Molded Case Circuit Breakers QOM1/QOM2 Class 736 CONTENTS Description Page Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Characteristic Tripping Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Data Description Construction Standards QOM1/QOM2 two pole thermal-magnetic circuit breakers are available from 70 through 225 amperes. Voltage rating – 120/240 Vac QOM1/QOM2 circuit breakers are built in accordance with Underwriters Laboratories Standard UL 489 and NEMA Standard AB1-1975. QOM1/QOM2 circuit breakers are UL Listed under File #E84905 and CSA Certified under File LR40970-5. 70–100 ampere circuit breakers meet Federal Specification W-C-375B/GEN Class 12a. Application 2-Pole QOM125 QOM1/QOM2 circuit breakers may be field or factory installed as a main breaker in QO circuit breaker load centers with convertible mains. These circuit breakers have lug orientation to allow for straight-in wiring and have horizontal handle operation to allow for top or bottom feed applications. Ratings QOM1/QOM2 circuit breaker catalog numbers and application information are shown in the table below: 2-Pole QOM225 Main Use with 10,000 AIR 22,000 AIR Lug Wire Circuit Convertible Size h Main Main Breaker Load Center AWG/kcmil Circuit Circuit Amp Mains Al or Cu Breaker Breaker Ratingq Rating QOM1 Frame Size 70 80 90 100 110 125 100–125 100–125 100–125 100–125 125 125 QOM70 QOM80 QOM90 QOM100 QOM110 QOM125 QOM70VH QOM80VH QOM90VH QOM100VH QOM110VH QOM125VH #4-#2/0 100 125 150 175 200 225 150–225 150–225 150–225 200–225 200–225 225 QOM2100 QOM2125 QOM2150 QOM2175 QOM2200 QOM2225 QOM2100VH QOM2125VH QOM2150VH QOM2175VH QOM2200VH QOM2225VH #4-300 The use of series connected ratings allows load centers with a 22,000 ampere interrupting rating (AIR) main circuit breaker and standard 10,000 AIR branch breakers to carry UL Listed short-circuit current ratings of 22,000 rms symmetrical amperes. Combinations suitable for this purpose are Listed by Underwriters Laboratories and appear in File E6294. Type Ampere No. of Ampere Type Rating Poles Rating QO 1 QOM1-VH QO 2 and 70-225 QO-GFI 1 & 2 QOM2-VH Q1 1 Q1 2 15-70 15-100 15-30 15-100 15-150 QOM1/QOM2 circuit breakers have individual thermal-magnetic trip elements in each pole. The trip element is calibrated for 40°C ambient temperature. Trip Indication When the circuit breaker is tripped, the handle assumes a center position between ON and OFF. The circuit breaker can be reset by pushing the handle to the extreme OFF position and then to the ON position. Accessories QOM2 circuit breakers can be supplied with factory shunt trip. For complete information on accessories, refer to Catalog Class 690 “Accessories for Molded Case Circuit Breakers” or the latest version of the Square D Digest. Series Connected Ratings Branch Circuit Breaker Tripping Mechanism QOM1/QOM2 circuit breakers have captive plated box-type lugs. The lugs are suitable for use with 75°C wire. q Do not exceed the load center mains rating. Main Circuit Breaker QOM1/QOM2 circuit breakers have an over-center, trip-free toggle mechanism with quick-make, quickbreak action and positive handle indication. An integral crossbar opens both poles simultaneously. Terminations QOM2 Frame Size QOM225 with Shunt Trip Operating Mechanism Series Connected Interrupting Ratings RMS Symmetrical Amperes Handle Padlock Attachment Handle padlock attachments are available to padlock QOM1/QOM2 circuit breakers in the OFF position. Frame Size Ampere Rating Attachment Catalog Number QOM1 QOM2 70–125 100–225 QOM1PA QOM2PA 120/240 Vac Max. 22,000 22,000 22,000 22,000 22,000 2 © 1997 Square D All Rights Reserved 10/97 Dimensions 70–125 Ampere Breakers — QOM1 2.40 3.47 3.00 1.75 88 2.30 76 1.54 61 58 39 44 .31 8 .16R Typ. 4 .39 .31 Typ. 10 8 .34 2.55 9 65 1.87 47 4.95 125 126 .41 Typ. 10 2.96 3.53 5.10 130 75 90 4.20 2.75 107 70 .63 Typ. 16 .31 Typ. 8 .89 .61 23 16 .71 1.99 51 18 2.22 56 3.05 77 .60 15 .39 10 1.06 1.81 27 46 1.70 43 Vents .25 6 1.24 31 3 10/97 © 1997 Square D All Rights Reserved Dimensions 100–225 Ampere Breakers — QOM2 .13 .26 3 7 .75 .81 19 21 2.24 57 3.06 .25 78 6 2.12 54 .75 19 .82 1.13 21 29 .18 Typ. 2.85 4 72 .97 .80 25 .19 Dia. Hole 20 2.28 5 58 1.81 46 .84 3.48 1.67 21 88 19 1.68 43 5.28 134 1.74 44 .50 3.62 5.60 13 92 142 .18R 5 1.02 .48 21 26 .21 5 .58 .13 15 .95 24 2.46 62 1.67 42 .76 19 5.07 3 .90 23 129 3.61 92 4 © 1997 Square D All Rights Reserved 10/97 Characteristic Tripping Curves 10000 9000 8000 QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-1 7000 6000 5000 CIRCUIT BREAKER INFORMATION 4000 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 70 & 80 120/240 2 3000 1 9 8 7 10000 9000 8000 6 6000 5 5000 4 4000 80 90 100 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 70 1 9 8 7 QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-2 7000 3 6 5 CIRCUIT BREAKER INFORMATION 4 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 90 & 100 120/240 2 3000 3 2000 2 2000 2 1500 1 1500 1 1000 900 800 1 9 8 1000 900 800 1 9 8 700 7 700 7 600 6 600 6 500 5 500 4 400 400 MAXIMUM SINGLE POLE TRIP TIME AT 25°C BASED ON NEMA AB-2, 1980 5 4 MAXIMUM SINGLE POLE TRIP TIME AT 25°C BASED ON NEMA AB-2, 1980 3 300 200 2 200 2 150 1 150 1 300 100 90 80 70 70 60 60 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 TIME IN SECONDS 100 90 80 5 4 3 2 4 3 2 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 80A .15 3 5 1.5 100A .15 70A 90A .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 M (A .02 .015 1 CYCLE (60 Hz) .015 1 CYCLE (60 Hz) .01 .009 .008 1 .01 .009 .008 1 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .7 .6 .5 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .005 .8 .9 1 .005 .7 .006 .6 2 CYCLE (60 Hz) .007 .006 .8 .9 1 2 CYCLE (60 Hz) .007 .5 TIME IN SECONDS .5 80 90 100 70 60 50 40 30 MULTIPLES OF RATED CURRENT 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF RATED CURRENT 5 10/97 © 1997 Square D All Rights Reserved Characteristic Tripping Curves QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-3 7000 6000 5000 CIRCUIT BREAKER INFORMATION 4000 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 110 120/240 2 3000 1 9 8 7 10000 9000 8000 6 6000 5 5000 4 4000 3 3000 80 90 100 60 50 40 30 20 15 8 9 10 7 6 5 4 2 1.5 .8 .9 1 .7 .6 70 10 90 80 70 QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-4 7000 60 50 CIRCUIT BREAKER INFORMATION Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 125 120/240 2 40 30 2000 2 2000 20 1500 1 1500 15 1000 900 800 1 9 8 1000 900 800 10 90 80 700 7 700 70 600 6 600 60 500 5 500 400 4 400 MAXIMUM SINGLE POLE TRIP TIME AT 25°C BASED ON NEMA AB-2, 1980 50 40 MAXIMUM SINGLE POLE TRIP TIME AT 25°C BASED ON NEMA AB-2, 1980 3 300 200 2 200 20 150 1 150 15 300 100 90 80 70 70 60 60 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 TIME IN SECONDS 100 90 80 5 4 3 2 30 5 4 3 2 1.5 1.5 1 .9 .8 1 .9 .8 .7 .7 .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 .15 .15 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 .02 .01 .009 .008 1 6 © 1997 Square D All Rights Reserved 10/97 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .005 .7 .005 .6 .006 .006 .5 2 CYCLE (60 Hz) .007 2 2 CYCLE (60 Hz) 1.5 1 .007 1 CYCLE (60 Hz) .7 .01 .009 .008 .015 .6 1 CYCLE (60 Hz) .8 .9 1 .02 .015 .5 TIME IN SECONDS .5 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 10000 9000 8000 3 MULTIPLES OF RATED CURRENT MULTIPLES OF RATED CURRENT Characteristic Tripping Curves QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-5 1 9 8 10000 9000 8000 7 7000 6000 6 6000 5000 5 5000 4 4000 7000 CIRCUIT BREAKER INFORMATION 4000 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 100 & 125 120/240 2 3000 3 80 90 100 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 70 1 9 8 QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-6 7 6 5 CIRCUIT BREAKER INFORMATION 4 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 150-175 120/240 2 3000 3 2000 2 2000 2 1500 1 1500 1 1000 900 800 1 9 8 1000 900 800 1 9 8 700 7 700 7 600 6 600 6 500 5 500 5 4 400 300 3 300 200 2 200 2 150 1 150 1 MAXIMUM SINGLE POLE TRIP TIMES AT 25° C BASED ON NEMA AB-2, 1980 400 100 90 80 70 70 60 60 50 50 40 40 30 30 20 20 15 15 10 9 8 10 9 8 7 7 6 6 TIME IN SECONDS 100 90 80 5 4 3 2 1.5 4 MAXIMUM SINGLE POLE TRIP TIMES AT 25° C BASED ON NEMA AB-2, 1980 3 5 4 3 2 1.5 125A 1 .9 .8 1 .9 .8 .7 175A .7 100A .6 .6 .5 .5 .4 .4 .3 .3 .2 .2 .15 .15 .1 .09 .08 .1 .09 .08 .07 .07 .06 .06 .05 .05 .04 .04 .03 .03 150A .02 1 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 .7 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .005 .8 .9 1 .005 .7 .006 .6 2 CYCLE (60 Hz) .007 .006 .6 .007 .01 .009 .008 3 2 CYCLE (60 Hz) 2 1 1 CYCLE (60 Hz) .5 .01 .009 .008 .015 1.5 1 CYCLE (60 Hz) .8 .9 1 .02 .015 .5 TIME IN SECONDS .5 80 90 100 70 60 50 40 MULTIPLES OF RATED CURRENT 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF RATED CURRENT 10000 9000 8000 7 10/97 © 1997 Square D All Rights Reserved Characteristic Tripping Curves 10000 9000 8000 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 MULTIPLES OF RATED CURRENT 1 9 8 QOM FAMILY MOLDED CIRCUIT BREAKERS CHARACTERISTIC TRIP CURVE NO. 736-7 7000 7 6 6000 5000 5 CIRCUIT BREAKER INFORMATION 4 4000 Circuit Breaker Prefix Continuous Ampere Rating Maximum AC Voltage Number of Poles QOM1, QOM1-VH 200-225 120/240 2 3000 3 2000 2 1500 1 1000 900 800 1 9 8 700 7 600 6 5 500 400 4 MAXIMUM SINGLE POLE TRIP TIMES AT 25° C BASED ON NEMA AB-2, 1980 300 3 200 2 150 1 100 90 80 70 60 50 40 30 20 15 10 9 8 TIME IN SECONDS 7 6 5 4 3 2 1.5 1 .9 .8 .7 .6 .5 225A .4 200A .3 .2 .15 .1 .09 .08 .07 .06 .05 .04 ( .03 .02 .015 1 CYCLE (60 Hz) .01 .009 .008 1 2 CYCLE (60 Hz) .007 .006 Square D Company 3700 Sixth Street SW Cedar Rapids, IA 52406 USA (319) 369-6600 80 90 100 70 60 50 40 30 20 15 8 9 10 7 6 5 4 3 2 1.5 .8 .9 1 .7 .6 .5 .005 Square D and s are registered trademarks of Square D Company 0736CT9701 Nov 97 Printed in U.S.A. © 1997 Square D All Rights Reserved