Comprehensive Maintenance Plan for Educational Facilities FY2016 Washington County Board of Education Justin M. Hartings, Ph.D., President Donna L. Brightman, Vice-President Members Paul W. Bailey Jacqueline B. Fischer Karen J. Harshman Wayne D. Ridenour Melissa A. Williams ◊ ◊ ◊ ◊ Clayton M. Wilcox, Ed. D. Superintendent of Schools The Board of Education of Washington County does not discriminate on the basis of race, color, sex, age, national origin, religion, disability, or sexual orientation in matters affecting employment or in providing access to programs to Washington County Public School System students. An employee who feels he or she is being discriminated against should inform his or her supervisor in writing. If an individual feels that the discussion of the subject with the supervisor would be inappropriate, he or she should document the incident and discuss it with the Director of Human Resources. COMPREHENSIVE MAINTENANCE PLAN Table of Contents CHAPTER 1 - INTRODUCTION Introduction ........................................................................................................ 1 CHAPTER 2 - STRUCTURE OF ORGANIZATION Facilities Maintenance Organization .................................................................. 4 CHAPTER 3 - SCHEDULED MAINTENANCE Facilities Assessment ........................................................................................ 8 Assessment Chart ........................................................................................... 25 Prevention Maintenance .................................................................................. 27 Scheduled Replacement with Modifications & Alterations ............................... 43 CHAPTER 4 - UNSCHEDULED MAINTENANCE Work Orders .................................................................................................... 52 Vandalism Data ............................................................................................... 54 CHAPTER 5 - DEFERRED MAINTENANCE Description of Deferred Maintenance .............................................................. 55 Introduction The buildings and grounds of Washington County Public Schools (WCPS) are maintained by the Facilities Maintenance and Operations Department. Work performed by staff of this department, along with contractors, ensure the schools are properly maintained and the classroom environment is both inviting and conducive to learning. As the age of the building inventory increases, the Washington County Board of Education and administration strive to procure increased funding from state and local government sources. The Facilities Maintenance and Operations Department is guided by the Washington County Public Schools vision statement. Vision Statement “Building a community that inspires curiosity, creativity, and achievement” Goals The goal of the Maintenance and Operations Department is for no school closures to occur from a maintenance related problem. This goal was accomplished in the fiscal year 2013-2014. The Maintenance and Operations staff are fully committed to resolving problems and keeping schools open and safe. Funding for maintenance activities is provided through: 1) the Operating Budget, in the “Maintenance of Plant” category, 2) State and Local Capital Improvement Programs, 3) Qualified Zone Academy Bond (QZAB) 4) Project Open Space, 4) Aging School Programs (ASP), and 5) Supplemental Grants. The facility maintenance needs are identified in the Facilities Assessment in Chapter 3. This comprehensive assessment was performed using the criteria presented in the “Task Force to Study Public School Facilities.” The criteria is a standardized and comparative survey performed on all schools in the system. Component scoring is weighted according to importance as it relates to overall condition of the school facility. The focus of the assessment is based on actual condition of the facility and not the ability of funding sources to supply the needed resources. Maintenance Washington County Public Schools’ (WCPS) Educational Facilities Master Plan, Capital Improvement Program Plan, and Comprehensive Maintenance Plan, are used to identify and determine the district’s maintenance needs. Each year the Facilities Maintenance and Operations Department identifies projects in various categories from parking lot overlays to roof replacements. 1 WCPS has replaced lighting and added roof insulation to reduce energy demands. Included in systemic heating, ventilation, air conditioning, (HVAC) projects is the upgrade from the pneumatic control to direct digital control technology. The direct digital control systems allow remote monitoring, control, and scheduling of the building HVAC equipment, which reduces the operating cost of these systems. Carbon dioxide demand ventilation control enhancements was installed in the large spaces to limit unnecessary outside air tempering when the space is unoccupied. The energy management analyst continues to be successful in obtaining lower cost fuel oil, gas, and electric bids to further curb the budget increase required for the operation of the school system buildings. Unprecedented fluctuations in energy costs, due to deregulation of electricity and volatility of petroleum production, require systems that allow the greatest amount of flexibility in operation. Building Renovations The department oversees minor building renovation projects such as flooring, locker, ceiling, and lighting replacements. The department also manages various sidewalks, paving, and fencing projects. Partitions were installed in open schools to better define the classroom space and improve the acoustics to limit noise while improving the learning environment. Handicap accessibility projects were conducted at several schools. Accessible sidewalks were added at various school sites. Projects are being planned to address American with Disability Act (ADA) compliance at WCPS buildings using the assessment conducted by a consultant specializing in ADA accessibility. Initiatives A cross-functional team was organized to address the work order process system-wide. Consulting with a process improvement specialist, the team addressed several areas for consideration. The Maintenance and Operations department are currently implementing the suggested improvement strategies and will measure the improvement throughout the year. The internship program for college students continues to be successful and was expanded to include other service departments in the school system. Interior spaces at four schools totaling more than 150,000 square feet were painted improving the learning environment. 2 Security vestibules were installed at fourteen elementary schools and one middle school. The projects were made possible through funding from the Security Initiative of the FY 2014 Public School Construction Capital Improvement Program. The inventory control software module was instrumental in improving inventory control system-wide. The inventory control initiative improved the ordering process, reduced storage requirements, and reduced inventory cost by $75,000. 3 Facilities Maintenance & Operations Organization Program Description The maintenance program provides the services necessary to create a safe physical environment while protecting the asset value of Washington County Public Schools’ 50 properties throughout the county. The department’s goal is to provide a positive learning environment, provide continuous use of facilities without disruptions to the education programs, and maintain assets in the most cost-efficient manner possible while following federal and state guidelines and Washington County Board of Education policies. Personnel Organization Director Maintenance and Operations M. Mills Admin. Secretary A. Knode Maintenance Project Manager Project Construction Energy Mgnt Analyst J. Harr Operations Manager A. Mayhugh 208 Custodians D. Diller Maintenance Environmental Safety Specialist Maint. Foreman Mechanical Maint. Foreman Electrical Maint. Foreman Structural T. Suranno D. Johns D. Campbell D. Unger IPM Coordinator / Turfcare Tech. P. Breakall Plumbers Electricians Locksmith R. Douglas J. Eichelberger C. Ellis J. Wollard F. Yeargan R. Ankeney R. Burger S. Hall J. Bowers Carpenters Painters J. Basore A. Knox HVAC Mechanics Vacant R. Green J. Pebble D. Stutzman J. Wolford General Maint. Workers D. Baker R. Haywood C. Ridenour D. Hays M. Dunn W. Niswarner M. Powers L. Shirley N. Sword Carpenter Helper Vacant Roofers P. Mackrell B. Miller Mason K. Brown Mason Helper Vacant 4 The Facilities Maintenance and Operations Department is broken into eight different areas: Pest Management/Turf Care, Structural, Electrical, Mechanical, Environmental Health & Safety, Project Management, and Energy Management. Pest Management/Turf Care: • Maintains athletic fields and storm water ponds, designs & builds irrigation systems, and builds fences. Structural: • Repairs doors and hardware, windows, constructs partitions, hangs chalkboards, builds cabinets, installs lockers, and patches roofs. • Designs and performs minor renovation projects, builds walls, stone work, brick work, concrete work, locksmith work, and key management. • Inspects and maintains playground equipment, overhead doors, gymnasium equipment such as backboards, bleachers, climbing ropes, scoreboards, and stage equipment including lights, cables, and curtains. Electrical/General: • Repairs and replaces lighting fixtures, electrical appliances, panels, breakers, plugs, wiring, emergency generators, elevators and lifts, fire alarm systems, and temperature control systems. • Paints and other general maintenance. Mechanical: • Operates, repairs, and replaces the mechanical equipment in schools including boilers, HVAC equipment, pumps, compressors, and motors. • Repairs and replaces plumbing fixtures including sewer and water lines, sinks, drinking fountains, and hot water heaters. • Performs preventive maintenance to HVAC equipment and associated pertinences. 5 Energy Management: • Proposes process changes and monitors results of energy management initiatives and investigate abnormalities in energy billing. • Develops methods of specifying bulk and consortium energy purchases to lower costs and reduce energy usage. • Maintains the Energy Management System and controls associated with heating, air conditioning, and ventilation systems. Environmental Safety Specialist • Oversees the Board's safety and environment program, which includes OSHA inspections, asbestos management, fire drills, well water testing, blood-borne pathogens training, radon management, indoor air quality testing, fire marshal inspections, and security systems. Operations Manager • Specifies and provides all custodial supplies throughout the system including paper products, chemicals, and equipment. • Provides technical support and training to the school-based custodial staff, and publishes the custodial handbook. • Manages the substitute custodian program. Maintenance Project Management • Oversees projects performed by outside contractors. These projects often require architectural and engineered services and bidding. 6 Program Highlights • Completed major systemic renovations at local schools improving the learning environment. These include but are not limited to replacement of: lighting, ceilings, HVAC equipment, doors, windows, and flooring. • Completed sidewalk and parking lot resurfacing at 14 locations. • Completed over 43 maintenance projects. • Completed 10 major systemic projects. • Completed over 6,800 work orders assigned to maintenance staff. • Painted interior spaces at Eastern, Emma K. Doub, Hickory, Potomac Heights, Western Heights, and Fountaindale Schools. • Completed ADA improvements at Smithsburg and North Hagerstown High Schools. • Resurfaced track and added an additional long jump pit at South Hagerstown High School. • Continued to upgrade automatic temperature control systems at various schools. • Replaced roof at Clear Spring Middle School. • Completed installation of high efficiency boiler and chiller at Marshall Street Center. • Replaced windows and doors at Springfield Middle, Boonsboro Middle, and Boonsboro High Schools to tighten the building envelop and improve security. • Installed a security vestibule at 15 school locations. • Purchased a 125 Kw trailer mounted generator and two 200 gallon water tanks for response to emergency outages caused by weather and other circumstances. 7 Inventory and Evaluation Background Washington County Public Schools (WCPS) conducts an annual inventory and evaluation of schools and facilities utilized in the education of its students. The assessment includes the physical and functional use of schools or facilities. The process is to determine the continuing condition and usefulness of each school or facility. Included in the assessment of each facility is the assumption that projects that are planned or under way for completion during 2014 will be completed on schedule. The assessment, as a component of the Educational Facilities Master Plan (EFMP), is used to determine the short-term and long-term facility needs, and the maintenance resources required to support the schools. Process WCPS updates the facilities assessment of each school and facility in the county on an annual basis. The assessment provides a rating system for the physical condition and functional adequacy of each school or facility. • Physical condition assessments include reviews of roofs, doors, windows, flooring, and mechanical systems, etc. • Functional adequacy assessments include reviews of instructional spaces, core facilities, playgrounds/athletic fields, and technology (updated in cooperation with the school administrators). • Scores are further adjusted for other factors such as age of the facility, enrollment versus. capacity, and site size. Each component is given a score from 55 to 95 based on the Maryland Public School Construction Program’s method of scoring. The scoring methodology is as follows: 95 85 75 65 55 Superior Rating Good Rating Adequate Rating Not Adequate Rating Poor Rating Component scoring is weighted according to importance as it relates to overall condition of the school or facility. A weight factor with a value from 1 to 3 is assigned to each category depending on the relative importance of the category, with a weight of 3 being of greatest importance. Each category’s score is multiplied by the corresponding weight factor and all of the resultant products are totaled in the “total points” column of Figure 3-4. (See Figure 3-4 at the end of this narrative.) The “Category Points” column in Figure 3-4 is the total of all the weight factors less any weight factors for categories that are not applicable to a given facility. The “Total Points” column is divided by the total “Category Points” column to arrive at a weighted average score. Finally, a five-point 8 adjustment is added to bring the total possible points to 100. The score is reported as a percentage of the total possible points applicable and listed in the “Overall Rating” column. Categories with a rating of Not Adequate or Poor are planned for replacement or repair and incorporated into the Capital Improvement Program (CIP) and EFMP. Critical needs are accomplished as soon as funding is available. For reference, an example calculation of a facility assessment rating is shown in Figure 3-1. Figure 3-1 SAMPLE CALCULATION OF FACILITY ASSESSMENT RATING FOR SHARPSBURG ELEMENTARY Total Points Category Points Quotient Percentage Adjustment Total Points 4,000 57 70 5 75 Calculation 4,000 ÷ 57 = 70 + 5 = 75 ÷ 100 = 75 % Table 3-2 identifies average life cycles used to assess various key building systems. Figure 3-2 AVERAGE LIFE CYCLES OF THE KEY BUILDING SYSTEMS Component Roofing Heating Air Conditioning / Air Handler / Chiller Electrical Projects Plumbing Fixture Plumbing / Supply DWV Fire / security system Drives & Parking Lot Sidewalk Projects Flooring Lighting / Ceiling Painting Athletic / Playgrounds Theatre / Auditorium Exterior Doors Windows Life Cycle Age 15-50* 30 20-30 30 20 40 25 15 15 15-60* 20 5-10 5-25* 30 15 25 *Dependent on type of system installed. 9 Figure 3-3 establishes criteria for the assessment of each category. Figure 3-3 CRITERIA FOR PHYSICAL AND FUNCTIONAL ASSESSMENTS Superior Layout of site allows separate bus and student drop off locations with ample handicap and accessible walkways and parking. Parking is available for daily activities and large after-school events. Signage and parking is clearly identified. Walkways, curbing, and macadam are free of cracks, potholes, and uneven joints. Good Adequate Not Adequate Physical Attribute Site Layout, Parking, Bus Drop Off, Walkways Layout of site Layout has Layout has allows separate shared bus and shared bus and bus and student student drop off student drop off drop off locations location. School is location with with ample close to street. congested traffic handicap and Handicap parking patterns. School accessible is adequate with is close to busy walkways and accessible path to street or parking. Parking main entrance. intersection is available for Parking is Handicap parking daily activities and available for daily is minimal with inafter-school activities and accessible path to events. Signage small after-school main entrance. and parking is events. Signage Parking is not clearly identified. and parking is available for daily Walkways, minimally marked. activities and curbing, and Walkways, small after-school macadam have curbing, and events. Signage minor cracks and macadam show and parking minor uneven signs of minor needs clearly joints. No signs deterioration and marked. of failure or require minor Walkways, potholes. repairs. curbing, and macadam show signs of major deterioration that requires repairs. 10 Poor Layout has shared bus and student drop off location with major traffic pattern concerns. School is close to busy street or intersection that causes safety concerns. Handicap parking is minimal with inaccessible path to main entrance. Parking is not available for daily activities and after-school events. Signage and parking is poorly marked. Walkways, curbing, and macadam show signs of serious deterioration that requires immediate repairs. Superior Good Adequate Not Adequate Exterior Conditions (doors and frames) 10 years old or 15 years old or 15 years old or 15 years old or newer constructed newer constructed newer constructed older constructed from metal or from metal or from metal or from wood with aluminum with aluminum with aluminum with wood frames and steel or aluminum steel or aluminum steel or aluminum signs of decay. frames. frames. frames and no Hardware is not Hardware is ADA Hardware is ADA signs of ADA compliant, compliant, secure, compliant, secure, deterioration. secure, or and available. Fit and available. Fit Hardware is not obsolete. Fit and and finish of and finish of ADA compliant, finish of opening opening is clean opening is clean secure, or shows signs of with no signs of with no signs of obsolete. Fit and age. Paint and water infiltration. water infiltration. finish of opening sealant is loose, show signs of and cracked with sagging and rust signs of excess and peeling paint. water infiltration. Exterior Conditions (windows) Commercial grade Residential Residential Non-insulated insulated insulated wood, insulated wood, wood or metal aluminum frame vinyl or metal vinyl or metal frame single pane double pane low frame double frame single pane glass with loose emissivity glass pane glass with glass with no or missing glazing with tight fit and tight fit and loose or missing and sealant. good sealant sealant. glazing and Signs of integrity. sealant. deterioration and Operable units air and water have good fit and infiltration. latching abilities. Masonry construction or steel framing and brick veneer with insulation R-value above R-14. Siding, brick, and mortar joints are tight with good fit and finished with no signs of water infiltration or structural cracks. Exterior Conditions (walls) Masonry Masonry Structural construction or construction with materials have steel framing and insulation R-value low insulation Rbrick veneer with below R-11. values. Structure insulation R-value Signs of loose has loose panels, above R-11. mortar and brick mortar, and brick Siding, brick, and with signs of with obvious signs mortar joints are minor structural of structural tight with good fit cracks and water cracks and water and finished with infiltration infiltration no signs of water infiltration or structural cracks. 11 Poor 25 years old or older constructed from wood with wood frames signs of severe decay. Hardware is not ADA compliant, secure, or obsolete. Fit and finish of opening is poor. 25 years or older single pane with signs of severe deteriorated sash, frame, and sealant. Signs of excessive damage due to air and water infiltration. Structural materials are crumbling and deteriorating showing signs of severe water infiltration and loss of structural integrity. Superior 10 years old or newer built up insulated flat roof, insulated standing seam metal or 50 year shingle. Semi-annual roof inspection score above 3.2. Water tight with no signs of blisters, punctures, or leaking. Structural materials are masonry construction with glazed block or steel framing with drywall and ceramic tile. Mortar joints are tight with good fit and finish with no signs of structural cracks. Overall appearance is excellent with a clean and bright finish with no signs of damage. There are no stained, broken, or missing ceiling tiles and grid. Lockers are in excellent condition. Interior has been painted in the last 5 years. Good Adequate Not Adequate Roof Conditions 15 years old or 20 years old or 30 years old or newer built up older built up older standing insulated flat roof, insulated flat roof metal seam, 50 or 50 year or 50 year year shingled shingled roof. shingled roof. 15 roof. 25 year old New EPDM or year old EPDM, EPDM or TPO TPO roofing TPO, or 35 year roofing system. system. 30 year old standing metal Semi-annual roof old standing metal seam roof. Semi- inspection score seam roofing annual roof below 1.8. system. Semiinspection score Evidence roof is in annual roof above 1.8. Some danger of inspection score signs of blisters, imminent failure above 2.8. No cracking, seams with signs of signs of splitting, and leaking and major immediate failure. some minor leaks. degradation of Evidence roof will roofing system. fail in the next five years. Interior Conditions (walls, ceiling, etc.) Structural Structural Structural materials are materials are materials have masonry masonry been worn and construction or construction or the paint finish is steel framing with steel framing with dull and dated. drywall and drywall and Structure has ceramic tile. painted finish. loose mortar and Mortar joints are Signs of loose brick with obvious tight with good fit mortar and signs of structural and finish with no drywall joints with cracks and signs structural of signs of minor damage. The cracks. Overall structural cracks ceiling has many appearance is and damage. stained, broken, good with a clean Interior is clean and missing finish with no but has scuff ceiling tiles and signs of damage. marks and paint dull grid. Lockers There are a few finish is dull. are damaged and stained, broken, There are various dented. Interior and missing areas with has not been ceiling tiles and stained, broken, painted in the last grid. Lockers are and missing 15 years. in good condition. ceiling tiles and Interior has been grid. Lockers are painted in the last slightly damaged 10 years. and dented. Interior has been painted in the last 15 years. 12 Poor 30 years old or older of all roof system types. Semi-annual roof inspection indicates major leaks and failure of roof system. Roof needs replacement as soon as possible. Structural materials have been worn and damaged; the paint finish is dull and dated and is in need of refinishing. Structure has obvious signs of structural cracks and damage. The ceiling has many stained, broken, and missing ceiling tiles and dull grid. Lockers are damaged and dented. Interior has not been painted in the last 20 years. Superior Flooring is clean and in excellent condition. Floor is free of loose tiles, cracks, tears, and exposed seams. Floor material is commercial grade, sustainable, and relatively new. Finish shines. 15 years old or newer with main feeder in conduit. Switchgear and load centers are dependable with spare circuits and load capacity. Spare parts are available for repairs and expansion. Breaker panels are located in locked electrical rooms with locked covers. Ground fault outlets and breakers at wet locations. Emergency generator with lighting and mechanical systems connected. Good Adequate Not Adequate Flooring (tile, carpet, etc.) Flooring is clean Flooring condition Flooring condition and in good shows signs of is worn with major condition. Floor wear with blemishes and has some minor blemishes, but is does not appear blemishes but is clean. There are clean. There are free of loose tiles, loose tiles, cracks, loose tiles, cracks, tears, and tears, or exposed exposed seams, exposed seams. seams. Floor tripping hazards, Floor material is material shows its rips, tears, and commercial age and is ready asbestos grade, for replacement containing sustainable, and and there are no materials. Floor does not show tripping hazards. should be signs of wear. Finish is dull with replaced. Finish is good. build-up. Electrical Distribution (outlets, power) 20 years old or 20 years old or 30 years old or newer with main older with main older with main feeder in conduit. feeder direct feeder direct No signs of buried or in buried or in insulation conduit. Switch conduit. Signs of breakdown. gear and load insulation breakSwitchgear and centers are at down with system load centers have capacity with few failures. spare circuits and spares for Switchgear and load capacity for expansion. Spare load centers are expansion. Spare parts are not at full capacity parts are available difficult to procure. with no room for for repairs and Breaker panels expansion. Spare expansion. are located in parts are Ground fault hallways, open unavailable or outlets and areas, or remanufactured. breakers at wet classrooms. Breaker panels locations. Ground fault are located in Breaker panels circuits were hallways, open are located in retrofitted at wet areas, or hallways with location. classrooms. locked covers. Emergency Circuits are not Emergency generator power clearly marked. generator with is unavailable. Emergency lighting and generator power mechanical is unavailable. systems Electrical system connected. needs replaced. 13 Poor Flooring is in poor condition, with many loose tiles, exposed seams, tripping hazards, rip, tears, and asbestos containing materials. Flooring cannot be cleaned properly and should be replaced. 30 years old or older with main feeder direct buried or in conduit. Signs of insulation breakdown with frequent system failures and outages. Switchgear and load centers are at full capacity with no room for expansion. Spare parts are unavailable do to obsolescence. Breaker panels are located in hallways, open areas, or classrooms. Circuits are not clearly marked. Emergency generator power is unavailable. Electrical system needs replaced. Superior Good Adequate Not Adequate Fire and Life Safety (sprinkler, alarm) 10 years old or 15 years old or 20 years old or 25 years old or newer. Building is newer. older. older. fully sprinkled, fire Building is fully Building is Building is nonextinguishers are sprinkled, fire partially sprinkled, sprinkled or sufficient. Fire extinguishers are fire extinguishers partially sprinkled. alarm is reliable sufficient. Fire are sufficient. Fire extinguishers and state of the alarm is reliable Fire alarm is are sufficient. Fire art. Fire and and state of the reliable but may alarm is reliable, smoke barriers art. Fire and not be an but past the life are intact. Exit smoke barriers addressable expectancy. Fire signs are located are intact. Exit system. Fire and and smoke properly and signs are located smoke barriers barriers are intact. evacuation routes properly and are intact. Exit Exit signs are are posted at evacuation routes signs are located located properly proper height and are posted at properly and and evacuation location. Fire proper height and evacuation routes routes are posted alarm pull stations location. Fire are posted at at proper height and audio visual alarm pull stations proper height and and location. Fire devices are and audio visual location. Fire alarm pull stations accessible. devices are alarm pull stations and audio visual Sprinkler heads accessible. and audio visual devices are are clean and not Sprinkler heads devices are accessible. blocked by are clean and not accessible. Sprinkler heads excessive blocked by Sprinkler heads are clean and not storage. excessive are clean and not blocked. storage. blocked. Lavatories 10 years old or 15 years old or 20 years old or 30 years old or newer fixtures that newer fixtures that older fixtures that older fixtures that are ADA are ADA do not meet do not meet compliant and compliant and current water current water water water conservation conservation conservation conservation measures and measures and devices. Number devices. Number meet the meet the of fixtures meets of fixtures meets minimum ADA minimum ADA or exceeds code current code code. Numbers of code. Numbers of requirements. requirements. fixtures meet code fixtures meet code Age appropriate Age appropriate at time of at time of sized fixtures with sized fixtures with construction. construction. one per one per Lavatories are Lavatories are classroom for classroom for shared by multiple shared by multiple elementary elementary classrooms. classrooms. schools. Partitions schools. Partitions are Partitions are are clean, bright, Partitions are clean with minor clean with minor and solid clean and bright blemishes. blemishes. materials. with no blemishes. 14 Poor 25 years old or older. Building is nonsprinkled, fire extinguishers are sufficient. Fire alarm is reliable, but past the life expectancy. Fire and smoke barriers are intact. Exit signs are located properly and evacuation routes are posted at proper height and location. Fire alarm pull stations and audio visual devices are accessible. 30 years old or older fixtures that do not meet current water conservation measures and meet the minimum ADA code. Numbers of fixtures meet code at time of construction. Lavatories are shared by multiple classrooms. Partitions are rusted with major blemishes and need repaired. Superior 10 years or newer commercial state of the art intercom and PA system. VOIP phone and data on fiber optic. Good Adequate Not Adequate Communications Systems (phone, intercom) 15 years old or 20 years old or 25 years old or newer commercial newer commercial older commercial state of the art intercom and PA intercom and PA intercom and PA system. VOIP system. VOIP system. VOIP phone and data phone and data phone and data on copper or on copper. on fiber optic. microwave. Municipal water or well water with water conditioning system. Low turbidity and good water pressure. Municipal water or well water with conditioning system. Low turbidity and adequate pressure. 15 years old or newer. Proven technology energy efficient units with dependable components and DDC controls and programming to reduce energy use. Four pipe system. Piping and insulation is sealed with no leaks or signs of air or water infiltration. Natural gas boilers, heat pumps, variable flow refrigerant, and geothermal units installed taking advantage of efficiency of equipment. Building is a high performance building. Excess capacity is only for designed expansion. 20 years old or newer. Proven technology energy efficient units with dependable components and DDC controls and programming to reduce energy use. Four pipe system. Piping and insulation is sealed with no leaks or signs of air or water infiltration. Natural gas boilers, heat pumps, variable flow refrigerant, and geothermal units installed taking advantage of efficiency of equipment. Building is a high performance building. Excess capacity is only for designed expansion. Potable Water Well water with water conditioning system. Meets safe guidelines for consumption. Heating Systems 20 years old or older. Older technology with large oil burning or dual fuel hot water or steam boilers. Electric reheat with conventional controls. Two pipe system. Piping has less than one inch of insulation and system shows signs of minor leaks. Boilers are sized for 80% of load or total redundancy. Control sequence does not take advantage of outside temperatures. System needs updated to more energy efficient alternative. Equipment is dependable. 15 Poor 25 years old or older commercial intercom and PA system. VOIP phone and data on copper. System needs replaced Well water with water conditioning system. Suitable to drink, but bottled water is still provided. Well water with water conditioning system. Unsuitable to drink and bottled water must be provided. 30 years old or older. Older technology with large oil burning or dual fuel hot water or steam boilers. Electric reheat with conventional controls. Two pipe system. Piping has less than one inch of insulation and system shows signs of minor leaks. Boilers are sized for 80% of load or total redundancy. Controls do not take advantage of energy saving techniques. System needs updated to more energy efficient alternative. Equipment is not dependable. 30 years old or older. Inefficient system with high energy usage. System has missing insulation and many leaks. Two pipe system. Equipment shows signs of probable future failure. Piping is old and in need of replacement. Pumps and components are past the useful life expectancy. Failures occur frequently and parts are obsolete. System requires replacement and upgrade in the immediate future. Superior Good Adequate Not Adequate Air Conditioning Systems (Central Plant) 10 years old or 15 years old or 20 years old or 30 years old or newer high newer high older equipment older equipment efficiency chilled efficiency chilled with minor failures with frequent water system with water system with due to age of failures due to DDC controls and DDC controls and equipment. age of equipment. optimal control optimal control Piping and Piping is past life sequences. sequences. insulation are expectancy and Piping and Piping and intact with signs of insulation is insulation is tight. insulation is tight. minor damage. degrading. Parts System is part of System is part of Parts are are very difficult to a four pipe system a four pipe system available for procure due to with tube inside with tube inside procurement. age of equipment. building with building with Chiller does not Chiller does not remote condenser remote condenser have frequency have frequency or cooling tower. or cooling tower. drive but does drive staging Refrigerant is Refrigerant is have staging capabilities or CFC free. Chiller CFC free. Chiller capabilities or variable speed has frequency has frequency variable speed pumping. drive or staging drive or staging pumping. System Compressor is capabilities for capabilities for is a four pipe inefficient and optimal energy optimal energy system but must uses too much efficiency. All efficiency. All be drained during energy. System associated associated heating season is part of a two components are components are due to the location pipe system or in excellent in good shape. of heat must be drained shape. exchanger. during heating season. Tube bundles have thin walls of tubing. 10 years old or newer equipment with required fresh air ventilation and DDC controls with economizer cycle. Central station variable air volume, heat pump, dedicated outside air units, energy recovery, or geothermal units. Insulation is tight and more than adequate. 20 years old or newer equipment with required fresh air ventilation and DDC controls with economizer cycle. Central station variable air volume, heat pump, dedicated outside air units, energy recovery, or geothermal units. Insulation is tight. Air Handling Systems 20 years old or 30 years old or older equipment older equipment with minimum with minimum fresh air fresh air ventilation and ventilation or DDC DDC controls. controls. Cabinet Cabinet unit unit ventilators, ventilators, and packaged packaged roof top roof top units with units with electric electric reheat. or hot water heat. Units show signs Units show signs of severe rust and of rust and duct leaks. deterioration and Insulation is have duct leaks. missing. Insulation is tight. Equipment needs replaced. 16 Poor 30 years old or older equipment with multiple failures due to age of equipment. Chiller does not have frequency drive, staging capabilities or variable speed pumping. Piping insulation is inadequate and shows signs of condensation leaks. System is part of two pipe system or must be drained during heating season. Piping is past life expectancy and has various leaks. Refrigerant used is obsolete. Equipment is obsolete and past it life expectancy. Tubing has thin walls. 30 years old or older equipment with no fresh air ventilation or DDC controls. Cabinet unit ventilators, ductless units, packaged roof top units with electric reheat. Units show signs of severe rust and duct leaks. Equipment is obsolete. Equipment needs replaced. Superior 10 years old or newer. Playground equipment and surface meets or exceeds current safety standards. Playfields are large, level, and easily accessible. Competition fields are well manicured with accessible seating. Practice fields are abundant and well cared for with excellent stand of grass. Track is level with 8 lanes. 10 years old or newer fixtures with lighting controls that use variable light levels, occupancy sensors, high efficiency lamps, and ballasts. Foot candles of light measured at desk height is above 45. As determined by the assessment of ADA compliance report. Items considered accessible entry to building and items to provide basic accessibility. Good Adequate Not Adequate Playgrounds, Athletic Fields 15 years old or 15 years old or 15 years old or newer. newer. older. Playground Playground Playground equipment is old equipment and equipment is and does not surface meets or dated and meets meet current exceeds current current safety safety standards. safety standards. standards. Playfields are Playfields are Playfields are level but not large, level, and level but not easily accessible. easily accessible. easily accessible. Competition fields Competition fields Competition fields are manicured are well are manicured with accessible manicured with with accessible seating. Practice accessible seating. Practice fields are small seating. Practice fields are with a good stand fields are adequate and well of grass. Track is adequate and well cared for with a level with 6 lanes. cared for with a good stand of Track and good stand of grass. Track is playground needs grass. Track is level with 6 lanes. replaced. level with 7 lanes. Track needs resurfaced. Lighting 20 years old or 20 years old or 30 years old or newer fixtures older fixtures with older fixtures with with lighting lighting controls no lighting controls that use that use variable controls that use variable light light levels, variable light levels, occupancy occupancy levels, occupancy sensors, high sensors, high sensors, high efficiency lamps, efficiency lamps, efficiency lamps, and ballasts. Foot and ballasts. Foot and ballasts. Foot candles of light candles of light candles of light measured at desk measured at desk measured at desk height is above height is above height is below 45. 35. 30. ADA Accessibility As determined by As determined by As determined by the assessment of the assessment of the assessment of ADA compliance ADA compliance ADA compliance report. Items report. Items report. Items considered considered considered accessible entry accessible entry accessible entry to building and to building and to building and items to provide items to provide items to provide basic basic basic accessibility. accessibility. accessibility. 17 Poor 15 years old or older. Playground equipment is old and does not meet current safety standards. Playfields are level but not easily accessible. Competition fields are manicured without accessible seating. Practice fields are small with a stand of grass. Track is level with 6 lanes. Track and playground needs replaced. Fields need upgraded. 30 years old or older fixtures with no lighting controls that use variable light levels, occupancy sensors, high efficiency lamps, and ballasts. Foot candles of light measured at desk height is below 30. As determined by the assessment of ADA compliance report. Items considered accessible entry to building and items to provide basic accessibility. Superior Good Classroom sizes are Pre-K and K, 1,000 ft2; grades 1 thru 5, 900 ft2; and grades 6 thru 12, 850 ft2. Primary grades have access to sinks, drinking fountain, and lavatory in individual classroom. Ample daylight and teaching station equipped with current teaching technologies. Classroom sizes are Pre-K and K, 1,000 ft2; grades 1 thru 5, 900 ft2; and grades 6 thru 12, 850 ft2. Primary grades have access to sinks, drinking fountain, and shared lavatory in individual classroom. Ample daylight and teaching station equipped with current teaching technologies. Wide corridors providing excellent, administrative control, student circulation, and full visibility. Large centrally located assembly area with sufficient group toilets for afterschool activities. Large storage areas for textbooks, furniture, and school supplies. Separate space for faculty workroom and parent volunteer groups. Wide corridors providing good, administrative control, student circulation, and full visibility. Large assembly area with group toilets for afterschool activities. Storage areas for textbooks, furniture, and school supplies. Separate space for faculty workroom and parent volunteer groups. Adequate Functional Attribute Classrooms Classroom sizes are Pre-K and K, < 1,000 ft2; grades 1 thru 5, <900 ft2; and grades 6 thru 12, < 850 ft2. Primary grades have access to sinks and drinking fountain in open classroom. Teaching station equipped with current teaching technologies. Gang lavatories for elementary grades. Core Facilities Corridors providing administrative control, student circulation, and partial visibility. Assembly area with group toilets for after-school activities. Storage areas for textbooks, furniture, and school supplies. Separate space for faculty workroom. 18 Not Adequate Poor Classroom sizes are Pre-K and K, < 900 ft2; grades 1 thru 5, < 800 ft2; and grades 6 thru 12, < 750 ft2. Primary grades do not have sinks and drinking fountain in classroom. Teaching station is not equipped with current teaching technologies or poorly located. Gang lavatories for elementary grades. Classroom sizes are Pre-K and K, < 800 ft2; grades 1 thru 5, < 700 ft2; and grades 6 thru 12, < 650 ft2. Primary grades do not have sinks and drinking fountain in classroom. Teaching station is not equipped with current teaching technologies or poorly located. Gang lavatories for elementary grades. Narrow corridors providing inadequate administrative control, poor student circulation, and poor visibility. Small assembly area without sufficient group toilets for afterschool activities. Limited storage areas for textbooks, furniture, and school supplies. Separate space for faculty workroom. Narrow corridors providing inadequate administrative control, poor student circulation, and poor visibility. Small assembly area without sufficient group toilets for afterschool activities. Limited storage areas for textbooks, furniture, and school supplies. Separate space for faculty workroom. Superior Good Adequate Not Adequate Specialty Instruction (Special Education, Summit) Classroom size Classroom size Classroom size Classroom size is between 850 ft2 between 750 ft2 between 650 ft2 less than 600 ft2. 2 2 2 and 1,000 ft . and 900 ft . and 750 ft . Accessible nonprivate facilities Accessible private Accessible private Accessible semifor proper facilities for proper facilities for proper private facilities restroom and restroom and restroom and for proper changing stations. changing stations. changing stations. restroom and Separate secure Separate secure changing stations. Time-out room is needed. Space is time-out room as time-out room as Separate secure inadequate and needed. Space is needed. Space is time-out room as flexible and meets flexible and meets needed. Space is does not meet the the needs of all the needs of all flexible and meets needs of all special instruction special instruction special instruction the needs of all requirements. requirements. special instruction requirements. requirements. English Language Learning (ESOL,Title III) Separate Separate Small or shared Small or shared classroom with classroom with space with space with between 700 ft2 between 500 ft2 adequate access inadequate to technology access to and 900 ft2 to and 700 ft2 to resources. Break- technology provide provide out space for resources. No specialized specialized specialize break-out space instruction for instruction for for specialized English language English language instruction. instruction. learning learning programs. programs. Instructional Resource Rooms Separate room Separate room Small or shared Small or shared with between 300 with between 200 space with space with ft2 and 500 ft2 to ft2 and 300 ft2 to adequate access inadequate to technology access to provide provide resources. Break- technology specialized specialized out space for resources. No instruction. instruction. break-out space Private office and Shared office and specialized for specialized storage space for storage space for instruction. instruction. instructional instructional resource staff. resource staff. Space is flexible and meets the instructional needs of students. Space has technologies required to meet needs of staff. 19 Poor Classroom size is less than 600 ft2. Accessible nonprivate facilities for proper restroom and changing stations. Time-out room is needed. Space is inadequate and does not meet the needs of all special instruction requirements. Small or shared space with inadequate access to technology resources. No break-out space for specialized instruction. Small or shared space with inadequate access to technology resources. No break-out space for specialized instruction. Superior Access control provided with security vestibule. Interior and exterior cameras covering all areas of building egress and ingress. Alarm system dials to call center in event of a breech in security. Classrooms exceed safe classrooms for schools standards. Separate areas dedicated to computer lab, study area, research area, and reading nook. Layout of media center allows for observation and is well lit with an abundance of natural light. Furnishings are comfortable and plentiful. State of the art technologies are available for use by students and instructors. Shelving is available for a great quantity of books and other research materials. Good Adequate Security Standards Access control Access control provided with provided without security vestibule. security vestibule. Interior and Interior and exterior cameras exterior cameras covering all areas covering all areas of building egress of building egress and ingress. and ingress. Alarm system Alarm system dials to call center dials to call center in event of a in event of a breech in security. breech in security. Classrooms meet Classrooms meet safe classroom for safe classroom for schools schools standards. standards. Separate areas dedicated to computer lab, study area, research area, and reading nook. Layout of media center allows for observation and is well lit with an abundance of natural light. Furnishings are comfortable and plentiful. Current technologies are available for use by students and instructors. Shelving is available for a great quantity of books and other research materials. Media Centers Areas dedicated to computer lab, study area, research area, and reading nook. Layout of media center allows for observation and has adequate lighting. Furnishings are comfortable and plentiful. Current technologies are available for use by students and instructors. Shelving is available for a good quantity of books and other research materials. 20 Not Adequate Poor Access control provided without security vestibule. Interior and exterior cameras covering all areas of building egress and ingress. Alarm system dials to call center in event of a breech in security. Classrooms meet safe classroom for schools standards. Access control provided without security vestibule. Interior and exterior cameras covering all areas of building egress and ingress. Alarm system dials to call center in event of a breech in security. Classrooms meet safe classroom for schools standards. Areas dedicated to computer lab, study area, research area, and reading nook. Layout of media center has adequate lighting and is difficult for overall observation of students. Furnishings are dated and need updated. Current technologies are available for use by students and instructors. Shelving is available for books and other research materials. Area is small and inefficient without separate designated areas for research, computer lab, and reading. Shelving and furniture is old and needs replaced. Less than minimal natural light and technologies available are outdated. Superior Separate areas dedicated to voice and instrumental instruction. Auditorium with stage equipped with performance lighting and seating. Abundance of storage for music equipment and art supplies. Separate room with kiln and exhaust. Sinks with available sediment and plaster trap. Abundance of natural light in the art area. Good Adequate Art and Music Areas Separate areas Shared areas for dedicated to voice voice and and instrumental instrumental instruction. instruction. Stage Auditorium with equipped with stage equipped performance with performance lighting and lighting and seating. Storage seating. Storage for music for music equipment and art equipment and art supplies. supplies. Separate room Separate room with kiln and with kiln and exhaust. Sinks exhaust. Sinks with available with available sediment and sediment and plaster trap. plaster trap. Limited natural Abundance of light in the art natural light in the area. art area. Health Services 800 or more 400 or more Less than 300 ft2 health suite with health suite with health room with three cots, private two cots, private one cot, private exam room, toilet, exam room, toilet, exam room, toilet, and private offices and office for and office for for nurse and nurse and nurse and physician. physician. physician. Location of the Location of the Location of the health office health office health office provides privacy provides privacy provides and confidentiality and confidentiality confidentiality. and a private and a private Secure storage consultation room. consultation room. for medical supplies and Secure storage Secure storage student for medical for medical medications. supplies and supplies and Meets minimum student student needs of student medications. medications. population. ft2 ft2 21 Not Adequate Poor No area dedicated to music and art instruction. Small stage equipped with limited seating capacity and lighting. Storage of music equipment and art supplies are kept on a cart and moved to classrooms as needed. Limited natural light in the art area. No area dedicated to music and art instruction. No stage area available and school has limited seating capacity. Storage for music equipment and art supplies is kept on a cart and moved to classrooms as needed. Little to no natural light in the art area. Less than 200 ft2 health room with a separate cot and semi-private exam room. Private office for nurse in health room. Secure storage for medical supplies and student medications. Meets minimum needs of student population. Less than 150 ft2 health room without a private exam room. No private office for nurse in health room. Secure storage for medical supplies and student medications. Meets minimum needs of student population. Superior Adequate serving lines, lighting, seating and space for the students being served. Kitchen has updated equipment and excellent work flow. Ample storage and prep area. Large gymnasium with seating, an abundance of space for student population, and community afterschool activities. Regulation sized primary and secondary courts. Secondary gymnasium for weight training and multipurpose space. Locker rooms and showers available for students and extracurricular teams. Plenty of organized storage with separate office for physical education instructors. Setup flexibility with lighting, sound system, and independent HVAC controls. Good Adequate Food Service Areas Adequate serving Adequate serving lines, lighting, lines, lighting, seating and space seating and space for the students for the students being served. being served. Kitchen has Kitchen updated equipment is equipment and outdated and good work flow. storage limited. Good storage and Layout is prep area. adequate. Not Adequate Poor Inadequate serving lines, lighting, seating and space for the students being served. Kitchen equipment needs replaced and layout is inefficient. Inadequate serving lines, lighting, seating and space for the students being served. Kitchen equipment needs replaced and layout is extremely inefficient. Storage is limited. Assembly, Physical Education Areas Large gymnasium Regulation sized Multipurpose with ample space gymnasium with room without for student minimum indoor regulation sized population and courts. Locker courts. Locker community afterroom and rooms are small school activities. showers available or not available. Secondary for current student Inadequate space multipurpose area population. No for student available. available auxiliary population and no Regulation sized or secondary community use court with gymnasium. space. Ceiling is auxiliary courts. Shared storage low and lighting is Locker rooms and and office area for inadequate. showers available physical Storage is small for students and education and inefficient. extracurricular instructors are Space is teams. Plenty of small and inadequate; a storage with inefficient. Set-up gymnasium is offices for flexibility, lighting, needed. physical and sound education system. instructors. Set-up flexibility with lighting, sound system, and independent HVAC controls. 22 Multipurpose room without regulation sized courts. Locker rooms are small or not available. Inadequate space for student population and no community use space. Ceiling is low and lighting is poor. Storage is small and inefficient. Space is poor and a gymnasium is needed. Superior Office suite with ample space for Principal, Assistant Principal, and Resource Officer. Separate secure storage space for student records in close proximity to offices. Separate work room, faculty dining, reception area, and staff toilets. Provisions for security. Layout of area is specifically designed for the instructional needs of the program. State of the art equipment available that will allow the most efficient use of all education resources. Area is safe and allows for excellent instruction. Good Adequate Not Adequate Administration Areas Office suite with Adequate office Inadequate office ample space for space for space for Principal, Principal, Principal, Assistant Assistant Assistant Principal, and Principal, and Principal, and Resource Officer. Resource Officer. Resource Officer. Separate secure Secure storage Secure storage storage space for space for student space for student student records in records in close records. Shared close proximity to proximity to work room and offices. Separate offices. Work faculty dinning. work room, faculty room, faculty Reception area dining, reception dining, reception does not have area, and staff area, staff toilets. appropriate toilets. Provisions Provisions for provisions for for security security. security. Technology Education Layout of area is Layout of area is Layout of area is specifically adequate to meet not ideal for designed for the the instructional delivery of instructional needs of the instructional needs of the program. program. program. State of Equipment is Equipment is the art equipment sufficient and outdated and available that will meets all current should be planned allow the most safety standards. for replacement. efficient use of all Area meets education minimum safety resources. Area is standards. Lack safe and allows of dedicated for good instruction area instruction. for programs. 23 Poor Inadequate office space for Principal, Assistant Principal, and Resource Officer. Secure storage space for student records. Shared work room and faculty dining. Reception area does not have appropriate provisions for security. Layout of area is inefficient and needs updating. Equipment is old and past useful life. Area meets minimum safety standards but must be updated. Lack of proper infrastructure to provide instructional programs. Superior Good Adequate Not Adequate Adjustments Analysis of energy management Entire mechanical Entire mechanical Adequate controls On off control, set point control, on off and set system has DDC system has DDC economizer controls, with CO2 controls, with CO2 point control, control, DDC with control for outside control for outside economizer control, DDC and mostly pneumatic air and overall air and overall controls. Basic energy efficiency. energy efficiency. pneumatic, CO2 control for outside programming Efficient systems Efficient systems Energy audit air and overall include include, heat energy efficiency. shows excess geothermal, heat recovery, VAV, energy usage. recovery, VAV, and high and variable flow efficiency fuel refrigerant burners. systems. Open School Characteristics Classrooms are Classrooms are Classrooms Open classrooms all self-contained self-contained partitions are not and corridor with with separate with open corridor floor to ceiling. sound proof closed corridors. connecting Sliding partitions partitions to Partitions are floor classrooms. separating 2 or separate spaces. to ceiling. Partitions are floor more spaces. Acoustics is to ceiling. distracting to students. Age of School 0 to 9 years 10 to 19 years 20 to 29 years 30 to 39 years Enrollment vs. State Rated Capacity (Elementary) 0 to 89% 90 to 98% 99 to 107 % 108 to 114 % Enrollment vs. State Rated Capacity (Middle) 0 to 89% 90 to 98% 99 to 107 % 108 to 114 % Enrollment vs. State Rated Capacity (High) 0 to 94% 95 to 99% 100 to 104 % 105 to 114 % Site Size (Elementary) Over 15 acres 12 to 14 acres 8 to 11 acres 4 to 7 acres Poor On off control, set point control, economizer control, DDC with mostly pneumatic controls. Basic programming. Energy audit shows excess energy usage. Open classrooms and corridor with no partitions to separate spaces. Acoustics is distracting to students and faculty. Over 40 years Over 115% Over 115% Over 115% Less than 3 acres Over 30 acres 25 to 29 acres Site Size (Middle) 20 to 24 acres 10 to 19 acres Less than 9 acres Over 60 acres 50 to 59 acres Site Size (High) 40 to 49 acres 30 to 39 acres Less than 29 acres 24 25 85 85 85 95 85 95 95 85 85 95 95 95 55 85 85 55 Hickory Elementary Lincolnshire Elementary Maugansville Elementary Old Forge Elementary Pangborn Elementary Paramount Elementary Pleasant Valley Elem. Potomac Heights Elem. Rockland Woods Elem. Ruth Anne Monroe Primary Salem Ave. Elementary Sharpsburg Elementary Smithsburg Elementary Williamsport Elementary Winter Street Elem. * Overall Scoring Scale: 85 85 Hancock Elementary 55 95 85 65 85 95 95 85 95 75 95 85 85 65 75 95 95 85 65 95 85 Greenbrier Elementary 85 Emma K. Doub Elem. 95 85 Eastern Elementary 80 85 75 Conococheague Elem. 85 Funkstown School 85 Clear Spring Elementary 95 Fountaindale Elementary 85 Cascade Elementary 75 95 85 85 3 Exterior Conditions (Doors) Fountain Rock Elem. 95 Boonsboro Elementary 1 Site Layout, parking, bus dropoff,walkways Bester Elementary Weight Factor SCHOOL NAME Exterior Conditions (Windows, Walls) Roof Conditions 65 87 95 95 85 96 95 95 97 91 95 83 95 89 75 80 97 79 95 71 88 77 76 85 84 76 95 3 Interior Conditions (Walls, Ceiling, Etc.) 65 95 85 75 85 95 95 85 85 85 95 75 95 85 75 85 75 85 75 85 90 85 65 85 95 85 95 2 85 95 85 55 85 95 95 85 85 85 95 85 95 85 85 85 85 85 85 85 75 85 65 85 95 85 95 2 Flooring (Tile, Carpet. Etc.) 95 - 100 = Superior 55 85 95 55 95 95 95 85 85 85 95 65 95 85 75 65 85 95 95 75 95 85 55 85 95 75 95 3 Electrical Distribution (Outlets, Power) 60 85 85 55 85 95 95 75 80 85 90 70 95 85 75 65 70 65 60 75 70 85 60 85 85 80 95 3 Fire and Life Safety (Sprinkler, Alarm) Lavatories 55 85 85 70 95 95 95 75 75 85 95 75 95 85 75 75 75 75 75 75 85 85 60 95 75 80 95 3 75 85 85 75 85 95 95 85 75 85 95 75 95 85 85 85 85 85 85 85 75 85 80 85 95 85 95 1 Communications Systems (Phone, Intercom 85 - 94 = Good 75 85 85 75 90 95 95 80 75 95 90 85 95 85 75 75 75 75 70 70 75 85 75 95 85 85 95 3 Potable water 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 75 85 85 75 85 85 50 85 85 85 95 1 Heating Systems Air Conditioning Systems (Central Plant) n/a 55 85 85 85 90 75 85 95 95 95 80 85 95 95 95 85 75 55 85 95 55 95 95 85 55 85 95 65 95 3 Air Handling or RTU Systems 85 90 n/a 95 n/a 95 n/a 95 n/a 95 85 95 95 n/a n/a 95 n/a 95 80 n/a 85 n/a 95 95 1 85 85 75 75 85 95 95 85 75 75 95 85 95 85 75 75 75 65 85 85 70 75 75 85 95 65 95 1 Playgrounds, Athletic Fields 75 - 84 = Adequate 65 85 75 95 95 95 95 85 95 85 95 95 95 75 75 85 85 95 95 95 95 85 75 85 90 95 95 3 Lighting 60 85 85 65 90 95 95 80 75 85 95 75 95 85 85 80 70 95 70 95 95 85 65 85 95 75 95 2 Accessibility (A.D.A.) Classrooms, Core Facilities 55 95 85 65 95 95 95 75 85 85 95 65 95 85 75 75 65 85 65 65 75 85 65 85 75 75 95 2 Specialty Instruction (Summit,Special Ed.) 55 85 85 75 95 95 95 85 85 85 95 55 95 85 85 75 85 85 75 75 85 95 70 75 85 85 95 1 55 75 55 n/a 55 95 95 55 n/a 55 n/a n/a 95 55 55 n/a 55 85 65 n/a 65 95 n/a n/a n/a 65 95 1 ELL ESOL 1 Instructional Resource Rooms 65 85 85 65 95 95 95 55 75 85 95 55 85 85 75 75 85 65 65 75 75 95 75 85 85 75 95 65 - 74 = Not Adequate 55 85 95 65 95 95 95 65 65 95 95 75 95 85 75 65 65 75 55 85 65 95 65 95 75 65 95 1 Security Standards 85 85 85 75 85 95 95 85 75 85 95 85 95 85 75 85 85 85 85 85 75 85 75 85 85 85 95 1 Media Centers Art, Music Areas 65 95 75 75 85 95 85 75 85 85 95 85 95 75 65 75 75 65 85 75 65 85 55 75 85 75 95 1 55 75 65 65 85 95 85 65 65 65 95 65 95 65 75 55 55 55 75 65 55 65 65 65 75 65 95 1 Health Services 1 Food Service Areas 65 85 75 65 75 95 95 65 55 75 95 75 95 55 65 65 65 65 55 95 75 65 55 75 65 65 95 64 or less = Poor 65 85 85 75 85 95 85 75 85 85 85 75 85 85 65 85 85 85 75 65 75 75 65 85 75 85 95 1 Assembly/Phys.Ed. Areas 65 85 85 75 85 95 95 65 65 75 95 75 95 75 75 65 75 65 75 75 75 85 65 75 65 75 95 1 Administration Areas 55 95 85 55 95 95 95 65 75 85 95 65 95 85 65 55 85 65 65 65 65 85 55 85 65 75 95 1 Technology Education n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a 1 Analysis of energy management 75 85 85 75 85 95 95 85 85 85 85 80 95 85 85 85 80 75 75 85 85 85 65 85 80 85 95 2 75 95 95 85 95 95 95 65 75 95 95 65 95 95 55 65 55 85 85 55 75 95 75 95 75 95 95 1 Open school characteristics ADJUSTMENTS 55 85 85 55 95 95 95 55 75 75 95 55 95 85 65 65 55 55 55 55 55 75 55 85 55 75 95 3 Age of School FUNCTIONAL 75 65 85 65 95 85 95 95 75 85 75 95 95 75 85 95 95 95 75 95 75 95 95 85 95 65 95 3 Enrollment vs. State Rated Capacity PHYSICAL Site Size 55 95 85 65 85 95 85 75 85 75 95 95 95 85 75 95 75 85 85 95 75 95 85 75 75 75 85 1 SCORING Functional Rating Physical Ratings 97% 5460 74% 4530 80% 4601 83% 4803 99% 5190 73% 4339 98% 5480 81% 4792 75% 4420 75% 4280 77% 4406 78% 4618 75% 4430 77% 4383 75% 4659 88% 4901 68% 3793 84% 4855 80% 4712 79% 4523 69% 92% 91% 77% 94% 65% 3640 91% 4991 83% 4900 72% 4000 90% 5150 100% 100% 5378 100% 89% 88% 92% 99% 85% 100% 90% 83% 80% 85% 87% 85% 85% 91% 89% 72% 92% 94% 85% 100% 100% 5500 Category Points 57 58 58 57 58 57 58 57 57 57 57 56 58 58 58 57 57 57 58 56 58 58 56 57 56 58 58 69% 91% 89% 75% 94% 99% 99% 84% 86% 89% 96% 82% 99% 88% 81% 80% 82% 86% 81% 83% 85% 90% 73% 90% 89% 83% 100% 2014 Overall Rating* PRIOR YEAR SCORING Total Points 2014 Facilities Assessment 71% 92% 89% 75% 94% 100% 99% 84% 87% 90% 97% 83% 99% 88% 81% 80% 83% 85% 83% 84% 87% 90% 74% 89% 89% 83% 73% 2013 Overall Rating* 26 85 75 85 85 85 95 95 75 North Hagerstown High Smithsburg High South Hagerstown High Wash. Co. Tech. High Williamsport High Antietam Academy Farview Outdoor Center Marshall Street Center * Overall Scoring Scale: 85 Hancock Middle/High 85 Western Heights Middle 85 85 Springfield Middle Clear Spring High 75 Smithsburg Middle 75 65 Northern Middle 65 75 E. Russell Hicks Middle Boonsboro High 85 Barbara Ingram School 85 Clear Spring Middle 1 Site Layout, parking, bus dropoff,walkways Boonsboro Middle Weight Factor SCHOOL NAME Exterior Conditions (Doors) 75 75 95 95 65 85 95 85 95 75 95 95 85 90 65 95 95 95 75 3 Exterior Conditions (Windows, Walls) Roof Conditions 81 78 97 75 97 75 75 90 95 65 97 95 84 91 84 85 92 95 65 3 Interior Conditions (Walls, Ceiling, Etc.) 70 75 95 85 75 85 75 85 65 85 75 95 80 85 85 85 85 85 85 2 75 65 95 85 85 85 85 85 75 85 75 95 80 85 85 85 75 85 85 2 Flooring (Tile, Carpet. Etc.) 95 - 100 = Superior 75 75 95 95 75 85 95 85 95 85 95 95 75 95 65 95 95 95 75 3 Electrical Distribution (Outlets, Power) 65 75 95 70 60 85 95 75 75 75 75 95 75 80 65 75 95 75 70 3 Fire and Life Safety (Sprinkler, Alarm) Lavatories 75 75 95 65 65 85 75 85 65 75 75 95 75 85 85 85 75 75 85 3 85 85 95 85 85 85 85 85 85 85 85 95 85 85 85 85 85 85 85 1 Communications Systems (Phone, Intercom 85 - 94 = Good 95 65 95 85 75 65 75 85 65 85 95 95 85 75 85 85 85 80 85 3 Potable water 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 85 1 Heating Systems Air Conditioning Systems (Central Plant) 85 n/a n/a 85 n/a 85 85 85 75 n/a n/a n/a 75 95 80 90 85 n/a n/a 1 Air Handling or RTU Systems 75 65 95 75 65 85 75 85 75 95 80 95 65 75 75 75 95 95 95 3 95 85 85 85 n/a 85 75 95 65 85 75 n/a 85 85 65 75 85 75 85 1 Playgrounds, Athletic Fields 75 - 84 = Adequate 95 75 95 85 65 85 95 85 75 85 95 95 75 75 85 85 85 95 95 3 Lighting 65 75 95 85 95 85 65 85 85 85 85 95 65 65 85 95 95 85 85 2 Accessibility (A.D.A.) Classrooms, Core Facilities n/a n/a 95 75 65 75 75 75 75 75 75 95 65 75 85 75 75 85 75 2 Specialty Instruction (Summit,Special Ed.) 55 85 95 75 85 85 75 65 75 75 65 95 75 75 85 75 75 85 75 1 n/a n/a n/a 85 55 55 55 55 55 55 55 n/a 65 55 75 85 75 55 55 1 ELL ESOL 1 Instructional Resource Rooms n/a 85 95 55 75 65 85 65 65 75 75 95 65 65 75 75 55 65 75 65 - 74 = Not Adequate 95 65 95 55 85 65 65 95 75 65 55 95 65 55 55 65 65 65 75 1 Security Standards 75 75 95 85 85 85 85 85 75 85 85 Art, Music Areas 75 n/a 95 65 85 75 75 75 75 75 85 85 75 85 85 65 75 75 75 1 75 75 95 75 65 85 65 55 65 55 65 95 75 55 65 55 75 55 65 1 Health Services 1 Food Service Areas 65 65 95 75 65 85 75 85 65 65 75 55 65 55 55 85 65 75 85 64 or less = Poor n/a n/a n/a 85 75 85 65 85 85 75 75 n/a 75 85 75 75 75 75 75 85 75 1 Media Centers 85 85 75 85 75 75 1 Assembly/Phys.Ed. Areas 65 85 85 65 n/a 65 65 65 65 55 75 n/a 85 85 85 75 65 75 85 1 Administration Areas 75 75 95 75 85 75 85 75 75 85 65 95 75 75 85 85 75 85 75 1 Technology Education 85 65 n/a 75 65 75 75 75 85 75 75 65 65 75 85 75 65 95 75 1 Analysis of energy management 75 65 95 75 80 85 65 75 75 75 75 95 75 75 85 75 85 85 85 2 75 85 95 95 85 95 95 95 85 65 85 95 75 65 65 75 95 65 65 1 Open school characteristics ADJUSTMENTS 65 65 95 55 55 85 55 75 55 65 65 95 65 65 65 65 55 65 65 3 Age of School FUNCTIONAL 95 95 95 85 95 65 85 85 75 95 85 85 85 95 65 95 95 95 95 95 85 65 85 95 95 65 95 95 85 1 Site Size 95 95 95 75 95 85 85 95 95 3 Enrollment vs. State Rated Capacity PHYSICAL Physical Ratings 84% 77% 97% 86% 80% 87% 87% 90% 84% 86% 90% 99% 82% 87% 82% 89% 92% 91% 87% SCORING Functional Rating 67% 4198 71% 3994 99% 5191 78% 4640 76% 4201 80% 4745 77% 4625 76% 4820 76% 4555 75% 4550 77% 4711 89% 4960 76% 4512 76% 4623 83% 4617 79% 4750 76% 4856 81% 4825 78% 4625 Category Points 55 54 55 59 56 59 59 59 59 58 58 54 59 59 59 59 59 58 58 81% 79% 99% 84% 80% 85% 83% 87% 82% 83% 86% 97% 81% 83% 83% 86% 87% 88% 85% 2014 Overall Rating* PRIOR YEAR SCORING Total Points 2014 Facilities Assessment 82% 79% 99% 83% 80% 85% 83% 87% 81% 84% 84% 97% 82% 83% 83% 86% 82% 87% 85% 2013 Overall Rating* PREVENTIVE MAINTENANCE MECHANICAL EQUIPMENT SCOPE This section is intended to provide definition of preventive maintenance and repair service to the Washington County Public School’s mechanical equipment located at 50 facilities. The Maintenance Department received and completed 774 work orders for preventive maintenance in FY2014. The preventive maintenance items as outlined on Schedules 1 – 13 are designed to maintain the mechanical equipment to a high level of performance and to extend its efficient operating life and cover the mechanical equipment located at all Washington County Public School facilities: Antietam Academy Barbara Ingram School for the Arts Boonsboro Elementary Boonsboro Middle Boonsboro High Cascade Elementary Clear Spring Elementary Clear Spring Middle Clear Spring High Conococheague Elementary E. Russell Hicks Middle Eastern Elementary Emma K. Doub Elementary Fairview Outdoor Center Fountain Rock Elementary Fountaindale Elementary Funkstown Elementary Greenbrier Elementary Hancock Elementary Hancock Middle-Senior High Hickory Elementary Lincolnshire Elementary Marshall St. Education Center Maugansville Elementary Northern Middle North Hagerstown High Old Forge Elementary Pangborn Elementary Paramount Elementary Pleasant Valley Elementary Potomac Heights Elementary Rockland Woods Elementary Ruth Ann Monroe Primary Salem Avenue Elementary Sharpsburg Elementary Smithsburg Elementary Smithsburg Middle Smithsburg High South Hagerstown High Springfield Middle Wash. Co. Tech High Western Heights Middle Williamsport Elementary Williamsport High Winter Street Elementary Seventy-Three (73) Relocatable Buildings 27 STEAM BOILERS SCHEDULE 1 Perform the indicated preventive maintenance at the following schools: Winter Street Elementary PRE-SEASON INSPECTION AND SEASONAL START-UP 1. 2. 3. 4. 5. 6. Inspect, clean, and lubricate the oil burner and combustion control equipment. Check draft fans. Check condensation pumps. Check auxiliary oil pump. Check auxiliary equipment operation. Start oil burner, check operating controls, test safety controls, and pressure relief valves. 7. Perform combustion tests and adjust oil burner for maximum efficiency. MONTHLY PREVENTIVE MAINTENANCE INSPECTION (Nov., Dec., Jan., Feb., Mar.) 1. 2. 3. 4. 5. Check condensation pumps. Inspect boiler and burner and adjust. Test low water cut-off and pressure relief valves. Check operating and safety controls. Perform efficiency test. 28 HOT WATER BOILER SCHEDULE 2 Perform the indicated preventive maintenance at the following schools: Antietam Academy Bester Elementary Boonsboro Elementary Boonsboro High Cascade Elementary Clear Spring Elementary Conococheague Elementary E. Russell Hicks Middle Eastern Elementary Emma K. Doub Elementary Fairview Outdoor Center Fountaindale Elementary Funkstown Elementary Hancock Middle-High Lincolnshire Elementary Marshall St. Education Center Maugansville Elementary North Hagerstown High Northern Middle Pangborn Elementary Paramount Elementary Pleasant Valley Elementary Rockland Woods Elementary Ruth Ann Monroe Primary Salem Avenue Elementary Sharpsburg Elementary Smithsburg Elementary South Hagerstown High Williamsport Elementary Williamsport High PRE-SEASON INSPECTION AND START-UP 1. Inspect, clean and lubricate the oil or dual fuel burner and combustion control equipment. 2. Check auxiliary oil pump. 3. Check draft fans. 4. Check auxiliary equipment operation. 5. Start burner, check operating controls, test safety controls and pressure relief valves. 6. Perform combustion tests and adjust burner for maximum efficiency. 7. Dual fuel burners shall be checked on both oil and gas. MONTHLY PREVENTIVE MAINTENANCE INSPECTION (Nov., Dec., Jan., Feb., Mar.) 1. 2. 3. 4. Inspect boiler and burner and adjust. Dual fuel burners shall be checked on both oil and gas. Perform combustion test. Check operating and safety controls. 29 GAS OR OIL FIRED HOT WATER HEATERS SCHEDULE 3 Perform the indicated preventive maintenance at the following schools: Antietam Academy Bester Elementary Boonsboro High Clear Spring Elementary Clear Spring High E. Russell Hicks Middle Eastern Elementary Hancock Middle High Lincolnshire Elementary Maugansville Elementary North Hagerstown High Northern Middle Paramount Elementary Ruth Ann Monroe Primary Smithsburg High South Hagerstown High Springfield Middle Wash. Co. Tech High Western Heights Middle Williamsport Elementary Williamsport High Winter Street Elementary ANNUAL INSPECTION 1. 2. 3. 4. Check operating controls. Clean burners. Lubricate controls. Check operation for efficiency. 30 RECIPROCATING AND ROTARY CHILLERS SCHEDULE 4 PRE-SEASON INSPECTION Perform the indicated preventive maintenance at the following schools: Boonsboro Elementary Center for Education Services Clear Spring Elementary E. Russell Hicks Middle Eastern Elementary Emma K. Doub Elementary Fountaindale Elementary Funkstown Elementary Hancock Elementary Hickory Elementary Lincolnshire Elementary Marshall St. Education Center Maugansville Elementary North Hagerstown High Pangborn Elementary Pleasant Valley Elementary Rockland Woods Elementary Salem Avenue Elementary Sharpsburg Elementary Smithsburg Elementary Smithsburg Middle Western Heights Middle Williamsport Elementary Williamsport High PRE-SEASON INSPECTION 1. 2. 3. 4. 5. 6. Check and inspect for refrigerant leaks. Check compressor oil level. Change oil and refrigerant filter drier as required. Perform Mega ohm test hermetic motor. Check compressor crankcase heater operation. Inspect electrical connections, contactors, relays and all operating and safety controls. 7. Check vibration eliminators. Replace or adjust as required. 8. Check belts, sheaves, and coupling alignment. Replace and adjust as required. 9. Fill and purge air from chilled water systems. 10. Inspect water-regulating valves and repair as may be required. 11. Provide refrigerant and repair all refrigerant leaks. 12. Follow all EPA, state, and local regulations for refrigerant handling. 13. Check air condensing coils and clean at least once per year. 14. Clean strainers including strainer in blow-down joints at least once a year. 31 SEASONAL START-UP 1. Check auxiliary equipment operation. 2. Review manufacturer’s recommendation for start-up. 3. Energize crankcase heater per manufacturer’s recommendation for crankcase warm-up. 4. Check and test all operating and safety controls. 5. Start chilled water pump, condenser water pump, and cooling tower. 6. Start water chiller. 7. Check refrigerant charge, oil level, and oil pressure. 8. Analyze refrigerant sample after any compressor burnout. MONTHLY PREVENTIVE MAINTENANCE INSPECTION (May, June, July, August, September) 1. Log all operating conditions. 2. Check for leaks, refrigerant and water. 3. Follow all EPA, state, and local regulations for refrigerant recovery, reclamation, and charging. 4. Inspect chiller and make adjustments as required. 5. Cycle operating controls and check capacity controls. SEASON END INSPECTION 1. Drain water from all parts of systems that are likely to freeze during the winter season. 2. Repair frozen coils and pipes on chilled water systems. 3. Clean chiller condenser and evaporator tube bundles. 4. Clean and paint external surfaces as required. 32 CENTRIFUGAL CHILLERS SCHEDULE 5 Perform the indicated preventive maintenance at the following schools: E. Russell Hicks Middle North Hagerstown High Northern Middle South Hagerstown High Springfield Middle Smithsburg High PRE-SEASON INSPECTION 1. Check main starter and control panel. 2. Check system for refrigerant leaks. 3. Follow all EPA, state, and local regulations for refrigerant handling. 4. Conduct mega ohm test on compressor motor and oil pump motor. 5. Brush condenser tubes at least once a year. 6. Change oil and filters. 7. Check operation of purge unit. 8. Clean purge drum and oil separator. 9. Change oil in purge pump motor and change belt. 10. Lubricate purge pump motor and change belt. 11. Lubricate inlet valve linkage. 12. Check oil sump heater operation. SEASONAL START-UP 1. Check auxiliary equipment operation. 2. Check refrigerant and oil operation. 3. Check sump heater and purge pump oil heater. 4. Adjust and check all operating and safety controls. 5. Fill chilled water system. 6. Purge air from system. 7. Start chilled water pump. 8. Start water chiller. 9. Check and adjust refrigerant controls. 10. Check purge unit operation. 33 MONTHLY PREVENTIVE MAINTENANCE INSPECTION (May, June, July, Aug., Sept.) 1. 2. 3. 4. 5. 6. 7. Check chiller for leaks. Inspect chiller and adjust as required. Follow all EPA, state and local regulations for refrigerant handling. Check operations of purge. Check oil level. Check electrical connections, contactors, and relays. Check operating and safety controls. END OF SEASON SHUTDOWN 1. 2. 3. 4. 5. 6. Turn off water chiller. Turn off chilled water pump and condenser water pump. Drain chilled water system. Clean strainers. Drain water from all parts of the systems to prevent freeze damage. Repair frozen coils and pipes on the chilled water system. 34 COOLING TOWERS SCHEDULE 6 Perform the indicated preventive maintenance at the following schools: E. Russell Hicks Middle Emma K. Doub Elementary Funkstown Elementary Marshall Street Center North Hagerstown High Northern Middle Sharpsburg Elementary Smithsburg High South Hagerstown High Springfield Middle Western Heights Middle Williamsport High START-UP INSPECTION 1. Remove all debris from condenser unit and flush as required. 2. Check and clean all strainers, bleed, over-flow and drain valves. 3. Check belts, motor sheaves and motor mounts. Replace and adjust as required. 4. Lubricate fan and motor bearings per manufacturer’s recommendations. 5. Change oil in gear reducer assembly. 6. Check float assembly and check for proper operation. 7. Maintain water level in cooling towers so as not to lose water from overflow. 8. Check motor operating conditions. 9. Inspect electrical connections, contactors, relays and operating and safety controls. 10. Check nozzles and clean or replace as required. MONTHLY PREVENTIVE MAINTENANCE INSPECTION (May, June, July, Aug., Sept.) 1. 2. 3. 4. 5. Inspect fan motor, belts, and couplings. Check oil level in gear reducer. Add oil as required. Check intake strainer, bleed and overflow valves. Check operating conditions and adjust as required. Check fan motor and fan blade on all air-cooled equipment. SEASON END INSPECTION 1. Drain water from cooling tower. 2. Clean strainers and spray nozzles. 35 AIR COOLED CONDENSERS SCHEDULE 7 Perform the indicated preventive maintenance at the following schools: Boonsboro Elementary Center for Education Services Clear Spring Elementary Eastern Elementary Fountaindale Elementary Hancock Elementary Hickory Elementary Lincolnshire Elementary North Hagerstown High Pangborn Elementary Pleasant Valley Elementary Rockland Woods Elementary Salem Avenue Elementary Smithsburg Elementary Smithsburg Middle Williamsport Elementary START-UP INSPECTION 1. Check and clean condenser coils at least once a year. 2. Straighten fins, as required. 3. Remove all debris from within and around unit. 4. Check and clean fan blades as required. 5. Check belts, sheaves, and mounts. Replace and adjust as required. 6. Lubricate fan and motor bearings. 7. Check for refrigerant leaks. 8. Check vibration eliminators. Replace or adjust as needed. 9. Check motor operation. 10. Check and test all operating and safety controls. 11. Inspect electrical connections, contactors, relays, operating and safety controls. 12. Check operation. MID-SEASON INSPECTION 1. Check belts, sheaves, and bearings. 2. Check for refrigerant leaks. Provide refrigerant, repair as needed following all EPA, state, and local regulations for recovery, reclamation, and charging. 3. Check coils and straighten fins. 4. Lubricate fan and motor bearings. 5. Check operating condition and adjust as required. 36 DX AIR HANDLERS AND ROOF TOP UNITS SCHEDULE 8 This schedule includes any self-contained DX package units and DX split system air handlers (air and water-cooled). Perform the indicated preventive maintenance at the following schools: Boonsboro Elementary Clear Spring Elementary E. Russell Hicks Middle Eastern Elementary Emma K. Doub Elementary Fountaindale Elementary Funkstown Elementary Hancock Middle High Lincolnshire Elementary Maugansville Elementary Northern Middle Pangborn Elementary Paramount Elementary Rockland Woods Elementary Sharpsburg Elementary Smithsburg Elementary South Hagerstown High Williamsport Elementary Williamsport High ANNUAL INSPECTION 1. Lubricate and adjust associated dampers and linkage to insure proper operation (package units only). 2. Check and clean all condensate pans and drains. 3. Visually inspect all DX evaporator and condenser coils and clean as required associated with the unit. 4. Check compressor oil level and mega ohm motor. 5. Check for refrigerant leaks. 6. Provide refrigerant and repair leaks as needed. 7. Follow all EPA, state, and local regulations for recovery, reclamation, and charging. 8. Perform any other preventative maintenance procedures recommended by manufacturer. 9. Verify operation of dampers and damper controls on all package units only. 10. Inspect and lubricate condenser fan and motor bearings. 11. Verify operation of crankcase heaters. 37 HEATING AND COOLING PUMPS SCHEDULE 9 Perform the indicated preventive maintenance at the following schools: Antietam Academy Bester Elementary Boonsboro Elementary Boonsboro High Cascade Elementary Center for Education Services Clear Spring Elementary Conococheague Elementary E. Russell Hicks Middle Eastern Elementary Emma K. Doub Elementary Fountaindale Elementary Funkstown Elementary Hancock Elementary Hancock Middle High Lincolnshire Elementary Marshall Street Center Maugansville Elementary North Hagerstown High Northern Middle Pangborn Elementary Paramount Elementary Rockland Woods Elementary Ruth Ann Monroe Primary Pleasant Valley Elementary Salem Avenue Elementary Sharpsburg Elementary Smithsburg Elementary Smithsburg Middle Smithsburg High Springfield Middle South Hagerstown High Williamsport Elementary Williamsport High ANNUAL INSPECTION 1. Check motor operation conditions. 2. Check visually pump alignment and pump coupling. 3. Tighten all nuts and bolts. 4. Check motor mount and vibration pads. 5. Lubricate pump bearing per manufacturer’s recommendations. 6. Lubricate motor bearing per manufacturer’s recommendations. 7. Inspect pump packing. 8. Inspect pump mechanical seals. 9. Replace as required. 10. Inspect electrical connection and contactors. 11. Repair or replace as required. 38 PACKAGED HEATING & COOLING SYSTEMS (Roof Top Units, Unit Ventilators, Air Handling Units, Duct and Unit Reheats) SCHEDULE 10 This schedule includes all DX roof top units, unit ventilators, and air-handling units and shall include any other air handlers and unit ventilators within the listed school. SEMI-ANNUAL INSPECTION Perform the indicated preventive maintenance at the following schools: Antietam Academy Boonsboro Middle Boonsboro High Center for Education Services Clear Spring Middle Clear Spring High Fountain Rock Elementary Greenbrier Elementary Hancock Elementary Hickory Elementary Maugansville Elementary Old Forge Elementary Pangborn Elementary Potomac Heights Elementary Rockland Woods Elementary Ruth Ann Monroe Primary Salem Avenue Elementary Smithsburg Middle Smithsburg High Springfield Middle Wash. Co. Tech High Western Heights Middle Winter Street Elementary HEATING – PRE-SEASON INSPECTION 1. 2. 3. 4. 5. 6. Check, clean, and lubricate the burner and combustion control equipment. Check burner sequence of operation and combustion air equipment. Check and clean all strainers and hand valves. Check and clean all humidifiers. (Potomac Heights Elementary ONLY) Check all combustion chambers. Check electrical connections, contactors, relays, operating and all safety controls. 7. Check all electric re-heat coils. Repair or replace as needed. 8. Check fan belts. 9. Inspect visually all DX coils and clean as required. 39 COOLING – PRE-SEASON INSPECTION 1. 2. 3. 4. Check and clean all strainers. Check and clean condensate pans and drains. Check and clean all humidifiers. (Potomac Heights Elementary ONLY) Check all electrical connections, contactors, relays, operating and safety controls. 5. Check unit operation and adjust as required. 6. Check compressor oil level, mega ohm motor, check crankcase heater operation. 7. Add oil as needed. 8. Start compressor, check operation, and adjust as needed. 9. Check for refrigerant leaks. 10. Provide refrigerant and repair leaks as needed. 11. Follow EPA, state, and local regulations for recovery, reclamation, and charging. 12. Inspect visually all DX evaporator and condenser coils and clean as required. 13. Inspect and lubricate condenser fan and motor bearings. 40 COMMUNICATION ROOM AIR CONDITIONING UNITS SCHEDULE 11 Perform the indicated preventive maintenance at the following schools: Antietam Academy Bester Elementary Boonsboro Elementary Boonsboro Middle Boonsboro High Center for Education Services Clear Spring Elementary Clear Spring Middle Clear Spring High E. Russell Hicks Middle Eastern Elementary Fountaindale Elementary Hancock Middle High Marshall St. Education Center Maugansville Elementary North Hagerstown High Northern Middle Pangborn Elementary Paramount Elementary Potomac Heights Elementary Rockland Woods Elementary Ruth Ann Monroe Primary Salem Avenue Elementary Smithsburg Elementary Smithsburg High Smithsburg Middle South Hagerstown High Springfield Middle Western Heights Middle Williamsport Elementary Winter Street Elementary Wash. Co. Tech. High ANNUAL INSPECTION 1. 2. 3. 4. 5. 6. 7. 8. 9. Inspect and lubricate fan and motor bearings. Check and clean all condensate pans and drains. Inspect visually all condenser coils and clean as required. Inspect all electrical connections, contactors, relays and operating/safety controls associated with the unit. Check compressor oil level and perform mega ohm motor test. Check for refrigerant leaks. Provide refrigerant and repair leaks as needed. Follow all EPA, state and local regulations for refrigerant handling. Perform any other preventative maintenance procedures recommended by manufacturer. 41 WATER TREATMENT (Cooling Towers and Chilled Water Systems Only) SCHEDULE 12 Perform the indicated preventive maintenance at the following schools: Cooling Tower Treatment Bester Elementary Center for Education Services E. Russell Hicks Middle Emma K. Doub Elementary Funkstown Elementary Marshall Street Education Center North Hagerstown High Northern Middle Sharpsburg Elementary Smithsburg High South Hagerstown High Springfield Middle Western Heights Middle Williamsport High Chiller Treatment Bester Elementary Boonsboro Elementary Clear Spring Elementary Eastern Elementary Emma K. Doub Elementary Hancock Elementary Hickory Elementary Marshall St. Education Center Maugansville Elementary Lincolnshire Elementary North Hagerstown High Northern Middle Pangborn Elementary Pleasant Valley Elementary Rockland Woods Elementary Salem Avenue Elementary Smithsburg Elementary Smithsburg Middle Smithsburg High South Hagerstown High Springfield Middle Western Heights Middle Williamsport High MONTHLY INSPECTION (May, June, July, Aug., Sept.) 1. 2. 3. 4. Analyze chilled water and condenser water for proper treatment. Service all chemical bleed and feed equipment. Adjust equipment controls to obtain proper operation. Inspect visually the open portions of the system for evidence of scale, algae, slime, and corrosion. 5. Furnish all treatment chemicals. 6. Slug treat biocide and antifoam to control slime and algae growth. 7. Inventory the remaining treatment chemicals and re-order as needed. 42 43 44 45 46 47 48 49 50 51 Work Order Unscheduled repairs are identified and managed via the work order system. 6,631 work orders for unscheduled maintenance and 774 preventive maintenance work orders were generated in fiscal year 2014 totaling 7,405 work orders. 6,340 work orders were completed and 1,070 are still in process. These work orders are spread over 18 different functional groups that span 50 buildings containing 3.3 million square feet on 1,175 acres. The work order system is an internet-based computer application that allows access to users wherever there is an internet connection. The system provides feedback to users on the status of work order as it flows from request initiator to maintenance worker. The system provides expected completion dates, parts required, estimated hours required to perform the task, and reason when request is declined. A preventive maintenance module was added to the work order system to plan and schedule maintenance for equipment and building systems on a recurring basis. The system allows the user to define the task procedures, frequency of the task, tools required, and parts required to perform preventive maintenance by equipment and location. Through the software a more detailed history of resources expended to maintain school system assets will be achieved. The Washington County Public School System has a twenty-four hour emergency notification procedure. If there is an emergency in any of the school buildings, a message is sent to the appropriate stakeholders notifying them of the circumstances of the emergency, which facilitates a timely response for emergency repairs. 52 Work Order Summary Total Work Orders Created and Completed JULY 1, 2013 THROUGH JUNE 30, 2014 DEPARTMENT -- TRADE TOTALS CARPENTRY 1,096 CONTRACTOR 61 CUSTODIAL EQUIPMENT REPAIRS 976 ELECTRICAL 1010 ELEVATORS/LIFTS 6 ENVIRONMENTAL IAQ 56 GENERAL DELIVERY 469 HVAC 357 LANDSCAPE/TREES 101 MASONRY 166 PAINTING 51 PESTICIDE 178 PLUMBING 560 ROOFING 150 KEYS AND LOCKS 286 MISCELLANOUS 20 PREVENTIVE MAINTENANCE 774 VANDALISM 23 TOTAL COMPLETED WORK ORDERS 53 6,340 School Vandalism REPORTED TO THE OFFICE OF MAINTENANCE AND OPERATIONS 2013-2014 PROPERTY DAMAGE $ 6,655.83 GLASS REPLACEMENT $ 1,727.55 EQUIPMENT/LARCENY $ STRUCTUAL $ .00 _________ TOTAL $ 9,270.88 54 887.50 Washington County Public Schools Deferred Maintenance Annual Report October 2014 Introduction Deferred maintenance is defined as postponing routine maintenance and replacement of building components, infrastructure, and architectural finishes. Accumulated deferred maintenance results from various influences including: • Lack of available resources to perform routine maintenance allows scheduled repair work and upkeep to evolve into more serious conditions. • Choices made during austere financial times when routine repairs and preventative maintenance are often deferred in order to meet more pressing fiscal requirements. • Inability to perform major repairs or the replacement of major building components that have reached the end of their useful life. • Decision to postpone repairs and systemic replacement when buildings are schedule for major renovation or replacement. Washington County Public Schools (WCPS) currently has a deferred maintenance backlog of approximately $36.4 million at school facilities. Additionally, there is $10.1 million in ADA related accessibility deficiencies reported in an assessment of ADA compliance conducted in 2010. The ADA deficiencies and deferred maintenance at school facilities is $46.5 million and $2.4 million at non-school facilities totaling $48.9 million. Many of the ADA deficiencies are large projects and cannot be corrected without a major renovation of the facility. These deficiencies should be considered when determining the overall burden to the school system regarding its facility needs. This report seeks to break down, clarify, and categorize the tasks and costs associated with the current deferred maintenance backlog. Categories and Definitions To interpret estimates of deferred maintenance, it is useful to consider two types of building deficiencies. The first type includes physical defects that must be corrected to maintain the building as it was originally designed. These defects are usually caused by physical deterioration, though in some cases they may be due to faulty construction. Many building components wear out with time and must be repaired or replaced. 55 This type of deferred maintenance can be further broken down into deferred normal maintenance and deferred renewal. Deferred normal maintenance includes preventive maintenance activities and minor repairs that should have been performed but were not. Normal maintenance activities are funded by the operating budget. Examples include painting, glazing windows, repairing small roof defects, and replacing broken parts, etc. Deferred renewal refers to replacement projects that are due but have not been executed. These are projects that have a maintenance cycle in excess of one year and are typically funded by the capital budget, though in recent years they have been accomplished with a mix of capital and operating funds. Examples include the replacement of roofs; heating, ventilation, and air conditioning (HVAC) equipment; and door and window replacement. The second type of building deficiency is the failure to meet codes and standards that have changed since the building was constructed. During the lifetime of many school buildings, there have been major changes in fire and life safety codes. Also, governments have established new standards for accessibility, energy conservation, and environmental health, including asbestos and indoor air quality. Finally, electrical standards have changed in order to accommodate increased usage of computers and other electronic equipment. Further complicating the analysis and prioritization of deferred maintenance tasks is the actual condition of equipment and infrastructure, regardless of its age. When performing assessments of buildings and systems, there are times when it is apparent that a piece of equipment that is 15 years old, and within its life expectancy, needs to be replaced immediately because of one deficiency or another. Likewise, there is other equipment that is operating long past its life expectancy that is still not in need of immediate replacement. For this reason, this report establishes three different priority rankings to best define maintenance that needs to be completed immediately versus maintenance that, although deferred, may not be as urgent. Priority 1: Priority one type of deferred maintenance is defined as those assets that are in such poor condition that a failure would cause the immediate closure of the building. Other assets included in Priority 1 would be those types that costs benefit analysis shows would cost significantly more to maintain than to repair or replace as soon as possible. Aging, “mission critical” assets that would have a negative impact on the safety or security of students and staff if they were to fail are also included in the Priority 1 list. Priority 1 deferred maintenance items are generally renewal type projects such as replacement of failing roofs, old and inadequate electrical panels and circuit breakers, HVAC equipment that is no longer supported by the manufacturers or is only partially operational, fire alarm systems that do not meet current life safety codes and/or are failing, and certain critical ADA accessibility modifications, etc. 56 Priority 2: Priority two type of deferred maintenance is the largest group of deferred maintenance and is made up of those assets that exceeded their expected life cycle and should be replaced, however whose failure would not result in a building closure. Examples of Priority 2 deferred maintenance tasks include many of the same items listed in Priority 1 which are not in imminent danger of failing, as well as window and door replacements, lighting replacements, plumbing fixture replacements, parking lot and sidewalk replacements, locker replacements, bleacher replacements, auditorium seating replacement, etc. Priority 3: Priority three type of deferred maintenance is defined as those assets that are beyond life expectancy but are still currently in satisfactory operating condition, or are located in buildings that will be modernized or replaced in the near future. Examples of Priority 3 type deferred maintenance include painting and any other piece of equipment or system that is beyond its scheduled life cycle but is in good working order. WCPS Deferred Maintenance Based on the above criteria developed by staff, a thorough analysis of WCPS facilities is conducted yearly. The outcome of this analysis is used to report the level of deferred maintenance in WCPS facilities. Because of the unplanned nature of many equipment and system failures, the level, prioritization, and plan to reduce deferred maintenance changes from year-to-year. As equipment and systems continue to age, it has been forecasted that almost 19 million dollars of new deferred maintenance may be added by year 2017 if resources are not used to reduce deferred maintenance. The reduction of deferred maintenance is managed by first considering Priority 1 tasks and improvements that have a direct impact on instruction. Priority 1 tasks often involve the replacement of large, expensive systems such as roofs and mechanical equipment; therefore, a limited number of these projects are able to be accomplished in a specific fiscal year. Funding is also targeted to accomplish Priority 2 and 3 tasks to facilitate the repair or replacement of the greatest amount of equipment and systems possible. The following tables represent the October 2014 analysis of deferred maintenance needs. 57 Elementary Schools Table 1 shows the overall total amount of deferred maintenance in WCPS elementary schools sorted by priority type. Priority School 1 2 3 Total Boonsboro Elementary $0 $0 $245,000 $245,000 Cascade Elementary $535,000 $190,000 $90,000 $815,000 Conococheague Elementary $489,000 $333,500 $225,000 $1,047,500 Eastern Elementary $0 $335,000 $0 $335,000 Emma K. Doub Elementary $55,000 $230,000 $210,000 $495,000 Fountain Rock Elementary $450,000 $675,000 $105,000 $1,230,000 Fountaindale Elementary $150,000 $150,000 $90,000 $390,000 Funkstown Elementary $350,000 $200,000 $120,000 $670,000 Greenbrier Elementary $45,000 $317,000 $185,000 $547,000 Hancock Elementary $0 $340,000 $195,000 $535,000 Hickory Elementary $570,000 $330,000 $70,000 $970,000 Lincolnshire Elementary $380,000 $90,000 $0 $470,000 Old Forge Elementary $0 $330,000 $105,000 $435,000 Paramount Elementary $685,000 $235,000 $0 $920,000 Pleasant Valley Elementary $0 $55,000 $85,000 $140,000 Potomac Heights Elementary $0 $160,000 $720,000 $880,000 Sharpsburg Elementary $0 $775,000 $45,000 $820,000 Smithsburg Elementary $320,000 $0 $0 $320,000 Winter Street Elementary $850,000 $335,000 $230,000 $1,415,000 Totals $4,879,000 $5,080,500 $2,720,000 $12,679,500 Table 1 – Total estimated value of deferred maintenance in elementary schools 58 Middle Schools Table 2 shows the overall total amount of deferred maintenance in WCPS middle schools sorted by priority type. Priority School 1 2 3 Boonsboro Middle $0 $573,000 $120,000 Clear Spring Middle $0 $166,000 $375,000 E. Russell Hicks Middle $0 $395,000 $305,000 Northern Middle $0 $405,000 $375,000 Smithsburg Middle $55,000 $805,000 $225,000 Springfield Middle $465,750 $255,000 $690,000 Western Heights Middle $2,340,000 $280,000 $140,000 Totals $2,860,750 $2,879,000 $2,230,000 Total $693,000 $541,000 $700,000 $780,000 $1,085,000 $1,410,750 $2,760,000 $7,969,750 Table 2 – Total estimated value of deferred maintenance in middle schools High Schools Table 3 shows the overall total amount of deferred maintenance in WCPS high schools sorted by priority type. Priority School 1 2 3 Total Boonsboro High School $75,000 $0 $315,000 $390,000 Clear Spring High $0 $440,000 $152,000 $592,000 Hancock Middle-Senior High $195,000 $665,000 $180,000 $1,040,000 North Hagerstown High $2,400,000 $880,000 $120,000 $3,400,000 Smithsburg High $1,900,000 $680,000 $420,000 $3,000,000 South Hagerstown High $2,415,000 $300,000 $0 $2,715,000 Wash. Co. Tech High School $1,200,000 $440,000 $145,000 $1,785,000 Williamsport High $2,215,000 $330,000 $275,000 $2,820,000 Totals $10,400,000 $3,735,000 $1,607,000 $15,742,000 Table 3 – Total estimated value of deferred maintenance in high schools 59 Other School Facilities Table 4 shows the overall total amount of deferred maintenance in other WCPS facilities sorted by priority type. Priority School 1 Marshall St. Education Center Totals 2 $0 $0 3 $816,000 $816,000 Total $85,000 $85,000 $901,000 $901,000 Table 4 – Total estimated value of deferred maintenance in other school facilities Overall Totals Table 5 shows the overall total value of deferred maintenance sorted by priority and school type. Priority School Elementary Middle High Other Totals 1 2 $4,879,000 $2,860,750 $10,400,000 $0 $18,139,750 $5,080,500 $2,879,000 $3,735,000 $816,000 $11,645,500 3 Total $2,720,000 $12,679,500 $2,230,000 $7,969,750 $1,607,000 $15,742,000 $85,000 $901,000 $6,602,000 $36,387,250 Table 5 – Total estimated value of deferred maintenance by school type ADA School Totals Table 6 shows the ADA related deferred maintenance in WCPS school facilities sorted by priority type. The assessment addresses only basic accessibility needs. Priority School Elementary Middle High Other 1 Totals 2 $265,330 $308,760 $179,700 $39,000 $792,790 3 $3,028,911 $2,455,493 $1,984,975 $375,640 $7,845,019 $546,125 $537,530 $309,852 $36,720 $1,430,227 Table 6 – Total estimated value of ADA deferred maintenance in all facilities 60 Total $3,840,366 $3,301,783 $2,474,527 $451,360 $10,068,036 The table below represents the amount of deferred maintenance at non-school buildings maintained by WCPS. The value of deferred maintenance from this table is not included in the $36.4 million referenced on page 55 of this document. The total deferred maintenance backlog, including the non-school buildings, is approximately $38.8 million. Non-School Facilities Table 7 shows the overall total amount of deferred maintenance in WCPS non-school facilities sorted by priority type. Priority School 1 2 3 Administration Center $485,000 $232,000 $250,000 Former Job Development Building $625,000.00 $175,000 $655,000 Totals $2,700,000 $1,007,000 $2,505,000 Table 7 – Total estimated value of deferred maintenance in non-school facilities 61 Total $967,000 $1,455,000 $2,422,000