KING OF PRUSSIA PLAZA King of Prussia, Pennsylvania

advertisement
Tenant Design Criteria
For
MECHANICAL AND ELECTRICAL WORK
KING OF PRUSSIA
PLAZA
King of Prussia,
Pennsylvania
SIMON PROPERTY GROUP
(Updated 11/05/2010)
KING OF PRUSSIA PLAZA
TABLE OF CONTENTS
General Information and Project Directory ............................................... Section 1
Heating, Ventilation and Air Conditioning................................................ Section 2
Vapor Removal Systems............................................................................ Section 3
Typical Roof Opening, Curbing and Specifications .................................. Section 4
Plumbing .................................................................................................... Section 5
Electrical Service ....................................................................................... Section 6
Natural Gas ................................................................................................ Section 7
Sprinkler System........................................................................................ Section 8
APPENDICES: Forms
ET-1 – Electrical Tabulation Form (Sample)
ET-1 – Electrical Tabulation Form
MT-1 – Mechanical Tabulation Form (Sample)
MT-1 – Mechanical Tabulation Form
APPENDICES: Drawings
D-1
Typical HVAC Installation
D-2
Typical Tenant Return Air Path
D-3
Typical Hood Exhaust Fan – Roof Mounted
Grease Exhaust Roof Protection Requirements
D-4
Typical Roof Opening Framing and Equipment Supports
D-5
Typical Sprinkler System Details
D-6
Typical Tenant Electrical Service One Line Diagram
D-7
Spaces #1306 Tenant Electrical Service One-Line Diagram
D-8
Typical Joist Reinforcement Detail at Concentrated Load
King of Prussia Plaza
General Information and Project Directory – Section 1
This design criteria provides information and lists requirements to be used in the preparation of
plans and specifications for Tenant’s mechanical and electrical work. Tenant’s plans and
specifications shall be prepared by and bear the seal of Architects and Engineers licensed by the
Commonwealth of Pennsylvania and shall comply with current code requirements and meet the
requirements of all governing agencies exercising jurisdiction.
Tenant’s plans and specifications, with calculations and supporting data, shall be submitted for
review by the Landlord. Work will not be permitted to commence without plans and
specifications having prior review and written acceptance of the Landlord, as well as that of all
governing bodies exercising jurisdiction. Landlord’s review is solely for conformance to this
criteria and landlord’s review shall not be construed to be a guarantee of design or function
adequacy.
Tenant shall field verify exact location and size of demised premises, all service characteristics
and locations as well as any interference to the installation of Tenant’s work. Tenant shall
immediately notify Landlord of any discrepancies or interference and shall not commence any
work prior to the resolution thereof.
Under no circumstances, will Landlord permit Tenant's sprinklers and other equipment to hang
from the metal deck. Sprinklers and equipment must be hung from beams and bar joists.
Sprinkler and equipment loads must be limited to less than 150 pounds at each connection.
Sprinkler and equipment support connections should be made at the top chord of bar joist at
panel points (where diagonal struts form a ^ shape). Sprinkler and equipment supports may also
be connected to the bottom chord of bar joists at panel points (where diagonal struts form a V
shape). Sprinkler and equipment supports should be sufficiently numerous and staggered so that
sprinkler loads are evenly distributed across all structural members. If sprinkler and equipment
supports are located more than 3 inches from a panel point, additional structural reinforcement
may be required, requiring review by Landlord’s structural engineer. Combined sprinkler and
equipment loads on any one joist (all loads of any type) exceeding 300 pounds require review by
Landlord’s structural engineer. See Appendix Reference Detail D-8.
Tenant’s work shall be performed by licensed contractors. Tenant shall require any personal
performing such work to guarantee the work to be free from any and all defects in materials and
workmanship for one (1) year from date of beneficial use or acceptance. Tenant shall also
require any such person to be responsible for the replacement or repair, without additional
charge, of any and all work done, or furnished by or through such person, which shall become
defective or inoperable within one (1) year after beneficial use or acceptance. The correction of
such work shall include, without additional charge, all expenses and damages in connection with
the removal, repair or replacement of any part of the work which may be damaged or disturbed
thereby. All warranties and guarantees as to materials or workmanship, with respect to Tenant’s
work, shall be contained in the contract or subcontract which shall be so written that such
warranties or guarantees shall insure to the benefit of both Landlord and Tenant, as their
respective interests appear, and can be directly enforced by either. Tenant covenants to give
landlord any assignment or other assurances necessary to effect the same.
King of Prussia Plaza
1.1
General Information and Project Directory – Section 1
Tenant’s work shall be coordinated with the work being done by Landlord and other tenants, to
such extent that the Tenant’s work will not interfere with or cause delay of any other associated
construction work or business conduct.
Tenant shall engage the services of licensed Architects, Engineers, and contractors who will
work in harmony with each other and those of the Landlord. To this end there shall be no labor
dispute which would interfere with the construction, completion and operation of the Mall.
Tenant shall provide public liability and property damage insurance, in such amounts as
stipulated by Landlord, for all work performed by the Tenant’s contractors, subcontractors and/or
their suppliers.
Tenant is responsible to procure any and all necessary permits and obtain written approvals from
Landlord and all governing agencies exercising jurisdiction including, but not limited to, hot
work permit or sprinkler permit.
At the Tenant’s expense, and with Landlord’s written approval, any and all existing mechanical,
electrical and/or plumbing services, equipment or portion thereof not scheduled for re-use as part
of the Tenant’s construction, shall be demolished or otherwise safely terminated. A Tenant
electing to re-use existing services, equipment or portion thereof is permitted to do so provided
that the Tenant’s Engineer and/or contractor deems these components acceptable for re-use in the
new design. Tenant accepts full responsibility for the operational integrity of any and all existing
equipment. The re-use of existing services, equipment or portion thereof does not relieve the
Tenant of the responsibility to furnish plans as aforementioned.
King of Prussia Plaza
1.2
General Information and Project Directory – Section 1
PROJECT DIRECTORY
DIRECTOR OF TENANT COORDINATION
Simon Property Group
The Atrium
234 Mall Boulevard
King of Prussia, PA 19406-2954
(610) 768-6341
TENANT COORDINATION ANALYST
(610) 768-6337
LANDLORD’S MANAGING AGENT
Simon Property Group
The Atrium
234 Mall Boulevard
King of Prussia, PA 19406-2954
(610) 768-6300
MALL MANAGEMENT
Plaza Management Office
160 North Gulph Road, Suite 2700
King of Prussia, PA 19406
(610) 265-5794
LANDLORD-SUPPLIED ITEMS
TELEPHONE SERVICE
Verizon
1350 Welsh Road
North Wales, PA 19454
1 (800) Verizon or 1 (800) 479-1919
CURRENT ARCHITECT FOR
SPACES 1306-1311 AND 2301-2308
McGillan Architecture, Inc.
Two Bala Plaza, Suite 502
333 City Line Avenue
Bala Cynwyd, PA 19004
(610) 664-6577
GAS SERVICE
PECO Energy
2301 Market Street
Philadelphia, PA 19102
1 (800) 494-4000
ARCHITECT
Thompson, Ventulett, Stainback &
Associates, Inc., Architects
2700 Promenade Two
1230 Peachtree Street, NE
Atlanta, GA 39309-3591
(404) 888-6600
HEALTH DEPARTMENT
Montgomery County Health Department
1430 Dekalb Street
Norristown, PA 19404-0311
(610) 278-5117
ELECTRICAL ENGINEER
KLG, LLC.
2136 Defoors Ferry Road NW
Atlanta, GA 30309
(404) 881-6565
PUBLIC WORKS DEPARTMENT
(CODE REVIEW AND BUILDING PERMITS)
Upper Merion Township
175 West Valley Forge Road
King of Prussia, PA 19406
(610) 265-2606
MECHANICAL ENGINEER
ZMM, Inc. (Design)
222 Lee Street, West
Charleston, WV 25302
(304) 342-0159
WATER, SEWER & ELECTRIC SERVICE
Mall Operations Department
Plaza Management Office
160 North Gulph Road
King of Prussia, PA 19406
(610) 337-9272
FACTORY MUTUAL
FM Global
Attn: Plan Review
2100 Reston Parkway, Suite 600
Reston, VA 20191
(703) 860-4101 y Fax: (703) 860-3187
LANDLORD’S ALARM CONTRACTOR
Siemens Building Technologies, Inc.
2000 Crawford Place
Mt. Laurel, NJ 08504
(856) 385-7521
King of Prussia Plaza
1.3
Heating, Ventilating and Air Conditioning – Section 2
Tenant shall install a heating, ventilating and air conditioning (HVAC) system as designed by
Tenant’s Engineer in strict accordance with the American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc. (ASHRAE), The International Codes 2009, National Fire
Protection Association (NFPA) recommended practice and this criteria. Tenant shall submit, for
Landlord’s review and acceptance, design documents and design load calculations including
cooling and electrical tabulation forms prepared and sealed by a registered Professional
Engineer.
Landlord’s HVAC system is based upon the following parameters:
1.
Landlord will supply medium pressure, variable volume, and constant temperature air for
cooling during Mall scheduled business hours. Under normal operating conditions,
cooling will not be provided during Mall scheduled non-business hours.
2.
Landlord will provide heat to Tenant spaces during non-business hours to prevent
freezing when necessary. Under normal operating conditions, heating will not be
supplied during Mall scheduled business hours.
3.
During Mall scheduled business hours, Landlord will supply minimum ventilation air in
accordance with ASHRAE 62.1.
4.
Landlord will install Variable Air Volume (VAV) terminal(s) to modulate supply air
quantity from 30% minimum to 100% of maximum required air volume. Landlord shall
furnish and install, at Tenant’s expense, a thermostat for control of VAV terminal.
5.
Cooling Design Conditions:
a)
Primary Air Supply: Summer Cooling – 58° FDB Nominal
b)
Space Conditions: Business Hours – 76° FDB Nominal
6.
Return Air: Tenant shall provide a means for return air to Landlord’s HVAC system
during all occupied and unoccupied hours. Return air openings shall have free area sized
for maximum velocity of 400 FPM of Tenant’s maximum air supply during occupied
hours, including door openings, and 800 FPM during unoccupied hours. Return openings
shall meet Architectural design criteria. Tenant shall return supply air to Mall unless
otherwise required by Landlord. Tenant shall not allow the return of objectionable odors
to Mall and shall provide means of exhausting same in a required manner.
7.
Tenant HVAC Construction:
a)
King of Prussia Plaza
Construction: Tenant’s HVAC ductwork shall be galvanized sheet steel, black
steel, or aluminum. Tenant’s toilet exhaust ductwork shall be fabricated from
galvanized sheet metal, and all vapor removal ductwork shall be fabricated from
stainless steel or black steel in accordance with ASHRAE standards and Sheet
Metal and Air Conditioning contractors National Association, Inc. (SMACNA)
manuals. Fiberglass ductwork will not be permitted.
2.1
Heating, Ventilating and Air Conditioning – Section 2
b)
Maximum allowable pressure drop through Tenant’s ductwork and equipment
downstream of Landlord’s VAV terminal shall not exceed 0.4 inch water column.
c)
Air Distribution Devices: Air distribution devices shall be commercial grade
registers or ceiling diffusers with individual manual volume control.
d)
Flexible ductwork: If used, flexible ductwork shall be equal to “Flexmaster
Triple Lock” aluminum insulating ductwork with a maximum length not to
exceed six (6) feet.
e)
Duct Insulation: All supply air ductwork shall be insulated with one (1) inch
thickness glass fiber insulation with foil vapor barrier. Internally lined ductwork
will not be permitted.
f)
Penetrations: Penetrations in any partitions having a fire rating of one hour or
more must be fire-stopped with approved materials and methods to prevent the
migration of smoke and to maintain the fire rating of the partition.
g)
Variable Air Volume (VAV) Terminals: Any and all Tenant requested revisions
to the existing VAV terminals shall be performed by the Landlord at the Tenant’s
expense.
h)
Access Panels: Access panels of suitable size to enable safe entry shall be
provided for all fire dampers, air balancing controls, valves, VAV terminals and
other equipment if rendered inaccessible by Tenant’s construction.
i)
Air Balancing: Tenant shall engage the services of a certified independent air
balance contractor. Tenant’s air balance report must be submitted to and accepted
by Landlord before the Premises will be allowed to open for business.
j)
Electric Heating Coil: If heating to the Premises is required during occupied
hours, Tenant’s Engineer shall provide for the installation of an electric duct
heating coil downstream of the VAV terminal. Tenant shall install appropriate
controls so that heating elements can be energized only when VAV terminal is in
30% supply air position. In the event the Tenant elects to install an electric duct
heating coil, Tenant shall (1) provide air flow safety switch and thermal overload
device and (2) design the electric heat capacity to minimum VAV terminal
setting. Landlord, at Tenant’s expense, shall adjust VAV terminal minimum stop
to 30% supply air position.
k)
Toilet Exhaust: Tenant shall provide a toilet exhaust fan with back-draft damper.
Where available, Tenant shall interconnect toilet exhaust fan discharge to the
Landlord toilet exhaust duct. Where toilet exhaust duct is not accessible or
available, the Tenant shall be required to exhaust at the roof level. Roof
membrane cutting and flashing shall be performed by the Landlord’s contractor at
the Tenant’s expense. Tenant’s contractor must contact Mall management office
prior to commencement of work.
King of Prussia Plaza
2.2
Heating, Ventilating and Air Conditioning – Section 2
7.
Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure Hot
Work Permit(s) from the Landlord. A Hot Work Permit is required for any and all open
flame welding or cutting such as but not limited to welding, soldering and brazing.
Reference Appendix:
D-1
Typical HVAC Installation
D-2
Typical Tenant Return Air Path
D-3
Typical Hood Exhaust Fan – Roof Mounted
D-8
Typical Joist Reinforcing at Concentrate Load
King of Prussia Plaza
2.3
Vapor Removal Systems – Section 3
Vapor removal system shall include, but not be limited to the following:
1. Hoods and/or canopies
2. Duct systems
3. Grease removal devices
4. Dampers
5. Air moving devices
6
Auxiliary equipment
7. Fire extinguishing equipment
Vapor removal system materials shall be new and designed for the intended application in
accordance with engineering data. All vapor removal equipment shall be installed in strict
accordance with the manufacturer’s recommendations for type and capacity. The installation of
energy efficient make-up air systems is encouraged.
Vapor systems shall conform to all applicable laws, codes, ordinances and governing regulations,
including, but not limited to the following:
1.
2.
3.
4.
National Fire Protection Association (NFPA)
National Electrical Code (NEC)
Underwriters Laboratories (UL)
International Building Code, International Mechanical Code, International Plumbing
Code
5. Factory Mutual Fire Insurance Underwriters(FM)
6. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
(ASHRAE)
Objectionable Odor Exhaust: Tenant applications such as, but not limited to, food service, hair
styling, pet shop, or as otherwise determined by the Landlord, may be required to install vapor
removal systems of a capacity not less than 105% of the supply air quantity to the Premises.
Tenant shall be responsible for all modifications and improvements to Tenant’s vapor removal
systems to avoid negatively impacting the Landlord’s or other Tenant’s HVAC systems.
Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure Hot Work
Permit(s) from Landlord. A Hot Work Permit is required for any and all open flame welding or
cutting such as, but not limited to welding, soldering and brazing.
Reference Appendix:
D-3
Typical Hood Exhaust Fan – Roof Mounted
D-4
Typical roof Opening Framing and Equipment Supports
D-8
Typical Joist Reinforcement Detail at Concentrated Load
King of Prussia Plaza
3.1
Typical Roof Opening, Curbing and Specification – Section 4
General Information:
1.
Roof membrane cutting, flashing and cutting roof deck must be performed by
Landlord’s roofing contractor at Tenant expense. Tenant’s contractor must contact
the Mall management office prior to commencement of work. All other work such
as, miscellaneous steel, welding must be performed by Tenant’s contractor.
2.
Submittals shall include three (3) installation drawings of structural support steel
prepared by a Licensed Engineer and forwarded to the Landlord’s Tenant Coordinator
prior to work commencement.
3.
Wood block-type supports set directly on the roof membrane will not be permitted.
4.
Abandoned equipment located over the Premise must be removed by Tenant.
Existing roof curbs not scheduled for re-use by the Tenant shall be removed by
Landlord’s roofing contractor at Tenant’s expense.
5.
Tenant’s Engineer shall submit dimensioned sketch of all surrounding existing rooftop equipment for Landlord’s review and acceptance.
6.
Submittals shall include details of roof supports for all exterior piping including a
roof plan of proposed routing for Landlord’s review and acceptance.
7.
The top of roof curb must be a minimum of 18” above the existing roof. Refer to
Appendix Drawing for requirements on typical roof-mounted exhaust fans.
8.
Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a Hot
Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open
flame welding or cutting such as, but not limited to welding, soldering and brazing.
Reference Appendix:
D-3
Typical Hood Exhaust Fan – Roof Mounted
Grease Exhaust Roof Protection Requirements
D-4
Typical Roof Opening Framing and Equipment Supports
D-8
Typical Joist Reinforcement Detail at Concentrated Load
King of Prussia Plaza
4.1
Plumbing – Section 5
1.
Where provided by Landlord, typical water and sewer connections to the Premise are as
follows:
Cold water supply – ¾”
Sanitary stub – 4”
Sanitary vent – 3”
If Tenant’s requirement(s) exceed the existing connections provided by Landlord, the
Tenant’s plans shall reflect such modifications for review ad approval by Landlord. Any
and all such modifications shall be at Tenant’s expense.
2.
All saw cutting of the floor slab shall be by Tenant’s contractor, after advance written
notification is submitted to Landlord’s Engineer for approval. Tenant and Contractor
must have a floor scan completed before saw cutting is completed. Tenant will be held
responsible for any lines cut during construction.
3.
Tenant shall furnish and install an electric water heater. Water heater shall be UL listed
and approved. The relief valve shall be piped to an open drain.
4.
Food Preparation Tenants shall provide at least one floor sink with integral sediment
bucket in each kitchen and/or food preparation area with accessible clean-outs as required
by applicable codes. Clean-outs shall terminate flush with the finished floor or wall.
Tenant shall install an accessible cleanout prior to the entry to Landlord’s sanitary main
within the Premise.
5.
All waste piping designed and installed for the drainage of grease-producing fixtures as
defined by the Plumbing Inspector and/or Landlord’s Engineer, such as pot sinks,
dishwashers and kitchen hood grease drains, shall discharge through an approved Tenant
provided, mechanical grease recovery unit(s) with sediment strainer prior to connection
to the Landlord’s sanitary system. The Tenant must comply with all local codes and
Landlord requirements for installation and maintenance of grease recovery units.
6.
Grease recovery units must be installed within Tenant’s Premises and above the finished
floor.
7.
All Tenant applications using chemical processes, such as photo finishing, dental
facilities, or as otherwise determined by the Landlord, must pre-treat all wastewater to
meet the required standards and regulations before discharge to Landlord’s sanitary
system.
8.
All piping systems must be compatible with the type of materials used by Landlord and
shall comply with the following requirements:
a) Drainage, Vent Pipe and Fittings: Below grade service shall be bell and spigot, cast
iron pipe and fittings with rubber gaskets. Above grade service shall be hubless cast
iron pipe and fittings. Joints shall be rubber sealing sleeve and stainless steel
coupling with stainless steel clamps and bolts as manufactured by Tyler Pipe or equal.
Pipe and joining couplings must be produced by the same manufacturer. Copper
King of Prussia Plaza
5.1
Plumbing – Section 5
drain, waste and vent piping is acceptable above Tenant floor elevation. Plastic pipe
will not be permitted.
b) Domestic Water Piping: All water piping shall be Type L copper tubing, seamless
drawn, hard temper with plain ends compatible with ASTM B-88. Neither type M
copper or any type of plastic pipe will be permitted. Fittings shall be wrought copper
with socket ends with lead-free ASTM 95/5 tin-antimony. Tenant’s plumbing
contractor will be required to certify to Landlord that all equipment and installation is
lead-free in compliance with Federal Drinking Water Standards. All valves for
domestic water use must be rated at 125 psi test.
c) Tenant shall install air chambers or shock absorbers in piping system to prevent noise
and damage due to water hammer. Branch piping shall include accessible service
valves and shut off valves to all fixtures.
d) Tenant shall provide dielectric fittings at all junctions of dissimilar metals.
9.
Pipe must be supported securely from hangers as follows:
a) Where required, and with Landlord’s approval, Tenant’s plumbing contractor is
responsible to install additional intermediate structural supports for hangers.
b) Hangers must not pierce insulation vapor barrier.
c) Cast iron pipe must be supported at least every five (5) feet and at every joint and
fitting. Cast iron pipe branches without support must have hangers installed a
maximum of four (4) feet on center.
d) Non-insulated copper pipe must be installed with either copper or plastic coated steel
hangers.
10.
Tenant shall furnish and install a water meter remote readout, of size and type approved
by Landlord and at a location designated by the Landlord’s Engineer.
11.
All tenants are required to install, test and maintain backflow prevention devices in series
after the water meter. No bypass is permitted. Tenant applications such as, but not
limited to, food service, hair styling, photographic reproduction, pet shop; must install a
Watts 009 Series reduced pressure zone (RPZ) backflow pressure device. All other
tenants shall install a Watts 007 Series double check valve assembly.
12.
Pipe Insulation:
a) All hot water piping and piping subject to condensation, including cold water and
condensate drain piping, must be insulated.
b) All insulation shall be fire and smoke hazard rated as tested by procedure ASTM E84, NFPA 225 and UL 723 and must not exceed a flame spread rating of 25 and
King of Prussia Plaza
5.2
Plumbing – Section 5
smoke developed rating of 50. Glass fiber insulation shall be of the type having a 4.0
pound density and a k-factor of 0.25, one inch minimum.
c) Insulation hangers shall be protected by a section of compressed glass fiber insulation
with a metal saddle on the outside of the insulation.
d) All exposed and concealed insulated piping is to have an all service jacket similar to
Owens-Corning Fiberglass ASJ25 with self-sealing lap joint sealing strips.
e) Pre-molded insulated fittings shall be of the same material and thickness as pipe
insulation. Provide Zeston PVC jackets or equivalent and must not exceed a flame
spread rating of 25 and smoke developed rating of 50.
f) All vapor barriers are to be continuous and completely sealed against moisture
penetration.
13.
Tenant applications such as, but not limited to, food service, hairstyling, pet shop, or as
otherwise determined by the Landlord, shall be required to install waterproof floor
membrane system(s).
14.
Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a Hot
Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open
flame welding or cutting such as, but not limited to welding, soldering and brazing.
15.
For all new installation of bathrooms, water closets must be wall-mounted tank-type per
Upper Merion Township effective 5/5/2006. Flush valve toilets and urinals are not
permitted.
16.
Upper Merion Township requires a mop sink or floor sink in each retail tenant space with
a toilet room. Confirm food court tenant requirements with local authorities.
King of Prussia Plaza
5.3
Electric Service – Section 6
1.
General Information:
a) Tenant’s electrical work shall be performed in full compliance with the most recent
edition of the National Electrical Code (NEC); State and local codes or ordinances.
A Certificate of Inspection, issued by the recognized inspection agency, must be
furnished to Landlord upon completion of the work.
b) The Tenant will be responsible for installing conductors from the Landlord’s Main
Service. The Tenant’s electrical distribution center, including main circuit breaker,
shall be coordinated with Tenant’s feeder size, panel board, transformer and all other
components necessary to meet the electrical requirement of the Premises.
c) Primary service to the Premise shall be 277/480 volts, 3-phase, 4-wire, plus full-size
ground, 60 hertz for all Tenants.
d) Tenant’s total connected electrical load shall not exceed twelve (12) watts per square
foot of Tenant’s leased area. Tenant’s Engineer shall complete the attached Electrical
Load Tabulation Form ET-1 and submit to Landlord for review. In the event the
electric service requirements of the Tenant exceeds the above-referenced capacity
provided by the Landlord, the Tenant shall reimburse the Landlord on demand for any
additional expense incurred by the Landlord for providing increased electric service
to the Premises.
e) The Landlord will not be obligated to provide the Tenant with temporary electric
service during the Tenant’s construction period. At the determination of the
Landlord’s Engineer, the Tenant will be responsible to reimburse the Landlord on
demand for electrical service, temporary or permanent, supplied from the Landlord’s
distribution system.
f) Lighting sources (lamps, ballasts and fixtures) used within tenant spaces shall be
compliant with the energy efficiency standards mandated by the Energy Policy Acts
(EPACT) of 1992 and 2005 and the Energy Independence and Security Act (EISA) of
2007. See Architectural Tenant Criteria for additional lighting requirements
2.
Electrical Equipment:
a) Transformers: Tenant shall furnish and install 277/480 volt, 3-phase, 4-wire to
120/208 volt, 3-phase, 4-wire transformer for secondary distribution loads.
Transformers shall be general purpose dry type with Class H insulation, mounted
below finished ceiling.
b) Metering: Tenant shall furnish and install meter base socket. Landlord shall provide
electrical meter at Tenant’s expense.
c) Panel boards: Panel boards shall be 277/480 volt and 120/208 volt, 3-phase, with
solid neutral. Circuit breakers in 277/480 and 120/208 volt panel boards shall be
bolted type. All panel boards shall contain twenty (20%) percent spare circuit breaker
King of Prussia Plaza
6.1
Electric Service – Section 6
capacity. Single-pole circuit breakers shall be quick-lag-type and 2-pole and 3-pole
circuit breakers shall be common trip. Handle ties are not acceptable. Panel board
loads shall be balanced. Tenant’s contractor shall be responsible for furnishing
completed panel board schedule.
d) Conduit and Contractors: Tenant’s electrical materials shall be new and bear the
Underwriters Laboratories (UL) label. All wiring shall be in metal raceway. Flexible
Metal (FM) conduit with full-sized ground may be used in concealed locations where
permitted by code. Non-metallic sheathed cable (Romex) will not be permitted.
Wire and cable shall be insulated copper conductors and color coded in accordance
with NEC. Minimum conductor size shall be #12 American Wire Gauge (AWG).
e) Motor Disconnect Switches: Motor disconnect switches shall be fused or non-fused,
standard duty horsepower rated, NEMA type, in enclosure suitable for the
application.
f) Nameplates: Tenant’s equipment such as, but not limited to, main service disconnect,
meter (if applicable), distribution panel boards, lighting panel boards, motor starters
and roof-mounted equipment shall be identified with individual permanent
nameplates.
g) Tenant’s electrical installation shall be readily accessible for service and
maintenance. All conduits shall be concealed wherever possible. Exposed conduits
shall be installed parallel with or at right angles to column lines or beams. Sleeves,
cored holes or other method of penetration of Tenant’s Premises shall be sealed and
fire safe as required.
h) Supports: Supporting systems for electrical installations such as, but not limited to,
hangers, miscellaneous steel, channels and rods shall be fastened to building
structural steel, concrete or masonry. Support from other piping systems will not be
permitted.
3.
Kiosk Electrical Service:
Electrical service to Kiosk locations are typically two (2) 20-amp 120-volt circuits.
4.
Telephone Service:
a) Tenant shall be responsible for contacting the local Telephone Company and for all
installation costs including service, conduit outlets, deposits and associated costs.
b) Landlord will supply 1” conduit with pull string from the service location to the
Premises. Any upgrades to this provision will be at Tenant’s expense.
c) Tenant’s electrical contractor shall install conduit with pull cord at all concealed
locations. Exposed conduits shall be installed parallel with or at right angles to
column lines or beams.
King of Prussia Plaza
6.2
Electric Service – Section 6
Reference Appendix:
D-6
Typical Tenant Service One Line Diagram
D-7
Space #1306 Tenant Electrical Service One Line Diagram
D-8
Typical Joist Reinforcement Detail at Concentrated Load
King of Prussia Plaza
6.3
Natural Gas – Section 7
1. Natural gas service will be available only to restaurant Tenants, at the Landlord’s
discretion. The installation thereof, if approved by Landlord, shall be subject to such
conditions of use as Landlord may impose. Gas service, if approved, may be used for
food preparation only. Flues will not be permitted. Installation of pressure-reducing
station, if required, and piping from point of service on Landlord’s roof shall be by
Tenant at Tenant’s expense. Installation shall meet all AGA and PECO Energy
standards. Any and all roof penetrations shall be performed by Landlord’s roofing
contractor at Tenant’s expense.
2. At the landlord’s discretion, natural gas service, will be made available from either the
gas main installed on the roof or to the gas main nearby underground. Distribution piping
from the discharge side of the Landlord-provided gas meter, regulators, and related
miscellaneous equipment required to make for a complete approved system will be the
sole responsibility of the Tenant who will bear all associated installation costs and fees
(including all permits and inspection fees related to said installation). Tenant shall
perform gas test as required by the gas utility and have witnessed by Landlord.
3. The Tenant will be responsible for obtaining all necessary approvals prior to the
installation of any piping, including approval of the utility company, Landlord’s
Insurance Underwriter and Landlord’s Engineer.
4. The gas piping installation shall be installed in accordance with NFPA Standard No. 54,
“National Fuel Gas Code,” and the rules and regulation of the utility company and any
other local and state agency involved in the regulation of this type of installation.
5. Interior gas piping shall be black steel electric resistance welded, Schedule 40, ASTM A53. Fittings shall be malleable iron 150 psig class, ASTM A-197.
6. Exterior gas piping shall be either galvanized Schedule 40-with galvanized malleable iron
150 psig fittings or Schedule 40 with black steel pipe with high-density poly coat with
welded fittings. Field applied polycoat must be applied to any bare metal.
7. Natural gas delivery pressure at the meter location will be 5 inches of water column.
Tenants requiring greater pressure of unusual capacity for the operation of their food
preparation equipment will be subject to all costs imposed by the Landlord to provide
such special service demands, including any costs which may be imposed on the
Landlord as a result of the Tenant’s requirements.
8. Provide Micro Industries (Midvale, Utah 1-801-566-3680) Model #02 pillow block pipe
stands for gas piping on roof. Supports shall consist of a nylon roller situated in a PVC
seat with a self-lubricating Teflon base. The pipe support is rigid PVC.
9. Automatic gas shut-offs are required.
King of Prussia Plaza
7.1
Sprinkler System – Section 8
Tenant’s sprinkler installation shall conform to NFPA 13, the requirements and
regulations of all governmental authorities exercising jurisdiction, Landlord’s Insurance
Underwriter, and these Tenant Criteria.
1.
Sprinkler contractors are required to submit working drawings to Landlord’s
Insurance Underwriter and to the local agencies exercising jurisdiction for approval
prior to work commencement. Contact information is included in the Project
Directory.
2.
Tenant shall be responsible to forward one (1) set of approved sprinkler system
drawings to the Landlord.
3.
Visible and audible fire alarms shall meet both Pennsylvania and
Upper Merion Township Americans with Disabilities Act (ADA)
requirements.
4.
Tenant shall provide sprinkler protection from Tenant’s sprinkler system to
Tenant’s service door alcove inside the lease line on rear service corridor.
5.
Food Preparation Tenants using open cooking equipment must install self-contained
fire suppression system or other approved systems. Per the Upper Merion
Township Fire Marshall, combustibles are not permitted within the tenant space
during construction until tenant’s sprinkler system is fully operational.
6.
Tenant’s sprinkler contractor shall connect Tenant’s valve to the capped or blank
flange outlet of the Landlord’s sprinkler system, according to Reference Appendix
D-5. Safe access to valve must be provided to Landlord. Tenant must identify
location.
7.
Pressure test(s) must be accomplished in accordance with the criteria established
Landlord’s Insurance Underwriters and industry standards and witnessed by
Landlord’s representative. Tenant’s sprinkler contractor must immediately make
repairs of any defects in the sprinkler installation.
8.
Fire hoses, cabinets, fire extinguishers and other required equipment within
Tenant’s Premises shall be installed in accordance with the requirements of the
Landlord’s Insurance Underwriter and all local agencies exercising jurisdiction.
9.
Prior to requesting a shutdown of the Landlord’s sprinkler system for connection of
or modification to the Tenant’s sprinkler system, the Tenant or the Tenant’s
sprinkler contractor, must obtain written approval from the Landlord’s Insurance
Underwriter and present same to Landlord.
10.
If required to drain down sprinkler system, Tenant’s Contractor to notify Mall
Management 24 hours prior to work to coordinate with all authorities. Sprinkler
system to be reactivated as required. There will be a $250.00 charge per
occurrence.
King of Prussia Plaza
8.1
Sprinkler System – Section 8
11.
Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a
Hot Work Permit(s) from Landlord. A Hot Work Permit is required for any and all
open flame welding or cutting such as but not limited to welding, soldering and
brazing.
12.
Tenant’s contractor shall not screw upward through the metal deck. Damaged
fireproofing must be restored. Sprinkler lines may not hang from the lower chord
of bar joists unless approved in advance by Landlord.
13.
Tenant’s sprinkler system must be fully operational and approved before the
Township will issue a Certificate of Occupancy.
14.
Tenant shall comply with the following mall-wide standard sprinkler specifications.
King of Prussia Plaza
8.2
Sprinkler System – Section 8
SECTION 15400 -TENANT FIRE PROTECTION SYSTEMS
SECTION DESCRIPTION
15401 GENERAL REQUIREMENTS
15402 FIRE PROTECTION DESIGN CRITERIA
15403 SPRINKLER EQUIPMENT
15404 SYSTEM ACTIVATION, TESTING AND CERTIFICATION
SECTION 15400 - FIRE PROTECTION SYSTEMS
15401 - GENERAL REQUIREMENTS
A.
GENERAL REQUIREMENTS
1.
The fire protection system shall be designed, fabricated, and installed by a
Licensed or NICET Fire Protection System Contractor. The engineer shall
provide specifications and diagrams to allow letting of a contract for the fire
protection portion of the project. The entire system design, material use and
installation shall comply with FM Global engineering guidelines as a
minimum.
2.
Plan submissions to Landlord’s Insurance Underwriter shall be made in
accordance to the contact on page 1.3 of the Project Directory:
3.
The sprinkler system shall be a wet pipe system serving all areas of the retail
space. Portions of the space that are unheated or exposed to freezing
temperatures shall be provided with an automatic dry pipe type system
complying with FM Global engineering guidelines and NFPA-13.
4.
Piping shall be fastened to the structural system of the building and concealed
in areas having a suspended ceiling. Install and/or upgrade seismic sway
bracing on existing systems where required for earthquake zones per local
codes and FM Global engineering guidelines. Seismic bracing for fire
systems must be designed and installed following FM Global Data Sheet 2-8.
5.
Drain piping is required at low points of piping systems. Drain down locations
shall be extended to locations that are accessible.
King of Prussia Plaza
8.3
Sprinkler System – Section 8
B.
FIRE PROTECTION FOR EXISTING TENANT SPRINKLER SYSTEMS
1.
Whenever an existing sprinkler system is being renovated, the integrity and
reliability of the existing system must be maintained. Original sprinkler shop
drawings shall be acquired through Mall Management. If these drawings are
not available, field verification will be required. If the sprinkler contractor
discovers a discrepancy from the original sprinkler shop drawings and actual
field conditions, he shall note the discrepancy on his renovated shop drawings.
2.
The hydraulic design criteria as a minimum shall match the hydraulic criteria
originally intended for the facility. At no time shall the hydraulic criteria be
less than Ordinary Hazard Group 2 occupancy as defined by NFPA-13. The
latest site water flow data to be used for hydraulic calculations shall be
obtained from FMGlobal Risk Consultants or Mall Management.
3.
Existing pipe schedule sprinkler systems are required to be calculated at the
FM Global density of 0.15 gpm per sq. ft. over the most hydraulically remote
2500 sq. ft.
4.
FM Approved materials for Ordinary Hazard Group 2 occupancy must be
used, including but not limited to sprinkler piping, hangers, sprinkler heads,
etc. Seismic bracing may be UL Listed.
5.
Sprinkler head spacing requirements for Ordinary Hazard Group 2 occupancy
shall be in strict compliance with the sprinkler head listings and approval.
6.
NFPA-13 and FM Global Data Sheets 2-8N latest editions shall be the
minimum design requirements along with any state and local requirements.
7.
A minimum of (4) sets of shop drawings along with hydraulic calculations (if
applicable) shall be submitted to FM Global for approval. Hydraulic
calculations shall be submitted for all tenant sprinkler system work regardless
of the scope of work involved. Plans shall be submitted to the local authorities
having jurisdiction for approval. Installation/renovation of sprinkler system
shall not begin until all approvals have been received.
8.
Four sets of material brochures shall also be submitted to FM Global for
review. Brochures shall be limited to new sprinklers heads, flexible drops and
valves. Plans shall indicate the type of piping being utilized with the gauge
indicated.
15402 - FIRE PROTECTION DESIGN CRITERIA
A.
GENERAL
1.
King of Prussia Plaza
Sprinkler head arrangement shall be in conjunction with architectural finishes
and provide allowance for partitions, columns, light fixtures, air diffusers, etc.
8.4
Sprinkler System – Section 8
2.
Sprinkler Shop Drawings shall not be considered final until all requirements
of FM Global, Landlord, and all Local and State Building Codes having
authority have been met, and the approval of each has been tendered.
3.
Minimum and maximum sprinkler head operating pressures shall be
consistent with their UL Listing/FM Approval.
4.
Design calculations for inside pipe should use C=100 for dry and pre-action
systems, and C=120 for wet or deluge systems.
5.
Minimum and maximum sprinkler spacing shall be in accordance with their
UL Listing/FM Approval.
6.
FM Global required minimum density for Sales/Retail/Storage spaces will be
0.15 gpm per sq. ft. over the most hydraulically remote 2500 sq. ft., using ½”
or 17/32” orifice, 165 degree F. rated heads. If the local AHJ requires an
NFPA-13 design density, 0.18 gpm per sq. ft. over the most hydraulically
remote 2500 sq. ft. shall be used unless specific approval is given otherwise
for special occupancies. The most remote area should have the dimensions
parallel to the branch line of at least 1.4 times the square-root of the area per
FM Global Data Sheet 2-8N. Quick-response (QR) sprinklers do not qualify
for a design area reduction per FM Global Data Sheet 3-26. The density
design should conform to the most stringent of either FM Global Data Sheet
3-26 or NFPA-13, Ordinary Group 2 occupancy.
7
Stockroom/storage areas over 200 sq. ft. must be protected for the maximum
storage height and configuration (bin-box/gondola/shelf or rack) per FM
Global Data Sheet 8-9. When storage exceeds 10 feet in height, the regional
FM Global plan reviewer shall be consulted for appropriate design densities.
Classify the commodities in tenant spaces as “Cartoned Expanded &
Unexpanded Plastics” for sprinkler design purposes. Sprinkler head spacing
shall not exceed 100 sq. ft. in storage areas unless approved for extended
coverage (i.e., EC-25).
8.
Big Box Stores require unique sprinkler system designs to meet the
requirements of FM Global Data Sheet 8-9 and NFPA-13, Chapter 12.
Contact Bill Cary with Global Risk Consultants for specific design
requirements based upon the proposed display / storage configuration and roof
deck height.
15403 - SPRINKLER EQUIPMENT
A.
GENERAL
1.
B.
Only sprinkler equipment bearing the FM Global Approval mark shall be
installed. Provide equipment as manufactured by: Automatic Sprinkler, Tyco,
Reliable, Viking Gem or equal.
SPRINKLER HEADS
1.
King of Prussia Plaza
Sprinkler heads shall be glass bulb type of a configuration as required for each
particular location. All heads on concealed piping shall be chrome plated with
8.5
Sprinkler System – Section 8
chrome plated escutcheon plates. Operating temperature shall be as required
for the type of occupancy.
2.
C.
Sprinkler heads in janitor’s closets, mechanical rooms, electrical rooms and
those mounted less than 8 feet above finished floor shall be protected with a
wire cage type guard.
SPRINKLER PIPING
1.
Aboveground piping shall be FM Approved Schedule 10 or 40 black steel.
Schedule 10 piping shall be joined with FM Approved roll-grooved fittings,
not threaded or plain-end. Fittings shall be cast iron or steel approved for a
minimum of 175 psi working pressure. Dry systems shall have FM Approved
galvanized piping and fittings for corrosion resistance.
2.
Threadable “lightwall” (XL) and “thinwall” pipe may not be utilized under
any circumstances.
3.
Hangers shall be FM Approved, and adaptable to various types of
construction. Hangers shall be supported from building structure and
structural steel headers shall be installed for supporting cross main hangers
where main is not directly below structural member. Roof deck hangers are
prohibited. All hangers shall comply with FM Global engineering guidelines.
4.
Under no circumstances, will Landlord permit Tenant's sprinklers and other
equipment to hang from the metal deck. Sprinklers and equipment must be
hung from beams and bar joists. Sprinkler and equipment loads must be
limited to less than 150 pounds at each connection. Sprinkler and equipment
support connections should be made at the top chord of bar joist at panel
points (where diagonal struts form a shape). Sprinkler and equipment
^
supports may also be connected to the bottom chord of bar joists at panel
points (where diagonal struts form a V shape). Sprinkler and equipment
supports should sufficiently numerous and be staggered so that sprinkler loads
are evenly distributed across all structural members. If sprinkler and
equipment supports are located more than 3 inches from a panel point,
additional structural reinforcement may be required, requiring review by
Landlord’s structural engineer. Combined sprinkler and equipment loads on
any one joist (all loads of any type) exceeding 300 pounds require review by
Landlord’s structural engineer. See Appendix Reference Detail D-8.
5.
D.
Wall plates shall be provided on exposed piping where pipe passes through
walls, partitions, ceilings, etc. and secured by setscrews.
VALVES
1.
At each connection to the Landlord’s sprinkler system, the Tenant will
provide an approved shut-off valve with supervisory switch.
2.
All valves and fittings shall be FM Approved and rated 175 lb. minimum.
King of Prussia Plaza
8.6
Sprinkler System – Section 8
3.
The switch shall be connected to the Landlord’s addressable alarm system
by the Landlord’s Alarm Contractor at the Tenant’s expense.
15404 - SYSTEM ACTIVATION, TESTING AND CERTIFICATION
1.
Sprinkler contractor shall install and activate the entire sprinkler system prior
to the bringing combustibles into the tenant space, and no later than
Certificate of Occupancy.
2.
Existing sprinkler systems shall be shut down and “red” tagged in strict
accordance with Landlord’s requirements. Under no circumstances should a
sprinkler system be left out of operation overnight without an appropriate “fire
watch” in place.
3.
All fire protection systems shall be tested as required by local authorities and
FM Global before any systems are concealed.
4.
Contractor shall conduct hydrostatic tests in compliance with FM Global Data
Sheet 2-8N and NFPA-13 (two hours at 200 psi or 50 psi over normal system
pressure minimum). Piping subject to freezing during test period shall be
tested with compressed air.
5.
Certificates of approval of installation shall be obtained from the Authority
having Jurisdiction and forwarded to Landlord.
6.
After tests are conducted and any repairs completed; completely flush the
piping systems with water until discharge shows no discoloration.
7.
Following sprinkler testing and approval, Landlord will lock the sprinkler
valve in the open position. Tenant will be charged a lock expense of $20.
King of Prussia Plaza
8.7
Sprinkler System – Section 8
Tenant Display Fixtures, Rack/Shelving/Storage Unit Requirements
•
Tenant display fixtures in the retail space and rack/shelving/storage units in the
stockroom must be designed to provide adequate clearance for the automatic (fire)
sprinkler system. No displays or storage should exceed 12 ft. and ceilings must be
installed to provide at least 18 in. of clearance between the top of storage and
sprinkler deflectors.
•
Tenant displays or storage higher than 12 ft. are classified as “high piled storage”,
which requires high hazard automatic (fire) sprinkler protection designed per FM
Global Loss Prevention Data Sheet 8-9 and NFPA-13-Chapter 12 for the storage of
“Group A Plastic” commodities. High piled storage also requires at least 36 in. of
clearance between the top of storage and sprinkler deflectors.
•
Tenant mobile (compact) storage systems should be constructed of wire mesh
shelves. However, if constructed with solid shelves (steel, wood), the units must be
equipped with 3 in. spacers to provide flue spaces at 4 ft. to 5 ft. maximum intervals.
•
Tenants Architect/General Contractor must provide the following information to the
Sprinkler Contractor regarding stock/storage area:
Type of storage units (Details of storage unit)
Type of shelving (wire mesh, solid, steel, wood, etc.)
Type of commodities (plastics, aerosol’s, clothing, etc.)
Elevation of highest shelf
Tenant shall be solely responsible for the display, installation and use of any display
or storage system within the Premises in compliance with applicable fire codes and
the requirements of any insurance rating bureaus. If anything done, omitted to be
done or suffered to be done by Tenant in, upon or about the Premises in regard to
such display or storage systems shall result in a fire code violation and Tenant fails
to take corrective action and/or pay the associated fine, regardless of whether
assessed against Tenant or Landlord, within the prescribed time period, then
Tenant shall be liable for all costs and expenses resulting from such violation and
Landlord shall have the right to correct any such condition at Tenant’s expense.
Reference Appendix:
D-5
Typical Sprinkler System Details
D-8
Typical Joist Reinforcing Detail at Concentrated Load
King of Prussia Plaza
8.8
Appendices: Forms
King of Prussia Plaza
Appendices: Forms
King of Prussia Plaza
Appendices: Forms
King of Prussia Plaza
Appendices: Forms
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Appendices: Drawings
King of Prussia Plaza
Download