INSTALLATION Conduit Sealing Instructions for Equipment in Hazardous Locations C903M-E (10/10) For IECEX and ATEX Only A certified flameproof “d” sealing device, such as a stopping box with setting compound, shall be provided either in the flameproof enclosure or immediately at the entrance thereto. For U.S. Reference Only This document is based on NEC installation requirements for equipment installed in hazardous locations in the United States of America. Description Conduit seals prevent explosions from spreading through conduit systems and igniting outside atmospheres. When properly installed and filled with a UL-listed sealing compound, they prevent the passage of gases, vapors, or flames from spreading from a hazardous location to a nonhazardous location. The information describes the main purposes for seal fittings: • Restrict the passage of gases, vapors, or flames from one part of the conduit system to another area of the system. • Limit explosions to the sealed enclosure. • Prevent precompression, or “pressure piling,” in conduit systems. WARNING: Failure to follow safety instructions may cause ignition of hazardous atmosphere resulting in serious personal injury and/or property damage. POURING OPENING SEALING CEMENT SF SEAL WITH DRAIN VALVE FIBER DAM EXPLOSION CONFINED WITHIN SEALED AREA PARTS LIST IGNITABLE GASES OR VAPORS IGNITED BY SPARK OF SWITCH For an example of possible system connections, refer to System Connection Examples on page 4. EHX*E SERIES ENCLOSURE AND PT1260EX PAN/TILT Qty 2 2 1 1 Description Nipple (supplied with enclosure) Sealing fitting (supplied with enclosure) Sealing fitting (supplied with pan/tilt) Nipple (supplied with pan/tilt) EXPLOSIONPROOF SWITCH EXSITE SERIES EXPLOSIONPROOF POSITIONING SYSTEM Figure 1. How Gases, Vapors, and Flames Are Contained Qty Description 1 Nipple (supplied with enclosure) 1 Sealing fitting (supplied with enclosure) USER-SUPPLIED PARTS EHX*E Series Enclosure and PT1260EX Pan/Tilt Qty 1 1 1 1 1 1 1 1 Description Explosionproof nipple Explosionproof elbow Explosionproof flexible conduit (Class 2 wiring) Explosionproof flexible conduit (Class 1 wiring) Explosionproof J-box Sealing fitting Sealing compound Fiber filler ExSite Series Explosionproof Positioning System Qty 1 1 1 1 1 Description Explosionproof nipple Explosionproof flexible conduit (Class 2 wiring) Sealing fitting Sealing compound Fiber filler NEC SEC. 501-5 HIGHLIGHTS ON SEALING FITTING REQUIREMENTS CLASS I, DIV. 1 AND 2 Seals must be placed in each conduit of a device that might produce arcs, sparks, or high temperatures. SEC. 501-5(A)(1) PERMITS EXPLOSIONPROOF UNIONS AND ELBOWS BETWEEN SEAL AND APPARATUS ENCLOSURE. 18 MAX ENCLOSURE TO BE SEALED Figure 2. Seals Within Conduit Smaller Than 2 Inches If the conduit is 2 inches or larger, a seal must be placed within 18 inches of the enclosure. 18 MAX 2 OR LARGER CONDUIT ENCLOSURE TO BE SEALED Figure 3. Seals Within Conduit Larger Than 2 Inches Sealing fittings must be installed at a boundary between a hazardous and nonhazardous area. Sealing fittings must also be installed at a boundary between a Class I, Div. 1 area and a Class I, Div. 2 area. HAZARDOUS AREA NONHAZARDOUS AREA ENCLOSURE TO BE SEALED NONHAZARDOUS AREA SEAL MAY BE POSITIONED ON EITHER SIDE OF BOUNDARY HAZARDOUS AREA NO UNION, COUPLING, BOX, OR FITTING IN CONDUIT IS PERMITTED BETWEEN SEALING FITTING AND POINT WHERE CONDUIT LEAVES HAZARDOUS AREA ENCLOSURE TO BE SEALED Figure 4. Sealing the Enclosures Other NEC Requirements: • Splices and taps are not to be used in sealing fittings. • Where moisture may accumulate in system, an approved method must be provided to remove such accumulation. • Depth of sealing compound should be to trade size of conduit, having a minimum thickness of 5/8 of an inch. Installation 1. Run the conductors through the fitting. 2. Pack the sealing fitting with fiber filler. In a horizontal run, place the fiber filling at both ends of the fitting (refer to Figure 5); in a vertical run, fill only the bottom end (refer to Figure 6). Fiber filler makes a dam that keeps the sealing compound in the chamber of the sealing fitting while it cures and hardens. The fiber dam is also used to separate the individual conductors so the sealing compound seals around each conductor. If the electrical conductors are not properly separated, gases can migrate through the seal, making the seal ineffective. SEALING COMPOUND SEALING COMPOUND FIBER FILLER FIBER FILLER Figure 5. Horizontal Fitting, Damming and Sealing Figure 6. Vertical Fitting, Damming and Sealing 3. Prepare the sealing compound. Use sealing compound suitable for the application and follow the instructions supplied by the sealing compound manufacturer. 4. Pour the sealing compound into the fitting. System Connection Examples NOTE: The following illustrations of system connections are provided only as a guideline. Actual connections are dictated by local authorities and the A&E specifications of the site. Pelco makes no recommendations on the connection of this system in a hazardous location. ì Nipples (supplied with enclosure) î Sealing fittings (supplied with enclosure) ï Explosionproof nipple ñ Explosionproof elbow ó Explosionproof flexible conduit, for Class 2 wiring r Explosionproof flexible conduit, for Class 1 wiring s Explosionproof J-box, for connection of pan/tilt and Class-1 camera; for ease of wire pulls, locate as close to the pan/tilt as possible ENCLOSURE t Sealing fitting, for separation of hazardous and nonhazardous locations u Sealing fitting (supplied provided pan/tilt) ~í Nipple (supplied with pan/tilt) PAN/TILT Figure 7. EHX*E Enclosure and PT1260EX Pan/Tilt ì Nipple (supplied with enclosure) î Sealing fitting (supplied with enclosure) ï Explosionproof nipple ñ Explosionproof flexible conduit, for Class 2 wiring ó Sealing fitting, for separation of hazardous and nonhazardous locations EXSITE POSITIONING SYSTEM Figure 8. ExSite Series Explosionproof Positioning System WARNING: Be sure to seal the cable entry conduit fitting with the appropriate sealant (not supplied) during installation. REVISION HISTORY Manual # C903M C903M-A C903M-B C903M-C Date 9/92 11/94 6/03 8/04 C903M-D C903M-E 4/10 10/10 Comments Original version. Revised format to two columns. Added an example system connection containing a figure and parts description. Added "For U.S. reference only." Changed "Example System Connection" to "System Connection Example." Changed "EHX" to EHX*E." Document rewritten and reformatted. Added information about NEC installation requirements, and added Introduction. Added another figure and parts description. Some information removed. Document rewritten and reformatted. Added "EECEX and ATEX Only" information. Added Parts List and User-Supplied Parts. Added a warning to install appropriate sealant. The materials used in the manufacture of this document and its components are compliant to the requirements of Directive 2002/95/EC. Pelco, Inc. Worldwide Headquarters 3500 Pelco Way, Clovis, California 93612 USA USA & Canada Tel (800) 289-9100 Fax (800) 289-9150 International Tel +1 (559) 292-1981 Fax +1 (559) 348-1120 www.pelco.com Pelco, the Pelco logo, and other trademarks associated with Pelco products referred to in this publication are trademarks of Pelco, Inc. or its affiliates. All other product names and services are the property of their respective companies. Product specifications and availability are subject to change without notice. ©Copyright 2010, Pelco, Inc. All rights reserved.