_ Outside Branch Circuits and Feeders i/)t2 How to apply the NEC rules for Art. 225 By Mike Holt, NEC Consultant utdoor conductors run ning to buildings aren’t necessarily service con ductors. They may be feeders or branch circuit conductors originating in another building. They may provide power for area lighting, outdoor equip ment, or a separate structure. To determine if outdoor conductors are service conductors, identify where the electric utility service point is, and review the Art. 100 definitions for feeders, branch circuits, and service conductors. If they’re service conductors, use Art. 230. Other wise, use Art. 225, which covers outside feeders and branch circuits (Fig. 1). Minimum size. You can use conductors 10 AWG or larger for overhead spans up to 50 ft. For spans more than 50 ft, use 8AWG or larger (unless supported by a messenger wire) [225.6(A)(1)], as shown in Fig. 2. Unless supported by messenger wire, overhead conductors for festoon lighting must be at least 12AWG. Spans longer than 40 ft must be supported by a messenger wire with strain insulators [225.6(B)]. Support and attachment. Do con ductors pass over a roof? If so, use sub stantial structures to securely support them. If practicable, make the supports independent of the building [225.19, and 230.29]. Don’t use trees or other vegetation to support overhead conduc tors [225.26]. The point of attachment for overhead conductors must be at least 10 ft above finished grade. Locate it so the whole span maintains the minimum conductor clear ance required by 225.18 [225.16(A)]. Attach open conductors to fittings ,c rn... M.,..k.... OflIO ..,.,..k Outside Branch Circuits and Feeders Scope 225.1 - Overhead Branch Circuit or Feeder Conductors iL Copynght 2011 w.M,keHt.coni ErLr Underground Branch Cwcuit or Feeder Fig. 1. Article 225 contains the installation requirements for outside branch circuits and feed run on or between buildings, structures, or poles. Outside Branch Circuits and Feeders Conductor Size Overhead Spans 225. 6(A)(1) - Minimum of 8 AWG or larger for spans over 50 ft. (no messenger wire) Minimum of 10 AWG or larger for spans up to 50 ft. (no messenger wire) Fig. 2. For spans over 50 ft, use 8 AWG or larger (unless supported by a messenger wire). identified for use with conductors, or to noncombustible, nonabsorbent insulators securely attached to the structure [225.16(B) and 230.27]. This point of attachment must meet the minimum clearances specified in 225.18 and 225.19— and in no case be less than 10 ft above finished grade. If you use a mast for overhead conductor support, it must have adequate mechanical strength, braces, or guy wires to withstand the strain caused by the conductors. Only feeder or branch circuit conductors can be attached to the feeder and/or branch circuit mast [225.17], as shown in Fig. 3 on page 18. Clearances from grade. Overhead conductor spans must maintain these vertical clearances from grade [225.18]: 10 ft above finished grade, sidewalks, platforms, or projec tions from which they might be accessible to pedestrians for 120V, 120/208V, 120/240V, or 240V circuits [225.18(1)]. • 12 ft above residential property and driveways, and those commercial areas not subject to truck traffic for 120V, 120/20 8V, 120/240V, 240V, 277V, 277/480V, or 480V circuits [225.18(2)). • 18 ft over public streets, alleys, roads, parking areas subject to truck traffic, driveways on other than residential property; and other areas traversed by vehicles (such as those used for cultivation, grazing, forestry, and orchards) [225.18(4)]. • 24½ ft over track rails of railroads [225.18(5)]. For overhead conductors above poois, outdoor spas, out door hot tubs, diving structures, observation stands, towers, or platforms, follow the clearance requirements in 680.8. Clearances from buildings. Overhead conductors must maintain a vertical clearance of 8 ft above the surface of a roof. Maintain that for a distance of at least 3 ft from the edge of the roof [225.19(A)], except: • If the roof is subject to pedestrian or vehicular traffic, follow 225.18 [225.19(A) Ex 1]. ‘vVhen the slope of the roof meets or exceeds 4 in. of verti cal rise for every 12 in. of horizontal run, you can reduce the overhead conductor clearances above the roof to 3 ft instead of 8 ft [225.19(A) Ex2]. • When no more than 6 ft of conductor of 120/208V or 120/240V circuits passes over no more than 4 ft of roof, you can reduce the clearance above only the roof overhang to 18 in [225.19(A) Ex 3], as shown in Fig. 4 on page 18. • If the point of attachment is on the side of the building below the roof, the 3 ft clearance from the roof edge doesn’t apply [225.19(A) Ex4]. Overhead conductors must maintain a clearance of at least 3 ft from: • Signs, chimneys, radio and television antennas, tanks, arid other nonbuilding or nonbridge structures [225.19(B)]. • Windows that open, doors, porches, balconies, ladders, stairs, fire escapes, or similar locations [225.19(D)(1)]. Also, overhead conductors must: Maintain a vertical clearance of at least 10 ft above plat forms, projections, or surfaces from which they might be reached. Maintain this vertical clearance for 3 ft measured horizontally from the platforms, projections, or surfaces from which they might be reached [225.19(D) (2)]. Not be installed under an opening through which materials might pass [225.19(D) (3)]. Not be installed where they will obstruct an entrance to building openings [225.19(D)(3)]. Raceways. Raceways on exterior surfaces of structures must be arranged to drain and be suitable for use in wet locations [225.22]. Underground raceways (used or unused) entering structures must be sealed in accordance with 300.5(G) to pre vent moisture from contacting energized live parts [225.2 71. Number of supplies. If more than one building or other structure is on the same property, each building/structure must be served by no more than one feeder or single or multiw ire branch circuit [225.30]. However, there are five exceptions to this. You can have additional supplies for: 1. Special conditions [225.30(A)]. These are: Fire pumps. • Emergency systems. • Legally required standby systems. • Optional standby systems. Parallel power production systems. youtube.com/southwirechannel Circle 40 on Reader Service Card or visit freeproductinto.net’ecm II’I Systems designed for connection to multiple sources of supply for the purpose of enhanced reliability. 2. Special occupancies. Multipleoccupancy buildings where there’s no available space for supply equipment accessible to all occupants, or a build ing/structure so large that two or more supplies are necessary but only with special permission [225.30(B)]. 3. Capacity requirements. ‘\‘Vhere the capacity requirements exceed 2,ODOA [225.30(C)]. 4. Different characterjstics. Different voltages, frequencies, or uses, such as control of outside lighting from multiple locations [225.30(D)]. 5. Documented switching procedures. Additional supplies are permitted where documented safe switching procedures are established and maintained for dis connection [225.30(E)]. Disconnects. A disconnecting means is required for all conductors that enter a building or structure [225.31]. Install it at a readily accessible location (either outside or inside) nearest the point of en trance of the conductors [225.32]. There are four exceptions to this rule: 1) If documented safe switching procedures are established, maintained, and monitored by qualified persons, the disconnecting means can be located else where on the premises [225.32 Ex 1]. 2) The building or structure qualifies under the provisions of Art. 685 [225.32 Ex2]. 3) For towers or poles used as light ing standards, the disconnecting means is permitted to be located elsewhere on the premises [225.32 Ex 3]. 4) For a pole or similar structure used only for the support of signs installed in accordance with Art. 600, the disconnect ing means is permitted to be located else where on the premises [225.32 Ex 4]. The building/structure disconnect ing means can consist of no more than six switches or six circuit breakers in a single enclosure or separate enclosures for each supply grouped in one location as permitted by 225.30 [225.33]. The building/structure disconnecting means must be grouped in one location, and marked to indicate the loads they serve as required byl 10.22 [225.34(A)]. Mast as Support for Power Conductors 225.17 VIOLA11ON Only branch circuit or feeder conductors can be attached to a power mast. Fig. 3. Only feeder or branch circuit conductors can be attached to the feeder and/or bran circuit mast. Clearance Above Roof 225.19(A) Ex 3 Maximum 6 ft of Conductors Over Roof Maximum 4 ft Over Roof Copyiight 2011. wwMkeHoIt,cvm Fig. 4. For 120V/208V or l2OV/240V circuits, conductor clearance can be 18 in., if no more th 6 ft of conductor pass over no more than 4 ft of roof. To minimize the possibility of ac cidental interruption of critical power systems, the disconnecting means for a fire pump or for standby power must be located remotely away from the normal power disconnect [225.34(B)]. In a multiple-occupancy building, each occupant must have access to the disconnecting means for their occupancy [225.35]. But if building management provides electrical maintenance und continuous supervision, manageme can make access available only to buil ing management [225.35 Ex]. The building/structure disconnecti means must be comprised of a circi breaker, molded case switch, general-u switch, or snap switch “suitable for use service equipment (225.36].” If more than one supply feeds •—büiBASICS building/structure, a permanent plaque or directory must be installed at each feeder disconnect location denoting all other feeders or branch circuits supply ing that structure and the area served by each [225.37]. The disconnecting means can consist of a manual switch or a power-operated switch or circuit breaker capable of being operated manually [225.38(A)].You can use a shunt-trip pushbutton to open a power-operated circuit breaker. In this case, the breaker (not the pushbutton) is the disconnecting means. The discon necting means for a building supplied by a feeder must plainly indicate whether it’s in the open or closed position [225.38(D)]. Rating. A single disconnecting means for a building/structure must have -an ampere rating at least equal to the cal culated load as determined by Art. 220. If the disconnecting means consists of ‘i more than one switch or circuit breaker, the combined ratings must be no less than the calculated load as determined per Art. 220 [225.39]. Minimum ratings for disconnecting means: • For installations consisting of a single branch circuit, the disconnecting means must have a rating of at least 1 5A [225.39(A)]. • For installations consisting of two 2-wire branch circuits, the feeder discon necting means must have a rating of at least 30A [225.39(B)]. • For a one-family dweffing, the feeder disconnecting means must have a rating of at least bOA, 3-wire [225.39(C)]. • For all other installations, the feeder or branch circuit disconnecting means must have a rating of at least 60A [225.39(D)]. Three’s a charm. It’s easyto overlook a detail in Art. 225. To avoid that, check your design to ensure you’re meetin these three goals: 1. Maintain clearances. Outdoc conductors present dangers from po sible contact that indoor conductoi don’t. 2. Support conductors. Outdoor cor ductors are subject to stresses that indo conductors aren’t. 3. Follow all rulesfor the installation disconnects. This is essential in order i provide a convenient and safe means I disconnect sources of electric power i case of fire or electrocution hazards. Methodically walk through your di sign, looking at all of the clearances fi conformance to Art. 225. Then repu with support requirements and discos EC&I nect rules. Holt i5 the owner ofMike HoltEnterpris6 Inc., Leesburg, F/a. He can be reached www. mikeholt. corn. L\J ccD - -:c 7- ,.i_- - , - \ s.-., ‘—“—-— — \ / -‘_‘ .. — _____:.—-- — Cable Management, Power Distribution and Airflow Solutions - k www.snaKetray.com Designing and maintaining state of the art facilities is difficult. There are obstacles every step of the way. Companies rely on Snake Tray to offer cost effective products. You can count on Snake Tray’s products, team of engineers and manufacturing capabilities to deliver the best solutions. Lean on us for your next project! Snake Tray® tm Snake Canyon Hand bendable cable management Cable tray that integrates with the access floor to manage data/power cables T: 800.308.6788 www.snaketray.com Made in the USA Mega Snake® Snake Box® Pre-configured high capacity Flexible power and data overhead cable tray distribution enclosures Snake TrayS prodocts are covered by one or more of the fokowin pateots: #6637704, #6637155, #o453704, #9460812, #84499r2, #6361000, #9347493. #6019323, #6347493, 5#4&3812,#5953870,#5639702,#6926239,#7i68212.#7659019. OtherPatents Pendn. Circle 42 on Reader Service Card or visit freeproductinfo.net/ecm Snake Air® solutions