Installation Sheets Manual Energy Conservation and Misc. Kits Section Technical Bulletin Issue Date 121 Q Q135 0300 Q135 Automatic Flue Damper System Figure 1: Q135 Automatic Flue Damper System Application This energy-saving, high-efficiency, automatic flue damper system retains heat that is normally wasted through the open flue when the appliance is not firing. It consists of a Y15 damper and an M35 actuator. The system is for use with certified gas fired appliances. It can be used with both standing pilot and electronic ignition systems. A wiring harness electrically interlocks the damper system to the appliance. Unplugging either end results in a system shut down. The output of the Q135 is safety relevant and must be supervised by the appliance throughout main burner operation. A position check during burner startup is not sufficient. IMPORTANT: © 2000 Johnson Controls, Inc. Part No. 24-8143-529, Rev. B Code No. LIT-121530 This product must be used only in conjunction with redundant gas valves (main burner flow must pass through both valve seats), and must not be used with valves that can be manually opened. 1 www.johnsoncontrols.com Table 1: Specifications Product Q135 Automatic Flue Damper Voltage 24 VAC, 50/60 Hz Operating Current 0.2 Ampere Output Contact Rating 5 Amperes Inrush 2 Amperes Steady Available Sizes 127 mm (5 in.) through 254 mm (10 in.) diameter Stack Material Cover/Case Stainless Steel Galvanized Steel Operating Temperature Range Actuator: Stack: 0 to 65°C (32 to 150°F) 0 to 385°C (32 to 725°F) Y184 Terminations Actuator End: Appliance End: Molex Receptacle Molex Plug (Standard) Bare or Terminals (Optional) Open Position Standard: ± 3° From Full Open Agency Listing Approved as part of the appliance. Specification Standards ANSI Standard Z21.10.3 prA2, EN 89 Enclosure Degree of Protection IP10 IMPORTANT: For applications that require EN certification, the damper flow characteristics test per prA2, EN 89 must be conducted as part of the approval testing of the application appliance. IMPORTANT: For applications that require EN certification, the 24V transformer must be a safety insulating transformer tested to EN60742 or equivalent, and it must be installed and protected according to the manufacturer’s specifications. IMPORTANT: The output of the Q135 is safety relevant and must be supervised by the appliance throughout main burner operation. A position check during burner startup is not sufficient. The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Refer to the Q135 Series Product Bulletin (LIT-4350760) for necessary information on operating and performance specifications of this product. 2 Q—Q135 Automatic Flue Damper System Technical Bulletin Operation The damper actuator opens and closes the damper blade upon demand of the system thermostat. The damper must be in the open position before the main burner circuit is energized. It will remain open while the main burner is operating. Visible on the front label of the actuator are a damper blade position indicator and a green light. The light signifies that power from the thermostat has opened the damper and that power is available to the appliance for main burner ignition. See Figure 2. Figure 2: Diagnostic Indicators The blade and the actuator are designed to rotate in only one direction and must not be turned manually except as described in the Emergency Operation Procedure section. The direction of rotation is clearly marked on the flue duct and the actuator. Any attempt to turn the blade in the opposite direction will cause damage to the unit and possible unsafe operation. ! CAUTION: Equipment Damage Hazard. Forcing the shaft in the wrong direction will damage the switches and cause unsafe operation. Q—Q135 Automatic Flue Damper System Technical Bulletin 3 Sequence of Operation The Q135 operates in the following manner: 1. Damper is in the closed position. 2. Thermostat contacts close on a call for heat. 3. M35 actuator rotates the damper blade to the open position. Power is available for main burner ignition (green light is on). 4. System thermostat reaches setpoint and contacts open. 5. The burner circuit is de-energized and the M35 closes the damper. 6. The system is now ready for the next heating cycle. Installation ! WARNING: Shock Hazard. Avoid electrical shock and equipment damage. Disconnect electrical power and turn off gas before wiring control into circuit. All installations must comply with local codes or, in the absence of local codes, with the National Fuel Gas Code (ANSI Z223.1) and National Electrical Code (ANSI/NFPA 70), or European National standards. Mounting ! WARNING: Asphyxiation Hazard. Do not install the stainless steel plug in the damper blade hole or use a model without a hole on a standing pilot application. This instruction sheet is intended as a guide for qualified personnel installing or servicing Johnson Controls Q135 flue damper. To mount the Q135: 1. Install the damper assembly vertically on the flue collar with the flow arrow pointed away from the appliance (see Figure 3). Secure according to the manufacturer’s recommendations. The damper assembly must be installed upstream of the appliance draft hood. 2. Mount the damper assembly with clearance not less than 6 inches from combustible materials. Install vertically on the flue collar with the flow arrow pointed away from the appliance. Figure 3: Mounting Position 4 Q—Q135 Automatic Flue Damper System Technical Bulletin Wiring ! WARNING: Asphyxiation Hazard. Do not negate the action of any existing safety or operational control. The M35 actuator is powered with 24V, 50/60 Hz supplied through the wiring harness. Install the wiring harness between the actuator and the appliance ignition circuit in accordance with the appliance manufacturer’s instructions. Carefully check the entire installation to be sure it is in compliance with instructions and codes. Note: For applications that require EN certification, the 24V transformer must be a safety insulating transformer tested to EN60742 or equivalent, and it must be installed and protected according to the manufacturer’s specifications. Connection Diagram Figure 4 illustrates the general connection diagram of the Q135 system and the connections of the Q135 actuator. Note: The Q135 provides power to the output when the damper is in the open position. Common 24 VAC Output Thermostat Fuse* 24 VAC Com Thermostat Q135 Ignition Control Y184 Wiring Harness Gas Valve * The fuse electrical rating should be determined by the application requirements to provide proper protection. Figure 4: Connection Diagram Q—Q135 Automatic Flue Damper System Technical Bulletin 5 Checkout Procedure Repairs and Replacement Turn on the electrical power and gas supply to the appliance. Before leaving the installation, observe three complete operating cycles as follows: 1. Turn the system thermostat to a high setting (call for heat). 2. Observe that the damper rotates open and that the ignition circuit is fully energized only after the damper is fully open, as shown by the position indicator and the green light on the actuator. 3. Turn the thermostat to a low setting. The ignition circuit should be immediately de-energized (the green light goes off), and the damper should rotate and stop in the closed position. 4. Return the thermostat to the normal setting. If the ignition circuit is not operating when the system thermostat is calling for heat and the damper is open with the green light on, check the appliance ignition circuit (valves, pilot, electronic ignition, etc.) If the damper is not in the open position with the green light on when the system thermostat is calling for heat, verify that the transformer, thermostat, limits, and wiring harness are not the problem. If it appears that the actuator has failed and a replacement Q135 is not readily available, the appliance may temporarily be returned to service by using the Emergency Operation Procedure detailed below. Emergency Operation Procedure 6 To temporarily return the appliance to service after an actuator failure, follow these steps: 1. Move the manual switch, located on the side of the actuator to the On position. 2. If the green light illuminates, the appliance is operational. 3. If the green light does not illuminate, it will be necessary to manually rotate the damper blade to the open position; refer to the Manual Opening section. Q—Q135 Automatic Flue Damper System Technical Bulletin Manual Opening ! CAUTION: Equipment Damage Hazard. Forcing the shaft in the wrong direction will damage the switches and cause unsafe operation. To manually open the damper blade, use a small wrench or pliers placed on the square indicator protruding through the cover of the actuator (see Figure 5). Slowly and gently turn the square indicator, only in the direction indicated by the rotational arrows on the cover of the actuator, until the green light comes on. If the light comes on and goes off, this indicates you have turned the blade too far. Do not reverse the direction of rotation but continue rotating the blade another 180 degrees. Repeat this procedure until the light remains on. Figure 5: Manual Rotation The flue damper will now remain in the open position and supply power to the ignition circuit on demand of the system thermostat. However, the flue damper will not provide energy savings until a replacement Q135 is obtained from the original equipment manufacturer. Field repairs, other than the procedure above, must not be made. Q—Q135 Automatic Flue Damper System Technical Bulletin 7 Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 8 Q—Q135 Automatic Flue Damper System Technical Bulletin www.johnsoncontrols.com FAN 121 Installation Sheets Manual Printed in U.S.A.