Lingo® SE Baseplate Installation Instructions Description The Lingo® SE Energy Infosystem is the next generation control processor that functions as a system network manager and control monitor in Novar’s Logic One® Advanced Building Control System. Lingo SE monitors and logs the operations of the local control modules, manages network communications, and provides expandable and integrated control of the building’s equipment. Lingo SE’s processing power, compatibility, and multiple network capabilities provide optimum control to cut energy costs, increase comfort, and reduce equipment maintenance. This document provides instructions for mounting and wiring the Lingo SE baseplate and checking the installation. Lingo SE Specifications Agency Approvals Listed device: Standards used: CUL/UL E90949 UL 916, Energy Management Equipment CSA C22.2, No. 205-M1983, Signal Equipment Power Requirements Voltage: Consumption: 24 VAC, Class 2 40 VA Input/Output Ratings Analog Inputs: Digital Inputs: Output (Fault): 4 to 20 mA Contact closure only 24 VAC or VDC, 1 amp, Class 2 Operating Environment Lingo SE with Touchscreen: Operating temperature: 41° to 122°F (5° to 50°C) 0–80% RH, noncondensing Storage: DOC. #569066200—C 8/17/06 –4° to 158°F (–20° to 70°C) 0–90% RH, noncondensing 1 Lingo® SE Baseplate Installation Instructions Lingo SE without Touchscreen Operating temperature: 32° to 140°F (0° to 60°C) 0–80% RH, noncondensing Storage: –40° to 158°F (–40° to 70°C) 0–90% RH, noncondensing Physical Dimensions (Baseplate only) Height: Width: Depth: Weight: 19.25 inches 13.25 inches 2.5 inches 8 lb (All aluminum enclosure) Precautions Take the following precautions during installation: § § Observe national and local electrical codes. § § Do not use the Lingo SE as a final safety device. § § Do not ground the secondary side of the transformer for this module. Connect 24 VAC power wiring to the terminals marked as 24 VAC only. Connection to other terminals will damage them. Make sure that the 24-VAC power wiring is connected to a dedicated 40 VA transformer. No other devices should be powered by the transformer connected to the Lingo SE. Make sure that the Lingo SE power cannot be switched off accidentally. The Lingo SE requires continuous power for proper operation. Mounting the Lingo SE Baseplate to the Wall The following items are needed to mount the Lingo SE baseplate to the wall: § § § The Lingo SE baseplate The hex wrench (included with the baseplate) Four screws (ap appropriate for mounting surface; not provided) NOTE! The baseplate assembly should be mounted in an accessible location with the top of the assembly not more than 6 feet from the floor. The wall should have a flat and smooth surface to prevent the baseplate from being bent. When the baseplate is mounted to paneling or drywall, hollow-wall anchors should be used to insure that the assembly remains secure. Use the following procedure and refer to Figure 1, as necessary, to mount the Lingo SE baseplate to the wall. 2 DOC. #569066200—C 8/17/06 Lingo® SE Baseplate Installation Instructions Step 1 Procedure Remove the baseplate’s cover. § § Use the hex wrench included with the baseplate to loosen the two screws at the bottom of the baseplate. Lift off the cover. 2 Position the baseplate against the wall. 3 Mark the wall to show the locations of the four slotted mounting holes in the corners of the baseplate. 4 Drill holes in the places marked on the wall. 5 Install the hollow-wall or other appropriate fasteners. 6 Turn appropriate screws into the fasteners until approximately one-quarter inch remains between the wall and the head of the screws. 7 Position the baseplate over the screws and slide it down until the screws slide into the slots. 8 Tighten the screws to secure the baseplate. Figure 1. DOC. #569066200—C 8/17/06 Lingo SE baseplate mounting holes 3 Lingo® SE Baseplate Installation Instructions Supplying the Lingo SE with Power The Lingo SE is powered by a 24-VAC, 40 VA, Class 2 transformer (not included—the transformer kit must be purchased separately). The transformer must be installed not more than 50 feet from the Lingo SE using minimum 18-gauge wire or mounted directly to the Lingo SE baseplate through the knockouts on the sides of the assembly. Refer to Figure 2, as necessary, when installing the 24 VAC, Class 2 transformer. Step Procedure 1 Connect the blue and yellow leads from the transformer secondary to the screw terminals labeled 24 VAC, Class 2, 40 VA, located on the Lingo SE terminal board. 2 Connect the transformer primary leads (white/black) to a 120-VAC source. 3 Connect the ground terminal (Terminal 36) to a suitable earth ground. 4 Apply power and check voltage at the 24 VAC terminals. § 5 Voltage should be approximately 24 to 28 VAC. Turn off the power until needed. Ground Terminal 36. 24-VAC, Class 2, 40 VA screw terminal. LISTED ENERGY MANAGEMENT EQUIPMENT SUBASSEMBLY ETHERNET 10/100 RS-232 PORT MAX ALLOWABLE AMBIENT TEMP: 60 C (140 F) ALL INPUTS AND OUTPUTS ARE CLASS 2. REFER TO INSTRUCTION MANUAL FOR SETUP AND INSTALLATION. 635205000 REV 0 - 6 7 + - 8 9 10 11 + - 12 13 + - 14 15 16 + 17 18 P1 Figure 2. 4 HUMIDITY INCOM OUTDOOR LIGHT OUTDOOR TEMP POWER DEMAND PULSE PHASE LOSS EMERGENCY STATUS SHLD + 5 AUX SHLD 4 LINGO/2 BPL PN 750110000 SYSTEM INPUTS LAN SHLD - 3 SHLD + 2 SHLD 1 COMMUNICATION NETWORKS C MODULE D MODULE SHLD - SHLD B MODULE US 20M1 PHONE LINE R A MODULE UL C 1 2 - + - + - + - + - + - + 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 SYSTEM FAULT 24V 1A 34 35 GND 24VAC 36 37 40VA P2 38 P3 Lingo SE baseplate wiring connections DOC. #569066200—C 8/17/06 Lingo® SE Baseplate Installation Instructions NOTE! The Lingo SE requires continuous power for proper operation. Make sure the Lingo SE power cannot be switched off accidentally. NOTE! The Lingo SE requires a dedicated transformer for the electronics. A separate transformer must be provided for its control outputs. Wiring the Lingo SE Inputs and Outputs Refer to Figure 2, as necessary, and use the procedure provided below to wire the Lingo SE input/output connections. NOTE! All digital inputs should be dry contact closures. Outdoor Light Sensor Novar’s 4-mA to 20-mA Analog Light Sensor (ALS) should be connected to the Lingo SE with two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) wiring. Step Procedure 1 Connect the white (+) wire from the sensor to the Lingo SE at Terminal 25 (+) at the Outdoor Light Sensor input connections. 2 Connect the black (–) wire from the sensor to the Lingo SE at Terminal 24 (–) at the Outdoor Light Sensor Input connections. Outdoor Temperature Sensor For outdoor temperature sensing, Lingo SE uses the 4- to 20-mA Outdoor Temperature Sensor (OTS/2). Two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) should be used to connect the sensor to the Lingo SE. Step DOC. #569066200—C 8/17/06 Procedure 1 Connect the white (+) wire from the sensor to Lingo SE’s Terminal 27 (+) at the Outdoor Temperature Sensor input connections. 2 Connect the black (–) wire from the sensor to Lingo SE’s Terminal 26 (–) at the Outdoor Temperature Sensor input connections. 5 Lingo® SE Baseplate Installation Instructions Outdoor Humidity Sensor Step Procedure 1 Connect the white (+) wire from the sensor to Lingo SE’s Terminal 23 (+) at the Humidity Sensor input connections. 2 Connect the black (–) wire from the sensor to Lingo SE’s Terminal 22 (–) at the Humidity Sensor input connections. Demand Pulse Input Step 1 Procedure Connect the isolated contacts of a pulse-type utility meter or watt transducer to Terminals 28 (–) and 29 (+), labeled Demand Pulse Input. Phase Loss Sensor Step 1 Procedure Connect the normally open, dry contact output of an electrical phase loss monitor to Terminals 30 (–) and 31 (+), labeled Phase Loss Sensor Input. Emergency Status Input Step 1 Procedure Connect the normally open, dry contact output of an emergency monitoring system to Terminals 32 (–) and 33 (+), labeled Emergency Status Input. System Fault Output Under normal operating conditions, a normally open set of contacts will be held closed. When an alarm occurs, the contacts open momentarily. This signal indicates a Lingo SE fault alarm. Module Communications Lingo SE can accept connections from 128 modules in Novar’s module network without using a Network Expander Module. (The maximum number of modules is subject to software limitations.) A maximum of 32 modules can be connected to each of the A, B, C, and D Module terminals (Terminals 1–12). NOTE! Modules with the same physical addresses must not be connected to the same port. For example, modules with addresses 00 and 64 have the same physical address, so they cannot both reside on the same COM port (A, B, C, or D). 6 DOC. #569066200—C 8/17/06 Lingo® SE Baseplate Installation Instructions Use two-conductor, shielded cable (Novar WIR-1010, Belden 8761, or equivalent) and the following procedure to make the module communications connections. Step Procedure 1 Connect the black wire from the cable to the negative (–) terminal. 2 Connect the shield wire to the SHIELD terminal. 3 Connect the white wire to the positive (+) terminal. NOTE! Novar’s Network Expander Module is not used with the Lingo SE. INCOM™ Lingo SE supports up to four demand meters and sixteen additional electrical submeters. Sixteen meter data collectors can be configured, each with 48 data points. Belden network cable is recommended. The following procedure should be used to connect INCOM Terminals (19–21). Step Procedure 1 Connect the black wire from the INCOM cable to Terminal 21 (INCOM 2). 2 Connect the white wire from the INCOM cable to Terminal 20 (INCOM 1). 3 Connect the shield wire from the INCOM cable to Terminal 19 (INCOM SHLD). Checking Installation Check the following items to ensure proper operation: § § Make sure the baseplate is attached securely to the wall. Check all wiring connections to make sure they are correct and secure. If the wiring is correct and the baseplate is secure, reattach the Lingo SE baseplate cover. Operation of the Lingo SE requires the Lingo SE electronics. The Lingo SE Electronics Installation Instructions (Doc. #569066100) provide information about installing the electronics, making all other required wiring connections, and verifying proper operation. DOC. #569066200—C 8/17/06 7 Lingo® SE Baseplate Installation Instructions Model and Part Numbers The part numbers shown in Table 1 should be used to order the necessary Novar parts. Table 1. Novar Part Numbers PRODUCT Lingo SE Baseplate MODEL NO. PART NO. Lingo/2-BPL 750110000 — 750017000 — — — — — — — 750018000 750018100 750017100 750017010 750017110 750018010 750018110 Lingo SE Electronics Assembly (no options) Options: Lingo SE with Integral Touchscreen Lingo SE with Integral Touchscreen & Modem Lingo SE with Modem Lingo SE with INCOM Lingo SE with Modem & INCOM Lingo SE with Touchscreen & INCOM Lingo SE with Touchscreen, Modem, & INCOM 24-VAC, 40 VA, Class 2 Transformer Kit 24V-XFR 730090000 Analog Light Sensor ALS-300 708100000 Outdoor Temperature Sensor OTS/2 735070000 Two-conductor, shielded cable (Belden 8761 equivalent) WIR-1010 709001000 Ethernet® Direct-Connect Crossover Cable — 770077000 Logic One® and Lingo® are registered trademarks of Novar. INCOM™ is a trademark of Eaton Cutler-Hammer. Ethernet® is a registered trademark of Xerox Corporation. The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. Novar makes no representations or warranties with respect to this manual. In no event shall Novar be liable for technical or editorial omissions or mistakes in this manual, nor shall it be liable for any damages, direct or incidental, arising out of or related to the use of this manual. No part of this manual may be reproduced in any form or by any means without prior written permission from Novar. Copyright © 2006 by Novar. All Rights Reserved. Printed in the U.S.A. Novar; 6060 Rockside Woods Blvd., Cleveland, OH 44131 Tel.: 800.348.1235 www.novar.com 8 DOC. #569066200—C 8/17/06