ACFoam ® Fastening Pattern Guide

advertisement
ACFoam
®
Polyiso Roof Insulation
Fastening Pattern Guide
Connecting Function with Facility™
Table of Contents
Product
Page
Installation Guidelines
3
BUR-8 Built-up or Selected Modified Bitumen Systems
4
FA-8 Fully Adhered Single Ply Systems
5
FA-11 Fully Adhered Single Ply Systems
6
FA-16 Fully Adhered Single Ply Systems
7
FA/HD-12 Fully Adhered Single Ply Systems
8
FA/HD-16 Fully Adhered Single Ply Systems
9
MF-5 Mechanically Fastened Single Ply Systems
10
MF/RB-6 Mechanically Fastened Systems
11
NB.1 Nailable Insulation Systems
12
NB.2 Nailable Insulation Systems
13
NB.3 Nailable Insulation Systems
14
15-16
Customer Service Policy
Back Cover
Manufacturing and Sales Locations
Updated: 09.20.16
2
ACFoam®
Polyiso Roof Insulation Fastening Pattern Guide
Before installation begins, the roof deck should be firm, well attached, even, clean and dry. Proper attachment of the insulation is necessary to prevent roof failures. Atlas is not responsible
for any damage caused by improper attachment. ACFoam® products can be attached to decks that are approved by FM Approvals and local codes. Atlas is not responsible for determining
the suitability of the deck.
ACFoam® shall be kept dry before, during and after installation. Install only as much ACFoam® as can be covered the same day with completed roofing. Although ACFoam® has been designed
to withstand normal foot traffic, protection from damage by construction traffic and/or abuse is extremely important. Roof surface protection such as plywood shall be used in areas where
storage and staging are planned and heavy or repeated traffic is anticipated during or after installation. Refer to Atlas Technical Bulletin TB-5.
Multi-Layer Installation
To minimize the effects of thermal bridging, Atlas strongly recommends the use of multiple layers when the total desired or specified R-value requires an insulation thickness greater than
2.7” thick. The joints in each layer should be offset in order to avoid a vertically continuous joint through the total insulation thickness. Two layers (or more) with joints staggered can provide
improved insulation performance by eliminating thermal bridges. This method also reduces condensation potential.
Mechanical Attachment
Mechanical fastening is the recommended method of attachment over nailable decks. General fastening frequency and spacing for steel, wood, cast-in-place structural concrete and poured
gypsum decks is covered in the ACFoam® & Nailable Roof Insulation Fastening Pattern Guide. Refer to the current FM Loss Prevention Data Sheet 1-29 for special considerations regarding
perimeter and corners of the roof. For further recommendations regarding attachment of insulation to lightweight insulating concrete decks or poured gypsum concrete decks, follow the
instructions as outlined in the current NRCA Roofing Manual. ACFoam® products shall not be adhered directly to these decks by any bitumen or adhesive attachment method. Refer to the
Nailable Insulation Guide for additional ACFoam® Nail Base and CrossVent® fastening
recommendations.
Adhesive Attachment (Does Not Apply to ACFoam® Composite Insulations, Nail Base or CrossVent®.)
For installing ACFoam® to a structural concrete deck, adhesive/bitumen attachment is the recommended method. When using hot bitumen on concrete decks, priming is necessary.
Precautions must be taken to prevent bitumen drippage. When using hot-applied bitumen for insulation attachment, the temperature of the bitumen should be approximately 50°F below
the interply hand mopping EVT. The deck must be dry and care must be taken to apply the bitumen in sufficient quantity to totally cover the available deck surface. Use 18 to 30 pounds
of bitumen per square to ensure proper attachment. To ensure embedment, the board must also be “stepped in” at several points while the bitumen is still hot enough to allow positive
attachment. The recommended ACFoam® insulation size for hot bitumen attachment is 4’ x 4’. When using polyurethane adhesives or cold applied asphalt adhesive follow the adhesive
manufacturer’s installation recommendation. In any case, roll or weigh down the insulation to ensure contact between the adhesive and the insulation board.
Vapor/Air Retarders
Moisture vapor tends to migrate from warmer to cooler areas. In building construction, vapor/air retarders are used to inhibit or block the passage of warm, moisture-laden air into walls or
roofing assemblies. To determine whether a vapor/air retarder is necessary, calculations based on interior relative humidity, interior temperature, and the outside design temperature must
be performed. Consult the current NRCA Roofing Manual for more information regarding vapor/air retarders and dew point calculations.
Special consideration should be given to construction-generated moisture as well. For example, construction generated moisture will be released when concrete floor slabs are placed after
the roof has been installed, which can drive large quantities of moisture into the roof system. Therefore, Atlas is not responsible for damage to the insulation when exposed to constructiongenerated moisture. Refer to the current NRCA Roofing Manual for recommendations regarding the use of a vapor retarder when construction-generated moisture is present. Refer to Atlas
Technical Bulletin TB-5. Consult vapor/air retarder manufacturer for recommended applications and details.
Storage
Factory applied packaging is intended only for protection during transit. When stored outdoors or on the job site, the insulation should be stacked on pallets at least three inches above
ground level and completely covered with a weatherproof covering such as a tarpaulin. The temporary factory-applied packaging should be slit or removed to prevent accumulation of
condensation. Roof insulation which has become wet or damaged should be removed and replaced with solid, dry insulation.
WARNING - DO NOT LEAVE EXPOSED
This product is a polyiso organic plastic foam and will burn if exposed to an ignition source of sufficient heat and intensity, or open flame, such as a welder’s torch. Like other organic
materials, this product will release smoke if ignited. Do not apply flame directly to ACFoam® roof insulations. This product should be used only in strict accordance with Atlas recommended
uses and application instructions.
Limitations of Liability
Other than the aforementioned representations and descriptions, Atlas Roofing Corporation (hereafter, “Seller”) makes no other representations or warranties as to the insulation sold herein.
The Seller disclaims all other warranties, express or implied, including the warranty of merchantability and the warranty of fitness for a particular purpose. Seller does, however, have a
limited warranty as to the LTTR-value of the insulation, the terms of which are available upon request from the Seller.
The Seller shall not be liable for any incidental or consequential damages including the cost of installation, removal, repair or replacement of this product. The Buyer’s remedies shall be
limited exclusively to, at Seller’s option, the repayment of the purchase price or resupply of product manufactured by Atlas in a quantity equal to that of the nonconforming product. Atlas
distributors, agents, salespersons or other independent representatives have no authority to waive or alter the above limitation of liability and remedies.
Updated: 09.20.16
3
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
24"
24"
24"
12"
24"
*FIELD- 8ea. Fasteners/Board (4'x8')
12"
48"
12"
12"
48"
24"
12"
48"
*FIELD- 4ea. Fasteners/Board (4'x4')
12"
24"
12"
12"
NOTES:
1. Minimum thickness of insulation shall be 1.3” ACFOAM®-II, -III OR -IV with mopped 0.5” Factory Mutual approved
perlite overlay.
NOTES:
2. Minimum
thickness
of insulation
shallBE
be1.3"
1.5”ACFOAM®-II,
ACFOAM®III-II,
OR -IV
with mopped
0.5” Factory
approved
1. MINIMUM
THICKNESS
OF INSULATION
SHALL
OR-III
IV WITH
MOPPED
0.5" FACTORY
MUTUAL Mutual
APPROVED
PERLITE
OVERLAY.
high
density wood fiber overlay.
2. MINIMUM THICKNESS OF INSULATION SHALL BE 1.5" ACFOAM®-II, III OR IV WITH MOPPED 0.5" FACTORY MUTUAL APPROVED HIGH
3. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
DENSITY WOOD FIBER OVERLAY.
4. Factory
Mutual 1-90
Fastening
Pattern.
3. MINIMUM
THICKNESS
SHALL
BE 1.5" WHEN
USING ACFOAM® COMPOSITE PB.
4. MINIMUM
THICKNESS
SHALL BE
2.0" WHEN
USING
ACFOAM®
COMPOSITE
FB.
5. Refer to
Factory Mutual
Global
Property
Loss
Prevention
Data Sheets
(1-29) or consult roof system manufacturer for
5. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
perimeter and corner design enhancement recommendations. 6. FACTORY MUTUAL 1-90 FASTENING PATTERN.
7. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
® PERIMETER AND CORNER
SYSTEM MANUFACTURER
FOR
ACFoam
-II & ACFoam®-III DESIGN ENHANCEMENT RECOMMENDATIONS.
Built-Up or Selected Modified Bitumen Systems
ACFoam®-II, ACFoam®-III & ACFoam®-IV
DWG #:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
BUILT-UP OR SELECTED MODIFIED BITUMEN SYSTEMS
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FMAtlas
Global,Roofing
Miami-Dade
County andhas
membrane
manufacturer
for additional
guidelines
well as design
Corporation
produced
this information
forinstallation
conceptual
designaspurposes
only. Prior to REVISION #:
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
installation,
Atlas
Roofing
Corporation
recommends
that
you
consult
your
local
building
code(s),
accepted all responsibility for verifying project specific fastening requirements prior to product installation. ISSUE DATE #:
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
Updated: 09.20.16
DWG #:
REVISION #:
ISSUE DATE:
BUR-8
BUR-8
1
02/29/2016
02/29/2016
03/04/2013
4
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
24"
24"
24"
12"
12"
12"
24"
12"
48"
*FIELD- 8ea. Fasteners/Board (4'x8')
48"
24"
12"
24"
*FIELD- 4ea. Fasteners/Board (4'x4')
12"
48"
12"
12"
NOTES:
1. Minimum single layer thickness of insulation shall be 2.0”.
2. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
NOTES:
FactorySINGLE
Mutual
1-90 THICKNESS
Fastening Pattern.
1. 3.
MINIMUM
LAYER
OF INSULATION SHALL BE 2.0".
4.
Refer
to
Factory
Mutual
Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
perimeter and corner design enhancement recommendations. 3. FACTORY MUTUAL 1-90 FASTENING PATTERN.
4. *REFER TO FACTORY MUTUAL GLOBAL
PROPERTY LOSS
PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
®
®
ACFoam -II & ACFoam -III
Fully Adhered Single Ply Systems
SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS.
DWG #:
ACFoam®-II, ACFoam®-III & ACFoam®-IV
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer
for additional
installationSINGLE
guidelines asPLY
well as SYSTEMS
design
FULLY
ADHERED
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted
all responsibility
for verifying
specific
fastening
requirements
prior to product
installation. Atlas Roofing
Corporation
hasproject
produced
this
information
for conceptual
design
purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening
requirements
prior to product installation.
Updated:
09.20.16
FA-8
REVISION #:
ISSUE DATE #:
DWG #:
REVISION #:
ISSUE DATE:
N/A
03/04/2013
FA-8
N/A
03/04/20135
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
24"
24"
24"
12"
18"
6"
12"
6"
18"
48"
*FIELD- 11ea. Fasteners/Board (4'x8')
24"
24"
24"
24"
48"
18"
18"
6"
24"
*FIELD- 6ea. Fasteners/Board (4'x4')
6"
12"
36"
48"
12"
6"
6"
NOTES:
1. Minimum single layer thickness of insulation shall be 1.5” to 1.9”.
2. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
NOTES:
Factory
Mutual
1-90 Fastening
Pattern.
1.3.
SINGLE
LAYER
THICKNESS
OF INSULATION
SHALL BE 1.5" to 1.9".
4.
Refer
to
Factory
Mutual
Global
Property
Data Sheets
(1-29)
or consult roof system manufacturer for
2. REFER TO FACTORY MUTUAL APPROVAL GUIDELoss
FOR Prevention
APPROVED FASTENERS
AND
PLATES.
perimeter and corner design enhancement recommendations.
3. FACTORY MUTUAL 1-90 FASTENING PATTERN.
4. *REFER TO FACTORY MUTUAL GLOBAL
PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
ACFoam®-II & ACFoam®-III
SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS.
Fully Adhered Single Ply Systems
DWG #:
ACFoam®-II, ACFoam®-III & ACFoam®-IV
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
FULLY ADHERED SINGLE PLY SYSTEMS
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted
responsibility
for verifying
project
specific this
fastening
requirements
prior to product
installation. AtlasallRoofing
Corporation
has
produced
information
for conceptual
design
purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
Updated:
09.20.16prior to product installation.
responsibility for verifying project specific fastening
requirements
REVISION #:
ISSUE DATE #:
DWG #:
REVISION #:
ISSUE DATE:
FA-11
N/A
03/04/2013
FA-11
N/A
6
03/04/2013
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
36"
12"
36"
6"
18"
12"
6"
6"
6"
12"
18"
12"
48"
12"
*FIELD- 16ea. Fasteners/Board (4'x8')
12"
12"
12"
24"
12"
12"
12"
48"
18"
18"
6"
6"
12"
18"
12"
48"
*FIELD- 8ea. Fasteners/Board (4'x4')
12"
18"
12"
6"
6"
12"
12"
12"
12"
NOTES:
1. Minimum single layer thickness of insulation shall be 1.3” to 1.4”.
NOTES:
2. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
1. SINGLE LAYER THICKNESS OF INSULATION SHALL BE 1.3" to 1.4".
3. Factory Mutual 1-90 Fastening Pattern.
2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
3. FACTORY
MUTUAL
1-90 FASTENING
PATTERN.
perimeter
and corner
design enhancement
recommendations. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
®
®
SYSTEM MANUFACTURER
FOR PERIMETER
AND CORNER
ACFoam
-II & ACFoam
-III DESIGN ENHANCEMENT RECOMMENDATIONS.
Fully Adhered Single Ply Systems
ACFoam®-II, ACFoam®-III & ACFoam®-IVDWG #:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FULLY for
ADHERED
SINGLE
PLY
FM Global, Miami-Dade County and membrane manufacturer
additional installation
guidelines
as wellSYSTEMS
as design
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
Atlas
Roofing
Corporation
has
produced
this
information
for
conceptual
design
purposes
accepted all responsibility for verifying project specific fastening requirements prior to product installation. only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
Updated: 09.20.16
FA-16
REVISION #:
N/A
ISSUE
03/04/2013
DWG
#: DATE #:FA-16
REVISION #:
N/A
ISSUE DATE:
03/04/2013
7
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
24"
24"
24"
12"
12"
12"
12"
12"
12"
48"
*FIELD- 12ea. Fasteners/Board (4'x8')
48"
24"
12"
*FIELD- 6ea. Fasteners/Board (4'x4')
12"
12"
48"
12"
12"
12"
NOTES:
1. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
2. Factory Mutual 1-75 Fastening Pattern.
NOTES:
3. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
1. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
perimeter and corner design enhancement recommendations. 2. FACTORY MUTUAL 1-75 FASTENING PATTERN.
®
3. *REFER TO FACTORY ACFoam
MUTUAL GLOBAL
LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
-HDPROPERTY
CoverBoard
SYSTEM MANUFACTURER
FOR PERIMETER
AND
CORNER
DESIGN ENHANCEMENT RECOMMENDATIONS.
Fully Adhered
Single
Ply
Systems
DWG #:
ACFoam®-HS Coverboard & ACFoam®-HD Coverboard
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
FULLY ADHERED SINGLE PLY SYSTEMS
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted all responsibility for verifying project specific fastening requirements prior to product installation. Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
Updated:
09.20.16
responsibility for verifying project specific fastening
requirements
prior to product installation.
FA/HD-12
N/A
REVISION #:
ISSUE DATE #:
DWG #:
02/29/2016
FA/HSHD-12
REVISION #:
N/A
ISSUE DATE:
02/29/2016
8
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
36"
12"
36"
6"
18"
12"
6"
6"
6"
12"
18"
12"
48"
12"
*FIELD- 16ea. Fasteners/Board (4'x8')
12"
12"
12"
24"
12"
12"
12"
48"
18"
18"
6"
6"
12"
18"
12"
48"
*FIELD- 8ea. Fasteners/Board (4'x4')
12"
18"
12"
6"
6"
12"
12"
12"
12"
NOTES:
1. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
2. Factory Mutual 1-90 Fastening Pattern.
NOTES:
3. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
1. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
perimeter and corner design enhancement recommendations. 2. FACTORY MUTUAL 1-90 FASTENING PATTERN.
3. *REFER TO FACTORY MUTUAL GLOBAL
PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
®
ACFoam -HD CoverBoard
Fully Adhered Single Ply Systems
SYSTEM MANUFACTURER FOR PERIMETER AND CORNER DESIGN ENHANCEMENT RECOMMENDATIONS.
ACFoam®-HD Coverboard
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer
for additional
installation
guidelines as
well asSYSTEMS
design
FULLY
ADHERED
SINGLE
PLY
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted
all responsibility
for verifying
project specific
requirements
prior to product
installation. Atlas Roofing
Corporation
has produced
thisfastening
information
for conceptual
design
purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening
requirements
prior to product installation.
Updated:
09.20.16
FA/HD-16
DWG #:
REVISION #:
N/A
ISSUE DATE #:
DWG #:
02/29/2016
FA/HD-16
REVISION #:
ISSUE DATE:
N/A
02/29/2016 9
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
42"
42"
6"
48"
18"
6"
6"
6"
18"
*FIELD- 5ea. Fasteners/Board (4'x8')
48"
24"
12"
24"
*FIELD- 4ea. Fasteners/Board (4'x4')
12"
48"
12"
12"
NOTES:
1. Minimum single layer thickness of insulation shall be 1.3”.
2. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
NOTES:
3. Factory Mutual 1-90 Fastening Pattern.
1. MINIMUM SINGLE LAYER THICKNESS OF INSULATION SHALL BE 1.3".
4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
perimeter and corner design enhancement recommendations. 3. FACTORY MUTUAL 1-90 FASTENING PATTERN.
®
®
4. *REFER TO FACTORY
MUTUAL GLOBAL
ACFoam
-II & PROPERTY
ACFoamLOSS
-IIIPREVENTION DATA SHEETS (1-29) OR CONSULT ROOF
SYSTEM MANUFACTURER
FOR PERIMETER
ANDSystems
CORNER DESIGN ENHANCEMENT RECOMMENDATIONS.
Mechanically
Fastened
DWG #:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
REVISION #:
MECHANICALLY FASTENED SINGLE PLY SYSTEMS
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted all responsibility for verifying project specific fastening requirements prior to product installation. ISSUE DATE #:
ACFoam®-II, ACFoam®-III & ACFoam®-IV
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
Updated:
09.20.16
responsibility for verifying project specific fastening
requirements
prior to product installation.
DWG #:
REVISION #:
ISSUE DATE:
MF-5
N/A
03/04/2013
MF-5
N/A
03/04/201310
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96"
40"
40"
8"
12"
8"
8"
8"
28"
32"
8"
48"
*FIELD- 6ea. Fasteners/Board (4'x8')
48"
24"
12"
12"
12"
24"
12"
48"
*FIELD- 4ea. Fasteners/Board (4'x4')
NOTES:
1. Minimum thickness of insulation shall be 0.5”.
NOTES:
2. Refer to Factory Mutual Approval Guide for approved fasteners and plates.
1. MINIMUM THICKNESS OF INSULATION SHALL BE 0.5".
3. Factory Mutual 1-90 Fastening Pattern.
2. REFER TO FACTORY MUTUAL APPROVAL GUIDE FOR APPROVED FASTENERS AND PLATES.
4. Refer to Factory Mutual Global Property Loss Prevention Data Sheets (1-29) or consult roof system manufacturer for
3. FACTORY MUTUAL 1-90 FASTENING PATTERN.
perimeter and corner design enhancement recommendations. 4. *REFER TO FACTORY MUTUAL GLOBAL PROPERTY LOSS PREVENTION DATA SHEETS (1-29) OR CONSULT ROOF SYSTEM
®
MANUFACTURER FOR PERIMETER
CORNER Board
DESIGN ENHANCEMENT RECOMMENDATIONS.
ACFoamAND
Recover
Mechanically Fastened Systems
ACFoam® Recover Board
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local
building code(s), contractFASTENED
documents, professional
engineer,
MECHANICALLY
SYSTEM
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
enhancements. UseCorporation
of Atlas Roofing
Corporation
fastening patterns
constitutesdesign
that thepurposes
user has personally
Atlas Roofing
has
producedconceptual
this information
for conceptual
only. Prior to
accepted
all responsibility
for verifying
project specific
fastening requirements
priorconsult
to product
installation. installation,
Atlas Roofing
Corporation
recommends
that you
your
local building code(s),
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
Updated: 09.20.16
DWG #:
REVISION #:
MF/RB-6
N/A
DWG
ISSUE#:DATE #:MF/RB-6
03/04/2013
REVISION #:
N/A
ISSUE DATE:
03/04/2013
11
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96''
22''
48''
24''
24''
22''
22''
3''
3''
21''
48''
22''
21''
2''
2''
48''
21''
2''
2''
21''
3''
3''
15 Fasteners per Board
(4'x8')
8 Fasteners per Board
(4'x4')
96''
22''
48''
24''
24''
22''
22''
3''
14''
22''
3''
14''
2''
48'' 14''
2''
48'' 14''
2''
2''
14''
14''
3''
20 Fasteners per Board
(4'x8')
3''
10 Fasteners per Board
(4'x4')
96''
22''
48''
24''
24''
22''
22''
3''
48''
22''
3''
2''
2''
48''
2''
2''
10.5" Typ.
3''
25 Fasteners per Board
(4'x8')
3''
10.5" Typ.
13 Fasteners per Board
(4'x4')
NOTES:
NOTES: 1. MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS.
2. MINIMUM THICKNESS OF ACFOAM®
NAIL BASE ®
SHALL BE 1.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS.
®
1. Minimum3. ATLAS
thickness
of ACFoam
CrossVent
shall be 2.5”
To OF
meet
FM
1-60, 1-90
or 1-105
requirements.
NAIL BASE
FASTENERS REQUIRED
FOR ATTACHMENT
AS PART
ATLAS
ACFOAM®
NAILABLE
INSULATION
SYSTEMS.
4. REFER TO ATLAS NAILABLE INSULATION
GUIDE FOR ADDITIONAL FASTENING REQUIREMENTS.
2. Minimum
thickness of ACFoam® Nail Base
shall be 1.5” To meet FM 1-60, 1-90 or 1-105 requirements.
®
3. Atlas Nail Base Fasteners required for attachment
as
part
of Atlas
ACFoam
Nailable
Insulation
Systems.
ACFoam® Nail
Base,
ACFoam®-III
Nail Base,
ACFoam® CrossVent
& ACFoam®-III
CrossVent
NAILABLE INSULATION
SYSTEMS
4. Refer to Atlas Nailable Insulation Guide for additional fastening
requirements
C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to
installation, Atlas Roofing Corporation recommends that you consult your local building code(s),
®
® Global, Miami-Dade® County and membrane
contract
documents, professional engineer, FM
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
ACFoam Nail Base & ACFoam CrossVent
Nailable Insulation Systems
REVISION #:
ISSUE DATE:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16
NB.1
DWG #:
N/A
08/13/14
DWG #:
REVISION #:
ISSUE DATE #:
NB.1
N/A
08/13/2014
12
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96''
22''
48''
24''
24''
22''
22''
3''
3''
8.4" Typ.
48''
22''
2''
2''
10.5" Typ.
48''
2''
2''
3''
3''
30 Fasteners per Board
(4'x8')
15 Fasteners per Board
(4'x4')
96''
22''
48''
24''
24''
22''
22''
3''
48''
22''
3''
7" Typ.
2''
2''
48''
2''
3''
3''
35 Fasteners per Board
(4'x8')
18 Fasteners per Board
(4'x4')
96.0''
22.0''
24.0''
24.0''
24.0''
22.0''
2''
24.0''
22.0''
3''
48''
2''
8.4" Typ.
22.0''
3''
2''
6" Typ.
48''
2''
2''
3''
3''
40 Fasteners per Board
(4'x8')
7" Typ.
20 Fasteners per Board
(4'x4')
NOTES:
NOTES: 1.
MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS.
®
MINIMUM THICKNESS
OF ACFOAM®
NAIL BASE®SHALL
1.5"2.5”
TO MEET
FM 1-60,FM
1-901-60,
OR 1-105
REQUIREMENTS.
1. Minimum2.thickness
of ACFoam
CrossVent
shallBEbe
To meet
1-90
or 1-105 requirements.
3. ATLAS NAIL BASE FASTENERS REQUIRED FOR ATTACHMENT AS PART OF ATLAS ACFOAM® NAILABLE INSULATION SYSTEMS.
®
2. Minimum4. REFER
thickness
of ACFoam
Nail Base
be 1.5” To
meet FM
1-60, 1-90 or 1-105 requirements.
TO ATLAS
NAILABLE INSULATION
GUIDEshall
FOR ADDITIONAL
FASTENING
REQUIREMENTS.
3. Atlas Nail Base Fasteners required for attachment as part of Atlas ACFoam® Nailable Insulation Systems.
ACFoam® Nail Base & ACFoam® CrossVent
4. Refer to Atlas Nailable Insulation Guide for additional fastening requirements
NAILABLE INSULATION SYSTEMS
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to
®
® that you consult your
® local building code(s),
installation,
Atlas Roofing Corporation recommends
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
ACFoam Nail Base & ACFoam CrossVent
Nailable Insulation Systems
C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg
REVISION #:
ISSUE DATE:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16
NB.2
DWG #:
N/A
08/13/14
DWG #:
REVISION #:
ISSUE DATE #:
NB.2
N/A
08/13/2014
13
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™
96''
22''
24''
24''
24''
22''
24''
22''
22''
3''
48''
3''
5.25" Typ.
2''
2''
48''
3''
3''
45 Fasteners per Board
(4'x8')
23 Fasteners per Board
(4'x4')
96''
22''
24''
24''
24''
22''
24''
22''
22''
3''
48''
2''
2''
6" Typ.
2''
3''
2''
4.6" Typ.
48''
2''
5.25" Typ.
3''
2''
3''
50 Fasteners per Board
(4'x8')
25 Fasteners per Board
(4'x4')
NOTES: NOTES:
1. MINIMUM THICKNESS OF ACFOAM® CROSSVENT SHALL BE 2.5" TO MEET FM 1-60, 1-90 OR 1-105 REQUIREMENTS.
®
®
1. Minimum2. thickness
of ACFoam
CrossVent
shallBEbe
To meet
1-90
or 1-105 requirements.
MINIMUM THICKNESS
OF ACFOAM®
NAIL BASE SHALL
1.5"2.5”
TO MEET
FM 1-60,FM
1-90 1-60,
OR 1-105
REQUIREMENTS.
3. ATLAS NAIL BASE FASTENERS REQUIRED
FOR ATTACHMENT AS PART OF ATLAS ACFOAM® NAILABLE INSULATION SYSTEMS.
®
2. Minimum
thickness
of
ACFoam
Nail
Base
shall
be
1.5”
To
meet
FM
1-60,
1-90
or
1-105 requirements.
4. REFER TO ATLAS NAILABLE INSULATION GUIDE FOR ADDITIONAL FASTENING REQUIREMENTS.
3. Atlas Nail Base Fasteners required for attachment as part of Atlas ACFoam® Nailable Insulation Systems.
ACFoam® Nail Base & ACFoam® CrossVent
4. Refer to Atlas Nailable Insulation Guide for additional fastening requirements
NAILABLE INSULATION SYSTEMS
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to
®
® that you consult your
® local building code(s),
installation,
Atlas Roofing Corporation recommends
contract documents, professional engineer, FM Global, Miami-Dade County and membrane
manufacturer for additional installation guidelines as well as design enhancements. Use of Atlas
Roofing Corporation conceptual fastening patterns constitutes that the user has personally accepted all
responsibility for verifying project specific fastening requirements prior to product installation.
ACFoam Nail Base & ACFoam CrossVent
Nailable Insulation Systems
C:\Users\a howard \De sktop\Atlas_ Corporate _Lo go_ -_B lack.jpg
REVISION #:
ISSUE DATE:
Atlas Roofing Corporation has produced this information for conceptual design purposes only. Prior to installation, Atlas
Roofing Corporation recommends that you consult your local building code(s), contract documents, professional engineer,
FM Global, Miami-Dade County and membrane manufacturer for additional installation guidelines as well as design
enhancements. Use of Atlas Roofing Corporation conceptual fastening patterns constitutes that the user has personally
accepted all responsibility for verifying project specific fastening requirements prior to product installation. Updated: 09.20.16
NB.3
DWG #:
N/A
08/13/14
DWG #:
REVISION #:
ISSUE DATE #:
NB.3
N/A
08/13/2014
14
Customer Service Policy
Roof and Wall Insulation Division
STANDARD PRODUCTS
• ACFoam®-II: 1.0”, 1.5”, 2.0”, 2.2”, 2.5”, 2.6”, 3.0”, 3.5”, 4.0” (4’ x 4’, 4’ x 8’)
• Tapered ACFoam®-II: AA, A, B, C, X, Y, Q Panels (4’ x 4’)
• ACFoam®-HD CoverBoard: (4’ x 8’)
• EnergyShield®: ½”, ¾”, 1.0”, 1.5”, 2.0” (4’ x 8’)
• EnergyShield® CGF: ½”, ¾”, 1.0”, 1.5”, (4’ X 8’)
• EnergyShield® PRO: 1.0”, 1.5”, 2.0”, 2.5”, 3.0” (4’ x 8’)
• EnergyShield® PRO2: 1.0”, 1.5”, 2.0”, 2.5”, 3.0” (4’ x 8’)
NON-STANDARD PRODUCTS
• Orders for non-standard products, which are not released for shipment within 30 days from date of original
shipment, will be subject to payment in full. Atlas may require sign-off of a Non-Standard Product Purchase
Agreement.
TAPERED SYSTEMS
• Tapered systems designed by Atlas will be scheduled and manufactured only with authorized, signed shop
drawings.
• Shop Drawings will be produced with a valid purchase order.
CUSTOMER PICKUP (CPU)
• Customer pickup will be permitted with prior confirmation by the Atlas sales department.
• Orders for material not picked up within 48 hours of the scheduled pickup date will be subject to rescheduling.
• Orders for non-standard material which have not been claimed within 30 days of scheduled pick up date will
be subject to payment in full.
• Tarping of CPU trucks will be at the discretion of the customer.
• Minimum pickup quantity will be the equivalent of 10 or more 4’ x 8’ and 20 or more 4’ x 4’ units.
• Pick-up allowance shall be $15.00 per equivalent unit of 4’ x 8’ x 4’ high regardless of final destination (except
in Toronto and Vancouver). Sheathing units ½” thru 1.5” are 2’ high so $7.50 allowance per unit is applied.
LESS THAN TRUCKLOAD ORDERS
• Orders for less than a truckload will be subject to deficit freight and fuel surcharge on the unused portion of
truck.
• Deficit freight is calculated on 24 4’ x 8 x 4’ high units less the balance shipped.
• Atlas will make every effort to pool partial loads. Such shipments will be subject to a stopover fee for each
individual delivery.
ADDITIONAL STOPS & FUEL SURCHARGE
• Stopovers will be charged $100 per stop.
• Stops must be within 150 miles of each other.
• Requests for more than two stops on a truck will be reviewed by Atlas to determine if feasible. Additional
charges will apply.
• Atlas passes through all carrier Fuel Surcharges as a separate line item on the invoice.
• Fuel Surcharges are calculated based on the US National Average Price of Diesel as reported weekly by the
Department of Energy for actual loaded miles for delivery.
Updated: 09.20.16
15
TRUCK DIVERSIONS
• Trucks diverted after shipment will be subject to a diversion fee plus additional mileage fees and fuel surcharges.
THIRD PARTY DELIVERY CHARGES
• Atlas cannot guarantee time of deliveries.
• Customer is responsible for billing the carrier for charges resulting from a late delivery.
• Atlas will make pre-calls confirming delivery if requested (contact name and phone number must be given at
time of order entry).
• Detention charges from the carrier will be passed on to the customer. Detention charges become effective
two hours from scheduled time of delivery.
• Unloading not completed prior to 5 p.m. will be subject to layover charges.
• Carrier assessed fuel surcharges will be passed on to the customer.
DATE CHANGES/CANCELLATIONS
• All re-dated orders will be subject to product availability.
• Date change/cancellation made within 48 hours of shipment will be charged $500 minimum per truckload.
Additional freight charges will be assessed once truck is in route.
DAMAGES
• Unless otherwise noted in this policy, all shipments are shipped and invoiced as FOB Origin/Freight Prepaid.
CPU (Customer Pickup) shipments are shipped and invoiced as FOB Origin/Freight Collect.
• Material damaged in route is the responsibility of the carrier.
• Customer must file all claims for damaged material directly with the carrier.
• Material shipped to replace damaged product will be invoiced separately.
SHORTAGES
• Customer and carrier must note shortages with signatures on the shipping document upon delivery and
prior to carrier departure.
RETURNS
• All returns require preauthorization by the Atlas Plant Manager and Region Sales Manager. Atlas reserves
the right to inspect material prior to return.
• Eligible material must be returned within 60 days of original ship date.
• All returns are subject to a 20% restocking fee plus outbound and inbound freight.
• Freight arrangements on returned material will be the responsibility of the customer.
• Credit will be given on resalable material only. Damaged material will not be eligible for credit.
• Customer must retrieve non-salable material valued over $500 within 30 days of notification. Any unclaimed
non-salable material will be subject to a disposal fee.
FORCE MAJEURE
• Atlas shall not be liable in damages for any delay or default to ship any order if such delay or default is
caused by conditions beyond Atlas’ control, including, but not limited to: Acts of God, Government restrictions, wars, acts of terrorism, fires, or shortage of raw materials.
Updated: 09.20.16
16
ACFoam
®
Polyiso Roof Insulation
Connecting Function with Facility™