Tenant Design Criteria For MECHANICAL AND ELECTRICAL WORK KING OF PRUSSIA PLAZA King of Prussia, Pennsylvania SIMON PROPERTY GROUP (Updated 11/05/2010) KING OF PRUSSIA PLAZA TABLE OF CONTENTS General Information and Project Directory ............................................... Section 1 Heating, Ventilation and Air Conditioning................................................ Section 2 Vapor Removal Systems............................................................................ Section 3 Typical Roof Opening, Curbing and Specifications .................................. Section 4 Plumbing .................................................................................................... Section 5 Electrical Service ....................................................................................... Section 6 Natural Gas ................................................................................................ Section 7 Sprinkler System........................................................................................ Section 8 APPENDICES: Forms ET-1 – Electrical Tabulation Form (Sample) ET-1 – Electrical Tabulation Form MT-1 – Mechanical Tabulation Form (Sample) MT-1 – Mechanical Tabulation Form APPENDICES: Drawings D-1 Typical HVAC Installation D-2 Typical Tenant Return Air Path D-3 Typical Hood Exhaust Fan – Roof Mounted Grease Exhaust Roof Protection Requirements D-4 Typical Roof Opening Framing and Equipment Supports D-5 Typical Sprinkler System Details D-6 Typical Tenant Electrical Service One Line Diagram D-7 Spaces #1306 Tenant Electrical Service One-Line Diagram D-8 Typical Joist Reinforcement Detail at Concentrated Load King of Prussia Plaza General Information and Project Directory – Section 1 This design criteria provides information and lists requirements to be used in the preparation of plans and specifications for Tenant’s mechanical and electrical work. Tenant’s plans and specifications shall be prepared by and bear the seal of Architects and Engineers licensed by the Commonwealth of Pennsylvania and shall comply with current code requirements and meet the requirements of all governing agencies exercising jurisdiction. Tenant’s plans and specifications, with calculations and supporting data, shall be submitted for review by the Landlord. Work will not be permitted to commence without plans and specifications having prior review and written acceptance of the Landlord, as well as that of all governing bodies exercising jurisdiction. Landlord’s review is solely for conformance to this criteria and landlord’s review shall not be construed to be a guarantee of design or function adequacy. Tenant shall field verify exact location and size of demised premises, all service characteristics and locations as well as any interference to the installation of Tenant’s work. Tenant shall immediately notify Landlord of any discrepancies or interference and shall not commence any work prior to the resolution thereof. Under no circumstances, will Landlord permit Tenant's sprinklers and other equipment to hang from the metal deck. Sprinklers and equipment must be hung from beams and bar joists. Sprinkler and equipment loads must be limited to less than 150 pounds at each connection. Sprinkler and equipment support connections should be made at the top chord of bar joist at panel points (where diagonal struts form a ^ shape). Sprinkler and equipment supports may also be connected to the bottom chord of bar joists at panel points (where diagonal struts form a V shape). Sprinkler and equipment supports should be sufficiently numerous and staggered so that sprinkler loads are evenly distributed across all structural members. If sprinkler and equipment supports are located more than 3 inches from a panel point, additional structural reinforcement may be required, requiring review by Landlord’s structural engineer. Combined sprinkler and equipment loads on any one joist (all loads of any type) exceeding 300 pounds require review by Landlord’s structural engineer. See Appendix Reference Detail D-8. Tenant’s work shall be performed by licensed contractors. Tenant shall require any personal performing such work to guarantee the work to be free from any and all defects in materials and workmanship for one (1) year from date of beneficial use or acceptance. Tenant shall also require any such person to be responsible for the replacement or repair, without additional charge, of any and all work done, or furnished by or through such person, which shall become defective or inoperable within one (1) year after beneficial use or acceptance. The correction of such work shall include, without additional charge, all expenses and damages in connection with the removal, repair or replacement of any part of the work which may be damaged or disturbed thereby. All warranties and guarantees as to materials or workmanship, with respect to Tenant’s work, shall be contained in the contract or subcontract which shall be so written that such warranties or guarantees shall insure to the benefit of both Landlord and Tenant, as their respective interests appear, and can be directly enforced by either. Tenant covenants to give landlord any assignment or other assurances necessary to effect the same. King of Prussia Plaza 1.1 General Information and Project Directory – Section 1 Tenant’s work shall be coordinated with the work being done by Landlord and other tenants, to such extent that the Tenant’s work will not interfere with or cause delay of any other associated construction work or business conduct. Tenant shall engage the services of licensed Architects, Engineers, and contractors who will work in harmony with each other and those of the Landlord. To this end there shall be no labor dispute which would interfere with the construction, completion and operation of the Mall. Tenant shall provide public liability and property damage insurance, in such amounts as stipulated by Landlord, for all work performed by the Tenant’s contractors, subcontractors and/or their suppliers. Tenant is responsible to procure any and all necessary permits and obtain written approvals from Landlord and all governing agencies exercising jurisdiction including, but not limited to, hot work permit or sprinkler permit. At the Tenant’s expense, and with Landlord’s written approval, any and all existing mechanical, electrical and/or plumbing services, equipment or portion thereof not scheduled for re-use as part of the Tenant’s construction, shall be demolished or otherwise safely terminated. A Tenant electing to re-use existing services, equipment or portion thereof is permitted to do so provided that the Tenant’s Engineer and/or contractor deems these components acceptable for re-use in the new design. Tenant accepts full responsibility for the operational integrity of any and all existing equipment. The re-use of existing services, equipment or portion thereof does not relieve the Tenant of the responsibility to furnish plans as aforementioned. King of Prussia Plaza 1.2 General Information and Project Directory – Section 1 PROJECT DIRECTORY DIRECTOR OF TENANT COORDINATION Simon Property Group The Atrium 234 Mall Boulevard King of Prussia, PA 19406-2954 (610) 768-6341 TENANT COORDINATION ANALYST (610) 768-6337 LANDLORD’S MANAGING AGENT Simon Property Group The Atrium 234 Mall Boulevard King of Prussia, PA 19406-2954 (610) 768-6300 MALL MANAGEMENT Plaza Management Office 160 North Gulph Road, Suite 2700 King of Prussia, PA 19406 (610) 265-5794 LANDLORD-SUPPLIED ITEMS TELEPHONE SERVICE Verizon 1350 Welsh Road North Wales, PA 19454 1 (800) Verizon or 1 (800) 479-1919 CURRENT ARCHITECT FOR SPACES 1306-1311 AND 2301-2308 McGillan Architecture, Inc. Two Bala Plaza, Suite 502 333 City Line Avenue Bala Cynwyd, PA 19004 (610) 664-6577 GAS SERVICE PECO Energy 2301 Market Street Philadelphia, PA 19102 1 (800) 494-4000 ARCHITECT Thompson, Ventulett, Stainback & Associates, Inc., Architects 2700 Promenade Two 1230 Peachtree Street, NE Atlanta, GA 39309-3591 (404) 888-6600 HEALTH DEPARTMENT Montgomery County Health Department 1430 Dekalb Street Norristown, PA 19404-0311 (610) 278-5117 ELECTRICAL ENGINEER KLG, LLC. 2136 Defoors Ferry Road NW Atlanta, GA 30309 (404) 881-6565 PUBLIC WORKS DEPARTMENT (CODE REVIEW AND BUILDING PERMITS) Upper Merion Township 175 West Valley Forge Road King of Prussia, PA 19406 (610) 265-2606 MECHANICAL ENGINEER ZMM, Inc. (Design) 222 Lee Street, West Charleston, WV 25302 (304) 342-0159 WATER, SEWER & ELECTRIC SERVICE Mall Operations Department Plaza Management Office 160 North Gulph Road King of Prussia, PA 19406 (610) 337-9272 FACTORY MUTUAL FM Global Attn: Plan Review 2100 Reston Parkway, Suite 600 Reston, VA 20191 (703) 860-4101 y Fax: (703) 860-3187 LANDLORD’S ALARM CONTRACTOR Siemens Building Technologies, Inc. 2000 Crawford Place Mt. Laurel, NJ 08504 (856) 385-7521 King of Prussia Plaza 1.3 Heating, Ventilating and Air Conditioning – Section 2 Tenant shall install a heating, ventilating and air conditioning (HVAC) system as designed by Tenant’s Engineer in strict accordance with the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE), The International Codes 2009, National Fire Protection Association (NFPA) recommended practice and this criteria. Tenant shall submit, for Landlord’s review and acceptance, design documents and design load calculations including cooling and electrical tabulation forms prepared and sealed by a registered Professional Engineer. Landlord’s HVAC system is based upon the following parameters: 1. Landlord will supply medium pressure, variable volume, and constant temperature air for cooling during Mall scheduled business hours. Under normal operating conditions, cooling will not be provided during Mall scheduled non-business hours. 2. Landlord will provide heat to Tenant spaces during non-business hours to prevent freezing when necessary. Under normal operating conditions, heating will not be supplied during Mall scheduled business hours. 3. During Mall scheduled business hours, Landlord will supply minimum ventilation air in accordance with ASHRAE 62.1. 4. Landlord will install Variable Air Volume (VAV) terminal(s) to modulate supply air quantity from 30% minimum to 100% of maximum required air volume. Landlord shall furnish and install, at Tenant’s expense, a thermostat for control of VAV terminal. 5. Cooling Design Conditions: a) Primary Air Supply: Summer Cooling – 58° FDB Nominal b) Space Conditions: Business Hours – 76° FDB Nominal 6. Return Air: Tenant shall provide a means for return air to Landlord’s HVAC system during all occupied and unoccupied hours. Return air openings shall have free area sized for maximum velocity of 400 FPM of Tenant’s maximum air supply during occupied hours, including door openings, and 800 FPM during unoccupied hours. Return openings shall meet Architectural design criteria. Tenant shall return supply air to Mall unless otherwise required by Landlord. Tenant shall not allow the return of objectionable odors to Mall and shall provide means of exhausting same in a required manner. 7. Tenant HVAC Construction: a) King of Prussia Plaza Construction: Tenant’s HVAC ductwork shall be galvanized sheet steel, black steel, or aluminum. Tenant’s toilet exhaust ductwork shall be fabricated from galvanized sheet metal, and all vapor removal ductwork shall be fabricated from stainless steel or black steel in accordance with ASHRAE standards and Sheet Metal and Air Conditioning contractors National Association, Inc. (SMACNA) manuals. Fiberglass ductwork will not be permitted. 2.1 Heating, Ventilating and Air Conditioning – Section 2 b) Maximum allowable pressure drop through Tenant’s ductwork and equipment downstream of Landlord’s VAV terminal shall not exceed 0.4 inch water column. c) Air Distribution Devices: Air distribution devices shall be commercial grade registers or ceiling diffusers with individual manual volume control. d) Flexible ductwork: If used, flexible ductwork shall be equal to “Flexmaster Triple Lock” aluminum insulating ductwork with a maximum length not to exceed six (6) feet. e) Duct Insulation: All supply air ductwork shall be insulated with one (1) inch thickness glass fiber insulation with foil vapor barrier. Internally lined ductwork will not be permitted. f) Penetrations: Penetrations in any partitions having a fire rating of one hour or more must be fire-stopped with approved materials and methods to prevent the migration of smoke and to maintain the fire rating of the partition. g) Variable Air Volume (VAV) Terminals: Any and all Tenant requested revisions to the existing VAV terminals shall be performed by the Landlord at the Tenant’s expense. h) Access Panels: Access panels of suitable size to enable safe entry shall be provided for all fire dampers, air balancing controls, valves, VAV terminals and other equipment if rendered inaccessible by Tenant’s construction. i) Air Balancing: Tenant shall engage the services of a certified independent air balance contractor. Tenant’s air balance report must be submitted to and accepted by Landlord before the Premises will be allowed to open for business. j) Electric Heating Coil: If heating to the Premises is required during occupied hours, Tenant’s Engineer shall provide for the installation of an electric duct heating coil downstream of the VAV terminal. Tenant shall install appropriate controls so that heating elements can be energized only when VAV terminal is in 30% supply air position. In the event the Tenant elects to install an electric duct heating coil, Tenant shall (1) provide air flow safety switch and thermal overload device and (2) design the electric heat capacity to minimum VAV terminal setting. Landlord, at Tenant’s expense, shall adjust VAV terminal minimum stop to 30% supply air position. k) Toilet Exhaust: Tenant shall provide a toilet exhaust fan with back-draft damper. Where available, Tenant shall interconnect toilet exhaust fan discharge to the Landlord toilet exhaust duct. Where toilet exhaust duct is not accessible or available, the Tenant shall be required to exhaust at the roof level. Roof membrane cutting and flashing shall be performed by the Landlord’s contractor at the Tenant’s expense. Tenant’s contractor must contact Mall management office prior to commencement of work. King of Prussia Plaza 2.2 Heating, Ventilating and Air Conditioning – Section 2 7. Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure Hot Work Permit(s) from the Landlord. A Hot Work Permit is required for any and all open flame welding or cutting such as but not limited to welding, soldering and brazing. Reference Appendix: D-1 Typical HVAC Installation D-2 Typical Tenant Return Air Path D-3 Typical Hood Exhaust Fan – Roof Mounted D-8 Typical Joist Reinforcing at Concentrate Load King of Prussia Plaza 2.3 Vapor Removal Systems – Section 3 Vapor removal system shall include, but not be limited to the following: 1. Hoods and/or canopies 2. Duct systems 3. Grease removal devices 4. Dampers 5. Air moving devices 6 Auxiliary equipment 7. Fire extinguishing equipment Vapor removal system materials shall be new and designed for the intended application in accordance with engineering data. All vapor removal equipment shall be installed in strict accordance with the manufacturer’s recommendations for type and capacity. The installation of energy efficient make-up air systems is encouraged. Vapor systems shall conform to all applicable laws, codes, ordinances and governing regulations, including, but not limited to the following: 1. 2. 3. 4. National Fire Protection Association (NFPA) National Electrical Code (NEC) Underwriters Laboratories (UL) International Building Code, International Mechanical Code, International Plumbing Code 5. Factory Mutual Fire Insurance Underwriters(FM) 6. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE) Objectionable Odor Exhaust: Tenant applications such as, but not limited to, food service, hair styling, pet shop, or as otherwise determined by the Landlord, may be required to install vapor removal systems of a capacity not less than 105% of the supply air quantity to the Premises. Tenant shall be responsible for all modifications and improvements to Tenant’s vapor removal systems to avoid negatively impacting the Landlord’s or other Tenant’s HVAC systems. Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure Hot Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open flame welding or cutting such as, but not limited to welding, soldering and brazing. Reference Appendix: D-3 Typical Hood Exhaust Fan – Roof Mounted D-4 Typical roof Opening Framing and Equipment Supports D-8 Typical Joist Reinforcement Detail at Concentrated Load King of Prussia Plaza 3.1 Typical Roof Opening, Curbing and Specification – Section 4 General Information: 1. Roof membrane cutting, flashing and cutting roof deck must be performed by Landlord’s roofing contractor at Tenant expense. Tenant’s contractor must contact the Mall management office prior to commencement of work. All other work such as, miscellaneous steel, welding must be performed by Tenant’s contractor. 2. Submittals shall include three (3) installation drawings of structural support steel prepared by a Licensed Engineer and forwarded to the Landlord’s Tenant Coordinator prior to work commencement. 3. Wood block-type supports set directly on the roof membrane will not be permitted. 4. Abandoned equipment located over the Premise must be removed by Tenant. Existing roof curbs not scheduled for re-use by the Tenant shall be removed by Landlord’s roofing contractor at Tenant’s expense. 5. Tenant’s Engineer shall submit dimensioned sketch of all surrounding existing rooftop equipment for Landlord’s review and acceptance. 6. Submittals shall include details of roof supports for all exterior piping including a roof plan of proposed routing for Landlord’s review and acceptance. 7. The top of roof curb must be a minimum of 18” above the existing roof. Refer to Appendix Drawing for requirements on typical roof-mounted exhaust fans. 8. Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a Hot Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open flame welding or cutting such as, but not limited to welding, soldering and brazing. Reference Appendix: D-3 Typical Hood Exhaust Fan – Roof Mounted Grease Exhaust Roof Protection Requirements D-4 Typical Roof Opening Framing and Equipment Supports D-8 Typical Joist Reinforcement Detail at Concentrated Load King of Prussia Plaza 4.1 Plumbing – Section 5 1. Where provided by Landlord, typical water and sewer connections to the Premise are as follows: Cold water supply – ¾” Sanitary stub – 4” Sanitary vent – 3” If Tenant’s requirement(s) exceed the existing connections provided by Landlord, the Tenant’s plans shall reflect such modifications for review ad approval by Landlord. Any and all such modifications shall be at Tenant’s expense. 2. All saw cutting of the floor slab shall be by Tenant’s contractor, after advance written notification is submitted to Landlord’s Engineer for approval. Tenant and Contractor must have a floor scan completed before saw cutting is completed. Tenant will be held responsible for any lines cut during construction. 3. Tenant shall furnish and install an electric water heater. Water heater shall be UL listed and approved. The relief valve shall be piped to an open drain. 4. Food Preparation Tenants shall provide at least one floor sink with integral sediment bucket in each kitchen and/or food preparation area with accessible clean-outs as required by applicable codes. Clean-outs shall terminate flush with the finished floor or wall. Tenant shall install an accessible cleanout prior to the entry to Landlord’s sanitary main within the Premise. 5. All waste piping designed and installed for the drainage of grease-producing fixtures as defined by the Plumbing Inspector and/or Landlord’s Engineer, such as pot sinks, dishwashers and kitchen hood grease drains, shall discharge through an approved Tenant provided, mechanical grease recovery unit(s) with sediment strainer prior to connection to the Landlord’s sanitary system. The Tenant must comply with all local codes and Landlord requirements for installation and maintenance of grease recovery units. 6. Grease recovery units must be installed within Tenant’s Premises and above the finished floor. 7. All Tenant applications using chemical processes, such as photo finishing, dental facilities, or as otherwise determined by the Landlord, must pre-treat all wastewater to meet the required standards and regulations before discharge to Landlord’s sanitary system. 8. All piping systems must be compatible with the type of materials used by Landlord and shall comply with the following requirements: a) Drainage, Vent Pipe and Fittings: Below grade service shall be bell and spigot, cast iron pipe and fittings with rubber gaskets. Above grade service shall be hubless cast iron pipe and fittings. Joints shall be rubber sealing sleeve and stainless steel coupling with stainless steel clamps and bolts as manufactured by Tyler Pipe or equal. Pipe and joining couplings must be produced by the same manufacturer. Copper King of Prussia Plaza 5.1 Plumbing – Section 5 drain, waste and vent piping is acceptable above Tenant floor elevation. Plastic pipe will not be permitted. b) Domestic Water Piping: All water piping shall be Type L copper tubing, seamless drawn, hard temper with plain ends compatible with ASTM B-88. Neither type M copper or any type of plastic pipe will be permitted. Fittings shall be wrought copper with socket ends with lead-free ASTM 95/5 tin-antimony. Tenant’s plumbing contractor will be required to certify to Landlord that all equipment and installation is lead-free in compliance with Federal Drinking Water Standards. All valves for domestic water use must be rated at 125 psi test. c) Tenant shall install air chambers or shock absorbers in piping system to prevent noise and damage due to water hammer. Branch piping shall include accessible service valves and shut off valves to all fixtures. d) Tenant shall provide dielectric fittings at all junctions of dissimilar metals. 9. Pipe must be supported securely from hangers as follows: a) Where required, and with Landlord’s approval, Tenant’s plumbing contractor is responsible to install additional intermediate structural supports for hangers. b) Hangers must not pierce insulation vapor barrier. c) Cast iron pipe must be supported at least every five (5) feet and at every joint and fitting. Cast iron pipe branches without support must have hangers installed a maximum of four (4) feet on center. d) Non-insulated copper pipe must be installed with either copper or plastic coated steel hangers. 10. Tenant shall furnish and install a water meter remote readout, of size and type approved by Landlord and at a location designated by the Landlord’s Engineer. 11. All tenants are required to install, test and maintain backflow prevention devices in series after the water meter. No bypass is permitted. Tenant applications such as, but not limited to, food service, hair styling, photographic reproduction, pet shop; must install a Watts 009 Series reduced pressure zone (RPZ) backflow pressure device. All other tenants shall install a Watts 007 Series double check valve assembly. 12. Pipe Insulation: a) All hot water piping and piping subject to condensation, including cold water and condensate drain piping, must be insulated. b) All insulation shall be fire and smoke hazard rated as tested by procedure ASTM E84, NFPA 225 and UL 723 and must not exceed a flame spread rating of 25 and King of Prussia Plaza 5.2 Plumbing – Section 5 smoke developed rating of 50. Glass fiber insulation shall be of the type having a 4.0 pound density and a k-factor of 0.25, one inch minimum. c) Insulation hangers shall be protected by a section of compressed glass fiber insulation with a metal saddle on the outside of the insulation. d) All exposed and concealed insulated piping is to have an all service jacket similar to Owens-Corning Fiberglass ASJ25 with self-sealing lap joint sealing strips. e) Pre-molded insulated fittings shall be of the same material and thickness as pipe insulation. Provide Zeston PVC jackets or equivalent and must not exceed a flame spread rating of 25 and smoke developed rating of 50. f) All vapor barriers are to be continuous and completely sealed against moisture penetration. 13. Tenant applications such as, but not limited to, food service, hairstyling, pet shop, or as otherwise determined by the Landlord, shall be required to install waterproof floor membrane system(s). 14. Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a Hot Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open flame welding or cutting such as, but not limited to welding, soldering and brazing. 15. For all new installation of bathrooms, water closets must be wall-mounted tank-type per Upper Merion Township effective 5/5/2006. Flush valve toilets and urinals are not permitted. 16. Upper Merion Township requires a mop sink or floor sink in each retail tenant space with a toilet room. Confirm food court tenant requirements with local authorities. King of Prussia Plaza 5.3 Electric Service – Section 6 1. General Information: a) Tenant’s electrical work shall be performed in full compliance with the most recent edition of the National Electrical Code (NEC); State and local codes or ordinances. A Certificate of Inspection, issued by the recognized inspection agency, must be furnished to Landlord upon completion of the work. b) The Tenant will be responsible for installing conductors from the Landlord’s Main Service. The Tenant’s electrical distribution center, including main circuit breaker, shall be coordinated with Tenant’s feeder size, panel board, transformer and all other components necessary to meet the electrical requirement of the Premises. c) Primary service to the Premise shall be 277/480 volts, 3-phase, 4-wire, plus full-size ground, 60 hertz for all Tenants. d) Tenant’s total connected electrical load shall not exceed twelve (12) watts per square foot of Tenant’s leased area. Tenant’s Engineer shall complete the attached Electrical Load Tabulation Form ET-1 and submit to Landlord for review. In the event the electric service requirements of the Tenant exceeds the above-referenced capacity provided by the Landlord, the Tenant shall reimburse the Landlord on demand for any additional expense incurred by the Landlord for providing increased electric service to the Premises. e) The Landlord will not be obligated to provide the Tenant with temporary electric service during the Tenant’s construction period. At the determination of the Landlord’s Engineer, the Tenant will be responsible to reimburse the Landlord on demand for electrical service, temporary or permanent, supplied from the Landlord’s distribution system. f) Lighting sources (lamps, ballasts and fixtures) used within tenant spaces shall be compliant with the energy efficiency standards mandated by the Energy Policy Acts (EPACT) of 1992 and 2005 and the Energy Independence and Security Act (EISA) of 2007. See Architectural Tenant Criteria for additional lighting requirements 2. Electrical Equipment: a) Transformers: Tenant shall furnish and install 277/480 volt, 3-phase, 4-wire to 120/208 volt, 3-phase, 4-wire transformer for secondary distribution loads. Transformers shall be general purpose dry type with Class H insulation, mounted below finished ceiling. b) Metering: Tenant shall furnish and install meter base socket. Landlord shall provide electrical meter at Tenant’s expense. c) Panel boards: Panel boards shall be 277/480 volt and 120/208 volt, 3-phase, with solid neutral. Circuit breakers in 277/480 and 120/208 volt panel boards shall be bolted type. All panel boards shall contain twenty (20%) percent spare circuit breaker King of Prussia Plaza 6.1 Electric Service – Section 6 capacity. Single-pole circuit breakers shall be quick-lag-type and 2-pole and 3-pole circuit breakers shall be common trip. Handle ties are not acceptable. Panel board loads shall be balanced. Tenant’s contractor shall be responsible for furnishing completed panel board schedule. d) Conduit and Contractors: Tenant’s electrical materials shall be new and bear the Underwriters Laboratories (UL) label. All wiring shall be in metal raceway. Flexible Metal (FM) conduit with full-sized ground may be used in concealed locations where permitted by code. Non-metallic sheathed cable (Romex) will not be permitted. Wire and cable shall be insulated copper conductors and color coded in accordance with NEC. Minimum conductor size shall be #12 American Wire Gauge (AWG). e) Motor Disconnect Switches: Motor disconnect switches shall be fused or non-fused, standard duty horsepower rated, NEMA type, in enclosure suitable for the application. f) Nameplates: Tenant’s equipment such as, but not limited to, main service disconnect, meter (if applicable), distribution panel boards, lighting panel boards, motor starters and roof-mounted equipment shall be identified with individual permanent nameplates. g) Tenant’s electrical installation shall be readily accessible for service and maintenance. All conduits shall be concealed wherever possible. Exposed conduits shall be installed parallel with or at right angles to column lines or beams. Sleeves, cored holes or other method of penetration of Tenant’s Premises shall be sealed and fire safe as required. h) Supports: Supporting systems for electrical installations such as, but not limited to, hangers, miscellaneous steel, channels and rods shall be fastened to building structural steel, concrete or masonry. Support from other piping systems will not be permitted. 3. Kiosk Electrical Service: Electrical service to Kiosk locations are typically two (2) 20-amp 120-volt circuits. 4. Telephone Service: a) Tenant shall be responsible for contacting the local Telephone Company and for all installation costs including service, conduit outlets, deposits and associated costs. b) Landlord will supply 1” conduit with pull string from the service location to the Premises. Any upgrades to this provision will be at Tenant’s expense. c) Tenant’s electrical contractor shall install conduit with pull cord at all concealed locations. Exposed conduits shall be installed parallel with or at right angles to column lines or beams. King of Prussia Plaza 6.2 Electric Service – Section 6 Reference Appendix: D-6 Typical Tenant Service One Line Diagram D-7 Space #1306 Tenant Electrical Service One Line Diagram D-8 Typical Joist Reinforcement Detail at Concentrated Load King of Prussia Plaza 6.3 Natural Gas – Section 7 1. Natural gas service will be available only to restaurant Tenants, at the Landlord’s discretion. The installation thereof, if approved by Landlord, shall be subject to such conditions of use as Landlord may impose. Gas service, if approved, may be used for food preparation only. Flues will not be permitted. Installation of pressure-reducing station, if required, and piping from point of service on Landlord’s roof shall be by Tenant at Tenant’s expense. Installation shall meet all AGA and PECO Energy standards. Any and all roof penetrations shall be performed by Landlord’s roofing contractor at Tenant’s expense. 2. At the landlord’s discretion, natural gas service, will be made available from either the gas main installed on the roof or to the gas main nearby underground. Distribution piping from the discharge side of the Landlord-provided gas meter, regulators, and related miscellaneous equipment required to make for a complete approved system will be the sole responsibility of the Tenant who will bear all associated installation costs and fees (including all permits and inspection fees related to said installation). Tenant shall perform gas test as required by the gas utility and have witnessed by Landlord. 3. The Tenant will be responsible for obtaining all necessary approvals prior to the installation of any piping, including approval of the utility company, Landlord’s Insurance Underwriter and Landlord’s Engineer. 4. The gas piping installation shall be installed in accordance with NFPA Standard No. 54, “National Fuel Gas Code,” and the rules and regulation of the utility company and any other local and state agency involved in the regulation of this type of installation. 5. Interior gas piping shall be black steel electric resistance welded, Schedule 40, ASTM A53. Fittings shall be malleable iron 150 psig class, ASTM A-197. 6. Exterior gas piping shall be either galvanized Schedule 40-with galvanized malleable iron 150 psig fittings or Schedule 40 with black steel pipe with high-density poly coat with welded fittings. Field applied polycoat must be applied to any bare metal. 7. Natural gas delivery pressure at the meter location will be 5 inches of water column. Tenants requiring greater pressure of unusual capacity for the operation of their food preparation equipment will be subject to all costs imposed by the Landlord to provide such special service demands, including any costs which may be imposed on the Landlord as a result of the Tenant’s requirements. 8. Provide Micro Industries (Midvale, Utah 1-801-566-3680) Model #02 pillow block pipe stands for gas piping on roof. Supports shall consist of a nylon roller situated in a PVC seat with a self-lubricating Teflon base. The pipe support is rigid PVC. 9. Automatic gas shut-offs are required. King of Prussia Plaza 7.1 Sprinkler System – Section 8 Tenant’s sprinkler installation shall conform to NFPA 13, the requirements and regulations of all governmental authorities exercising jurisdiction, Landlord’s Insurance Underwriter, and these Tenant Criteria. 1. Sprinkler contractors are required to submit working drawings to Landlord’s Insurance Underwriter and to the local agencies exercising jurisdiction for approval prior to work commencement. Contact information is included in the Project Directory. 2. Tenant shall be responsible to forward one (1) set of approved sprinkler system drawings to the Landlord. 3. Visible and audible fire alarms shall meet both Pennsylvania and Upper Merion Township Americans with Disabilities Act (ADA) requirements. 4. Tenant shall provide sprinkler protection from Tenant’s sprinkler system to Tenant’s service door alcove inside the lease line on rear service corridor. 5. Food Preparation Tenants using open cooking equipment must install self-contained fire suppression system or other approved systems. Per the Upper Merion Township Fire Marshall, combustibles are not permitted within the tenant space during construction until tenant’s sprinkler system is fully operational. 6. Tenant’s sprinkler contractor shall connect Tenant’s valve to the capped or blank flange outlet of the Landlord’s sprinkler system, according to Reference Appendix D-5. Safe access to valve must be provided to Landlord. Tenant must identify location. 7. Pressure test(s) must be accomplished in accordance with the criteria established Landlord’s Insurance Underwriters and industry standards and witnessed by Landlord’s representative. Tenant’s sprinkler contractor must immediately make repairs of any defects in the sprinkler installation. 8. Fire hoses, cabinets, fire extinguishers and other required equipment within Tenant’s Premises shall be installed in accordance with the requirements of the Landlord’s Insurance Underwriter and all local agencies exercising jurisdiction. 9. Prior to requesting a shutdown of the Landlord’s sprinkler system for connection of or modification to the Tenant’s sprinkler system, the Tenant or the Tenant’s sprinkler contractor, must obtain written approval from the Landlord’s Insurance Underwriter and present same to Landlord. 10. If required to drain down sprinkler system, Tenant’s Contractor to notify Mall Management 24 hours prior to work to coordinate with all authorities. Sprinkler system to be reactivated as required. There will be a $250.00 charge per occurrence. King of Prussia Plaza 8.1 Sprinkler System – Section 8 11. Hot Work Permit: Tenant’s contractor shall be responsible to obtain and secure a Hot Work Permit(s) from Landlord. A Hot Work Permit is required for any and all open flame welding or cutting such as but not limited to welding, soldering and brazing. 12. Tenant’s contractor shall not screw upward through the metal deck. Damaged fireproofing must be restored. Sprinkler lines may not hang from the lower chord of bar joists unless approved in advance by Landlord. 13. Tenant’s sprinkler system must be fully operational and approved before the Township will issue a Certificate of Occupancy. 14. Tenant shall comply with the following mall-wide standard sprinkler specifications. King of Prussia Plaza 8.2 Sprinkler System – Section 8 SECTION 15400 -TENANT FIRE PROTECTION SYSTEMS SECTION DESCRIPTION 15401 GENERAL REQUIREMENTS 15402 FIRE PROTECTION DESIGN CRITERIA 15403 SPRINKLER EQUIPMENT 15404 SYSTEM ACTIVATION, TESTING AND CERTIFICATION SECTION 15400 - FIRE PROTECTION SYSTEMS 15401 - GENERAL REQUIREMENTS A. GENERAL REQUIREMENTS 1. The fire protection system shall be designed, fabricated, and installed by a Licensed or NICET Fire Protection System Contractor. The engineer shall provide specifications and diagrams to allow letting of a contract for the fire protection portion of the project. The entire system design, material use and installation shall comply with FM Global engineering guidelines as a minimum. 2. Plan submissions to Landlord’s Insurance Underwriter shall be made in accordance to the contact on page 1.3 of the Project Directory: 3. The sprinkler system shall be a wet pipe system serving all areas of the retail space. Portions of the space that are unheated or exposed to freezing temperatures shall be provided with an automatic dry pipe type system complying with FM Global engineering guidelines and NFPA-13. 4. Piping shall be fastened to the structural system of the building and concealed in areas having a suspended ceiling. Install and/or upgrade seismic sway bracing on existing systems where required for earthquake zones per local codes and FM Global engineering guidelines. Seismic bracing for fire systems must be designed and installed following FM Global Data Sheet 2-8. 5. Drain piping is required at low points of piping systems. Drain down locations shall be extended to locations that are accessible. King of Prussia Plaza 8.3 Sprinkler System – Section 8 B. FIRE PROTECTION FOR EXISTING TENANT SPRINKLER SYSTEMS 1. Whenever an existing sprinkler system is being renovated, the integrity and reliability of the existing system must be maintained. Original sprinkler shop drawings shall be acquired through Mall Management. If these drawings are not available, field verification will be required. If the sprinkler contractor discovers a discrepancy from the original sprinkler shop drawings and actual field conditions, he shall note the discrepancy on his renovated shop drawings. 2. The hydraulic design criteria as a minimum shall match the hydraulic criteria originally intended for the facility. At no time shall the hydraulic criteria be less than Ordinary Hazard Group 2 occupancy as defined by NFPA-13. The latest site water flow data to be used for hydraulic calculations shall be obtained from FMGlobal Risk Consultants or Mall Management. 3. Existing pipe schedule sprinkler systems are required to be calculated at the FM Global density of 0.15 gpm per sq. ft. over the most hydraulically remote 2500 sq. ft. 4. FM Approved materials for Ordinary Hazard Group 2 occupancy must be used, including but not limited to sprinkler piping, hangers, sprinkler heads, etc. Seismic bracing may be UL Listed. 5. Sprinkler head spacing requirements for Ordinary Hazard Group 2 occupancy shall be in strict compliance with the sprinkler head listings and approval. 6. NFPA-13 and FM Global Data Sheets 2-8N latest editions shall be the minimum design requirements along with any state and local requirements. 7. A minimum of (4) sets of shop drawings along with hydraulic calculations (if applicable) shall be submitted to FM Global for approval. Hydraulic calculations shall be submitted for all tenant sprinkler system work regardless of the scope of work involved. Plans shall be submitted to the local authorities having jurisdiction for approval. Installation/renovation of sprinkler system shall not begin until all approvals have been received. 8. Four sets of material brochures shall also be submitted to FM Global for review. Brochures shall be limited to new sprinklers heads, flexible drops and valves. Plans shall indicate the type of piping being utilized with the gauge indicated. 15402 - FIRE PROTECTION DESIGN CRITERIA A. GENERAL 1. King of Prussia Plaza Sprinkler head arrangement shall be in conjunction with architectural finishes and provide allowance for partitions, columns, light fixtures, air diffusers, etc. 8.4 Sprinkler System – Section 8 2. Sprinkler Shop Drawings shall not be considered final until all requirements of FM Global, Landlord, and all Local and State Building Codes having authority have been met, and the approval of each has been tendered. 3. Minimum and maximum sprinkler head operating pressures shall be consistent with their UL Listing/FM Approval. 4. Design calculations for inside pipe should use C=100 for dry and pre-action systems, and C=120 for wet or deluge systems. 5. Minimum and maximum sprinkler spacing shall be in accordance with their UL Listing/FM Approval. 6. FM Global required minimum density for Sales/Retail/Storage spaces will be 0.15 gpm per sq. ft. over the most hydraulically remote 2500 sq. ft., using ½” or 17/32” orifice, 165 degree F. rated heads. If the local AHJ requires an NFPA-13 design density, 0.18 gpm per sq. ft. over the most hydraulically remote 2500 sq. ft. shall be used unless specific approval is given otherwise for special occupancies. The most remote area should have the dimensions parallel to the branch line of at least 1.4 times the square-root of the area per FM Global Data Sheet 2-8N. Quick-response (QR) sprinklers do not qualify for a design area reduction per FM Global Data Sheet 3-26. The density design should conform to the most stringent of either FM Global Data Sheet 3-26 or NFPA-13, Ordinary Group 2 occupancy. 7 Stockroom/storage areas over 200 sq. ft. must be protected for the maximum storage height and configuration (bin-box/gondola/shelf or rack) per FM Global Data Sheet 8-9. When storage exceeds 10 feet in height, the regional FM Global plan reviewer shall be consulted for appropriate design densities. Classify the commodities in tenant spaces as “Cartoned Expanded & Unexpanded Plastics” for sprinkler design purposes. Sprinkler head spacing shall not exceed 100 sq. ft. in storage areas unless approved for extended coverage (i.e., EC-25). 8. Big Box Stores require unique sprinkler system designs to meet the requirements of FM Global Data Sheet 8-9 and NFPA-13, Chapter 12. Contact Bill Cary with Global Risk Consultants for specific design requirements based upon the proposed display / storage configuration and roof deck height. 15403 - SPRINKLER EQUIPMENT A. GENERAL 1. B. Only sprinkler equipment bearing the FM Global Approval mark shall be installed. Provide equipment as manufactured by: Automatic Sprinkler, Tyco, Reliable, Viking Gem or equal. SPRINKLER HEADS 1. King of Prussia Plaza Sprinkler heads shall be glass bulb type of a configuration as required for each particular location. All heads on concealed piping shall be chrome plated with 8.5 Sprinkler System – Section 8 chrome plated escutcheon plates. Operating temperature shall be as required for the type of occupancy. 2. C. Sprinkler heads in janitor’s closets, mechanical rooms, electrical rooms and those mounted less than 8 feet above finished floor shall be protected with a wire cage type guard. SPRINKLER PIPING 1. Aboveground piping shall be FM Approved Schedule 10 or 40 black steel. Schedule 10 piping shall be joined with FM Approved roll-grooved fittings, not threaded or plain-end. Fittings shall be cast iron or steel approved for a minimum of 175 psi working pressure. Dry systems shall have FM Approved galvanized piping and fittings for corrosion resistance. 2. Threadable “lightwall” (XL) and “thinwall” pipe may not be utilized under any circumstances. 3. Hangers shall be FM Approved, and adaptable to various types of construction. Hangers shall be supported from building structure and structural steel headers shall be installed for supporting cross main hangers where main is not directly below structural member. Roof deck hangers are prohibited. All hangers shall comply with FM Global engineering guidelines. 4. Under no circumstances, will Landlord permit Tenant's sprinklers and other equipment to hang from the metal deck. Sprinklers and equipment must be hung from beams and bar joists. Sprinkler and equipment loads must be limited to less than 150 pounds at each connection. Sprinkler and equipment support connections should be made at the top chord of bar joist at panel points (where diagonal struts form a shape). Sprinkler and equipment ^ supports may also be connected to the bottom chord of bar joists at panel points (where diagonal struts form a V shape). Sprinkler and equipment supports should sufficiently numerous and be staggered so that sprinkler loads are evenly distributed across all structural members. If sprinkler and equipment supports are located more than 3 inches from a panel point, additional structural reinforcement may be required, requiring review by Landlord’s structural engineer. Combined sprinkler and equipment loads on any one joist (all loads of any type) exceeding 300 pounds require review by Landlord’s structural engineer. See Appendix Reference Detail D-8. 5. D. Wall plates shall be provided on exposed piping where pipe passes through walls, partitions, ceilings, etc. and secured by setscrews. VALVES 1. At each connection to the Landlord’s sprinkler system, the Tenant will provide an approved shut-off valve with supervisory switch. 2. All valves and fittings shall be FM Approved and rated 175 lb. minimum. King of Prussia Plaza 8.6 Sprinkler System – Section 8 3. The switch shall be connected to the Landlord’s addressable alarm system by the Landlord’s Alarm Contractor at the Tenant’s expense. 15404 - SYSTEM ACTIVATION, TESTING AND CERTIFICATION 1. Sprinkler contractor shall install and activate the entire sprinkler system prior to the bringing combustibles into the tenant space, and no later than Certificate of Occupancy. 2. Existing sprinkler systems shall be shut down and “red” tagged in strict accordance with Landlord’s requirements. Under no circumstances should a sprinkler system be left out of operation overnight without an appropriate “fire watch” in place. 3. All fire protection systems shall be tested as required by local authorities and FM Global before any systems are concealed. 4. Contractor shall conduct hydrostatic tests in compliance with FM Global Data Sheet 2-8N and NFPA-13 (two hours at 200 psi or 50 psi over normal system pressure minimum). Piping subject to freezing during test period shall be tested with compressed air. 5. Certificates of approval of installation shall be obtained from the Authority having Jurisdiction and forwarded to Landlord. 6. After tests are conducted and any repairs completed; completely flush the piping systems with water until discharge shows no discoloration. 7. Following sprinkler testing and approval, Landlord will lock the sprinkler valve in the open position. Tenant will be charged a lock expense of $20. King of Prussia Plaza 8.7 Sprinkler System – Section 8 Tenant Display Fixtures, Rack/Shelving/Storage Unit Requirements • Tenant display fixtures in the retail space and rack/shelving/storage units in the stockroom must be designed to provide adequate clearance for the automatic (fire) sprinkler system. No displays or storage should exceed 12 ft. and ceilings must be installed to provide at least 18 in. of clearance between the top of storage and sprinkler deflectors. • Tenant displays or storage higher than 12 ft. are classified as “high piled storage”, which requires high hazard automatic (fire) sprinkler protection designed per FM Global Loss Prevention Data Sheet 8-9 and NFPA-13-Chapter 12 for the storage of “Group A Plastic” commodities. High piled storage also requires at least 36 in. of clearance between the top of storage and sprinkler deflectors. • Tenant mobile (compact) storage systems should be constructed of wire mesh shelves. However, if constructed with solid shelves (steel, wood), the units must be equipped with 3 in. spacers to provide flue spaces at 4 ft. to 5 ft. maximum intervals. • Tenants Architect/General Contractor must provide the following information to the Sprinkler Contractor regarding stock/storage area: Type of storage units (Details of storage unit) Type of shelving (wire mesh, solid, steel, wood, etc.) Type of commodities (plastics, aerosol’s, clothing, etc.) Elevation of highest shelf Tenant shall be solely responsible for the display, installation and use of any display or storage system within the Premises in compliance with applicable fire codes and the requirements of any insurance rating bureaus. If anything done, omitted to be done or suffered to be done by Tenant in, upon or about the Premises in regard to such display or storage systems shall result in a fire code violation and Tenant fails to take corrective action and/or pay the associated fine, regardless of whether assessed against Tenant or Landlord, within the prescribed time period, then Tenant shall be liable for all costs and expenses resulting from such violation and Landlord shall have the right to correct any such condition at Tenant’s expense. Reference Appendix: D-5 Typical Sprinkler System Details D-8 Typical Joist Reinforcing Detail at Concentrated Load King of Prussia Plaza 8.8 Appendices: Forms King of Prussia Plaza Appendices: Forms King of Prussia Plaza Appendices: Forms King of Prussia Plaza Appendices: Forms King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza Appendices: Drawings King of Prussia Plaza