Product Bulletin

advertisement
Product Bulletin
PB 243
DeviceBus® Cables
Belden® introduces two
new DeviceBus cables
with TPE Jackets along
with adding Red jackets
to some cables to designate
DeviceNetTM Safety.
Belden Offers An Extensive
Line Of DeviceBus Cables For
DeviceNet Applications
About DeviceNet
Features of DeviceNet Networks
DeviceNet is an ODVA device-level
communication protocol for industrial
automation. A DeviceNet network is an open,
low-cost system link between industrial
devices such as sensors and actuators and
higher-level devices such as programmable
logic controllers and PCs. DeviceNet networks
use the network-independent protocol called
Common Industrial Protocol (CIP) to provide
its control, configure and data collection
capabilities. Additional flexibility is offered
via the network’s ability to work with
devices from multiple vendors.
A DeviceNet network can support up to 64
nodes and the network end-to-end distance
is variable, based on network speed. At 125
Kb/s, the maximum network distance is up
to 500m. At the highest speed, 500 Kb/s,
the maximum network distance is up to
100m. The bus topology is a trunklinedropline linear bus.
Other DeviceNet system benefits include:
•Eliminates the expense associated with
hardwiring and traditional “homerun”
cabling practices
•Gives users the ability to use
device-level diagnostics
•Allows users to configure many products
in real time; they can even replace devices
on a live network
•Offers a boost in overall system
performance (because DeviceNet is
able to provide both event-based and
timer-based options).
Be Certain with Belden
A feature unique to DeviceNet is the ability
to add a power tap at any point (with a
maximum power pair ampacity of 8 amps),
allowing for redundant power supplies.
The Red-jacketed cables designate DeviceNet
Safety. The DeviceNet Safety standard allows
users to place safety devices on the same
network as their standard controls.
DeviceNet typically uses data and power
conductors from the same cable, such as
Product No. 3082A. In the DeviceBus line,
Product No. 3082KP is the exception to
the data/power pair rule since it has four
power conductors.
DeviceBus cables are typically designated
as either Class 1 (600V) or Class 2 (300V)
“Thick,” “Thin,” or “Mid” cable and they
can be used for either trunk or drop
applications, dependent on the system
speed and overall end-to-end distance.
(See Communications Rate Table.)
DeviceNet Communications Rate Table
Maximum Distance
Communications
Rate
7897A
Ft.
7896A
m
Ft.
7900A
m
3082A
Ft.
m
Ft.
3082F
m
Ft.
m
1345F
Ft.
3083A
m
Ft.
m
125 Kbps
1640 500 1378 420
328
100 1640 500
1640 500 1640 500 1640 500
250 Kbps
820
250
656
200
328
100
820 250
820 250
820
250
820
250
500 Kbps
328
100
328
100
328
100
328 100
328 100
328
100
328
100
Maximum Distance
Communications
Rate
3084A
3084F
1346F
3085A
7895A
Ft.
m
Ft.
m
Ft.
m
Ft.
m
Ft.
m
125 Kbps
328
100
328
100
328
100
328
100
984
300
250 Kbps
328
100
328
100
328
100
328
100
820
250
500 Kbps
328
100
328
100
328
100
328
100
328
100
Features and Benefits
Belden DeviceBus cables provide the
following features and benefits:
•Fully compliant with ODVA specifications
•TC-ER and PLTC-ER ratings are applicable
on certain cables
•Data and power functionality in one cable
•Reduced cable and installation costs
•Noise resistant
•New Red jackets on products designating
DeviceNet Safety
•Fully compliant with
ROHS Directive
Most DeviceBus cables have heavy-duty,
sunlight- and oil-resistant PVC-jacketed
constructions. Two Class 2 cables — Product
Nos. 3083A and 3085A — are offered with
Yellow CPE jackets for extremely harsh
industrial environments.
New Products, 1345F and 1346F with
TPE jackets, provide flexible performance
at low temperatures, along with excellent
oil, solvent and abrasion resistance in
harsh environments.
In the paired cables, the power pairs have PVC
or PVC/nylon insulation; the data pairs have
either FEP or F-R Polypropylene insulation.
Class 1 Product Nos. 7896A, 7897A and 7900A
are designated for cable tray use and are
able to occupy the same tray or conduit as
600-Volt cables.
Class 2 Thick Product Nos. 3082A, 3082F,
1345F and 3083A are designated for power
limited tray use and are able to occupy the
same tray or conduit as 300-Volt cables.
Belden has long been a leader in the
manufacture of DeviceNet cables and in
conjunction with its active membership in
ODVA, Belden spearheads the development
of many innovative cabling solutions.
Be sure to contact Belden about other
DeviceNet cabling options.
3085A
2
Industrial Data Solutions® — Industrial Data
DeviceBus for ODVA DeviceNet
Description
Part
No.
UL NEC/ Standard Lengths
C(UL) CEC
Type
Ft.
m
Standard
Unit Weight
Lbs.
kg
Conductor
(stranding)
Diameter
Nom. DCR
Shielding
Materials
Nom. DCR
Color
Code
Nominal
OD
Inch
mm
Nominal
Nom. Nom.
Capacitance
Imp. Vel.
of
(W) Prop.
pF/Ft. pF/m
Nominal
Attenuation
dB/
dB/
MHz 100
Ft. 100m
600V Class 1 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*
PVC/Nylon Insulation (Power) • FEP Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
High Velocity 7897A
NEC:
500 152.4
69.5 31.6 (2)15 AWG TC
Thick
TC-ER
1000 304.8 135.0 61.3
(19x28)
600V 75°C
CEC: 2000 609.6 274.0 124.4
3.6Ω/Mʹ FT1 11.8Ω/km
(2)18 AWG TC
(19x30)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .460 11.70
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
—
75%
12.0
39.4 .125
.500
1.000
.13
.25
.40
.43
.82
1.31
* 18 AWG stranded (19x30) tinned copper drain wire.
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
600V Class 1 ODVA Cable V • 16 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain
Wire*
PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
600V 75°C
7896A
NEC:
500 152.4
89.0 40.4 (2)16 AWG TC
TC-ER
1000 304.8 168.0 76.2
(19x29)
CEC: 2000 609.6 340.0 154.2
4.9Ω/Mʹ FT1 16.1Ω/km
(2)18 AWG TC
(19x30)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .525 13.34
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
—
64%
14.7
48.2 .125
.500
1.000
.13
.25
.40
.43
.82
1.31
* 16 AWG stranded (19x29) tinned copper drain wire.
C(UL) AWM I/II A/B
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
600V Class 1 ODVA Cable IV • 16 and 18 AWG Stranded Tinned Copper • Unshielded
PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
Drop
7900A
NEC:
500 152.4
51.0 23.1 (2)16 AWG TC Unshielded Power Pair: .430 10.92
600V 75°C
TC-ER
1000 304.8 105.0 47.6
(19x29)
Red & Black
CEC:
4.9Ω/Mʹ FT1
16.1Ω/km
(2)18 AWG TC
Data Pair:
Data:
(19x30)
Blue & White
120
6.9Ω/Mʹ
22.6Ω/km
—
64%
14.7
48.2 .125
.500
1.000
.13
.25
.40
.43
.82
1.31
C(UL) AWM I/II A/B
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-C
DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • F -R = Flame-retardant • TC = Tinned Copper • TC-ER = Tray Cable Exposed Run per 2005 NEC Article 336.
3
Industrial Data Solutions — Industrial Data
DeviceBus for ODVA DeviceNet
Description
Part
No.
UL NEC/ Standard Lengths
C(UL) CEC
Type
Ft.
m
Standard
Unit Weight
Lbs.
kg
Conductor
(stranding)
Diameter
Nom. DCR
Shielding
Materials
Nom. DCR
Color
Code
Nominal
OD
Inch
mm
Nominal
Nom. Nom.
Capacitance
Imp. Vel.
of
(W) Prop.
pF/Ft. pF/m
Nominal
Attenuation
dB/
dB/
MHz 100
Ft. 100m
300V Class 2 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*
PVC Insulation (Power) • FPE Insulation (Data) • Gray or Red Sunlight/Oil-resistant PVC Jacket
Thick
3082A
NEC:
500† 152.4 71.0 32.2
75°C
CMG, PLTC-ER 1000
304.8 138.0 62.6
CEC: 2000† 609.6 280.0 127.0
CMG FT4
(2)15 AWG TC
(19x28)
3.6Ω/Mʹ 11.8Ω/km
(2)18 AWG TC
(19x30)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .480 12.19
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
High-Flex
3082F
NEC:
500† 152.4 72.5 32.9 (2)15 AWG TC
Thick
CMG, PLTC-ER 1000
304.8 140.0 63.5
(65x33)
75°C
CEC: 2000† 609.6 284.0 128.8
3.6Ω/Mʹ CMG FT4
11.8Ω/km
(2)18 AWG TC
(65x36)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .480 12.19
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
—
75%
12.0
39. .125
.13
.43
39.4 .125
.500
1.000
.13
.25
.36
.43
.82
1.18
39.4 .125
.500
1.000
.13
.25
.36
.43
.82
1.18
.500
.25
.82
1.000
.36 1.18
* 18 AWG stranded (19x30) tinned copper drain wire.
† 500 ft. and 2000 ft. put-ups available in Gray only.
UL AWM 20201(600V) • C(UL) AWM I/II A
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
—
75%
12.0
* 18 AWG stranded (65x36) tinned copper drain wire.
† 500 ft. and 2000 ft. put-ups available in Gray only.
UL AWM 20201(600V) • C(UL) AWM I/II A
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil/Weld Splatter-resistant TPE Jacket
High-Flex
1345F
NEC:
1000 304.8 135.0 61.3
Thick
u CMG, PLTC-ER
75°C
CEC: Oil Res I
CMG FT4
* 18 AWG stranded (65x36) tinned copper drain wire.
Operating temperature: -30ºC to +75ºC
UL AWM 20201(600V) • C(UL) AWM I/II A
Meter marks on jacket to aid users in installation.
(2)15 AWG TC
(65x33)
3.6Ω/Mʹ 11.8Ω/km
(2)18 AWG TC
(65x36)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .480 12.19
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
—
75%
12.0
DCR = DC Resistance • FPE = Foam Polyethylene • PLTC-ER = Power Limited Tray Cable Exposed Run per 2005 NEC Article 725 • TC = Tinned Copper­
4
Industrial Data Solutions — Industrial Data
DeviceBus for ODVA DeviceNet
Description
Part
No.
UL NEC/ Standard Lengths
C(UL) CEC
Type
Ft.
m
Standard
Unit Weight
Lbs.
kg
Conductor
(stranding)
Diameter
Nom. DCR
Shielding
Materials
Nom. DCR
Color
Code
Nominal
OD
Inch
mm
Nominal
Nom. Nom.
Capacitance
Imp. Vel.
of
(Ω)
Prop. pF/Ft. pF/m
Max.
Attenuation
dB/
dB/
MHz 100
Ft. 100m
300V Class 2 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*PVC
PVC Insulation (Power) • FPE Insulation (Data) • Yellow CPE Jacket
Thick
3083A
NEC:
1000 304.8 135.0 61.3 (2)15 AWG TC
75°C
CMG, PLTC 2000 609.6 278.0 126.1
(19x28)
CEC: 3.6Ω/Mʹ CMG FT4 11.8Ω/km
(2)18 AWG TC
(19x30)
6.9Ω/Mʹ
22.6Ω/km
100%
Power Pair: .475 12.07
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
1.8Ω/Mʹ
5.9Ω/km
—
75%
12.0
39.4 .125
.500
1.000
.13
.25
.36
.43
.82
1.18
* 18 AWG stranded (19X30) tinned copper drain wire.
Operating temperature: -30ºC to +75ºC
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-A
300V Class 2 Thin • 22 and 24 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*
PVC Insulation (Power) • FPE Insulation (Data) • Gray or Red Sunlight/Oil-resistant PVC Jacket
Thin
3084A
NEC:
500†
152.4 22.0 10.0 (2)22 AWG TC
75°C
CL2 CMG 1000
304.8 47.0 21.3
(19x34)
†
CEC: 2000 609.6 96.0 43.6 17.5Ω/Mʹ CMG FT4 57.4Ω/km
(2)24 AWG TC
(19x36)
28.0Ω/Mʹ
91.9Ω/km
100%
Power Pair: .280 7.11
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
3.2Ω/Mʹ
10.5Ω/km
—
75%
12.0
39.4 .125
.500
1.000
.29
.50
.70
.95
1.64
2.30
12.0
39.4 .125
.500
1.000
.29
.50
.70
.95
1.64
2.30
* 22 AWG stranded (19x34) tinned copper drain wire.
† 500 ft. and 2000 ft. put-ups available in Gray only.
C(UL) AWM I/II A
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-C
High-Flex
3084F
NEC:
500†
152.4 20.5 9.3 (2)22 AWG TC
Thin
CL2 CMG 1000
304.8 45.0 20.4
(154x44)
†
75°C
CEC: 2000 609.6 90.0 40.9 17.5Ω/Mʹ CMG FT4 57.4Ω/km
(2)24 AWG TC
(105x44)
28.0Ω/Mʹ
91.9Ω/km
100%
Power Pair: .275 6.99
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
3.2Ω/Mʹ
10.5Ω/km
—
75%
* 22 AWG stranded (26x36) tinned copper drain wire.
† Put-ups available in Gray only.
C(UL) AWM I/II A
Operating temperature: -30ºC to +75ºC. Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-C
DCR = DC Resistance • FPE = Foam Polyethylene • PLTC = Power Limited Tray Cable • TC = Tinned Copper if conductor, or Tray Cable if NEC rating.
5
Industrial Data Solutions — Industrial Data
DeviceBus for ODVA DeviceNet
Description
Part
No.
UL NEC/ Standard Lengths
C(UL) CEC
Type
Ft.
m
Standard
Unit Weight
Lbs.
kg
Conductor
(stranding)
Diameter
Nom. DCR
Shielding
Materials
Nom. DCR
Color
Code
Nominal
OD
Inch
mm
Nominal
Nom. Nom.
Capacitance
Imp. Vel.
of
(Ω)
Prop. pF/Ft. pF/m
Max.
Attenuation
dB/
dB/
MHz 100
Ft. 100m
300V Class 2 Thin • 22 and 24 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*
PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil/Weld Splatter-resistant TPE Jacket
High-Flex
1346F
NEC:
1000
304.8 45.0 20.4 (2)22 AWG TC
Thin
u CL2 CMG (154x44)
75°C
CEC: 17.5Ω/Mʹ Oil Res I
CMG FT4
57.4Ω/km
(2)24 AWG TC
(105x44)
28.0Ω/Mʹ
91.9Ω/km
100%
Power Pair: .275­ 6.99
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
3.2Ω/Mʹ
10.5Ω/km
—
75%
12.0
39.4 .125
.500
1.000
.29
.50
.70
.95
1.64
2.30
12.0
39.4 .125
.500
1.000
.29
.50
.70
.95
1.64
2.30
* 22 AWG stranded (26x36) tinned copper drain wire.
C(UL) AWM I/II A
Operating temperature: -30ºC to +75ºC
Meter marks on jacket to aid users in installation.
PVC Insulation (Power) • FPE Insulation (Data) • Yellow CPE Jacket
Thin
3085A
NEC:
500
152.4 25.0 11.4
75°C
CL2 CMG 1000
304.8 47.0 21.3
CEC: 2000
609.6 96.0 43.6
CMG FT4
* 22 AWG stranded (19x34) tinned copper drain wire. Operating temperature: -30ºC to +75ºC
Meter marks on jacket to aid users in installation.
Allen-Bradley P/N 1485 CPI-C
(2)22 AWG TC
(19x34)
17.5Ω/Mʹ 57.4Ω/km
(2)24 AWG TC
(19x36)
28.0Ω/Mʹ
91.9Ω/km
100%
Power Pair: .280 7.11
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
3.2Ω/Mʹ
10.5Ω/km
—
75%
300V Class 2 ODVA Cable III • 20 and 18 AWG Stranded TC • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*
PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket
Mid
7895A
NEC:
500 152.4 41.0 18.6
75°C
CMG PLTC 1000 304.8 84.0 38.1
CEC: CMG FT4
* 20 AWG stranded (19x32) tinned copper drain wire
UL AWM 20201(600V)
Meter marks on jacket to aid users in installation.
(2)18 AWG TC
(19x30)
6.9Ω/Mʹ 22.6Ω/km
(2)20 AWG TC
(19x32)
10.9Ω/Mʹ
35.8Ω/km
100%
Power Pair: .378 9.60
Individual Red & Black
Foil
+ Overall
65%
Data Pair:
Data:
TC Braid Blue & White
120
3.2Ω/Mʹ
10.5Ω/km
—
75%
12.0
39.4 .125
.500
1.000
.29
.50
.70
.95
1.64
2.30
DCR = DC Resistance • FPE = Foam Polyethylene • PLTC = Power Limited Tray Cable • TC = Tinned Copper if conductor, or Tray Cable if NEC rating.
DeviceNet is an Open DeviceNet Vendor Association, Inc. trademark.
Belden Technical Support 1.800.BELDEN.1 (1.800.235.3361)
© Copyright 2011, Belden Inc.
www.belden.com
PB243 Rev. 2