Operating Manual Control Unit for Island mode Gensets KEA 092 - INS TA92IX1-E June 2011 Replaces: April 2004 OFF CONTROLS ON START INDICATION AUTOM. DEVICE LOCKED OVERCRANK / ENGINE FAULT ALARM 1 ALARM 6 ALARM 2 ALARM 7 ALARM 3 ALARM 8 ALARM 4 ALARM 9 ALARM 5 ALARM 10 MANUAL AUTO TEST START LED TEST ALARM OFF APPLICATION OF THE CONTROL UNIT The control unit KEA 092 is designed for controlling island mode gensets. It has the same dimensions as the KEA 082. Two phases of the generator voltage are monitored for − Under- and overvoltage, − Under- and overfrequency, The software covers: − Start by a remote command, − Switching to generator supply, − Frequency control of gensets voltage, − Genset monitoring and protection, − Cooling-down/shutdown of the genset at the end of a remote operation, − Software for sprinkler mode. The control unit is fitted with the following facilities for monitoring of the assembly and the genset: − Voltage sensor for generator, − 10 externally connected alarm signals, − 4 alarms of the generator voltage monitoring, programmable to alarms 1 to 10, − DC battery voltage monitor. Ten relays, max. contact rating 35 DC, 1 amp., are provided for the controlling of the genset and the assembly. The functions of 7 relays are programmable via an RS 232 communication port. The unit is delivered with the standard alarm labelling (easy to change by paper strips) and standard parameters. A customers programming and labelling is available for extra charge. A common control system can also be connected to the RS 232 port. Alfred Kuhse GmbH, D-21423 Winsen/Luhe, An der Kleinbahn 39 Telefon +49 (0)4171 798-0, Fax +49 (0)4171 798-117, http: //www.kuhse.de Certificated ISO 9001 since 1995 TA92IX1-E -2/6- 06/2011 Precaution Hints All applicable regulations, especially those of VDE, are to be observed. Programming of the unit must be carried out in such a way that any danger to people or equipment is impossible. A thorough knowledge of this Operating Manual is essential for design and commissioning. A faulty connection may cause permanent damage to the unit. Contents Operation Operation mode OFF Operation mode MANUAL Operation mode AUTO Operation mode TEST Push-button START Push-button LED TEST Push-button ALARM OFF Frequency control Emergency Stop / Emergency off Sprinkler mode page 2 page 3 page 3 page 3 page 3 page 3 page 3 page 3 page 3 page 4 page 4 Basic indications Controls on Automatic device locked Start indication Overcrank / Engine fault Mimic diagram / Voltage sensors Alarms 9 and 10 Alarm signals Overcranking / Engine fault Generator CB tripped Internal alarms of the volt. sensor Technical data Order number page 4 page 4 page 4 page 4 page 4 page 5 page 5 page 5 page 5 page 5 page 5 page 6 page 6 OPERATION LEDs for basic indications LEDs for alarms LED Gen. voltage CONTROLS ON START INDICATION AUTOM. DEVICE LOCKED OVERCRANK / ENGINE FAULT ALARM 1 ALARM 6 ALARM 2 ALARM 7 ALARM 3 ALARM 8 ALARM 4 ALARM 9 ALARM 5 ALARM 10 Push-button Gen. on Push-button Gen. off Signal: Gen. is on OFF MANUAL AUTO TEST Push-buttons for mode select START LED TEST ALARM OFF common push-buttons The operating modes are selected by four pushbuttons with integrated LEDs, showing the actual selected mode. The push-button selector may be electrically locked by an input (eg. by connecting a key-operated control switch). This avoids an unintentional or unacceptable change of a decided selection. The following modes are selected by the four push-buttons. TA92IX1-E -3/6- 06/2011 OPERATING MODE OFF This operating mode is automatically selected − Switching-off of all indicated alarm signals, when the supply voltage is applied to the unit. except alarm signals 13 and 14, as long as the When this mode is selected from an active mode, corresponding alarm contact is active, the following is initiated: − Reset of the control unit, in case the external − Shutdown of the genset (if running), EMERGENCY STOP contact is not active. OPERATION MODE MANUAL The engine may be started by pressing the pushhas no affect in case the generator voltage is not button START in the MANUAL mode. The load is within its programmed limits. switched on with the push-button GEN. ON if the The remote start command does not affect an engine is running and the generator voltage and automatic generator circuit breaker closing. To frequency are within their programmed limits. On stop the genset, the operating mode is to be set to pressing the push-button GEN. OFF, the generator OFF (no remote start command alive) to AUTOC.B. is disconnected again. Pressing the ON button MATIC. OPERATION MODE AUTO The genset will start after the start delay time by a When remote start command is removed, the generator C.B. is switched off. To prevent the engine remote start command. If the genset should not be from a heat increase, the genset will run unloaded running after the complete cranking sequence, the for an adjusted cooling down period, and then will alarm signal OVERCRANK/ENGINE FAULT will be shutdown. occur and the control unit will be locked. When the genset, after running up, has reached Additionally to the remote start command the gennominal voltage and frequency, the generator cirset start can be initiated also by the SPRINKLER cuit breaker is closed. MODE (see further down). OPERATION MODE TEST The starting sequence is initiated on selecting this The generator is switched on if during the TEST operating mode. The genset can be loaded with the mode operation a remote start command is given. push-button GEN. ON (I), if the engine is running To stop the genset, the operating mode is to be set to OFF or (no remote start command alive) to and the generator voltage and frequency are within their programmed limits. Switching off the load AUTOMATIC takes place by the push-button GEN. OFF(O). PUSH-BUTTON START In case operating mode MANUAL is selected, the In case the diesel engine requires pre-glowing, engine can be cranked by pressing the push-button arrangements for this must be realized externally. START. If the starting sequence is programmed When another operating mode is selected or when for a gas engine, this sequence will run. generator set is running, the push-button is not active. PUSH-BUTTON LED TEST The operative readiness of all LEDs can be this test other signal lights, assembled in checked by this push-button, without initiating or switchboard panels, a relay can be programmed to suppressing an actual alarm signal. To include in this function. PUSH-BUTTON ALARM OFF By a pulse of this push-button, the audible signal ble LED signal may be switched-off by pressing caused by an alarm signal, will be silenced. After the push-button once again. having eliminated the source of trouble, the visiFREQUENCY CONTROL AT INSULAR SUPPLY MODE If this function is enabled, the control unit emits limit values. There is a break between two speed adjusting pulses to the speed control device if the commands, which enables the engine to follow frequency of the genset is not within programmed the command. TA92IX1-E -4/6- 06/2011 EMERGENCY STOP / EMERGENCY OFF (EXTERNAL) The EMERGENCY STOP / EMERGENCY OFF func− the generator is switched off, tion must be provide by external push-buttons. − the genset is shutdown, Additional a signal must be given to the input − the automatic operation is locked, indicated by IMMEDIATE STOP of the KEA. By this, independAUTOMATIC DEVICE LOCKED. ent of the operating mode, SPRINKLER MODE The following functions are provided for the op− Termination of sprinkler mode automatically eration of a fire-fighting pump: or manually, − Changing of the shutdown mode of the alarms − Disconnection of consumer load for switching to warning mode, on of the sprinkler pump. − 10 starting attempts, If the control unit is programmed for manual shutdown, the LED of the operating mode OFF is blinking at the end of a sprinkler command. In this case the engine must be shut down either by the button Off or by the external Emergency stop. . BASIC INDICATIONS The both upper rows with LEDs show important status and fault information of the system. The following four basics indications are provided. CONTROLS ON After starting-up of the genset, this green LED until the alarm monitoring is on. The indication is signal indicates, that the delayed monitored switched-off, as soon as the shutdown procedure alarms are activated. As soon as the engine has is beginning. reached the firing speed, the LED start blinking AUTOMATIC MODE LOCKED To reset the control unit, the push-button selector This indication shows, that an external EMERhas to be set to position OFF (RESET). Prior to this, GENCY STOP push-button has been pressed or that an alarm signal has caused the genset to shutthe reason for the trouble has to be eliminated, or down. The red LED indicates, that the control unit the EMERGENCY STOP push-button has to be unloas well as the genset is locked for any further cked. starting attempt. START INDICATION This signal is lighting, if there is a starting deflashing. When the start is enabled, the LED mand, processed by the control unit at AUTOchanges to steady light. MATIC mode or if the operating mode MANUAL or The indication is switched-off as soon as the dyTEST is selected. As long as there is no enable namo D+ signalises the exceeding the firing signal for starting, the LED START INDICATION is speed. Now, it is not possible, to actuate the starter motor, not even manually. OVERCRANK / ENGINE FAULT This signal is switched-on, in case control unit (with signal AUTOMATIC UNIT 1. the genset has not started after the complete LOCKED), starting sequence (simultaneously with signal 3. the genset is still running even after complete AUTOMATIC UNIT LOCKED), stop time has elapsed (without signal AUTO2. the genset came to a standstill without any MATIC UNIT LOCKED). shut-down command emitted by the automatic TA92IX1-E -5/6- 06/2011 MIMIC DIAGRAM / VOLTAGE SENSOR The mimic diagram shows the genset and the bus its. The generator supply is indicated by the green bar. The green LED below the generator symbol LEDs below the OFF (O) push-buttons. shows that the generator voltage is within its limALARM SIGNALS If an alarm signal comes up, the corresponding LED is blinking and the audible signal is switched on. The audible signal is cancelled either automatically after it's programmed operating time or by one push of the button ALARM OFF. The LED indication changes then to a steady lighting. A next alarm signal coming up acts in the same manner, i.e. its LED is blinking, the audible signal is on. The LED can be cancelled, if the alarm signal was only warning and the reason for it is not active anymore. Alarm signals, shutting the engine down, lock the automatic operation. This is shown by the signal Autom. Device locked. The operation mode OFF must be selected for unlocking the automatic operation. If during the automatic mode the generator trips due to a warning signal (eg. Generator Overload) the engine will shutdown after the cooling down period and lock the automatic operation. GENERATOR CB TRIPPED The alarm signal is internally triggered in case no place after running out of the generator closing pulse. feed back signal GENERATOR CB IS ON takes INTERNAL ALARMS OF THE VOLTAGE SENSOR The frequency and voltage faults of the generator That means, if eg. a mains undervoltage occurs, may be indicated as alarm signals. For this, one or the engine starts and the alarm MAINS UNDERmore function has to be programmed with a valid VOLTAGE is triggered. If the voltage is later on (1..10) alarm signal number. Such an alarm has no within its limits, the engine shuts down but the affect to the actual state of the voltage monitors. alarm is monitored until it is cancelled. ALARMS 9 AND 10 These two alarms may be delayed from contract however without the audible signal. Criteria, closing 0 up to 250 sec., i.e. the alarm contact which have to be always monitored, can be conmust be active for the programmed time delay to nected here (eg. tank filling level, leakage warninitiate an alarm signal. Furthermore these two ing). alarms are also active in the operating mode OFF, TA92IX1-E -6/6- 06/2011 TECHNICAL DATA DESIGN − Flush mounted unit − Dimensions (W/H/D) 260 x 170 x 80 mm − Weight: approx. 2.2 kg − Mounting position any − Protective grade IP 44 (built-in) − Ambient temperature storage -20°...+70°C operation: 0°...+55°C − Standards: DIN VDE 0160 POWER SUPPLY − selectable: 9-12-15 or 14-24-35 volts DC ANALOGUE INPUTS Two phase generator voltage monitor, settable in steps of 1 volt: − UNom 3x400 volts, range from 240 - 480 volts. − Generator frequency 45 to 65 Hz, can be continuously set 40 to 70 Hz. − Battery voltage monitor. DIGITAL IN- / OUTPUTS − Input for charging dynamo D+ with preexcitation − 10 terminals for alarm signal contacts − 8 terminal for common signals − 10 outgoing relays, 7 of them can be programmed, max. contact rating 35 volts DC, 1 amp. Serial Interface RS 232 port for programming, for coupling to a common control system via extra hard- / software or to the remote telephone monitoring TELEMON. Order number: 2A92I60.xx