ACFoam ® Polyiso Roof Insulation Fastening Pattern Guide Connecting Function with Facility™ Table of Contents Product Page Installation Guidelines 3 BUR-8 Built-up or Selected Modified Bitumen Systems 4 FA-8 Fully Adhered Single Ply Systems 5 FA-11 Fully Adhered Single Ply Systems 6 FA-16 Fully Adhered Single Ply Systems 7 FA/HD-12 Fully Adhered Single Ply Systems 8 FA/HD-16 Fully Adhered Single Ply Systems 9 MF-5 Mechanically Fastened Single Ply Systems 10 MF/RB-6 Mechanically Fastened Systems 11 NB.1 Nailable Insulation Systems 12 NB.2 Nailable Insulation Systems 13 NB.3 Nailable Insulation Systems 14 15-16 Customer Service Policy Back Cover Manufacturing and Sales Locations Updated: 09.20.16 2 ACFoam® Polyiso Roof Insulation Fastening Pattern Guide Before installation begins, the roof deck should be firm, well attached, even, clean and dry. Proper attachment of the insulation is necessary to prevent roof failures. Atlas is not responsible for any damage caused by improper attachment. ACFoam® products can be attached to decks that are approved by FM Approvals and local codes. Atlas is not responsible for determining the suitability of the deck. ACFoam® shall be kept dry before, during and after installation. Install only as much ACFoam® as can be covered the same day with completed roofing. Although ACFoam® has been designed to withstand normal foot traffic, protection from damage by construction traffic and/or abuse is extremely important. Roof surface protection such as plywood shall be used in areas where storage and staging are planned and heavy or repeated traffic is anticipated during or after installation. Refer to Atlas Technical Bulletin TB-5. Multi-Layer Installation To minimize the effects of thermal bridging, Atlas strongly recommends the use of multiple layers when the total desired or specified R-value requires an insulation thickness greater than 2.7” thick. The joints in each layer should be offset in order to avoid a vertically continuous joint through the total insulation thickness. Two layers (or more) with joints staggered can provide improved insulation performance by eliminating thermal bridges. This method also reduces condensation potential. Mechanical Attachment Mechanical fastening is the recommended method of attachment over nailable decks. General fastening frequency and spacing for steel, wood, cast-in-place structural concrete and poured gypsum decks is covered in the ACFoam® & Nailable Roof Insulation Fastening Pattern Guide. Refer to the current FM Loss Prevention Data Sheet 1-29 for special considerations regarding perimeter and corners of the roof. For further recommendations regarding attachment of insulation to lightweight insulating concrete decks or poured gypsum concrete decks, follow the instructions as outlined in the current NRCA Roofing Manual. ACFoam® products shall not be adhered directly to these decks by any bitumen or adhesive attachment method. Refer to the Nailable Insulation Guide for additional ACFoam® Nail Base and CrossVent® fastening recommendations. Adhesive Attachment (Does Not Apply to ACFoam® Composite Insulations, Nail Base or CrossVent®.) For installing ACFoam® to a structural concrete deck, adhesive/bitumen attachment is the recommended method. When using hot bitumen on concrete decks, priming is necessary. Precautions must be taken to prevent bitumen drippage. When using hot-applied bitumen for insulation attachment, the temperature of the bitumen should be approximately 50°F below the interply hand mopping EVT. The deck must be dry and care must be taken to apply the bitumen in sufficient quantity to totally cover the available deck surface. Use 18 to 30 pounds of bitumen per square to ensure proper attachment. To ensure embedment, the board must also be “stepped in” at several points while the bitumen is still hot enough to allow positive attachment. The recommended ACFoam® insulation size for hot bitumen attachment is 4’ x 4’. When using polyurethane adhesives or cold applied asphalt adhesive follow the adhesive manufacturer’s installation recommendation. In any case, roll or weigh down the insulation to ensure contact between the adhesive and the insulation board. Vapor/Air Retarders Moisture vapor tends to migrate from warmer to cooler areas. In building construction, vapor/air retarders are used to inhibit or block the passage of warm, moisture-laden air into walls or roofing assemblies. To determine whether a vapor/air retarder is necessary, calculations based on interior relative humidity, interior temperature, and the outside design temperature must be performed. Consult the current NRCA Roofing Manual for more information regarding vapor/air retarders and dew point calculations. Special consideration should be given to construction-generated moisture as well. For example, construction generated moisture will be released when concrete floor slabs are placed after the roof has been installed, which can drive large quantities of moisture into the roof system. Therefore, Atlas is not responsible for damage to the insulation when exposed to constructiongenerated moisture. Refer to the current NRCA Roofing Manual for recommendations regarding the use of a vapor retarder when construction-generated moisture is present. Refer to Atlas Technical Bulletin TB-5. Consult vapor/air retarder manufacturer for recommended applications and details. Storage Factory applied packaging is intended only for protection during transit. When stored outdoors or on the job site, the insulation should be stacked on pallets at least three inches above ground level and completely covered with a weatherproof covering such as a tarpaulin. The temporary factory-applied packaging should be slit or removed to prevent accumulation of condensation. Roof insulation which has become wet or damaged should be removed and replaced with solid, dry insulation. WARNING - DO NOT LEAVE EXPOSED This product is a polyiso organic plastic foam and will burn if exposed to an ignition source of sufficient heat and intensity, or open flame, such as a welder’s torch. Like other organic materials, this product will release smoke if ignited. Do not apply flame directly to ACFoam® roof insulations. This product should be used only in strict accordance with Atlas recommended uses and application instructions. Limitations of Liability Other than the aforementioned representations and descriptions, Atlas Roofing Corporation (hereafter, “Seller”) makes no other representations or warranties as to the insulation sold herein. The Seller disclaims all other warranties, express or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose. Seller does, however, have a limited warranty as to the LTTR-value of the insulation, the terms of which are available upon request from the Seller. The Seller shall not be liable for any incidental or consequential damages including the cost of installation, removal, repair or replacement of this product. The Buyer’s remedies shall be limited exclusively to, at Seller’s option, the repayment of the purchase price or resupply of product manufactured by Atlas in a quantity equal to that of the nonconforming product. Atlas distributors, agents, salespersons or other independent representatives have no authority to waive or alter the above limitation of liability and remedies. Updated: 09.20.16 3 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 24" 24" 24" 12" 24" *FIELD- 8ea. Fasteners/Board (4'x8') 12" 48" 12" 12" 48" 24" 12" 48" *FIELD- 4ea. Fasteners/Board (4'x4') 12" 24" 12" 12" NOTES: 1. Minimum thickness of insulation shall be 1.3” ACFOAM®-II, -III OR -IV with mopped 0.5” Factory Mutual approved perlite overlay. NOTES: 2. Minimum thickness of insulation shallBE be1.3" 1.5”ACFOAM®-II, ACFOAM®III-II, OR -IV with mopped 0.5” Factory approved 1. MINIMUM THICKNESS OF INSULATION SHALL OR-III IV WITH MOPPED 0.5" FACTORY MUTUAL Mutual APPROVED PERLITE OVERLAY. high density wood fiber overlay. 2. MINIMUM THICKNESS OF INSULATION SHALL BE 1.5" ACFOAM®-II, III OR IV WITH MOPPED 0.5" FACTORY MUTUAL APPROVED HIGH 3. Refer to Factory Mutual Approval Guide for approved fasteners and plates. DENSITY WOOD FIBER OVERLAY. 4. Factory Mutual 1-90 Fastening Pattern. 3. MINIMUM THICKNESS SHALL BE 1.5" WHEN USING ACFOAM® COMPOSITE PB. 4. MINIMUM THICKNESS SHALL BE 2.0" WHEN USING ACFOAM® COMPOSITE FB. 5. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 5. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 6. FACTORY MUTUAL 1-90 FASTENING PATTERN. 7. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF ® PERIMETER AND CORNER SYSTEM MANUFACTURER FOR ACFoam -II & ACFoam®-III DESIGN ENHANCEMENT RECOMMENDATIONS. Built-Up or Selected Modified Bitumen Systems ACFoam®-II, ACFoam®-III & ACFoam®-IV DWG #: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas BUILT-UP OR SELECTED MODIFIED BITUMEN SYSTEMS Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FMAtlas Global,Roofing Miami-Dade County andhas membrane manufacturer for additional guidelines well as design Corporation produced this information forinstallation conceptual designaspurposes only. Prior to REVISION #: enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally installation, Atlas Roofing Corporation recommends that you consult your local building code(s), accepted all responsibility for verifying project specific fastening requirements prior to product installation. ISSUE DATE #: contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 DWG #: REVISION #: ISSUE DATE: BUR-8 BUR-8 1 02/29/2016 02/29/2016 03/04/2013 4 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 24" 24" 24" 12" 12" 12" 24" 12" 48" *FIELD- 8ea. Fasteners/Board (4'x8') 48" 24" 12" 24" *FIELD- 4ea. Fasteners/Board (4'x4') 12" 48" 12" 12" NOTES: 1. Minimum single layer thickness of insulation shall be 2.0”. 2. Refer to Factory Mutual Approval Guide for approved fasteners and plates. NOTES: FactorySINGLE Mutual 1-90 THICKNESS Fastening Pattern. 1. 3. MINIMUM LAYER OF INSULATION SHALL BE 2.0". 4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 3. FACTORY MUTUAL 1-90 FASTENING PATTERN. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF ® ® ACFoam -II & ACFoam -III Fully Adhered Single Ply Systems SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS. DWG #: ACFoam®-II, ACFoam®-III & ACFoam®-IV Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installationSINGLE guidelines asPLY well as SYSTEMS design FULLY ADHERED enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying specific fastening requirements prior to product installation. Atlas Roofing Corporation hasproject produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 FA-8 REVISION #: ISSUE DATE #: DWG #: REVISION #: ISSUE DATE: N/A 03/04/2013 FA-8 N/A 03/04/20135 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 24" 24" 24" 12" 18" 6" 12" 6" 18" 48" *FIELD- 11ea. Fasteners/Board (4'x8') 24" 24" 24" 24" 48" 18" 18" 6" 24" *FIELD- 6ea. Fasteners/Board (4'x4') 6" 12" 36" 48" 12" 6" 6" NOTES: 1. Minimum single layer thickness of insulation shall be 1.5” to 1.9”. 2. Refer to Factory Mutual Approval Guide for approved fasteners and plates. NOTES: Factory Mutual 1-90 Fastening Pattern. 1.3. SINGLE LAYER THICKNESS OF INSULATION SHALL BE 1.5" to 1.9". 4. Refer to Factory Mutual Global Property Data Sheets (1-29) or consult roof system manufacturer for 2. REFER TO FACTORY MUTUAL APPROVAL GUIDELoss FOR Prevention APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 3. FACTORY MUTUAL 1-90 FASTENING PATTERN. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF ACFoam®-II & ACFoam®-III SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS. Fully Adhered Single Ply Systems DWG #: ACFoam®-II, ACFoam®-III & ACFoam®-IV Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design FULLY ADHERED SINGLE PLY SYSTEMS enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted responsibility for verifying project specific this fastening requirements prior to product installation. AtlasallRoofing Corporation has produced information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all Updated: 09.20.16prior to product installation. responsibility for verifying project specific fastening requirements REVISION #: ISSUE DATE #: DWG #: REVISION #: ISSUE DATE: FA-11 N/A 03/04/2013 FA-11 N/A 6 03/04/2013 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 36" 12" 36" 6" 18" 12" 6" 6" 6" 12" 18" 12" 48" 12" *FIELD- 16ea. Fasteners/Board (4'x8') 12" 12" 12" 24" 12" 12" 12" 48" 18" 18" 6" 6" 12" 18" 12" 48" *FIELD- 8ea. Fasteners/Board (4'x4') 12" 18" 12" 6" 6" 12" 12" 12" 12" NOTES: 1. Minimum single layer thickness of insulation shall be 1.3” to 1.4”. NOTES: 2. Refer to Factory Mutual Approval Guide for approved fasteners and plates. 1. SINGLE LAYER THICKNESS OF INSULATION SHALL BE 1.3" to 1.4". 3. Factory Mutual 1-90 Fastening Pattern. 2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. 4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 3. FACTORY MUTUAL 1-90 FASTENING PATTERN. perimeter and corner design enhancement recommendations. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF ® ® SYSTEM MANUFACTURER FOR PERIMETER AND CORNER ACFoam -II & ACFoam -III DESIGN ENHANCEMENT RECOMMENDATIONS. Fully Adhered Single Ply Systems ACFoam®-II, ACFoam®-III & ACFoam®-IVDWG #: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FULLY for ADHERED SINGLE PLY FM Global, Miami-Dade County and membrane manufacturer additional installation guidelines as wellSYSTEMS as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally Atlas Roofing Corporation has produced this information for conceptual design purposes accepted all responsibility for verifying project specific fastening requirements prior to product installation. only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 FA-16 REVISION #: N/A ISSUE 03/04/2013 DWG #: DATE #:FA-16 REVISION #: N/A ISSUE DATE: 03/04/2013 7 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 24" 24" 24" 12" 12" 12" 12" 12" 12" 48" *FIELD- 12ea. Fasteners/Board (4'x8') 48" 24" 12" *FIELD- 6ea. Fasteners/Board (4'x4') 12" 12" 48" 12" 12" 12" NOTES: 1. Refer to Factory Mutual Approval Guide for approved fasteners and plates. 2. Factory Mutual 1-75 Fastening Pattern. NOTES: 3. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 1. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 2. FACTORY MUTUAL 1-75 FASTENING PATTERN. ® 3. *REFER TO FACTORY ACFoam MUTUAL GLOBAL LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF -HDPROPERTY CoverBoard SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS. Fully Adhered Single Ply Systems DWG #: ACFoam®-HS Coverboard & ACFoam®-HD Coverboard Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design FULLY ADHERED SINGLE PLY SYSTEMS enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all Updated: 09.20.16 responsibility for verifying project specific fastening requirements prior to product installation. FA/HD-12 N/A REVISION #: ISSUE DATE #: DWG #: 02/29/2016 FA/HSHD-12 REVISION #: N/A ISSUE DATE: 02/29/2016 8 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 36" 12" 36" 6" 18" 12" 6" 6" 6" 12" 18" 12" 48" 12" *FIELD- 16ea. Fasteners/Board (4'x8') 12" 12" 12" 24" 12" 12" 12" 48" 18" 18" 6" 6" 12" 18" 12" 48" *FIELD- 8ea. Fasteners/Board (4'x4') 12" 18" 12" 6" 6" 12" 12" 12" 12" NOTES: 1. Refer to Factory Mutual Approval Guide for approved fasteners and plates. 2. Factory Mutual 1-90 Fastening Pattern. NOTES: 3. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 1. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 2. FACTORY MUTUAL 1-90 FASTENING PATTERN. 3. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF ® ACFoam -HD CoverBoard Fully Adhered Single Ply Systems SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS. ACFoam®-HD Coverboard Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well asSYSTEMS design FULLY ADHERED SINGLE PLY enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific requirements prior to product installation. Atlas Roofing Corporation has produced thisfastening information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 FA/HD-16 DWG #: REVISION #: N/A ISSUE DATE #: DWG #: 02/29/2016 FA/HD-16 REVISION #: ISSUE DATE: N/A 02/29/2016 9 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 42" 42" 6" 48" 18" 6" 6" 6" 18" *FIELD- 5ea. Fasteners/Board (4'x8') 48" 24" 12" 24" *FIELD- 4ea. Fasteners/Board (4'x4') 12" 48" 12" 12" NOTES: 1. Minimum single layer thickness of insulation shall be 1.3”. 2. Refer to Factory Mutual Approval Guide for approved fasteners and plates. NOTES: 3. Factory Mutual 1-90 Fastening Pattern. 1. MINIMUM SINGLE LAYER THICKNESS OF INSULATION SHALL BE 1.3". 4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. perimeter and corner design enhancement recommendations. 3. FACTORY MUTUAL 1-90 FASTENING PATTERN. ® ® 4. *REFER TO FACTORY MUTUAL GLOBAL ACFoam -II & PROPERTY ACFoamLOSS -IIIPREVENTION DATA SHEETS (1-29) OR CONSULT ROOF SYSTEM MANUFACTURER FOR PERIMETER ANDSystems CORNER DESIGN ENHANCEMENT RECOMMENDATIONS. Mechanically Fastened DWG #: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design REVISION #: MECHANICALLY FASTENED SINGLE PLY SYSTEMS enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. ISSUE DATE #: ACFoam®-II, ACFoam®-III & ACFoam®-IV Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all Updated: 09.20.16 responsibility for verifying project specific fastening requirements prior to product installation. DWG #: REVISION #: ISSUE DATE: MF-5 N/A 03/04/2013 MF-5 N/A 03/04/201310 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96" 40" 40" 8" 12" 8" 8" 8" 28" 32" 8" 48" *FIELD- 6ea. Fasteners/Board (4'x8') 48" 24" 12" 12" 12" 24" 12" 48" *FIELD- 4ea. Fasteners/Board (4'x4') NOTES: 1. Minimum thickness of insulation shall be 0.5”. NOTES: 2. Refer to Factory Mutual Approval Guide for approved fasteners and plates. 1. MINIMUM THICKNESS OF INSULATION SHALL BE 0.5". 3. Factory Mutual 1-90 Fastening Pattern. 2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES. 4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for 3. FACTORY MUTUAL 1-90 FASTENING PATTERN. perimeter and corner design enhancement recommendations. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF SYSTEM ® MANUFACTURER FOR PERIMETER CORNER Board DESIGN ENHANCEMENT RECOMMENDATIONS. ACFoamAND Recover Mechanically Fastened Systems ACFoam® Recover Board Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contractFASTENED documents, professional engineer, MECHANICALLY SYSTEM FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. UseCorporation of Atlas Roofing Corporation fastening patterns constitutesdesign that thepurposes user has personally Atlas Roofing has producedconceptual this information for conceptual only. Prior to accepted all responsibility for verifying project specific fastening requirements priorconsult to product installation. installation, Atlas Roofing Corporation recommends that you your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 DWG #: REVISION #: MF/RB-6 N/A DWG ISSUE#:DATE #:MF/RB-6 03/04/2013 REVISION #: N/A ISSUE DATE: 03/04/2013 11 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96'' 22'' 48'' 24'' 24'' 22'' 22'' 3'' 3'' 21'' 48'' 22'' 21'' 2'' 2'' 48'' 21'' 2'' 2'' 21'' 3'' 3'' 15 Fasteners per Board (4'x8') 8 Fasteners per Board (4'x4') 96'' 22'' 48'' 24'' 24'' 22'' 22'' 3'' 14'' 22'' 3'' 14'' 2'' 48'' 14'' 2'' 48'' 14'' 2'' 2'' 14'' 14'' 3'' 20 Fasteners per Board (4'x8') 3'' 10 Fasteners per Board (4'x4') 96'' 22'' 48'' 24'' 24'' 22'' 22'' 3'' 48'' 22'' 3'' 2'' 2'' 48'' 2'' 2'' 10.5" Typ. 3'' 25 Fasteners per Board (4'x8') 3'' 10.5" Typ. 13 Fasteners per Board (4'x4') NOTES: NOTES: 1. MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS. 2. MINIMUM THICKNESS OF ACFOAM® NAIL BASE ® SHALL BE 1.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS. ® 1. Minimum3. ATLAS thickness of ACFoam CrossVent shall be 2.5” To OF meet FM 1-60, 1-90 or 1-105 requirements. NAIL BASE FASTENERS REQUIRED FOR ATTACHMENT AS PART ATLAS ACFOAM® NAILABLE INSULATION SYSTEMS. 4. REFER TO ATLAS NAILABLE INSULATION GUIDE FOR ADDITIONAL FASTENING REQUIREMENTS. 2. Minimum thickness of ACFoam® Nail Base shall be 1.5” To meet FM 1-60, 1-90 or 1-105 requirements. ® 3. Atlas Nail Base Fasteners required for attachment as part of Atlas ACFoam Nailable Insulation Systems. ACFoam® Nail Base, ACFoam®-III Nail Base, ACFoam® CrossVent & ACFoam®-III CrossVent NAILABLE INSULATION SYSTEMS 4. Refer to Atlas Nailable Insulation Guide for additional fastening requirements C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), ® ® Global, Miami-Dade® County and membrane contract documents, professional engineer, FM manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. ACFoam Nail Base & ACFoam CrossVent Nailable Insulation Systems REVISION #: ISSUE DATE: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 NB.1 DWG #: N/A 08/13/14 DWG #: REVISION #: ISSUE DATE #: NB.1 N/A 08/13/2014 12 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96'' 22'' 48'' 24'' 24'' 22'' 22'' 3'' 3'' 8.4" Typ. 48'' 22'' 2'' 2'' 10.5" Typ. 48'' 2'' 2'' 3'' 3'' 30 Fasteners per Board (4'x8') 15 Fasteners per Board (4'x4') 96'' 22'' 48'' 24'' 24'' 22'' 22'' 3'' 48'' 22'' 3'' 7" Typ. 2'' 2'' 48'' 2'' 3'' 3'' 35 Fasteners per Board (4'x8') 18 Fasteners per Board (4'x4') 96.0'' 22.0'' 24.0'' 24.0'' 24.0'' 22.0'' 2'' 24.0'' 22.0'' 3'' 48'' 2'' 8.4" Typ. 22.0'' 3'' 2'' 6" Typ. 48'' 2'' 2'' 3'' 3'' 40 Fasteners per Board (4'x8') 7" Typ. 20 Fasteners per Board (4'x4') NOTES: NOTES: 1. MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS. ® MINIMUM THICKNESS OF ACFOAM® NAIL BASE®SHALL 1.5"2.5” TO MEET FM 1-60,FM 1-901-60, OR 1-105 REQUIREMENTS. 1. Minimum2.thickness of ACFoam CrossVent shallBEbe To meet 1-90 or 1-105 requirements. 3. ATLAS NAIL BASE FASTENERS REQUIRED FOR ATTACHMENT AS PART OF ATLAS ACFOAM® NAILABLE INSULATION SYSTEMS. ® 2. Minimum4. REFER thickness of ACFoam Nail Base be 1.5” To meet FM 1-60, 1-90 or 1-105 requirements. TO ATLAS NAILABLE INSULATION GUIDEshall FOR ADDITIONAL FASTENING REQUIREMENTS. 3. Atlas Nail Base Fasteners required for attachment as part of Atlas ACFoam® Nailable Insulation Systems. ACFoam® Nail Base & ACFoam® CrossVent 4. Refer to Atlas Nailable Insulation Guide for additional fastening requirements NAILABLE INSULATION SYSTEMS Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to ® ® that you consult your ® local building code(s), installation, Atlas Roofing Corporation recommends contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. ACFoam Nail Base & ACFoam CrossVent Nailable Insulation Systems C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg REVISION #: ISSUE DATE: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 NB.2 DWG #: N/A 08/13/14 DWG #: REVISION #: ISSUE DATE #: NB.2 N/A 08/13/2014 13 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ 96'' 22'' 24'' 24'' 24'' 22'' 24'' 22'' 22'' 3'' 48'' 3'' 5.25" Typ. 2'' 2'' 48'' 3'' 3'' 45 Fasteners per Board (4'x8') 23 Fasteners per Board (4'x4') 96'' 22'' 24'' 24'' 24'' 22'' 24'' 22'' 22'' 3'' 48'' 2'' 2'' 6" Typ. 2'' 3'' 2'' 4.6" Typ. 48'' 2'' 5.25" Typ. 3'' 2'' 3'' 50 Fasteners per Board (4'x8') 25 Fasteners per Board (4'x4') NOTES: NOTES: 1. MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS. ® ® 1. Minimum2. thickness of ACFoam CrossVent shallBEbe To meet 1-90 or 1-105 requirements. MINIMUM THICKNESS OF ACFOAM® NAIL BASE SHALL 1.5"2.5” TO MEET FM 1-60,FM 1-90 1-60, OR 1-105 REQUIREMENTS. 3. ATLAS NAIL BASE FASTENERS REQUIRED FOR ATTACHMENT AS PART OF ATLAS ACFOAM® NAILABLE INSULATION SYSTEMS. ® 2. Minimum thickness of ACFoam Nail Base shall be 1.5” To meet FM 1-60, 1-90 or 1-105 requirements. 4. REFER TO ATLAS NAILABLE INSULATION GUIDE FOR ADDITIONAL FASTENING REQUIREMENTS. 3. Atlas Nail Base Fasteners required for attachment as part of Atlas ACFoam® Nailable Insulation Systems. ACFoam® Nail Base & ACFoam® CrossVent 4. Refer to Atlas Nailable Insulation Guide for additional fastening requirements NAILABLE INSULATION SYSTEMS Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to ® ® that you consult your ® local building code(s), installation, Atlas Roofing Corporation recommends contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. ACFoam Nail Base & ACFoam CrossVent Nailable Insulation Systems C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg REVISION #: ISSUE DATE: Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer, FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16 NB.3 DWG #: N/A 08/13/14 DWG #: REVISION #: ISSUE DATE #: NB.3 N/A 08/13/2014 14 Customer Service Policy Roof and Wall Insulation Division STANDARD PRODUCTS • ACFoam®-II: 1.0”, 1.5”, 2.0”, 2.2”, 2.5”, 2.6”, 3.0”, 3.5”, 4.0” (4’ x 4’, 4’ x 8’) • Tapered ACFoam®-II: AA, A, B, C, X, Y, Q Panels (4’ x 4’) • ACFoam®-HD CoverBoard: (4’ x 8’) • EnergyShield®: ½”, ¾”, 1.0”, 1.5”, 2.0” (4’ x 8’) • EnergyShield® CGF: ½”, ¾”, 1.0”, 1.5”, (4’ X 8’) • EnergyShield® PRO: 1.0”, 1.5”, 2.0”, 2.5”, 3.0” (4’ x 8’) • EnergyShield® PRO2: 1.0”, 1.5”, 2.0”, 2.5”, 3.0” (4’ x 8’) NON-STANDARD PRODUCTS • Orders for non-standard products, which are not released for shipment within 30 days from date of original shipment, will be subject to payment in full. Atlas may require sign-off of a Non-Standard Product Purchase Agreement. TAPERED SYSTEMS • Tapered systems designed by Atlas will be scheduled and manufactured only with authorized, signed shop drawings. • Shop Drawings will be produced with a valid purchase order. CUSTOMER PICKUP (CPU) • Customer pickup will be permitted with prior confirmation by the Atlas sales department. • Orders for material not picked up within 48 hours of the scheduled pickup date will be subject to rescheduling. • Orders for non-standard material which have not been claimed within 30 days of scheduled pick up date will be subject to payment in full. • Tarping of CPU trucks will be at the discretion of the customer. • Minimum pickup quantity will be the equivalent of 10 or more 4’ x 8’ and 20 or more 4’ x 4’ units. • Pick-up allowance shall be $15.00 per equivalent unit of 4’ x 8’ x 4’ high regardless of final destination (except in Toronto and Vancouver). Sheathing units ½” thru 1.5” are 2’ high so $7.50 allowance per unit is applied. LESS THAN TRUCKLOAD ORDERS • Orders for less than a truckload will be subject to deficit freight and fuel surcharge on the unused portion of truck. • Deficit freight is calculated on 24 4’ x 8 x 4’ high units less the balance shipped. • Atlas will make every effort to pool partial loads. Such shipments will be subject to a stopover fee for each individual delivery. ADDITIONAL STOPS & FUEL SURCHARGE • Stopovers will be charged $100 per stop. • Stops must be within 150 miles of each other. • Requests for more than two stops on a truck will be reviewed by Atlas to determine if feasible. Additional charges will apply. • Atlas passes through all carrier Fuel Surcharges as a separate line item on the invoice. • Fuel Surcharges are calculated based on the US National Average Price of Diesel as reported weekly by the Department of Energy for actual loaded miles for delivery. Updated: 09.20.16 15 TRUCK DIVERSIONS • Trucks diverted after shipment will be subject to a diversion fee plus additional mileage fees and fuel surcharges. THIRD PARTY DELIVERY CHARGES • Atlas cannot guarantee time of deliveries. • Customer is responsible for billing the carrier for charges resulting from a late delivery. • Atlas will make pre-calls confirming delivery if requested (contact name and phone number must be given at time of order entry). • Detention charges from the carrier will be passed on to the customer. Detention charges become effective two hours from scheduled time of delivery. • Unloading not completed prior to 5 p.m. will be subject to layover charges. • Carrier assessed fuel surcharges will be passed on to the customer. DATE CHANGES/CANCELLATIONS • All re-dated orders will be subject to product availability. • Date change/cancellation made within 48 hours of shipment will be charged $500 minimum per truckload. Additional freight charges will be assessed once truck is in route. DAMAGES • Unless otherwise noted in this policy, all shipments are shipped and invoiced as FOB Origin/Freight Prepaid. CPU (Customer Pickup) shipments are shipped and invoiced as FOB Origin/Freight Collect. • Material damaged in route is the responsibility of the carrier. • Customer must file all claims for damaged material directly with the carrier. • Material shipped to replace damaged product will be invoiced separately. SHORTAGES • Customer and carrier must note shortages with signatures on the shipping document upon delivery and prior to carrier departure. RETURNS • All returns require preauthorization by the Atlas Plant Manager and Region Sales Manager. Atlas reserves the right to inspect material prior to return. • Eligible material must be returned within 60 days of original ship date. • All returns are subject to a 20% restocking fee plus outbound and inbound freight. • Freight arrangements on returned material will be the responsibility of the customer. • Credit will be given on resalable material only. Damaged material will not be eligible for credit. • Customer must retrieve non-salable material valued over $500 within 30 days of notification. Any unclaimed non-salable material will be subject to a disposal fee. FORCE MAJEURE • Atlas shall not be liable in damages for any delay or default to ship any order if such delay or default is caused by conditions beyond Atlas’ control, including, but not limited to: Acts of God, Government restrictions, wars, acts of terrorism, fires, or shortage of raw materials. Updated: 09.20.16 16 ACFoam ® Polyiso Roof Insulation Connecting Function with Facility™ Camp Hill, PA (800) 688-1476 LaGrange, GA (800) 955-1476 Diboll, TX (800) 766-1476 Northglenn, CO (800) 288-1476 East Moline, IL (800) 677-1476 Phoenix, AZ (800) 477-1476 Toronto, ON (888) 647-1476 Vancouver, BC (855) 267-1476 ©2016 Atlas Roofing Corporation