Suggested Ampacities Assigning a current rating to a wire is really a problem of wire transfer. The watts generated at the conductor must be dissipated through the insulation to the ambient without overheating the conductor or insulation. While current ratings for power cables have been officially assigned by such groups as the Insulated Cable Engineers Association and the National Electric Code, no such ratings have been officially developed for appliance wires or apparatus cables. Since appliance and apparatus designs vary widely, any effort to standardize actual current ratings is just about impossible. SUGGESTED AMPACITIES (All Types of Single Conductor Insulation) AWG 80C 90C 30 28 26 24 22 20 18 16 14 12 10 2 3 4 6 8 10 15 18 20 25 35 3 4 5 7 9 12 16 20 25 30 40 30 40 50 60 70 80 90 100 125 150 200 1.00 .88 .75 .58 .35 - 1.00 .90 .80 .67 .52 .30 - 105C 125C 150C 200C 250C* 3 5 6 8 12 15 22 29 40 50 70 4 6 7 10 13 17 24 32 45 55 75 4 6 8 11 14 19 29 37 39 54 73 1.00 .96 .91 .87 .82 .76 .71 .65 .50 - 1.00 .97 .93 .91 .87 .84 .80 .77 .66 .54 - 1.00 .98 .95 .95 .93 .90 .87 .85 .72 .65 .49 AMPERES PER CONDUCTOR 3 4 5 7 10 13 18 24 33 45 58 3 5 6 8 11 14 20 26 40 50 70 CORRECTION FACTORS FOR VARIOUS AIR TEMPERATURES 1.00 .92 .82 .73 .61 .46 .30 - 1.00 .95 .89 .83 .76 .69 .61 .51 - Current ratings for different conductor materials may be calculated by multiplying the appropriate copper conductor ratings by the following factors: *NICKEL PLATED COPPER: 0.87 NICKEL: 0.43 IEWC • 5001 S. Towne Drive, New Berlin, WI 53151 | Toll-Free: 800-344-2323 | Web: www.iewc.com IEWC assumes no responsibility for the use of, or reliance on the information provided herein and disclaims all liability for any and all damages arising out of the use of, or reliance on, this information. SUGGESTED CURRENT CARRYING CAPACITY TABLE (Base Temperature at 40C) 24 22 20 18 16 14 12 10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 150C Tinned Copper 200C Tinned Copper NPC 2% - 10% 250C NPC 2% - 10% 250C “A” Nickel 250C NPI 450C NPC - 27% 450C “A” Nickel 6.6 9 13 17 22 34 43 55 76 96 120 143 160 186 215 251 288 332 365 414 461 495 563 7.2 9.6 14 18 24 36 45 60 83 110 125 152 171 197 229 260 297 346 385 436 486 522 593 8 10.8 15 20 26 39 54 73 93 117 148 166 191 215 244 273 308 361 398 452 503 540 613 4 5 7 9.4 12 18 25 34 43 55 69 78 90 101 114 128 144 169 187 212 236 254 288 3.3 4.4 6 8 11 16 22 30 39 49 62 69 80 90 102 114 129 151 167 190 211 226 257 9 12 18 23 30 45 56 75 104 138 162 182 210 236 268 300 338 397 - 4.3 5.6 8 11 14 21 26 35 49 65 76 85 99 110 126 141 159 186 - NOTE: For allowable ampacities for fixture wire, please see the National Electrical Code Handbook. For ambient temperatures other than 40C (104F), multiply the ampacities shown above by the appropriate factor shown below. WIRE TEMPERATURE RATING Ambient Temperature (C) 200C 250C 450C Ambient Temperature (F) 41-50 51-60 61-70 71-80 81-90 91-100 101-120 121-140 141-160 161-180 181-200 201-225 226-250 251-275 176-300 301-325 326-350 351-375 376-400 0.97 0.94 0.90 0.87 0.83 0.72 0.71 0.61 0.50 0.35 - 0.98 0.95 0.93 0.90 0.87 0.85 0.79 0.71 0.65 0.58 0.49 0.35 - 0.99 0.99 0.96 0.95 0.93 0.92 0.89 0.86 0.84 0.81 0.78 0.74 0.69 0.65 0.60 0.55 0.49 0.42 0.34 106-122 124-140 142-158 160-176 177-194 195-212 213-248 249-284 285-320 321-356 357-392 393-437 439-482 483-527 528-572 573-617 618-662 663-707 708-752 NOTE: The use of this table for establishing ampacity ratings is an inexact procedure. This table should only be used as a starting point when establihsing ratings for any given situations. It is recommended that design engineers desiring accurate ampacity data study the National Electrical Code Handbook - Article 310-13-310-84. IEWC • 5001 S. Towne Drive, New Berlin, WI 53151 | Toll-Free: 800-344-2323 | Web: www.iewc.com IEWC assumes no responsibility for the use of, or reliance on the information provided herein and disclaims all liability for any and all damages arising out of the use of, or reliance on, this information. SUGGESTED AMPACITIES (All Types of Insulations) COPPER ALUMINUM Not More Than 3 Conductors in Raceway or Cable Not More Than 3 Conductors in Raceway or Cable Single Conductor in Free Air CONDUCTOR TEMPERATURE RATING AWG or MCM 85-90C Temp (185F) 110C Temp (230F) 85-90C Temp (185F) CONDUCTOR TEMPERATURE RATINGS 110C Temp (230F) 125C Temp (257F) 200C Temp (392F) 85-90C Temp (185F) 110C Temp (230F) AMPERES PER CONDUCTOR (100% Load Factor) 14 12 10 8 6 4 2 1 0 00 000 0000 250 300 350 400 500 600 700 750 800 900 1000 25 30 40 55 70 95 125 145 165 190 215 250 275 310 340 365 415 460 500 515 535 565 590 30 35 45 60 80 105 135 160 190 215 245 275 315 345 390 420 470 525 560 580 600 680 30 40 55 75 100 135 185 215 250 290 335 390 440 485 550 595 675 750 825 855 885 950 1020 Single Conductor in Free Air 40 50 65 85 120 160 210 245 285 330 385 445 495 555 610 665 765 855 940 980 1020 1165 85-90C Temp (185F) 110C Temp (230F) 125C Temp (257F) 200C Temp (392F) AMPERES PER CONDUCTOR (100% Load Factor) 40 50 70 90 125 170 225 265 305 355 410 475 530 590 655 710 815 910 1005 1045 1085 1240 45 55 75 100 135 180 240 280 325 370 430 510 - 25 30 40 55 75 100 110 130 145 170 195 220 250 270 295 335 370 405 420 430 465 485 25 35 45 60 80 105 125 150 170 195 215 250 275 310 335 380 425 455 470 485 560 30 45 55 80 105 140 165 190 220 255 300 330 375 415 450 515 585 645 670 695 750 800 40 50 65 95 125 165 190 220 255 300 345 385 435 475 520 595 675 745 775 805 930 40 55 70 100 135 175 205 240 275 320 370 415 460 510 555 635 720 795 825 855 990 45 60 80 105 140 185 220 255 290 335 400 - 0.90 0.80 0.67 0.52 0.30 - 0.94 0.87 0.79 0.71 0.61 0.50 - 0.95 0.89 0.83 0.76 0.69 0.61 0.51 - 0.91 0.87 0.84 0.80 0.77 0.69 0.59 CORRECTION FACTORS FOR VARIOUS AMBIENT AIR TEMPERATURES 40C 50C 60C 70C 80C 90C 100C 120C 140C 0.90 0.80 0.67 0.52 0.30 - 0.94 0.87 0.79 0.71 0.61 0.50 - 0.90 0.80 0.67 0.52 0.30 - 0.94 0.87 0.79 0.71 0.61 0.50 - 0.95 0.89 0.83 0.76 0.69 0.61 0.51 - 0.91 0.87 0.84 0.80 0.77 0.69 - 0.90 0.80 0.67 0.52 0.30 0.59 0.94 0.87 0.79 0.71 0.61 0.50 - *Based on an ambient temperature of 30C (86F) IEWC • 5001 S. Towne Drive, New Berlin, WI 53151 | Toll-Free: 800-344-2323 | Web: www.iewc.com IEWC assumes no responsibility for the use of, or reliance on the information provided herein and disclaims all liability for any and all damages arising out of the use of, or reliance on, this information.