Certificazione sistema di Qualità TECHNICAL REPORT CSQ ISO9001 CSQ n° 9101.TESA POWER TRANSFORMER pag. 1/15 Ability to Withstand Dynamic Effects of Short Circuit Comparative Statement DATA: 28/03/10 ISSUED BY APPROVED BY Page 1 of 15 Certificazione sistema di Qualità TECHNICAL REPORT CSQ ISO9001 CSQ n° 9101.TESA POWER TRANSFORMER pag. 2/15 Ability to Withstand Dynamic Effects of Short Circuit Comparative Statement The IEC 60076-5 standard gives the comparison criteria to verify the applicability of a short-circuit withstand test performed on a transforer to a similar transformer. The technical feature to be taken into consideration are prescribed in the Annex B “Guidance for the identification of a similar transformer” and showed in Table 1 below. Tesar has positively tested a Cast-Resin Transformer 2500 kVA at CESI Laboratory (test certificate n. A7030507 dtd 3rd Ddecember 2007): This test certificate is applicable to the transformers having characteristics according to the content of Table 1 and Table 2 Table 1 Critical features as per IEC 60076.5 same type of operation: same conceptual design: same arrangement of main windings and geometrical sequence same type of winding conductors same type of main windings absorbed power for at short circuit between 30% and 130% of that of the reference unit axial forces and relative winding stresses at short circuit not exceeding 110% of those in the reference unit same manufacturing process same clamping and supporting arrangement Tested Transformer 2500 kVA distribution type cast resin, core type with concentric and circular windings HV : cast LV: pre-preg Geometrical sequence : HV outside , LV inside Al layer for LV and HV coils from 12.038,52 up to 52166,93 p.u. as per design HV : cast LV : pre-preg Correlated to the short circuit current Similar Transformers distribution type cast resin, core type with concentric and circular windings Same as the tested transformer Same as the tested transformer layer for LV and HV coils ≤ 52.166,93 p.u. Transformers in Table 2 have forces and stresses within the limit required Same Same arrangement , correlated to the short circuit current Table 2 2 Certificazione sistema di Qualità TECHNICAL REPORT CSQ ISO9001 CSQ n° 9101.TESA POWER TRANSFORMER Tested transformer Rated Power Impedance Absorbed power at S.C. Range 30% Range 130% [kVA] [%] [pu] [pu] [pu] 2500 6,23 40.128,41 12.038,52 52.166,93 Rated Impeda nce [%] 4 4 6 6 6 6 6 6 6 6 6 Absorbed Impedance Impedance power at min max S.C. [pu] [pu] [pu] 12.500,00 0,96 4,15 15.750,00 1,21 5,23 13.333,33 1,53 6,65 16.666,67 1,92 8,31 20.833,33 2,40 10,38 25.000,00 2,88 12,46 26.666,67 3,07 13,29 33.333,33 3,83 16,61 41.666,67 4,79 20,77 45.000,00 5.17 22,43 50.000,00 5,75 24,92 pag. 3/15 Similar transformer Rated Power [kVA] 500 630 800 1000 1250 1500 1600 2000 2500 2700 3000 3 4 5 6 7 8 9 10 11 12 13 14 15