TRANSFORMER PROTECTION Extent of damage Fault level Duration of fault Winding failures Voltage regulating load changers Transformer faults Transformer bushing failure Transformer core problem Miscellaneous failures Insulation breakdown Time Ageing of insulation Temperature Condition leading to faults Over heating due to excitation Oil contamination% & oil leakage Reduced cooling Improve cooling system of possible Reduced load FAULT OF TRANSFORMER Earth fault on H.V external connection Phases to phase fault on H.V external connection Internal earth fault on H.V windings Internal phase to phase fault on H.V windings. Short circuit between turns L.V windings. Earth fault on L.V external winding Phase to phase fault on L.V external connection. Internal earth fault on L.V windings Internal phase to phase fault on L.V winding Short circuit b/w turn L.V windings Earth fault on tertiary windings Short circuit b/W turns tertiary windings Sustained system phase to phase fault Sustained system earth fault Differential relay L.V side three phase over current and earth fault relay 132KV/11KV POWER TRANSFORMER H.V side three phases over current and earth fault relay D.C trip circuit supervision relay Trip and lock out relay Percentage biased Transformer differential relay High REF impedance Circulating current differential protection HV side over current and earth fault relay LV side over current and earth fault relay Over excitation relay 220/132/11KV AUTO TRANSFORMER Thermal over load relay Overall percentage biased differential relay L.H&H.V Connection circulating protection Tertiary over current protection D.C trip circuit supervision relay Percentage biased Transformer differential relay High REF impedance Circulating current differential protection HV side over current and earth fault relay LV side over current and earth fault relay Over excitation relay 500/220KV AUTO TRANSFORMER Thermal over load relay Overall percentage biased differential relay L.H&H.V Connection circulating protection Tertiary over current protection D.C trip circuit supervision relay Over voltage relay Transformer buchhloz relay Tap changer buchhloz relay MECHANICAL PROTECTION: Winding Temperature 0IL temperature Pressure relieve valve • Factors: • The shape, magnitude and duration of the inrush current depend on the factors: • Size of power transformer • Source Impendence • The magnetic properties of the core i.e. saturation density • The remanence of core • Resistance in power system from source to transformer. • The moment when transformer is switch on. Effect of magnetising current Appears on one side of transformer only Seen as fault by differential relay Normal steady state magnetising current is less than relay setting Transient magnetising inrush could cause relay to operate • The vector group shows the connection of windings of transformer and numerical index (hour numbers) for displacement of vector of two star voltages. • Capital Letter DY11 Small letter ( clock dial reference) • The first capital letter donates the connection of high voltage winding of transformer • The small letter represent the connection of low voltage secondary winding of transformer • Yy0d5 • • The first capital letter Y is referred to H.V or primary winding, the second letter y is referred as secondary winding and third letter is referred as tertiary winding. • Primary winding is taken as phase referred ‘O’ means that phase angle b/W H.V and M.V winding is zero. Whereas ‘5’ denotes that phase angle b/W H.V and tertiary winding is 150 (5x30) OVER CURRENT PROTECTION As it names implies, relay will pick up when it exceeds its present value TYPES: The types of over current relay are based on the relay characteristics over can be classified into three groups. • Definite current or instantaneous • Definite time • Inverse time Vécurent Relay Applied to a Transformer 51 51 51 HV2 HV1 LV HV1 HV2 Time LV IF(LV) IF(HV) 1.2IF(LV) Current Use of Instantaneous Overcurrent Protection Source LV 50 51 Differential Protection • Overall differential protection may be justified for larger transformers (generally > 5MVA). • Provides fast operation on any winding • Measuring principle : • Based on the same circulating current principle as the restricted earth fault protection • However, it employs the biasing technique, to maintain stability for heavy thro’ fault current • Biasing allows mismatch between CT outputs. • It is essential for transformers with tap changing facility. • Another important requirement of transformer differential protection is immunity to magnetising inrush current. PROTECTED ZONE HV LV R • Correct application of differential protection requires CT ratio and winding connections to match those of transformer. • CT secondary circuit should be a “replica” of primary system. • Consider : • (1) Difference in current magnitude • (2) Phase shift • (3) Zero sequence currents Biased Differential Scheme Differentia l Current I1 BIAS OPERATE BIAS I2 I1 - I2 OPERATE I1 - I2 RESTRAIN I1 + I2 2 Bias = Differential (or Spill) Current Mean Through Current Mean Thro Current Restricted E/F Protection Low Voltage Windings (1) A B C N LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated Restricted E/F Protection Low Voltage Windings (2) A B C N LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated Delta Winding Restricted Earth Fault Source Protected zone REF Delta winding cannot supply zero sequence current to system Stability : Consider max LV fault level Recommended setting : less than 30% minimum earth fault level Protection of Auto-Transformer by High Impedance Differential Relays (2) (b) Phase and Earth Fault Scheme A B C a b c 87 87 87 n ` Combined Differential and Restricted Earthfault Protection A2 A1 a1 P1 P2 S1 S2 a2 REF P1 S1 P2 S2 P2 P1 S1 S2 To differential relay Integral Vectorial and Ratio Compensation Power transformer Ratio correction Vectorial correction Virtual interposing CT Differential element Virtual interposing CT In Zone Earthing Transformer P1 P2 a2 a1 A1 A2 S2 S1 T2 T1 P1 P2 P2 P1 S2 S1 Three Winding Transformer 63MVA 132KV 300/5 25MVA 11KV 1600/5 50MVA 33KV 1000/5 4.59 5.51 10.33 2.88 5 2.88 5 All interposing C.T. ratio’s refer to common MVA base (63MVA Transformer Magnetising Characteristic Twice Normal Flux Normal Flux Normal No Load Current No Load Current at Twice Normal Flux Parallel Transformers T1 T2 N A B C Inter-Turn Fault E CT Shorted turn Nominal turns ratio Fault turns ratio Current ratio - 11,000 / 240 - 11,000 / 1 - 1 / 11,000 Requires Buchholz relay Load Buchholz Relay Installation 3 x internal pipe diameter (minimum) Conservator 5 x internal pipe diameter (minimum) Oil conservator 3 minimum Transformer Buchholz Relay Petcock Alarm bucket Mercury switch To oil conservator Trip bucket Counter balance weight Oil level From transformer Aperture adjuster Drain plug Deflector plate Overfluxing Basic Theory V = kf Causes 2m m Low frequency High voltage Geomagnetic disturbances Ie Effects Tripping of differential element (Transient overfluxing) Damage to transformers (Prolonged overfluxing) EFFECTS OF OVER FLUXING: • • • • Increase in magnetizing current Increase in winding temperature Increase in noise and vibration Overheating of laminations and metal parts (cause by stray flux) V/Hz Overfluxing Protection V K f Trip and alarm outputs for clearing prolonged overfluxing Alarm : Definite time characteristic to initiate corrective action Trip : IDMT or DT characteristic to clear overfluxing condition Settings Pick-up 1.5 to 3.0 i.e. 110V x 1.05 = 2.31 50Hz DT setting range 0.1 to 60 seconds V/H CHARACTERISTIC: Over-fluxing Relay Ex G VT AVR RL THERMAL OVERLOAD: • EFFECT OF OVER LOAD ON TRANSFORMER INSULATION LIFE: Overheating Protection Trip I load Alarm TD setting Top oil of power transformer On Fan control I load Off On Pump control Off Temp. indication Heater Local Thermal replica Temperature sensing resistor Remote Overload Protection • Overcurrent protection designed for fault condition • Thermal replica provides better protection for overload – – – – – Time Current based Flexible characteristics Single or dual time constant Reset facility Non-volatile Current Thermal Overload Oil Filled Transformers Trip time (s) 10000 Single characteristic: = 120 mins 1000 Dual characteristic 100 10 1 ZA 2 3 4 5 6 Current (multiple of thermal setting) Single characteristic: = 5 mins DIGITAL RELAYS FOR TRANSFORMER THERMAL WINDING PROTECTION