Universal current sensitive RCCBs B type and F type

advertisement
GE
Industrial Solutions
Universal current sensitive
RCCBs B type and F type
Ultimate protection of people
and equipment
ge.com/ex/industrialsolutions
Type B applications
Controllers and variable speed drives | Battery chargers and inverters | Frequency
converters | Photovoltaic systems, a.c side | Charging stations for electric vehicles
| Installation in general where we can expect d.c. smooth direct residual currents |
Variable speed machine tools | UPS, Computer Data Centers |
Elevator controls | Cranes of all kinds | Test set-ups in laboratories
| Backed-up power supplies | Electronic equipment on construction sites |
RCCBs
Residual Current Circuit Breakers
Residual Current Protection Devices
Types of Wave form detected by RCCBs and classification
Type AC Type A-Ai
Waveform
definition
Type F
Type B
Current
waveform
Tripping current
✓
✓
✓
✓
0,5 to 1 IΔn
Pulsating half wave
✗
✓
✓
✓
0,35 to 1,4 IΔn
Pulsating 90º/135º
wave
✗
✓
✓
✓
Current delay angle 90º: 0,25 to 1,4 Iδn
✗
✓
✓
✓
Current delay angle 135º: 0,11 to 1,4 IΔn
Pulsating Half wave +
diret current (6mA)
✗
✓
✓
✓
max. 1,4 IΔn+6mA
Pulsating Half wave +
diret current (10mA)
✗
✗
✓
✓
max. 1,4 IΔn+10mA
Composite wave
✗
✗
✓
✓
0,5 to 1,4 IΔn
High frequency
(up to 1KHz)
✗
✗
✓
✓
Current Frequency 150Hz 0,5 to 2,4 IΔn
✗
✗
✓
✓
Current Frequency 400Hz 0,5 to 6 IΔn
✗
✗
✓
✓
Current Frequency 1000Hz 1 to 14 IΔn
✗
✗
✗
✓
0,5 to 2 IΔn
Two phase rectified
full wave
General view
Sine wave
Three phase rectified
full wave
Direct current
Discover advantages: Type F
Offer the same range of protection and functionality as
a Type A RCD; this means that release with sinusoidal AC
currents as well as pulsating DC currents.
In addition to this, they are capable of detecting residual
currents from mixed frequencies of up to 1000 Hz, which
can often occur on the outgoing feeder side of singlephase frequency converters.
Type B
In adition to release residual current waveforms
of type A, B type RCCBs are used to detect
smooth DC residual currents. B Type RCCBs are
recommended for use with EV Charge and drives
and inverters for supplying motors for pumps,
lifts, textile machines, machine tools… since they
recognise a continuous fault current with low
level ripple.
This prevents undesirable interruptions to the electrical
supply if, for example, pulsed leakage currents of up to
ten milliseconds occur at activation of filter capacitors.
Type AC: Release with sinusoidal currents which occur suddenly or slowly rise in magnitude.
Type A-Ai: Release with sinusoidal currents and also with pulsating direct current which occur
suddenly or slowly rise in magnitude.
Type S-Si (type A-Ai): Time delay release with sinusoidal currents and also with pulsating direct
current which occur suddenly or slowly rise in magnitude.
3
RCCBs
RCCB with overcurrent protection
RCCBs - Residual Current Circuit Breakers
Series FP
EN 62423/ VDE 0664-40
Type B
Add-on devices
FP
Auxiliaries(1)
Motor operator(2)
(1) Series CA - Tele L - Tele U - PBS - TeleREC Plus
(2) Only at right side end of the extreme pin busbar
Performance
Rated current In
Residual current I∆
Rated Voltage AC Un
(A) 16, 25, 40, 63, 80
(mA) 30, 100, 300, 500
(V) 2P: 230
4P: 230/400
Minimum operating voltage U min 30 mA (V) 2P: 176
4P: 306
100,300,500 mA (V) 2P: 117
4P: 205
20.000/10.000
Mechanical/electrical endurange
Tropicalisation acc. to
95%RH at 55ºC
EN/IEC 60068-2-28/2-30 and DIN 40046
Terminal capacity flexible/rigid cable (mm2) 1,5-50
2, 4
Poles
3000A 8/20 msc
Nuisance tripping resistance
(ºC) -25 up to 40
Ambient temperature
(g) 2P: 340
Weight
(g) 4P: 420
Short-circuit capacity
Acc. To EN/IEC 61008-1
Making and Breaking capacity
Im=500A from 16A up to 40A
Im=10In from 63 up to 80A
Residual making and braking capacity I∆m=50In from 16A up to 40A
I∆m=10In from 63A up to 80A
Inc=10000A at 230/400V
Short-circuit capacity
fuse 80A gG
4
Series FP
Type B
30 mA
100 mA
300 mA
500 mA
Cat. No.
Ref. No.
Cat. No.
Ref. No.
Cat. No.
Ref. No.
Cat. No.
Ref. No. Pack
16
25
40
63
80
FPB 2 16/030
FPB 2 25/030
FPB 2 40/030
FPB 2 63/030
FPB 2 80/030
565353
565357
565361
565365
565369
FPB 2 16/100
FPB 2 25/100
FPB 2 40/100
FPB 2 63/100
FPB 2 80/100
565354
565358
565362
565366
565370
FPB 2 16/300
FPB 2 25/300
FPB 2 40/300
FPB 2 63/300
FPB 2 80/300
565355
565359
565363
565367
565371
FPB 2 16/500
FPB 2 25/500
FPB 2 40/500
FPB 2 63/500
FPB 2 80/500
565356
565360
565364 1/3
565368
565370
16
25
40
63
80
FPB 4 16/030
FPB 4 25/030
FPB 4 40/030
FPB 4 63/030
FPB 4 80/030
565333
565337
565341
565345
565349
FPB 4 16/100
FPB 4 25/100
FPB 4 40/100
FPB 4 63/100
FPB 4 80/100
565334
565338
565342
565346
565350
FPB 4 16/300
FPB 4 25/300
FPB 4 40/300
FPB 4 63/300
FPB 4 80/300
565335
565339
565343
565347
565351
FPB 4 16/500
FPB 4 25/500
FPB 4 40/500
FPB 4 63/500
FPB 4 80/500
565336
565340
565344 1/3
565348
565352
Series FP
In (A)
Wiring
Serie FP - Type B
Serie FP - Type B
1
N
1
3
5
N
2
N
2
4
6
N
Dimensions
5
RCCBs
RCCB with overcurrent protection
RCCBs - Residual Current Circuit Breakers
Series FP
EN/IEC EN 62423/ VDE 0664-40
Type F
Add-on devices FP
Auxiliaries (1)
Performance
Rated current In
Residual current I∆
Rated Voltage AC Un
Minimum operating voltage U min Motor operator (2)
(1) Series CA - Tele L - Tele U - PBS - TeleREC Plus
(2) Only at right side end of the extreme pin busbar
(A) 25, 40, 63, 80
(mA) 30
(V) 2P: 240
4P: 240/415
30 mA (V) 2P: 176
4P: 306
20.000/10.000
Mechanical/electrical endurange
Tropicalisation acc. to
EN/IEC 60068-2-28/2-30 and DIN 40046
Terminal capacity flexible/rigid cable (mm2)
Poles
Nuisance tripping resistance
(ºC)
Ambient temperature
(g)
Weight
(g)
95%RH at 55ºC
1,5-50 (1,5-50)
2, 4 (4)
3000A 8/20 msc
-25 up to 40
2P: 220
4P: 385
Short-circuit capacity
Acc. To EN/IEC 61008-1
Making and Breaking capacity
Available
soon
Im=500A from 16A up to 40A
Im=10In from 63 up to 80A
Im=1000A (100A)
Im=1250A (125A)
Residual making and braking capacity I∆m=500 from 16A up to 80A
I∆m=10In from 63A up to 80A
Inc=10000A at 240/415V (230V/400V)
Short-circuit capacity
fuse 80A gG
6
Series FP
Type F
30 mA
In (A)
Cat. No.
Ref. No.
Pack
FPF 2 25/030
FPF 2 40/030
FPF 2 63/030
FPF 2 80/030
565373
565374
565375
565376
1/6
25
40
63
80
FPF 4 25/030
FPF 4 40/030
FPF 4 63/030
FPF 4 80/030
565377
565378
565379
565380
1/3
Series FP
25
40
63
80
Wiring
Serie FP - Type F
Serie FP - Type F
1/2
3 /4
1/2
3/4 5/6
N
2 /1
4 /3
2 /1
4/3 6/5
N
Dimensions
7
RCCBs
Auxiliaries
RCCB with overcurrent protection
Series CA
Function
1/2 mod.
H
S/H
S/H
Cat. No.
Ref. No.
CA H
672567
CA S/H
672568
CA S/H G
672569
Pack
1/40
golden contacts
Series CB
Function
1/2 mod.
SH/HH
Cat. No.
CB SH/HH-R(1)
(1) Coupling on the right
Wiring
Serie CA
H
8
Serie CB
Ref. No.
Pack
672570
1/40
Add-on Devices
Tele MP - Motor operator
Cat. No.
Voltage
TELE MP
Pack
672580
1
Ref. No.
Pack
Auxiliary - Add-on Devices
AC 230V
Ref. No.
3 mod.
Tele L - Shunt trip
Voltage
AC 24-60V
DC 24-48V
Cat. No.
672573
TELE L-1
1
AC 110-415V
DC 110-125V TELE L-2
672574
Tele U - Undervoltage release
Voltage
AC 240V
AC/DC 12V
AC/DC 24V
AC/DC 48V
Cat. No.
Ref. No.
TELE U-230
672575
TELE U-12
672576
TELE U-24
672577
TELE U-48
672578
Pack
1
PBS - Panel board switch
Cat. No.
PBS
Ref. No.
Pack
672572
1
1/2 mod.
Wiring
Tele MP
Tele L
Tele U
PBS
9
RCCBs
RCCB with overcurrent protection
Technical data
10
Series
Standards
Magnetic tripping characteristics
Residual tripping characteristic
Tripping time at I Δn
Instantaneous
ms
Selective
ms
Rated current
A
Rated residual current I Δn
mA
Calibration temperature
ºC
Number of poles versus modules
Rated voltage Un
2P AC
V
3P AC
4P AC
V
Frequency
Hz
Maximum service voltage Ubmax
V
Minimum service voltage Ubmin (30 mA)
V
Minimum service voltage Ubmin (100, 300, 500 mA)
V
Minimum voltage for leakage protection
Power supply
Energy limiting class
Rated making and breaking capacity (Im)
A
Residual making and breaking capacity (IΔ m)
A
Conditional short-circuit capacity (Inc)
A
Conditional residual short-circuit capacity (IΔ c)
A
Rated Short-circuit capacity (Icn)
A
Grid distance (safety distance between two devices)
Isolator application
Insulation degree
Insulation voltage
V(DC)
Shock voltage (1.2/50μs)
kV
Insulation resistance
Mohm
Dielectric strength
V
Shock resistance (in x, y, z direction) (EN/IEC 60077/16.3)
Vibration resistance (in x, y, z direction) (EN/IEC 60068-2-6)
Endurance electrical at Un, In
mechanical at Un, In
Protection degree (outside/inside electrical enclosure with door)
Self extinguish degree (according to UL94)
Tropicalisation (according to EN/IEC 60068-2, DIN 40046) ºC/RH
Pollution degree (acc. EN/IEC 60947-1)
Operating temperature
Storage temperature
Terminals capacity Rigid cable min/max (top)
mm2
Flexible cable min/max (top)
mm2
Rigid cable min/max (bottom)
mm2
Flexible cable min/max (bottom)
mm2
Torque Top/Bottom
Nm
Add-on devices (side add-on) Auxiliary contacts
Tele U
Tele L
Tele M
PBS
Busbars systems
Pin
Fork
# Poles
Dimensions (HxDxW) 86x70xW
Weight
Package
Approvals
CE-marking
FP Type B
FP Type F
EN 62423/ VDE 0664-40
B
<300
16, 25, 40, 63, 80
30, 100, 300, 500
30
2P = 4 mod.; 4P = 4 mod.
230
230/400
50/60
2P=265/4P=460
2P=160/4P=258
2P=117/4P=205
Voltage independent
Top/Bottom
500 (or 10In)
500 (or 10In)
10000 fuse 80A gLgG
10000 fuse 80A gLgG
35
yes
440
6
1000
2500
40g 18 shocks 5ms
1,5g. 30 min, 0..80Hz
10000
20000
IP20/IP40
V2
55/95%
3
-25ºC…+40ºC
-25ºC…+70ºC
1,5/50 (1,5/35)
1,5/35 (1,5/25)
1,5/50 (1,5/35)
1,5/35 (1,5/25)
5/5
yes
yes
yes
yes
yes
yes
yes
2-4
72
2P=340 ; 4P=420
1/3
VDE
yes
EN 62423/ VDE 0664-40
F
<300
25, 40, 63, 80
30
30
2P = 2 mod.; 4P = 4 mod.
240
415
50/60
2P=265/4P=455
2P=160/4P=258
Voltage independent
Top/Bottom
500 (or 10In)
500 (or 10In)
10000 fuse 80A gLgG
10000 fuse 80A gLgG
35
yes
440
6
1000
2500
40g 18 shocks 5ms
1,5g. 30 min, 0..80Hz
10000
20000
IP20/IP40
V2
55/95%
3
-25ºC…+40ºC
-25ºC…+70ºC
1,5/50 (1,5/35)
1,5/35 (1,5/25)
1,5/50 (1,5/35)
1,5/35 (1,5/25)
5/5
yes
yes
yes
yes
yes
yes
yes
2-4
36/72
2P=220 ; 4P=385
2P=1/6; 4P=1/3
yes
115315
GE
Industrial Solutions
GE Industrial Solutions is a first class global supplier of low and medium
voltage products including wiring devices, residential and industrial
electrical distribution components, automation products, enclosures
and switchboards. Demand for the company’s products comes
from wholesalers, installers, panelboard builders, contractors,
OEMs and utilities worldwide.
Belgium
GE Industrial Belgium
Nieuwevaart 51
B-9000 Gent
Tel. +32 (0)9 265 21 11
Finland
GE Industrial Solutions
Kuortaneenkatu 2
FI-00510 Helsinki
Tel. +358 (0)10 394 3760
France
GE Industrial Solutions
Paris Nord 2
13, rue de la Perdrix
F-95958 Roissy CDG Cédex
Tel. +33 (0)800 912 816
Germany
GE Industrial Solutions
Robert-Bosch Str. 3
D-50354 Hürth-Efferen
Tel. +49 (0) 2233/ 9719-0
Hungary
GE Hungary Kft .
Vaci ut 81-83.
H-1139 Budapest
Tel. +36 1 447 6050
ge.com/ex/industrialsolutions
Italy
GE Industrial Solutions
Centro Direzionale Colleoni
Via Paracelso 16
Palazzo Andromeda B1
I-20864 Agrate Brianza (MB)
Tel. +39 039 637 371
Netherlands
GE Industrial Solutions
Parallelweg 10
Nl-7482 CA Haaksbergen
Tel. +31 (0)53 573 03 03
Poland
GE Power Controls
Ul. Towarowa 25A, Ip
00-869 Warszawa
Tel. +48 22 520 53 53
Ul. Leszczyńska 6
43-300 Bielsko-Biała
Tel. +48 33 828 62 33
Russia
GE Industrial Solutions
27/8, Electrozavodskaya street
Moscow, 107023
Tel. +7 495 937 11 11
South Africa
GE Industrial Solutions
Unit 4, 130 Gazelle Avenue
Corporate Park Midrand 1685
P.O. Box 76672 Wendywood 2144
Tel. +27 11 238 3000
Spain
GE POWER CONTROLS IBÉRICA, S.L.
Calle Miño 122 Naves E-F
Polígono Industrial Santa Margarita
08223 Terrassa (Barcelona)
Tel. +34 900 993 625
United Arab Emirates
GE Industrial Solutions
Injaz Building, 3rd Floor
Dubai Internet City
PO Box 11549, Dubai
Tel. +971 4 4546912
United Kingdom
GE Industrial Solutions
2 The Arena, Downshire Way
Bracknell, Berkshire
RG12 1PU
Tel. +44 (0)800 587 1239
680896
Ref. R/2536/E/EX 1.0 Ed. 05/15
* Trademark of General Electric Company
© Copyright GE Industrial Solutions 2015
Download