Product Bulletin PB 243 DeviceBus® Cables Belden® introduces two new DeviceBus cables with TPE Jackets along with adding Red jackets to some cables to designate DeviceNetTM Safety. Belden Offers An Extensive Line Of DeviceBus Cables For DeviceNet Applications About DeviceNet Features of DeviceNet Networks DeviceNet is an ODVA device-level communication protocol for industrial automation. A DeviceNet network is an open, low-cost system link between industrial devices such as sensors and actuators and higher-level devices such as programmable logic controllers and PCs. DeviceNet networks use the network-independent protocol called Common Industrial Protocol (CIP) to provide its control, configure and data collection capabilities. Additional flexibility is offered via the network’s ability to work with devices from multiple vendors. A DeviceNet network can support up to 64 nodes and the network end-to-end distance is variable, based on network speed. At 125 Kb/s, the maximum network distance is up to 500m. At the highest speed, 500 Kb/s, the maximum network distance is up to 100m. The bus topology is a trunklinedropline linear bus. Other DeviceNet system benefits include: •Eliminates the expense associated with hardwiring and traditional “homerun” cabling practices •Gives users the ability to use device-level diagnostics •Allows users to configure many products in real time; they can even replace devices on a live network •Offers a boost in overall system performance (because DeviceNet is able to provide both event-based and timer-based options). Be Certain with Belden A feature unique to DeviceNet is the ability to add a power tap at any point (with a maximum power pair ampacity of 8 amps), allowing for redundant power supplies. The Red-jacketed cables designate DeviceNet Safety. The DeviceNet Safety standard allows users to place safety devices on the same network as their standard controls. DeviceNet typically uses data and power conductors from the same cable, such as Product No. 3082A. In the DeviceBus line, Product No. 3082KP is the exception to the data/power pair rule since it has four power conductors. DeviceBus cables are typically designated as either Class 1 (600V) or Class 2 (300V) “Thick,” “Thin,” or “Mid” cable and they can be used for either trunk or drop applications, dependent on the system speed and overall end-to-end distance. (See Communications Rate Table.) DeviceNet Communications Rate Table Maximum Distance Communications Rate 7897A Ft. 7896A m Ft. 7900A m 3082A Ft. m Ft. 3082F m Ft. m 1345F Ft. 3083A m Ft. m 125 Kbps 1640 500 1378 420 328 100 1640 500 1640 500 1640 500 1640 500 250 Kbps 820 250 656 200 328 100 820 250 820 250 820 250 820 250 500 Kbps 328 100 328 100 328 100 328 100 328 100 328 100 328 100 Maximum Distance Communications Rate 3084A 3084F 1346F 3085A 7895A Ft. m Ft. m Ft. m Ft. m Ft. m 125 Kbps 328 100 328 100 328 100 328 100 984 300 250 Kbps 328 100 328 100 328 100 328 100 820 250 500 Kbps 328 100 328 100 328 100 328 100 328 100 Features and Benefits Belden DeviceBus cables provide the following features and benefits: •Fully compliant with ODVA specifications •TC-ER and PLTC-ER ratings are applicable on certain cables •Data and power functionality in one cable •Reduced cable and installation costs •Noise resistant •New Red jackets on products designating DeviceNet Safety •Fully compliant with ROHS Directive Most DeviceBus cables have heavy-duty, sunlight- and oil-resistant PVC-jacketed constructions. Two Class 2 cables — Product Nos. 3083A and 3085A — are offered with Yellow CPE jackets for extremely harsh industrial environments. New Products, 1345F and 1346F with TPE jackets, provide flexible performance at low temperatures, along with excellent oil, solvent and abrasion resistance in harsh environments. In the paired cables, the power pairs have PVC or PVC/nylon insulation; the data pairs have either FEP or F-R Polypropylene insulation. Class 1 Product Nos. 7896A, 7897A and 7900A are designated for cable tray use and are able to occupy the same tray or conduit as 600-Volt cables. Class 2 Thick Product Nos. 3082A, 3082F, 1345F and 3083A are designated for power limited tray use and are able to occupy the same tray or conduit as 300-Volt cables. Belden has long been a leader in the manufacture of DeviceNet cables and in conjunction with its active membership in ODVA, Belden spearheads the development of many innovative cabling solutions. Be sure to contact Belden about other DeviceNet cabling options. 3085A 2 Industrial Data Solutions® — Industrial Data DeviceBus for ODVA DeviceNet Description Part No. UL NEC/ Standard Lengths C(UL) CEC Type Ft. m Standard Unit Weight Lbs. kg Conductor (stranding) Diameter Nom. DCR Shielding Materials Nom. DCR Color Code Nominal OD Inch mm Nominal Nom. Nom. Capacitance Imp. Vel. of (W) Prop. pF/Ft. pF/m Nominal Attenuation dB/ dB/ MHz 100 Ft. 100m 600V Class 1 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC/Nylon Insulation (Power) • FEP Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket High Velocity 7897A NEC: 500 152.4 69.5 31.6 (2)15 AWG TC Thick TC-ER 1000 304.8 135.0 61.3 (19x28) 600V 75°C CEC: 2000 609.6 274.0 124.4 3.6Ω/Mʹ FT1 11.8Ω/km (2)18 AWG TC (19x30) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .460 11.70 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km — 75% 12.0 39.4 .125 .500 1.000 .13 .25 .40 .43 .82 1.31 * 18 AWG stranded (19x30) tinned copper drain wire. Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-A 600V Class 1 ODVA Cable V • 16 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket 600V 75°C 7896A NEC: 500 152.4 89.0 40.4 (2)16 AWG TC TC-ER 1000 304.8 168.0 76.2 (19x29) CEC: 2000 609.6 340.0 154.2 4.9Ω/Mʹ FT1 16.1Ω/km (2)18 AWG TC (19x30) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .525 13.34 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km — 64% 14.7 48.2 .125 .500 1.000 .13 .25 .40 .43 .82 1.31 * 16 AWG stranded (19x29) tinned copper drain wire. C(UL) AWM I/II A/B Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-A 600V Class 1 ODVA Cable IV • 16 and 18 AWG Stranded Tinned Copper • Unshielded PVC/Nylon Insulation (Power) • F-R Polypropylene Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket Drop 7900A NEC: 500 152.4 51.0 23.1 (2)16 AWG TC Unshielded Power Pair: .430 10.92 600V 75°C TC-ER 1000 304.8 105.0 47.6 (19x29) Red & Black CEC: 4.9Ω/Mʹ FT1 16.1Ω/km (2)18 AWG TC Data Pair: Data: (19x30) Blue & White 120 6.9Ω/Mʹ 22.6Ω/km — 64% 14.7 48.2 .125 .500 1.000 .13 .25 .40 .43 .82 1.31 C(UL) AWM I/II A/B Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-C DCR = DC Resistance • FEP = Fluorinated Ethylene-propylene • F -R = Flame-retardant • TC = Tinned Copper • TC-ER = Tray Cable Exposed Run per 2005 NEC Article 336. 3 Industrial Data Solutions — Industrial Data DeviceBus for ODVA DeviceNet Description Part No. UL NEC/ Standard Lengths C(UL) CEC Type Ft. m Standard Unit Weight Lbs. kg Conductor (stranding) Diameter Nom. DCR Shielding Materials Nom. DCR Color Code Nominal OD Inch mm Nominal Nom. Nom. Capacitance Imp. Vel. of (W) Prop. pF/Ft. pF/m Nominal Attenuation dB/ dB/ MHz 100 Ft. 100m 300V Class 2 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC Insulation (Power) • FPE Insulation (Data) • Gray or Red Sunlight/Oil-resistant PVC Jacket Thick 3082A NEC: 500† 152.4 71.0 32.2 75°C CMG, PLTC-ER 1000 304.8 138.0 62.6 CEC: 2000† 609.6 280.0 127.0 CMG FT4 (2)15 AWG TC (19x28) 3.6Ω/Mʹ 11.8Ω/km (2)18 AWG TC (19x30) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .480 12.19 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km High-Flex 3082F NEC: 500† 152.4 72.5 32.9 (2)15 AWG TC Thick CMG, PLTC-ER 1000 304.8 140.0 63.5 (65x33) 75°C CEC: 2000† 609.6 284.0 128.8 3.6Ω/Mʹ CMG FT4 11.8Ω/km (2)18 AWG TC (65x36) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .480 12.19 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km — 75% 12.0 39. .125 .13 .43 39.4 .125 .500 1.000 .13 .25 .36 .43 .82 1.18 39.4 .125 .500 1.000 .13 .25 .36 .43 .82 1.18 .500 .25 .82 1.000 .36 1.18 * 18 AWG stranded (19x30) tinned copper drain wire. † 500 ft. and 2000 ft. put-ups available in Gray only. UL AWM 20201(600V) • C(UL) AWM I/II A Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-A — 75% 12.0 * 18 AWG stranded (65x36) tinned copper drain wire. † 500 ft. and 2000 ft. put-ups available in Gray only. UL AWM 20201(600V) • C(UL) AWM I/II A Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-A PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil/Weld Splatter-resistant TPE Jacket High-Flex 1345F NEC: 1000 304.8 135.0 61.3 Thick u CMG, PLTC-ER 75°C CEC: Oil Res I CMG FT4 * 18 AWG stranded (65x36) tinned copper drain wire. Operating temperature: -30ºC to +75ºC UL AWM 20201(600V) • C(UL) AWM I/II A Meter marks on jacket to aid users in installation. (2)15 AWG TC (65x33) 3.6Ω/Mʹ 11.8Ω/km (2)18 AWG TC (65x36) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .480 12.19 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km — 75% 12.0 DCR = DC Resistance • FPE = Foam Polyethylene • PLTC-ER = Power Limited Tray Cable Exposed Run per 2005 NEC Article 725 • TC = Tinned Copper­ 4 Industrial Data Solutions — Industrial Data DeviceBus for ODVA DeviceNet Description Part No. UL NEC/ Standard Lengths C(UL) CEC Type Ft. m Standard Unit Weight Lbs. kg Conductor (stranding) Diameter Nom. DCR Shielding Materials Nom. DCR Color Code Nominal OD Inch mm Nominal Nom. Nom. Capacitance Imp. Vel. of (Ω) Prop. pF/Ft. pF/m Max. Attenuation dB/ dB/ MHz 100 Ft. 100m 300V Class 2 Thick • 15 and 18 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire*PVC PVC Insulation (Power) • FPE Insulation (Data) • Yellow CPE Jacket Thick 3083A NEC: 1000 304.8 135.0 61.3 (2)15 AWG TC 75°C CMG, PLTC 2000 609.6 278.0 126.1 (19x28) CEC: 3.6Ω/Mʹ CMG FT4 11.8Ω/km (2)18 AWG TC (19x30) 6.9Ω/Mʹ 22.6Ω/km 100% Power Pair: .475 12.07 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 1.8Ω/Mʹ 5.9Ω/km — 75% 12.0 39.4 .125 .500 1.000 .13 .25 .36 .43 .82 1.18 * 18 AWG stranded (19X30) tinned copper drain wire. Operating temperature: -30ºC to +75ºC Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-A 300V Class 2 Thin • 22 and 24 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC Insulation (Power) • FPE Insulation (Data) • Gray or Red Sunlight/Oil-resistant PVC Jacket Thin 3084A NEC: 500† 152.4 22.0 10.0 (2)22 AWG TC 75°C CL2 CMG 1000 304.8 47.0 21.3 (19x34) † CEC: 2000 609.6 96.0 43.6 17.5Ω/Mʹ CMG FT4 57.4Ω/km (2)24 AWG TC (19x36) 28.0Ω/Mʹ 91.9Ω/km 100% Power Pair: .280 7.11 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 3.2Ω/Mʹ 10.5Ω/km — 75% 12.0 39.4 .125 .500 1.000 .29 .50 .70 .95 1.64 2.30 12.0 39.4 .125 .500 1.000 .29 .50 .70 .95 1.64 2.30 * 22 AWG stranded (19x34) tinned copper drain wire. † 500 ft. and 2000 ft. put-ups available in Gray only. C(UL) AWM I/II A Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-C High-Flex 3084F NEC: 500† 152.4 20.5 9.3 (2)22 AWG TC Thin CL2 CMG 1000 304.8 45.0 20.4 (154x44) † 75°C CEC: 2000 609.6 90.0 40.9 17.5Ω/Mʹ CMG FT4 57.4Ω/km (2)24 AWG TC (105x44) 28.0Ω/Mʹ 91.9Ω/km 100% Power Pair: .275 6.99 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 3.2Ω/Mʹ 10.5Ω/km — 75% * 22 AWG stranded (26x36) tinned copper drain wire. † Put-ups available in Gray only. C(UL) AWM I/II A Operating temperature: -30ºC to +75ºC. Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-C DCR = DC Resistance • FPE = Foam Polyethylene • PLTC = Power Limited Tray Cable • TC = Tinned Copper if conductor, or Tray Cable if NEC rating. 5 Industrial Data Solutions — Industrial Data DeviceBus for ODVA DeviceNet Description Part No. UL NEC/ Standard Lengths C(UL) CEC Type Ft. m Standard Unit Weight Lbs. kg Conductor (stranding) Diameter Nom. DCR Shielding Materials Nom. DCR Color Code Nominal OD Inch mm Nominal Nom. Nom. Capacitance Imp. Vel. of (Ω) Prop. pF/Ft. pF/m Max. Attenuation dB/ dB/ MHz 100 Ft. 100m 300V Class 2 Thin • 22 and 24 AWG Stranded Tinned Copper • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil/Weld Splatter-resistant TPE Jacket High-Flex 1346F NEC: 1000 304.8 45.0 20.4 (2)22 AWG TC Thin u CL2 CMG (154x44) 75°C CEC: 17.5Ω/Mʹ Oil Res I CMG FT4 57.4Ω/km (2)24 AWG TC (105x44) 28.0Ω/Mʹ 91.9Ω/km 100% Power Pair: .275­ 6.99 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 3.2Ω/Mʹ 10.5Ω/km — 75% 12.0 39.4 .125 .500 1.000 .29 .50 .70 .95 1.64 2.30 12.0 39.4 .125 .500 1.000 .29 .50 .70 .95 1.64 2.30 * 22 AWG stranded (26x36) tinned copper drain wire. C(UL) AWM I/II A Operating temperature: -30ºC to +75ºC Meter marks on jacket to aid users in installation. PVC Insulation (Power) • FPE Insulation (Data) • Yellow CPE Jacket Thin 3085A NEC: 500 152.4 25.0 11.4 75°C CL2 CMG 1000 304.8 47.0 21.3 CEC: 2000 609.6 96.0 43.6 CMG FT4 * 22 AWG stranded (19x34) tinned copper drain wire. Operating temperature: -30ºC to +75ºC Meter marks on jacket to aid users in installation. Allen-Bradley P/N 1485 CPI-C (2)22 AWG TC (19x34) 17.5Ω/Mʹ 57.4Ω/km (2)24 AWG TC (19x36) 28.0Ω/Mʹ 91.9Ω/km 100% Power Pair: .280 7.11 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 3.2Ω/Mʹ 10.5Ω/km — 75% 300V Class 2 ODVA Cable III • 20 and 18 AWG Stranded TC • 100% Individually Foil Shielded + Overall 65% TC Braid • Drain Wire* PVC Insulation (Power) • FPE Insulation (Data) • Gray Sunlight/Oil-resistant PVC Jacket Mid 7895A NEC: 500 152.4 41.0 18.6 75°C CMG PLTC 1000 304.8 84.0 38.1 CEC: CMG FT4 * 20 AWG stranded (19x32) tinned copper drain wire UL AWM 20201(600V) Meter marks on jacket to aid users in installation. (2)18 AWG TC (19x30) 6.9Ω/Mʹ 22.6Ω/km (2)20 AWG TC (19x32) 10.9Ω/Mʹ 35.8Ω/km 100% Power Pair: .378 9.60 Individual Red & Black Foil + Overall 65% Data Pair: Data: TC Braid Blue & White 120 3.2Ω/Mʹ 10.5Ω/km — 75% 12.0 39.4 .125 .500 1.000 .29 .50 .70 .95 1.64 2.30 DCR = DC Resistance • FPE = Foam Polyethylene • PLTC = Power Limited Tray Cable • TC = Tinned Copper if conductor, or Tray Cable if NEC rating. DeviceNet is an Open DeviceNet Vendor Association, Inc. trademark. Belden Technical Support 1.800.BELDEN.1 (1.800.235.3361) © Copyright 2011, Belden Inc. www.belden.com PB243 Rev. 2