IM-2000 - ASCO Power Technologies

advertisement
FTA2000
HIGH VOLTAGE
FIRE PUMP CONTROLLER
STANDARD DRAWING PACKAGE
NOTE: The drawings included herein are for standard controllers.
Actual "as built" drawings may differ from those seen here.
Technologies
ASCOPower
Product Description
High Voltage Fire Pump Controllers
2300-7200 Volt
Description—Firetrol® FTA2000 combined automatic
and manual class E2 high voltage controllers are intended for starting of squirrel cage motors driving listed
fire pumps. Maximum ratings are as follows:
Max. HP
1500
2000
2500
3500
3-Phase Voltage
2200 - 2500
3200 - 3500
4000 - 5000
5000 - 7200
Approvals—Firetrol fire pump controllers are listed
by Underwriters' Laboratories, Inc., in accordance with
UL218, Standard for Fire Pump Controllers, CSA,
Standard for Industrial Control Equipment, and approved by Factory Mutual. They are built to meet or
exceed the requirements of the approving authorities
as well as NEMA and the latest editions of NFPA 20,
Installation of Centrifugal Fire Pumps, and NFPA 70,
National Electrical Code.
Standard Features—The following are included as
standard with each controller:
n Isolating Switch - NEMA Rating, 7200 Volts, 400
Amps with external operating handle with electrical and mechanical interlocks to prevent opening
of the high voltage compartment door with the isolating switch or the main contactor closed. Interlocks prevent opening the isolating switch with the
main contactor closed.
n Vacuum Contactor - NEMA Rating, 7200 Volts,
400 Amps
• FTA2000
n Emergency Manual Run Mechanism to mechanically close motor contactor contacts in an emergency condition
n Built-in Start and Stop push-buttons to bypass
automatic start circuits
n Door mounted display/interface panel featuring a
40 Character Vacuum Fluorescent Display, Membrane Type User Control Push-buttons and easy
to read LED Indicators
n Normal-Off-Test Selector Switch - Internally
mounted for functional test of control system only,
requires that isolating switch be open and a separate 120 volt AC power source be supplied.
n POWER ON LED
n PUMP RUN LED
n PHASE FAILURE LED
n PHASE REVERSAL LED
n LOW PRESSURE LED
n DELUGE OPEN LED
n INTERLOCK ON LED
n Minimum Run Timer / Off Delay Timer
n Daylight Savings Time Option
n Weekly Test Timer
n Elapsed Time Meter
n Digital Pressure Display
n 1.44M Floppy Disk Drive
n Data Log
n Event Log (3000 Events)
n True RMS Metering with simultaneous 3 phase
display of amps and volts
n Disk Error message
n Disk Near Full message
n Pressure Error message
n Motor Over 320% message
n Local Start message
n Remote Start message
n Emergency Start message
n Fail To Start message
n Undervoltage message
n Overvoltage message
n Low Suction Pressure message
n High Speed Open Serial Communications Port
n NEMA Type 2 enclosure