
17
35
140
167
217
E 400/630
445
108
18.5
46
96.8
48.9
43
57
160
15.5
46
186
218
270
E 800/1250
520
166
18.5
84.5
158
63.8
58.5
90
250
15
70
280
322
380
SPECTRA - Overall dimensions
Three-pole withdrawable type V circuit breakers E160 to E1250,
rear connections.
B
58
A
A1
B
C
C1
D
E
F
G
H
J
J1
J2
K
K1
E 160
28.75
28.75
43
37.5
37.5
66.75
219.5
203.5
7
6
81
126.5
138
150
178
E 250
31.5
26
43
51
48
85.75
257.5
241.5
7
6
97
144
157
169
197
Drilling diagrams: see B.73
fixation points for fixed part
E 400/630
43
60
60
104.5
295
324
5
97
180
202
222
250
E 800/1250
50
80
80
147.5
395
394
5
140
268
285
395
425
L
M
N
P
P1
P2
R
S
T
U
V
W
X
Y
E 160
350
82
15
29.6
72.3
38.15
32
35
70
17
35
105
132
182
E 250
350
82
15
29.6
72.3
40.15
32
35
70
17
35
105
132
182
E 400/630
445
77
10
46
96.8
48.9
43
57.5
115
15.5
46
140
172
225
E 800/1250
520
154.5
19.5
84.5
158
63.8
58.5
90
180
15
70
210
252
310
SPECTRA - Overall dimensions
Four-pole withdrawable type V circuit breakers E160 to E1250,
rear connections.
B
59
A
A1
B
C
C1
D
E
F
G
H
J
J1
J2
K
K1
E 160
28.75
28.75
43
37.5
37.5
66.75
219.5
203.5
7
6
81
126.5
138
150
178
E 250
31.5
26
43
51
48
85.75
257.5
241.5
7
6
97
144
157
169
197
Drilling diagrams: see B.73
fixation points for fixed part
E 400/630
43
60
60
104.5
295
324
5
97
180
202
222
250
E 800/1250
50
80
80
147.5
395
394
5
140
268
285
395
425
L
M
N
P
P1
P2
R
S
T
U
V
W
X
Y
E 160
350
82
15
29.6
72.3
38.15
32
35
105
17
35
140
167
217
E 250
350
82
15
29.6
72.3
40.15
32
35
105
17
35
140
167
217
E 400/630
445
77
10
46
96.8
48.9
43
57
160
15.5
46
186
218
270
E 800/1250
520
154.5
19.5
84.5
158
63.8
58.5
90
250
15
70
280
322
380
SPECTRA - Overall dimensions
Electrical controls for circuit breakers E160 and E250
3 poles
81 E160
97 E250
105
37
35
23
17.5
circuit breaker
plug-in device
122
23.5 E160
12.5 E250
1
B
4 poles
105
126.5 E160
144 E250
35
1
17.5
122
12.5
60
fixation points for fixed part
fixation points
120.3 E160
121.3 E250
SPECTRA - Overall dimensions
Electrical controls for circuit breakers E400 to E1250
3 poles
RONIS
OPTIONAL
B
61
4 poles
(CIRCUIT BREAKER)
(WITHDRAWABLE)
A
B
C
D
E
F
G
H
L
M
N
P
E 400/630
97
180
163.5
41
32
12.5
47
140
157
31.2
7.3
13
E 800/1250
140 (1)
268
181.5
67.5
32
15
70
210
222
18
83
15
(1) PAR circuit breaker: 3P: 182 mm
4P: 184.5 mm
fixation points for fixed part
fixation points
SPECTRA - Overall dimensions
Rotary controls for circuit breakers E160 to E1250,
direct on unit
3 poles
RONIS
OPTIONAL
B
62
4 poles
(CIRCUIT BREAKER)
(WITHDRAWABLE)
A
B
C
D
E
F
G
H (3P)
E 160
81
126.5
29
79
40
55
31
48.5
E 250
97
144
29
79
40
55
31
48.5
(1) PAR circuit breaker: 3P: 182 mm
4P: 184.5 mm
fixation points for fixed part
fixation points
E 400/630
97
180
54.5
132
32
100
59
93.5
E 800/1250
140 (1)
268
54.5
132
32
100
72
127
H (4P)
J
K
L
M
N
P
E 160
48.5
104.5
65.5
31.9
7.4
27
92.8
E 250
48.5
104.5
65.5
31.9
18.4
27
92.8
E 400/630
93
139
105.5
42.5
4
31
135.5
E 800/1250
127
209
141.5
134.2
33.2
46
188.5
SPECTRA - Overall dimensions
Rotary controls for E160 to E1250,
direct through door or panel.
3 poles
4 poles
B
63
(CIRCUIT BREAKER)
(WITHDRAWABLE)
RONIS
OPTIONAL
Drilling diagram
3 poles
4 poles
fixation points for fixed part
fixation points
A
B
C
D
E
F
G
H (3P)
H (4P)
J
K
L
M
E160
81
126.5
22.5
57
40
55
31
48.5
48.5
146
86.5
31.9
7.4
E250
97
144
24.5
57
40
55
31
48.5
48.5
146
86.5
31.9
18.4
E400/630
97
180
53
84
32
100
59
93,5
93
181
126.5
42.5
4
E800/1250
140 (1)
268
50
84
32
100
72
127
127
251
162.5
134.2
33.2
(1) Circuit breaker with rear horizontal terminal: 3P: 182 mm
4P: 184.5 mm
N
P
R
S
T
U
V (3P)
V (4P)
W
X
Y
Z
E160
52.3
143
100
26.6
51.1
17.5
35
35
55.5
55.5
8
63.5
E250
52.3
143
100
37.6
51.1
17.5
35
35
55.5
55.5
8
63.5
E400/630
56.3
186
100
40.7
79.2
23
57.5
57
73.5
79.5
2
85
E800/1250
71.3
239
140
81.4
182.4
35
90
90
108.5
108.5
8
111.5
SPECTRA - Overall dimensions
Rotary controls for fixed or withdrawable circuit breakers E160 to E1250,
behind door or panel.
3 poles
4 poles
89.5
89.5
59.25
59.25
F
F
Max.5
B
Min.80
G 30.25
G 30.25
64
89.5
89.5
E
E
24.5
B1 mini
A
B2 maxi
circuit breaker
4 poles
60°
Ø28.5
G
3xØ6
60°
60°
G
Ø28.5
3 poles
G
G
F
3xØ6
Ø39
Ø39
F
4 poles
G
G
F
F
A
B1
B2
C
D
E
F
G
E 160
81
90
350
67
40
55
31
7.4
4 poles
F
F
60°
3 poles
E 250
97
90
350
67
40
55
31
18.4
E 400/630
97
120
378
97
32
100
59
4
(1) Circuit breaker with rear horizontal terminal: 3P: 182 mm
4P: 184.5 mm
E 800/1250
140(1)
120
370
97
32
100
72
33.2
fixation points for fixed part
fixation points
D
Ronis
optional
Drilling diagram (installation at 90°)
3 poles
C
SPECTRA - Overall dimensions
Padlocking the control handle
Circuit breakers E160/250
B
65
A
Circuit breakers E400/630
Circuit breakers E800/1250
E 160
110
E 250
126
SPECTRA - Overall dimensions
Sealable terminal covers mounted on circuit breakers E160/250
3 poles
4 poles
B
66
A
C
D
E
F
H
E 160
124
90
90
320
8
86
E 250
124
118
123
381
10.5
103
fixation points
SPECTRA - Overall dimensions
Sealable terminal covers mounted on circuit breakers + MIR (E160/250)
3 poles
4 poles
B
67
A
B
C
D
E
F
H
E 160
124
132
90
90
452
8
86
E 250
124
132
118
106
496
10.5
103
fixation points
SPECTRA - Connections
Fixed circuit breakers E160
Plug-in circuit breakers E160
Tunnel terminals (series) for cables without lug
Screw CHC 27/64 : hex key # 5
≥ 10 mm2 17 N.m
Torque : ≤ 6mm2 4 N.m
Front connections (series) for bar or cable with crimp lug
Screw CHC M8-16 : hex key # 6
Torque : 10 N.m
Note : if power is on the downline it is possible to connect bars or cables
with lugs (consult us)
UPLINE
Connection
width: 20
thickness: 8.5 max.
0 min.
B
68
DOWNLINE
Rear connections (optional) for bar or cable with crimp lug
Nut H M6 : key 10
Screw CHC M5-10 : hex key # 4
Torque : 3 N.m
Torque : 6 N.m
Tunnel terminals (can be mounted) for cables without lug
Screw CHC 27/64 : hex key # 5
≥ 10 mm2 17 N.m
Torque : ≤ 6 mm2 4 N.m
UPLINE
Connection
width: 20
thickness: 10 max.
Terminal to be taken
from circuit breaker
DOWNLINE
Rear connections (series) for bar or cable with crimp lug
Screw H M10-20 : key 17
Torque : 28 N.m
Vertical position only.
Connection
width: 20
thickness: 8.5 max.
2 min.
SPECTRA - Connections
Fixed circuit breakers E250
Circuit breakers type EN
Front connections (series) for bar or cable with crimp lug
Screw CHC M8-16 : hex key # 6
Torque : 10 N.m
Connection
width: 20
thickness: 8.5 max.
0 min.
Circuit breakers type EH - EL - EM (2 possibilités)
1) Tunnel terminals (series) for connection up- or downline with cables
without lug
Screw CHC 5/8 : hex key # 8
≥ 35 mm2 31 N.m
Torque : ≤ 25 mm2 17 N.m
UPLINE
B
69
Tunnel terminals (optional) for cables without lug.
Screw CHC 5/8 : hex key # 8
≥ 35 mm2 31 N.m
Torque : ≤ 25 mm2 17 N.m
DOWNLINE
2) Tunnel terminals upline for cables without lug, and front connections
(remove terminals) for insulated bars or cables with insulated crimp lug.
Terminals : Screw CHC 5/8 : hex key # 8
≥ 35 mm2 31 N.m
Torque : ≤ 25 mm2 17 N.m
Sections : Screw CHC M8 + washer (not supplied) : hex key # 6
Torque : 10 N.m
Circuit breakers EN - EH - EL - EM
Rear connections (optional) for bar or cable with crimp lug
Nut H M8 : key 13
Screw CHC M6-16 : hex key # 5
Torque : 7 N.m
Torque : 10 N.m
Connection
width: 25
thickness: 10 max.
UPLINE
Range and connection capacity
identical to EN
DOWNLINE
SPECTRA - Connections
B
Plug-in circuit breakers E250
Fixed circuit breakers E400/630
Front connections (series) for bar or cable with crimp lug
Screw CHC M8-16 : hex key # 6
Torque : 10 N.m
Front connections (series) for bar or cable with crimp lug
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m
Connection
width: 25
thickness: 8.5 max.
0 min.
70
Connection
width: 32
thickness: 11.5 max.
1.5 min.
Rear connections (series) for bar or cable with crimp lug
Screw H M10-20 : key 17
Torque : 28 N.m
Rear connections (optional) for bar or cable with crimp lug
Nuts H M14 : key 22
Torque : 27 N.m
Screw CHC M10-25 : hex key # 8
Torque : 36 N.m
&
&
Connection
width: 25
thickness: 8.5 max.
2 min.
Connection
width: 40
thickness: 10 max.
3P : 2 x 76 mm + 1 x 124 mm
4P : 2 x 76 mm + 2 x 124 mm
Tunnel terminals (optional for EN and can be mounted for EH - EL - EM) for
cables without lug
Screw CHC 5/8 : hex key # 8
≥ 35 mm2 31 N.m
Torque : ≤ 25 mm2 17 N.m
For EH - EL - EM the
terminal to be taken from
the circuit breaker
SPECTRA - Connections
Fixed circuit breakers E400/630
Tunnel terminals (optional) for cables without lug
Screw CHC M10-20 : hex key # 8
≥ 70 mm2 42 N.m
Torque : ≤ 50 mm2 31 N.m
Tunnel terminals (optional) for cables without lug
Screw CHC 11/16 : hex key # 8
≥ 70 mm2 42 N.m
Torque : ≤ 50 mm2 31 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m
B
71
Screw and washer to
be taken from circuit
breaker
Front connection extension (optional) for bar or cable with crimp lug
Screw H M12 (not supplied) : key 19
Torque : 48 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m
Extensions for front connections (optional) for bar or cable with crimp lug
Screw H M12 x 25 : key 19
Torque : 40 N.m
Screw H M12 (not supplied)
Torque : 48 N.m
Connection
width: 40
thickness: 10
3P : 2 A + 1 B
4P : 2 A + 2 B
Plug-in circuit breakers E400/630, front connections
Connection
width: 40
thickness: 10
Front connections (series) for bar or cable with crimp lug
Screw H M12-25 : key 19
Torque : 40 N.m
Connection
width: 40
thickness: 13 max.
0 min.
3P : 2 A + 1 B
4P : 2 A + 2 B
SPECTRA - Connections
Plug-in circuit breakers E400/630, rear connections
Rear connections (series) for bar or cable with crimp lug
Screw H M12-25 : key 19
Screw CHC M5-16 : hex key # 4
Torque : 40 N.m
Torque : 6 N.m
Horizontal position
Vertical position
2) With extension for bar or cable with crimp lug
Screw CHC M12-30 : hex key # 10
Torque : 48 N.m
Screw H M12-40 : key 19
Torque : 48 N.m
B
72
Connection
width: 40
thickness: 13 max.
0 min.
Tunnel terminals (optional) for cables without lug
Screw CHC 11/16 : hex key # 8
≥ 70 mm2 42 N.m
Torque : ≤ 50 mm2 31 N.m
Screw CHC M12-25 : hex key # 10
Torque : 40 N.m
Rear connections in mandatory horizontal position
Screw and washer to be taken from circuit breaker
Connection
width: 50
thickness: 16 max.
0 min.
Tunnel terminals (option) for cables without lug
Screw CHC 3/4 : hex key # 10
Torque : 42 N.m
Screw CHC 12-45 : hex key # 10
Torque : 45 N.m
Fixed circuit breakers E 800/1250
Front connections (series) 2 installation options
1) Without extension for bars
Screw CHC M12-30 : hex key # 10
Torque : 48 N.m
Rear connections (optional) for bar or cable with crimp lug
Screw H M12-40 : key 19
Torque : 48 N.m
Screw CHC M10-30 : hex key # 8
Torque : 36 N.m
Vertical position only
Connection
width: 40
thickness: 13 max.
6 min.
Connection
width: 60
thickness: 16 max.
0 min.
SPECTRA - Connections
Plug-in circuit breakers E800/1250, front connections
Plug-in circuit breakers E 800/1250, rear connections
Front connections (series) for bar or cable with crimp lug
Screw H M12-50 : key 19
Torque : 48 N.m
Rear connections (series) for bar or cable with crimp lug
Screw H M12-45 : key 19
Torque : 48 N.m
Vertical position
B
73
Connection
width: 50
thickness: 20 max.
0 min.
Tunnel terminals (optional) for cables without lug.
Screw CHC 3/4 : hex key # 10
Torque : 42 N.m
Screw CHC M12-45 : hex key # 10
Torque : 45 N.m
Horizontal position
Connection
width: 50
thickness: 15 max.
0 min.
Tunnel terminals (optional) for cables without lug.
Screw CHC 3/4 : hex key # 10
Torque : 42 N.m
Screw H M12 (not supplied) : key 19
Torque : 48 N.m
Mandatory horizontal position
Screw H M12x60 nut supplied
SPECTRA - Drilling diagrams
Circuit breakers E160 with rear connections
Basic unit
3 poles
Circuit breakers E250 with rear connections
Basic unit
4 poles
3 poles
4 poles
B
74
Basic unit + MIR
Basic unit + MIR
3 poles
4 poles
3 poles
4 poles
SPECTRA - Drilling diagrams
Circuit breakers E400/630 with rear connections
Basic unit
3 poles
Circuit breakers E800/1250 with rear connections
Basic unit
4 poles
3 poles
B
75
Basic unit + MIR
3 poles
4 poles
4 poles
SPECTRA - Drilling diagrams
Withdrawable circuit breakers E160/1250 and type V, front or rear connections.
B
76
fixing points for fixed part of withdrawable unit
A
B
C
D
E
F
G
H
J
K
L
M
N
P
E 160
3 poles
102
70
16
169
35
75
12
12
35
48.5
48.5
60
7.5
5.7
4 poles
137
105
16
169
35
75
12
12
35
66
31
60
7.5
5.7
E 250
3 poles
102
70
16
206
35
99
20
17
35
48.5
48.5
62
20
5.7
4 poles
137
105
16
206
35
99
20
17
35
66
31
62
20
5.7
E 400/630
3 poles
144
115
14.5
254
45
120
22
22
57.5
48.5
48.5
60
30
5.7
4 poles
190
160
15
254
45
120
22
22
57
71.5
25.5
60
30
5.7
E 800/1250
3 poles
206
180
13
355
60
160
37.5
37.5
90
48.5
48.5
60
50
9
4 poles
276
250
13
355
60
160
37.5
37.5
90
83.5
13.5
60
50
9
SPECTRASPECTRA
- Drilling diagrams
- Weights
Weights(kg)
Basic unit
Fixed circuit breaker type EN
Fixed circuit breaker type EH
Fixed circuit breaker type EL
Fixed circuit breaker type EM
Rating plug
All ratings
MIR Differential unit
Internal electrical auxiliaries
AS auxiliary switch
BA Bell alarm
ST Voltmetric shunt release
UV Undervoltage release
Electrical controls
Locking of the electrical control
Rotary controls
Direct on the unit
Direct through door or panel
Behind door or panel
Safety accessories
Lead sealing for circuit breaker control settings
Sealable terminal covers
Connections
Box-type terminals for bare cable
Rear connections for bars or crimp lug cables
Extensions for bars or crimp lug cables
Complete plug-in unit (without circuit breaker)
Front connection plug-in unit
Rear- conection plug-in unit
Complete type V withdrawable unit (without circuit breaker)
Front connection withdrawable unit type V
Rear connection withdrawable unit type V
E 160
E 250
E 400/630
E 800/1250
3 poles 4 poles
3 poles 4 poles
3 poles 4 poles
3 poles 4 poles
2.280
2.320
2.370
2.370
2.990
3.030
3.080
3.080
3.230
3.270
3.320
3.320
4.280
4.320
4.370
4.370
6.090
6.130
6.180
6.180
8.290
8.330
8.380
8.380
21.390
21.430
21.480
21.480
28.250
28.290
28.340
28.340
0.033
1.410
0.033
1.510
0.033
1.540
0.033
1.630
0.033
3.230
0.033
3.320
0.033
-
0.033
-
0.122
0.122
0.103
0.102
1.690
0.012
0.122
0.122
0.103
0.102
1.690
0.012
0.122
0.122
0.103
0.102
1.690
0.012
0.122
0.122
0.103
0.102
1.690
0.012
0.122
0.122
0.103
0.102
4.300
0.012
0.122
0.122
0.103
0.102
4.300
0.012
0.122
0.122
0.103
0.102
7.500
0.012
0.122
0.122
0.103
0.102
7.500
0.012
0.261
0.283
0.904
0.261
0.283
0.904
0.261
0.283
0.904
0.261
0.283
0.904
0.850
1.000
1.500
0.850
1.000
1.500
1.950
2.200
2.650
1.950
2.200
2.650
0.017
0.370
0.017
0.370
0.017
0.476
0.017
0.476
0.017
-
0.017
-
0.017
-
0.017
-
0.062
0.132
-
0.076
0.170
-
0.132
0.280
-
0.168
0.380
1.145
0.540
1.150
1.571
0.710
1.630
1.413
0.985
3.250
1.875
1.324
4.630
2.380
2.210
3.030
2.860
2.500
2.390
3.240
3.080
9.110
8.350
11.450
10.750
-
-
3.830
3.900
4.590
4.450
4.030
3.930
4.860
4.570
11.470 14.180
10.000 12.750
32.000 39.000
29.660 36.800
B
77
SPECTRA - Drilling diagrams
Aantekeningen
B
78
Download