Tech Brief Circuit Breaker Trip Defeat Switch by Jim Bowen Powell Electrical Manufacturing Co. T out of the circuit and replaced with he circuit breaker trip defeat switch allows the owner to take the functional an indicating light and a dropping testing of the protective relay scheme and extend it all the way to the trip resistor. The dropping resistor is coil without opening the circuit breaker, thus confirming that the relay’s sized to make the circuit draw the output contacts will indeed pick up the lockout relays and that the lockout contacts will energize the trip coil of the circuit breaker. This action combined with a healthy coil monitor device or a healthy coil light tests the circuit CS HEALTHY 86-1 86-2 86-3 86-4 T to the final element without openR ing the circuit breaker. With the increased reliability of relaying and the pressure for extending the main95 ISW tenance intervals, more equipment 95 ISW 95 ISW NOR DEF DEF owners are asking for the capability to do final element functional testing on RES 52/a the circuit breakers feeding loads that they can not afford to de-energize TRIP TRIP SIMULATOR DEFEATED LT LT on a regular basis. As the failure rate LIGHT POSITION TC of relays goes down, the equipment owner would prefer to functionally 95 ISW 95 ISW check the protective relay scheme NOR DEF and setpoint yearly and then pull the relays for a full calibration check every second or third year. The circuit breaker trip defeat switch requires Circuit Breaker Trip Defeat Switch a two-position control switch (95 Switch Shown in the Normal Position device). Position one is the normal trip mode (see sketch). In this position the trip coil is in the circuit. The 95 ISW DEF second position is the trip defeated mode. In the trip defeated position the circuit breaker’s trip coil is cut ANNUNCIATOR WINDOW www.netaworld.org Winter 2006-2007 NETA WORLD same amount of current as the trip coil. Due to the critical nature of defeating the trip coil, a separate contact should be wired to the substation annunciator and to an amber light mounted in the front of the breaker panel to indicate when the breaker is in the trip defeated mode. With the switch in the trip defeated position, the technician can function the relays and trip lockouts to see that the lockout would have energized the trip coil by observing the indicating light. Once the testing is complete the technician confirms that the lockouts are reset and the trip light is de-energized. Then the circuit breaker trip defeat switch can be transferred back to the normal mode. Now for my note as a circuit breaker manufacturer, this scheme allows a much more comprehensive check of the protection system than we have done in the past, but don’t forget the circuit breaker. NETA WORLD Winter 2006-2007 Yes, we have tested the protective logic all the way to the trip coil, but the breaker has just gone another year without functioning and the grease, without exercise, hardens over time. Granted, in an air-conditioned substation, the interval between maintenance can be extended but not indefinitely. If we can help with this or any other topic please don’t hesitate to call. Jim Bowen graduated from Texas A&M University in 1976 with a BSEE. He has worked for SIP Engineering as a Power Engineer and for Exxon in all facets of electrical engineering in the petrochemical process. He held the position of regional engineer for Exxon Chemicals Europe for three years. In January of 1997, Jim joined Powell Electrical Manufacturing Company as Technical Director, providing leadership, training and mentoring to both internal and external electrical communities. www.netaworld.org