Lingo® Baseplate Installation Instructions Description The Lingo® Energy Infosystem is the next generation control processor that functions as a system network manager and control monitor in Novar’s Logic One® Advanced Building Control System. Lingo monitors and logs the operations of the local control modules, manages network communications, and provides expandable and integrated control of the building’s equipment. Lingo’s processing power, compatibility, and multiple network capabilities provide optimum control to cut energy costs, increase comfort, and reduce equipment maintenance. This document provides the installation procedures for mounting the Lingo baseplate, connecting power and network communications, and making other appropriate wiring connections. Lingo Specifications Agency Approvals Listed device: Standards used: CUL/UL E90949 UL 916, Energy Management Equipment CSA C22.2, No. 205-M1983, Signal Equipment Power Requirements Voltage: Consumption: 24 VAC, Class 2 40 VA Input/Output Ratings Analog Inputs: Digital Inputs: Output (Fault): 4 to 20 mA Contact closure only 24 VAC or VDC, 2 amp (pilot duty) Class 2 Operating Environment Temperature: Humidity: 32° to 140°F (0° to 60°C) 0 to 95% Relative, noncondensing Physical Dimensions (Baseplate only) Height: Width: Depth: Weight: DOC. #569065000—B 8/17/06 30 inches 13.25 inches 2.5 inches 7.0 lb (All aluminum enclosure) 1 Lingo® Baseplate Installation Instructions Precautions Take the following precautions during installation: § Observe national and local electrical codes. § Connect 24 VAC power wiring to the terminals marked as 24 VAC only. Connection to other terminals will damage them. § Do not use the Lingo as a final safety device. § Make sure that the 24-VAC power wiring is connected to a dedicated 40 VA transformer. No other devices should be powered by the transformer connected to the Lingo. § Do not ground the secondary side of the transformer for this module. § Make sure that the Lingo power cannot be switched off accidentally. The Lingo requires continuous power for proper operation. Mounting the Lingo Baseplate to the Wall The following items are needed to mount the Lingo baseplate to the wall: § The Lingo baseplate § The hex wrench (included with the baseplate) § Four screws (not provided) NOTE! The baseplate assembly should be mounted in an accessible location with the top of the assembly not more than 6 feet from the floor. The wall should have a flat and smooth surface to prevent the baseplate from being bent. When the baseplate is mounted to paneling or drywall, hollow-wall anchors should be used to insure that the assembly remains secure. Use the following procedure and refer to Figure 1, as necessary, to mount the Lingo baseplate to the wall. 2 DOC. #569065000—B 8/17/06 Lingo® Baseplate Installation Instructions Step 1 Procedure Remove the baseplate’s cover. § § Use the hex wrench included with the baseplate to loosen the two screws at the bottom of the baseplate. Lift off the cover. 2 Position the baseplate against the wall. 3 Mark the wall to show the locations of the four slotted mounting holes in the corners of the baseplate. 4 Drill holes in the places marked on the wall. 5 Install the hollow-wall or other appropriate fasteners. 6 Turn appropriate screws into the fasteners until approximately one-quarter inch remains between the wall and the head of the screws. 7 Position the baseplate over the screws and slide it down until the screws slide into the slots. 8 Tighten the screws to secure the baseplate. PHONE LINE ETHERNET 25 14 1 20 37 1 13 19 RS-232 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 OUTDOOR LIGHT SENSOR 24 VAC 38 38 37 37 CLASS 2 OUTDOOR TEMP SENSOR WARNING: AVERTISSEMENT: 11 12 12 CE DISPOSITIF NE CONSTUTUE PAS UN DISPOSITIF DE SECURITE FINAL. 36 USE COPPER CONDUCTORS ONLY PHASE LOSS SENSOR INPUT 35 WARNING: AVERTISSEMENT: NETWORK "D" 'A' MODULE NETWORK TO REDUCE THE RISK OF ELECTRICAL SHOCK OR FIRE, DO NOT INTERCONNECT THE OUTPUTS OF DIFFERENT CLASS 2 CIRCUITS. 33 POUR REDUIRE LE RISQUE DE CHOC ELECTRIQUE OU D'INCENDIE, NE PAS RELIER LES SORTIES DE CIRCUITS CLASSE 2 DISTINCTS. 'B' MODULE 34 BACnet 'C' MODULE 'D' MODULE 35 34 33 32 32 31 31 30 30 OUT SHIELD 13 36 LonWorks TORQUE TERMINALS TO .5 LB.IN. MAX ALLOWABLE AMBIENT TEMP: 50 C (122 F) EMERGENCY STATUS INPUT SYSTEM FAULT OUTPUT SERVICE ALL INPUTS AND OUTPUTS ARE CLASS 2 DEMAND PULSE INPUT IN 11 30 VA THIS UNIT IS NOT INTENDED TO BE USED AS A FINAL SAFETY DEVICE. 14 SHIELD 15 16 17 SHIELD 18 19 20 SHIELD 21 22 23 NOVARNET SHIELD 24 25 26 29 29 28 28 27 LINGO/T 0R0 13 Figure 1. DOC. #569065000—B 8/17/06 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Lingo baseplate mounting holes 3 Lingo® Baseplate Installation Instructions Supplying the Lingo with Power The Lingo is powered by a 24-VAC, 40 VA, Class 2 transformer (not included—the transformer kit must be purchased separately). It must be installed not more than 50 feet from the Lingo using minimum 18-gauge wire or mounted directly to the Lingo baseplate through the knockouts on the sides of the assembly. Refer to Figure 2, as necessary, when installing the 24 VAC, Class 2 transformer. 24-VAC, Class 2 40 VA screw terminal. Terminals 1–4 and Demand Pulse Input and Phase Loss Sensor Input terminals. Ground Terminal 36. PHONE LINE ETHERNET 14 25 20 37 1 13 1 19 RS-232 1 1 2 2 OUTDOOR LIGHT SENSOR 24 VAC 38 38 37 37 36 36 35 35 34 34 33 33 32 32 31 31 30 30 29 29 28 28 CLASS 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 OUTDOOR TEMP SENSOR WARNING: AVERTISSEMENT: 12 CE DISPOSITIF NE CONSTUTUE PAS UN DISPOSITIF DE SECURITE FINAL. USE COPPER CONDUCTORS ONLY PHASE LOSS SENSOR INPUT LonWorks TORQUE TERMINALS TO 4.5 LB.IN. NETWORK MAX ALLOWABLE AMBIENT TEMP: 60 C (140 F) WARNING: AVERTISSEMENT: EMERGENCY STATUS INPUT SYSTEM FAULT OUTPUT SERVICE ALL INPUTS AND OUTPUTS ARE CLASS 2 DEMAND PULSE INPUT NETWORK "D" IN 12 40 VA THIS UNIT IS NOT INTENDED TOB E USED AS A FINAL SAFETY DEVICE. 'A' MODULE POUR REDUIRE LE RISQUE DE CHOC ELECTRIQUE OU D'INCENDIE, NE PAS RELIER LES SORTIES DE CIRCUITS CLASSE 2 DISTINCTS. 'B' MODULE BACnet 'C' MODULE 'D' MODULE OUT SHIELD 13 TOR EDUCE THE RISK OF ELECTRICAL SHOCK OR FIRE, DON OT INTERCONNECT THE OUTPUTS OF DIFFERENT CLASS 2 CIRCUITS. 14 SHIELD 15 16 17 SHIELD 18 19 20 SHIELD 21 22 23 NOVARNET SHIELD 24 25 26 27 LINGO/T 0R0 13 Figure 2. 4 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Lingo baseplate terminal strips for wiring connections DOC. #569065000—B 8/17/06 Lingo® Baseplate Installation Instructions Step Procedure 1 Connect the blue and yellow leads from the transformer secondary to the screw terminals labeled 24 VAC, Class 2, 40 VA, located on the Lingo terminal board. 2 Connect the transformer primary leads (white/black) to a 120-VAC source. 3 Connect the ground terminal (Terminal 36) to a suitable earth ground. 4 Apply power to check voltage at the 24 VAC terminals. § 5 Voltage should be approximately 24 to 28 VAC. Turn off the power until needed. NOTE! The Lingo requires continuous power for proper operation. Make sure the Lingo power cannot be switched off accidentally. NOTE! The Lingo requires a dedicated transformer for the electronics. A separate transformer must be provided for its control outputs. Wiring the Lingo Inputs and Outputs Refer to Figure 2, as necessary, and use the procedure provided below to wire the Lingo input/output connections. NOTE! All digital inputs should be dry contact closures. Outdoor Light Sensor Novar’s 4- to 20-mA Analog Light Sensor (ALS) should be connected to the Lingo with two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) wiring. Step DOC. #569065000—B 8/17/06 Procedure 1 Connect the white (+) wire from the sensor to the Lingo at Terminal 2 (+) at the Outdoor Light Sensor input connections. 2 Connect the black (–) wire from the sensor to the Lingo at Terminal 1 (–) at the Outdoor Light Sensor Input connections. 5 Lingo® Baseplate Installation Instructions Outdoor Temperature Sensor For outdoor temperature sensing, Lingo uses the 4 to 20-mA Outdoor Temperature Sensor (OTS/2). Two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) should be used to connect the sensor to the Lingo. Step Procedure 1 Connect the white (+) wire from the sensor to Lingo’s Terminal 4 (+) at the Outdoor Temperature Sensor input connections. 2 Connect the black (–) wire from the sensor to Lingo’s Terminal 3 (–) at the Outdoor Temperature Sensor input connections. Demand Pulse Input Step 1 Procedure Connect the isolated contacts of a pulse-type utility meter or watt transducer to the terminals labeled Demand Pulse Input. Phase Loss Sensor Step 1 Procedure Connect the normally open, dry contact output of an electrical phase loss monitor to the terminals labeled Phase Loss Sensor Input. Emergency Status Input Step 1 Procedure Connect the normally open, dry contact output of an emergency monitoring system to the terminals labeled Emergency Status Input. System Fault Output Under normal operating conditions, a normally open set of contacts will be held closed. When an alarm occurs, the contacts open momentarily. This signal indicates a Lingo fault alarm. 6 DOC. #569065000—B 8/17/06 Lingo® Baseplate Installation Instructions Module Communications Lingo can accept connections from 128 modules in Novar’s module network without using a Network Expander Module. (The maximum number of modules is subject to software limitations.) A maximum of 32 modules can be connected to each of the A, B, C, and D Module terminals located along the bottom of the Lingo’s terminal board. NOTE! Modules with the same physical addresses must not be connected to the same port. For example, modules with the address 00 and 64 have the same physical address, so they cannot both reside on the same COM port (A, B, C, or D). Use two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) and the following procedure to make the module communications connections. Step Procedure 1 Connect the black wire from the cable to the minus (–) terminal. 2 Connect the shield wire to the SHIELD terminal. 3 Connect the white wire to the plus (+) terminal. NOTE! Novar’s Network Expander Module is not used with the Lingo. Checking Installation Check the following items to ensure proper operation: § § Make sure the baseplate is attached securely to the wall. Check all wiring connections to make sure they are correct and secure. If the wiring is correct and the baseplate is secure, reattach the Lingo baseplate cover. Operation of the Lingo requires the Lingo electronics. The Lingo Electronics Installation Instructions (Doc. #569066000) provide information about installing the electronics, making all other required wiring connections, and verifying proper operation. DOC. #569065000—B 8/17/06 7 Lingo® Baseplate Installation Instructions Model and Part Numbers The part numbers supplied in Table 1 should be used to order the necessary Novar parts. Table 1. Novar Part Numbers PRODUCT MODEL NO. PART NO. Lingo Baseplate Lingo-BPL 750100000 Lingo Electronics Assembly (no options) Lingo 750000000 Options: Lingo with Integral Touchscreen Lingo with Integral Touchscreen and Modem Lingo with Modem 750007000 750004000 750005000 24-VAC, 40 VA, Class 2 Transformer Kit 24V-XFR 730090000 Analog Light Sensor ALS-300 708100000 Outdoor Temperature Sensor OTS/2 735070000 Two-conductor, shielded cable (Belden 8761 equivalent) WIR-1010 709001000 Regulatory Compliance Safety This device has been tested and found to be in compliance with the requirements set forth in UL 916, Energy Management Equipment, and is listed by Underwriters Laboratories, Inc., for installations in the United States. This device has been tested and found to be in compliance with the requirements set forth in C22.2, No. 205-M1983, Signal Equipment, and is Certified by Underwriters Laboratories, Inc., for installations in Canada. Logic One® and Lingo® are registered trademarks of Novar. The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. Novar makes no representations or warranties with respect to this manual. In no event shall Novar be liable for technical or editorial omissions or mistakes in this manual, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this manual. No part of this manual may be reproduced in any form or by any means without prior written permission from Novar. Copyright © 2006 by Novar. All Rights Reserved. Printed in the U.S.A. Novar; 6060 Rockside Woods Blvd., Cleveland, OH 44131 Tel.: 800.348.1235 www.novar.com 8 DOC. #569065000—B 8/17/06