CHARTS FOR TROUBLESHOOTING THERMOCOUPLESAND POWERPILE SYSTEMS TROUBLESHOOTINGCHARTS Thesechartsare to assistthe technicianin properly diagnosingproblemswith 30 millivolt thermocouple systemsand 750millivolt PowerpileSystems. Charts I and 2 are for useon 30 millivolt systems. Chart I is for useon systemswith no built in ECO (EnergyCutoff). Chart 2 is for systemswith an ECO, typically all water heatersare required to havean ECO as a safetyto shut offthe millivolts to the water heater control is the water temperaturereaches1950F. It is a onetime fusible link devicethat if it opensit will mean repldcingthe water heatercontrol. Charts3 and 4 are for the older 250 millivolt controls that were usedon a lot of wall furnacesand thru the wall room heaters.Chart 3 is for diagnosingthe Pilotstatpart of the control.Chart 4 is for the valvecoil itself. Charts 5 and 6 are for the 750millivolt valvesfor testingand diagnosingthe power units (magnet assembly).Chart 5 coversthe older 23 ohm assemblies. Chart 6 is for the newercombinationgasvalvessuchas HoneywellVS-820,Robertshawand White Rodgers newer valves. Chart 7 is for troubleshootingthe 750millivolt valve circuit. MILLIVOLT CHARTS TESTII{G 3O.MILLIVOLT CIRCUITS a F J J30 ) l\ \-() t.t. <20 s r{ !D a $ro F f c F l ^'OUTPUT OPEN CIRCUIT MILLIVOLTS Chart 1-3 0 MiIIivoIt Pilotstat Control. NO ECO ,.. 40 o F .J lco ) CHECKPILOTFLAMEANO E L E C T R I C ACLO N N E C T I O N S ACCEPTAELE RANGE z t\ S b Sto CHECK UNIT POWER A N OH I L I M I T $ s '{l h s{ bro F f oF f . '. ..;:,,-*.;OUTPVTOPEN CIRCUIT MILLIVOLTS-.' Chart 2-30 Millivolt Piiotstat and Hi Limit. WITH ECO TESTING clRculTs 250-MttlrvoLT a I = = \ $ c s(') ql o d F f (L F l o -,- *.,-"OUTPUT OPEN CIRCUITMILLIVOLTS Chart 3 -250 MiIIivoIt Pilotstat Control. IMPORTANT: Make certain Powerpile valve is disconnectedwhen testing Pilotstat control. o 5 CHECKPILOT FLAME AND E L E C T R I C A LC O N N E C T I O N S -J J ACCEPTABLE E RANG = |\ s (J t s CHECK POWERPILEVALVE s t{l (., s $ F oF f ....,,.,'*'-.*- OUTPUTOPE N CI RCUI T MILLIVOLTS Chart 4-250 Millivolt Powerpile Valve. IMPORTANT: Make certain Pilotstat power unit is disconnected when testing Powerpile valve. TESTING CIRCUITS CTIART 5 T5O.MILLIVOLT U) F ACCEPTABLE RANGE CHECKPILOTFLAMEANO E L E C T R I C ACLO N N E C T I O N S ) J -) = }\ \ () e 400 (J s qJ (D a \J () 200 F l (L l o .,OUTPUT OPEN CIRCUITMILLIVOLTS23 OHM Chart 5-?50 Millivolt Piiotstat Control' IMPORTANT : Make certain Powerpile valve is dis connectedwhen testing Pilotstat Control. CIIART 6 -spectnl ll oHM PowERuNtr(vsg2o4) r 800 I a h = |\ d CHECKPILOTFLAMEANO ELECTRICAL CONNECTIONS .a 4OO $ a \(/) o :.1 s zoo REPLAC E IHERMOPILE ffi f F f -_l ;o o DROPOUT RANqE 44: i E 200 t- 400 540 800 OPEN CIRCUIT M I L L I V O II OHM CHART 7 .TEsrrNG powEBprLE vALVEcr'curr 7so MV (NOM.l SYSTEM t @ CI|ECI( ?ILOT TLATE ATD , ltlctilcaL corttcttoxa;i ! o J J s () t 600 CXECK POWERPILE VALVE TD ALL COXTROL3 wllH col{TRoLl AT VALVE C H E C XP O W E R P I I C VALVE (J a l{ (rt o d AT IN CI F PULL.IN RANGE $'ITH F o I NE?LACE THERMOPILE OUTPUT OPEHClRCUlf utrrrvoLrs-} SPECIAL NOTE: Shaded area in upper band is based on the resistance of the T586A thermostat and 30 feet of 18-gage cable. IF THERMOSTAT HAS NO HEAT ANTICIPATION IIEATER, AND THERE IS A SHORT RUN OF WIRX TO THE THERMOSTAT-readings falling between the upper and lower diagonal bands also represent proper system operation