fluorescent dimming systems |selection guide

advertisement
|
fluorescent dimming systems selection guide
Lutron
®
| fluorescent dimming systems
Lutron World Headquarters,
Coopersburg, Pennsylvania
Innovation and quality from the world leader in lighting controls.
Lutron invented the world's first electronic
dimming ballast over 30 years ago. From that
point forward, Lutron has delivered value through
a wide range of fluorescent dimming options.
Lutron offers an extensive selection of ballasts
and controls, providing complete fluorescent
dimming systems to our customers.
NEW EcoSystem™ T5 Digital Ballast
Lutron’s first principle:
Taking care of you, our customer.
Worldwide sales
and service
Commitment to innovation
For over 40 years, Lutron has been dedicated to providing
innovative products, services and technologies. We help you
design, specify, and deliver the best performance, quality,
and value to your customers.
The Lutron Team is here to
support you wherever and
whenever you need us.
Technical Support:
24 Hours/7 Days
1.800.523.9466
World-class quality
Lutron quality is fueled by a relentless pursuit of the highest
standards. Constant improvement includes an integrated
quality system, strict engineering guidelines, and world-class
quality and manufacturing processes.
Customer Service:
8am-8pm ET
1.888.LUTRON1
Comprehensive lighting control solutions
Lutron is your comprehensive resource for lighting control
solutions for any commercial or institutional application.
Internet Support:
www.lutron.com
Lighting Control Institute:
1.610.282.6280
Field Service:
1.800.523.9466
How to use this selection guide:
The Lutron Fluorescent Dimming Systems Selection Guide helps you:
•
•
•
Determine the dimming range required for your application
Choose the appropriate Lutron dimming ballast
Choose your Lutron fluorescent control
In other sections of the Lighting Controls for Commercial
Applications binder you will find information on:
•
•
•
•
Architectural dimming systems
Low-voltage switching systems
Architectural dimming ballasts
Theatrical dimming capabilities
•
•
•
•
Integrated lighting automation systems
Motorized window treatments
Floor plan based control software
Factory service plans
|
Lutron 01
Lutron
®
| table of contents
Why dim fluorescent?
03
Lutron quality
04
Ballast control types
06
Multi-input digital control
07
Measured light vs. perceived light
08
Dimming applications
09
Benefits of 1% dimming
10
Hi-lume® 1% 3-wire dimming ballasts
12
Compact SE™ 5% 3-wire dimming ballasts
14
Tu-Wire® 5% 2-wire dimming ballasts
16
Eco-10™ 10% 3-wire dimming ballasts
18
TVE™ 10% 0-10V dimming ballasts
20
EcoSystem™ 10% multi-input digital dimming ballasts
22
Select your dimming ballasts
24
Ballast case dimensions
32
Fluorescent dimming controls
34
EcoSystem components
36
Select your fluorescent dimming controls
38
Please see the Lutron Fluorescent Dimming
Systems Technical Guide (P/N 366-606)
for details on dimming ballast installation,
wiring, and other important information.
|
02 Lutron
Lutron
®
| why dim fluorescent?
The benefits of dimming
Create enticing ambiance
Dimming creates a rich visual experience
and adds flexibility to any room, providing
the right lighting environment for a variety
of activities.
Give employees greater
personal control
Allowing employees to set preferred light levels
for specific tasks results in greater employee
comfort and improved performance.
Save electricity, maintain lamp life,
and save the environment
Dimming saves electricity and reduces
the demand on HVAC systems. Dimming
fluorescent lighting instead of repeated
switching helps to maintain lamp life.
Combine lighting control strategies
to enhance building performance
Using occupancy sensors, daylight sensors
and time clocks with fluorescent dimming can
help manage the lighting in an entire building
and further reduce electric demand.
Dimming fluorescents saves energy
Fluorescent lighting uses much less power
than incandescent lighting. In a typical
installation, a 32 watt compact fluorescent
lamp provides approximately the same light
output as a 100 watt incandescent lamp.
As both sources are dimmed, fluorescent
lamps continue to be a more energy
efficient light source.
100W
Power consumed by incandescent source
Power
80
Over 60 watts of power
is saved per fixture by using
fluorescent lamps
60
40
Power consumed by fluorescent source
20
0
0
20
40
60
80
100%
Measured Light
|
Lutron 03
Lutron
®
| quality
Superior components
Lutron ballasts are manufactured to the highest
level of quality, using carefully selected components.
Maximum ballast lifetime is achieved by using only
long-life components with significant performance
history. In many cases, Lutron works with
component suppliers to design custom parts
in order to improve overall ballast quality.
Thermal Foldback
Lutron’s patented Thermal Foldback technology
is included in high-power ballasts, and actively
monitors the ballast temperature. Power delivery
to the lamps is automatically reduced, or “folded
back,” to regulate ballast temperature, with minimal
impact on light output. Thermal Foldback is
designed to activate only if the ballast calibration
point exceeds its rating. This maintains the ballast
|
04 Lutron
Additionally, Lutron uses only metal ballast
enclosures, allowing for optimal heat transfer
to the lighting fixture.
temperature to within 5ºC of its rating, preventing
premature ballast failure from overheating. In a
properly designed application, Thermal Foldback
will not engage.
Refer to Fluorescent Dimming Systems Technical
Guide P/N 366-606 for information about proper
installation and the calibration point.
100% Test
Lutron tests the performance of every ballast
prior to shipment. This important step eliminates
ballasts that do not meet specifications.
Failure Rate
100% Burn-in
Lutron “burns in” every ballast prior to shipment.
Defects due to faulty components are screened
out in this process, resulting in a dramatic
reduction of early failures in the field.
Extending ballast lifetime
All electronic ballasts use components with a finite
lifetime. A major factor for ballast lifetime is operating
temperature. Lutron dimming ballasts are designed
to maximize ballast lifetime.
You have an opportunity to extend the lifetime
of the ballast even further by designing or
choosing fixtures that operate the ballast at a
lower temperature. For every 10ºC reduction in
ballast case temperature, the ballast lifetime
will be doubled.
Customer receives
Lutron ballast
Running ballasts 10˚C Cooler
Useful life
Low
failure rate
DOUBLES useful life
Time
Lutron test
and burn-in
Dimming by Lutron® OEM Program
Lutron offers on-site factory training to OEM fixture
manufacturers through the Dimming by Lutron OEM
Program. Additionally, the program allows OEM
fixture manufacturers to work together with Lutron
to grow sales, strengthen customer loyalty and
satisfaction, and differentiate products. Doing
business with Lutron has never been easier.
For more information on the Dimming by
Lutron OEM Program, please email Lutron at
OEMadmin@lutron.com.
|
Lutron 05
Lutron
®
| ballast control types
In addition to offering ballasts with different low-end
dimming levels, Lutron offers dimming ballasts with
a variety of industry-standard control options.
Hot
Dimmed Hot
Neutral
Dimmed Hot
Neutral
Hot
Neutral
Control (+)
Control (–)
Hot
Neutral
Control
Control
|
06 Lutron
3-wire
3-wire control is a line-voltage phase-control dimming method.
Along with Hot and Neutral, the dimming signal is communicated
via a third wire called Dimmed Hot. All three wires are rated Class 1
and can be run within the same conduit. 3-wire control is stable over
long wire runs, allows for maximum circuit loading, and is very easy
to wire.
2-wire
2-wire control is a line-voltage phase-control dimming method.
The ballast receives the dimming signal through the Dimmed Hot
wire. Intended for small-scale retrofit applications, the 2-wire control
method is often the easiest way to implement dimming in existing
fluorescent fixtures.
0-10V
0-10V control is a low-voltage DC dimming method. Power
wires are rated Class 1 and control wires are rated Class 2.
This separation allows multiple circuits to use the same dimming
signal without additional power equipment. 0-10V control is not
recommended for dimming below 10%, as fixture-to-fixture
tracking can be significantly affected by control wire length.
Multi-input digital
Multi-input digital control is a wired communication technology that
facilitates individual ballast addressing, connection of multiple control
devices, and control of ballasts individually or in groups. The digital
wires are polarity insensitive and may be wired in any topology. Digital
communication wires may be run with the mains voltage (Class 1) or
isolated from mains (Class 2). Multi-input digital control allows for the
quick connection of devices and re-configurability.
Lutron
®
| multi-input digital control
A revolution in light control for
open offices and classrooms
A breakthrough in fluorescent lighting control,
multi-input digital control solutions start with a
simple but essential building block – a digital
multi-input ballast – which replaces a non-dim
ballast in a fixture. This single fixture is now the
centerpiece of an efficient lighting ecosystem, in
which a variety of sensors and wallstations are
connected directly to the ballast. Personal control
can be achieved via IR receiver and remote.
EcoSystem™ lighting controls are an example
of multi-input digital controls. Benefits:
•
•
•
•
•
•
•
Simple to design
Fewer components
Can be wired topology- and polarity-free
No interfaces required
Easy to maintain
No reprogramming when components are replaced
Infinite re-configurability without Class 1 rewiring
Cost effective
Costs less than other solutions available today
Fewer parts and pieces to install
For detailed information, please see the Lutron
EcoSystem Technical Guide (P/N 367-1028) and
visit www.lutron.com/ecosystem.
Photograph © Peter Aaron/Esto.
Architect: Davis Brody Bond Architects.
Lighting design: Fisher Marantz Stone.
|
Lutron 07
Lutron
®
| measured light vs. perceived light
The human eye responds to low light levels by
enlarging the pupil, allowing more light to enter the
eye. This response results in a difference between
measured and perceived light levels. A lamp
that is dimmed to 10% of its maximum measured
light output is perceived as being dimmed to
only 32%. Likewise, a lamp dimmed to 1%
is perceived to be at 10%.
1% Architectural dimming
5% High performance dimming
10% Lighting management dimming
100%
90
80
70
60
Measured
Light
50
40
30
20
10
5
1
0
10
22
32
40
50
60
70
80
90
100%
Perceived Light
Measured Light (%)
100
Formula:
Perceived Light (%) = 100 x
Source:
IESNA Lighting Handbook, 9th Edition, (New York: IESNA, 2000), 27-4.
|
08 Lutron
Lutron
®
| dimming applications
5%
High performance dimming
1%
Architectural dimming
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Conference room/Boardroom
Lecture hall
Patient room/Examination
and treatment room
House of worship
Theater
Convention area
Restaurants
Air traffic control center
Industrial control room
Partitioned meeting room
Graphic art workstation
CAD/CAM workstation
Private office
Retail
Presentation spaces
•
•
•
•
Small meeting room
Lobby
Hotel guest room
Residential (See page 28 for
appropriate ballast types.)
10%
Lighting management dimming
•
•
•
•
•
•
Large open office
Corridor/Stairwell
Utility room
Restroom
Customer service area/
Call center
Classroom
Design example
At full brightness, the measured light in a space is 60 foot-candles.
At the lowest dimmed level, 10% perceived light is desired.
1% measured light (0.6 fcd)
is perceived as 10%
(desired result)
5% measured light (3 fcd)
is perceived as 22%
(2x brighter than desired)
10% measured light (6 fcd)
is perceived as 32%
(3x brighter than desired)
|
Lutron 09
Lutron
®
| benefits of 1% dimming
Architectural dimming
Architectural spaces often have a strong
focus on aesthetics and comfort, creating an
environment that portrays class and distinction.
Architects and designers create these spaces
for maximum versatility and require subtle
control of the lighting. At Lutron, we design
fluorescent dimming ballasts to respond
to the finest lighting adjustments required.
Hi-lume® dimming ballasts allow control
of your fluorescent lights through full-range
100% to 1% light output, providing the
greatest available functionality for architectural
fluorescent lighting.
|
10 Lutron
Photograph © Nikolas Koenig.
Architect: Richard Meyer & Partners, Architects.
Lighting design: L'Observatoire International.
Hi-lume
®
| 1%
Photograph © Nikolas Koenig.
Restaurants
Hi-lume® 1% applications
For years, 1% dimming has been the standard
for conference room lighting. 1% CFL (compact
fluorescent lamps) dimming has opened up new
areas for fluorescents, giving required performance
while meeting strict energy codes.
In restaurants, combining Hi-lume with inviting,
colored reflectors creates a warm and intimate
atmosphere for distinctive dining.
Patient care areas need dimmed lights at
night, but require bright light and true color
rendering for accurate medical examinations.
Fluorescent sources, with their consistent
color temperature throughout the dimming
range, are an ideal source.
Patient
Care Areas
Partitioned spaces, like conference rooms
or ballrooms, require 1% dimming for specific
tasks, allowing for a variety of activities to use
the same space.
Partitioned Spaces
|
Lutron 11
Lutron
®
| 1% architectural dimming
Hi-lume
®
Experience the benefits of true full-range 100%
to 1% fluorescent dimming. Designed to meet
the most demanding lighting requirements,
Hi-lume ballasts enable you to provide the
ideal visual environment for any application.
The Hi-lume family is extensive, featuring the
world's only 100% to 1% dimming ballasts
for T4 compact fluorescent lamps. Integrating
Hi-lume 1% technology into your designs
affords you full control over the lighting
in any space.
For maximum flexibility, Lutron offers a
full line of Hi-lume ballasts and compatible
3-wire controls.
Photograph © Kerun Ip,
courtesy of Pei Partnership Architects.
Lutron ballasts are tested for performance
with Philips®, Sylvania®, and GE® lamps.
For the complete listing of Hi-lume ballasts
by Lutron, please see pages 24-27.
•
Dims T5-HO linear lamps
•
Slim-profile design –
just 1" high x 1.18" wide
•
|
Color-keyed push-in connectors
12 Lutron
•
Dims T8 linear
and U-bent lamps
•
Dims T4 triple-tube
compact lamps
•
Slim-profile design – just 1" high
•
Color-keyed push-in connectors
•
Available with or without
mounting studs
Hi-lume
®
Performance
| 1%
Specifications
•
Continuous, flicker-free dimming
from 100% to 1%
•
Architectural dimming from 100% to 1%
relative light output
•
Models available for T4 triple-tube CFL,
T5-HO, and T8 lamps
•
No visible flicker
•
Total Harmonic Distortion (THD) less than 10%
•
Power factor greater than .95
•
Ballast factor greater than .85 for T8 lamps
•
Ballast factor greater than .95 for T4 lamps
•
Ballast factor equal to 1.0 for T5-HO lamps
•
Frequency of operation greater than 25 kHz
for T8 lamps
•
Frequency of operation greater than 42 kHz
for T4 and T5-HO lamps
•
3-wire line voltage control for consistent
fixture-to-fixture dimming
•
Lamps turn on at any dimmed level
without flashing to full brightness
•
Low harmonic distortion
•
Miswire protection
•
Slim-profile and standard designs available
•
100% performance tested
•
Ultra-quiet operation
•
Inaudible in 27 dBA ambient environment
•
Designed and assembled in the USA
•
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
Inrush current limiting circuitry built-in
(maximum of 7 amps for 120V
and 3 amps at 277V)
•
Internal fusing
•
Minimum lamp starting temperature 10°C (50°F)
•
Maximum ballast case temperature 75°C (167°F)
3-wire control
For the full offering of Hi-lume dimming ballast controls
by Lutron, please see pages 38 and 39.
Hot
120/277VAC
60Hz Feed
Control
Hot
Dimmed Hot
Dimming
Ballast
Neutral
Neutral
|
Lutron 13
Lutron
®
| 5% high performance dimming
Compact SE
™
For designs requiring the energy savings
and aesthetic appeal of dimmed compact
fluorescent lamps, Compact SE dimming
ballasts are your solution. The Compact SE
product family includes ballasts for nearly
every type of compact fluorescent lamp.
Compact SE dimming ballasts deliver
high performance 100% to 5% dimming,
making them ideal for use in a variety of
applications. In addition, Compact SE
ballasts are compatible with the full line
of 3-wire controls by Lutron.
Photograph © Kerun Ip,
courtesy of Pei Partnership Architects.
For the complete listing of Compact SE
ballasts by Lutron, please see pages 24-27.
•
|
Dims T5 twin-tube lamps
14 Lutron
•
Dims T4 quad- and triple-tube
compact lamps
•
Slim-profile design – just 1” high
•
Color-keyed push-in connectors
•
Available with or without mounting studs
Compact SE
™
Performance
•
| 5%
Specifications
Continuous, flicker-free dimming from
100% to 5% (for 1% dimming of compact
fluorescent lamps, see page 12)
•
3-wire line voltage control for consistent
fixture-to-fixture dimming
•
Lamps turn on at any dimmed level
without flashing to full brightness
•
Low harmonic distortion
•
Miswire protection
•
Slim-profile design
•
100% performance tested
•
Ultra-quiet operation
•
Designed and assembled in the USA
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
•
High performance dimming from 100% to 5%
relative light output
•
No visible flicker
•
Total Harmonic Distortion (THD) less than 10%
•
Power factor greater than .95
•
Ballast factor greater than .85 for
T5 twin-tube lamps
•
Ballast factor greater than .95 for
T4 quad- and triple-tube compact lamps
•
Frequency of operation greater than 27 kHz
for T5 twin-tube lamps
•
Frequency of operation greater than 42 kHz
for T4 quad- and triple-tube compact lamps
•
Inaudible in 27 dBA ambient environment
•
Inrush current limiting circuitry built-in
(maximum of 7 amps for 120V
and 3 amps at 277V)
•
Internal fusing
•
Minimum lamp starting temperature 10°C (50°F)
•
Maximum ballast case temperature 75°C (167°F)
3-wire control
For the full offering of Compact SE dimming ballast controls
by Lutron, please see pages 38 and 39.
Hot
120/277VAC
60Hz Feed
Control
Hot
Dimmed Hot
Neutral
Dimming
Ballast
Neutral
|
Lutron 15
Lutron
®
| 5% high performance dimming
Tu-Wire
®
Retrofit and small-space applications can
benefit from the ease of installation offered
by Lutron Tu-Wire dimming ballasts.
Tu-Wire ballasts offer high performance
100% to 5% dimming for linear and
compact fluorescent lamps.
Tu-Wire ballasts require only two wires
(hot and neutral) for power and control.
Lutron offers a wide range of compatible
2-wire controls, making Tu-Wire a perfect
choice for many applications. Additionally,
one-lamp T4 models have been designed to
meet FCC Part 18 consumer requirements.
Interiors by Staffelbach
Design Associates.
For the complete listing of Tu-Wire ballasts
by Lutron, please see page 28.
•
Dims T8 lamps
•
Slim-profile design – just 1" high x 1.18" wide
•
Color-keyed push-in connectors
|
16 Lutron
•
Dims T4 quad- and triple-tube
compact lamps
•
Slim-profile design – just 1” high
•
Color-keyed push-in connectors
•
Available with or without mounting studs
Tu-Wire
®
Performance
| 5%
Specifications
•
Continuous, flicker-free dimming
from 100% to 5%
•
High performance dimming from 100% to 5%
relative light output
•
2-wire line voltage control for retrofit
applications
•
No visible flicker
•
Total Harmonic Distortion (THD) less than 20%
•
Power factor greater than .95
•
Ballast factor greater than .85 for T4 lamps
•
Ballast factor equal to 1.0 for T8 lamps
•
Frequency of operation greater than 42 kHz
•
Inaudible in 27 dBA ambient environment
•
Inrush current limiting circuitry built-in
(maximum of 7 amps inrush current
per ballast)
•
Internal fusing
•
Minimum lamp starting temperature 10°C (50°F)
•
Maximum ballast case temperature 75°C (167°F)
•
Lamps turn on at any dimmed level
without flashing to full brightness
•
Low harmonic distortion
•
Slim-profile design
•
One-lamp T4 models meet FCC Part 18
consumer requirements for residential use
(FCC ID: JPZB001)
•
100% performance tested
•
Ultra-quiet operation
•
Designed and assembled in the USA
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
2-wire control
For the full offering of Tu-Wire dimming ballast controls
by Lutron, please see page 40.
Control
Hot
120VAC
60Hz Feed
Dimmed Hot
Neutral
Dimming
Ballast
Neutral
|
Lutron 17
Lutron
®
| 10% lighting management dimming
Eco-10
™
To maximize the benefits of a lighting
management system, use Eco-10 dimming
ballasts by Lutron. Eco-10 offers 100%
to 10% dimming, and is ideal for use in any
space where saving energy is the primary
goal, and critical performance is secondary.
Eco-10 ballasts are available for a large
range of lamps, making them an ideal
choice for applications with many different
fixture types. In addition, Eco-10 ballasts
are fully compatible with Lutron's complete
line of 3-wire fluorescent controls.
Photograph © Peter Aaron/Esto.
Architect: Robert A.M. Stern Architects.
For the complete listing of Eco-10 ballasts
by Lutron, please see pages 24-27.
•
|
Dims T5 twin-tube lamps
18 Lutron
•
Dims T8 linear and U-bent, T5 linear, and
T5-HO linear lamps
•
Dims 2' and 3' T5 lamps
•
Slim-profile design –just 1" high x 1.18" wide
•
Color-keyed push-in connectors
Eco-10
™
Performance
| 10%
Specifications
•
Continuous, flicker-free dimming
from 100% to 10%
•
Lighting management dimming from 100% to 10%
relative light output
•
3-wire line-voltage control for consistent
fixture-to-fixture dimming
•
No visible flicker
•
Total Harmonic Distortion (THD) less than 20%
•
Power factor greater than .95
•
Ballast factor greater than .85 for T8 lamps
and T5 twin-tube lamps
•
Lamps turn on at any dimmed level
without flashing to full brightness
•
Low harmonic distortion
•
Slim-profile and standard designs available
•
Ballast factor equal to 1.0 for T5 and T5-HO lamps
•
100% performance tested
•
•
Ultra-quiet operation
Frequency of operation greater than 25 kHz
for T8 lamps and T5 twin-tube lamps
•
Designed and assembled in the USA
•
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
Frequency of operation greater than 42 kHz
for T5 and T5-HO lamps
•
Inaudible in 27 dBA ambient environment
•
Inrush current limiting circuitry built-in
(maximum of 7 amps for 120V
and 3 amps at 277V)
•
Internal fusing
•
Minimum lamp starting temperature 10°C (50°F)
•
Maximum ballast case temperature 75°C (167°F)
3-wire control
For the full offering of Eco-10 dimming ballast controls
by Lutron, please see pages 38 and 39.
Hot
120/277VAC
60Hz Feed
Control
Hot
Dimmed Hot
Dimming Ballast
Neutral
Neutral
|
Lutron 19
Lutron
®
| 10% lighting management dimming
TVE
™
For applications requiring the use of 0-10V
control, Lutron offers the TVE family of
fluorescent dimming ballasts. TVE ballasts
are designed to work seamlessly with
0-10V lighting management systems,
including daylight harvesting and
occupancy detection schemes.
Lutron offers many choices for 0-10V
controls, including interfaces to many of
our dimming systems.
For the complete listing of TVE ballasts
by Lutron, please see page 29.
|
20 Lutron
•
Dims T8 linear and U-bent lamps
•
0-10V control
•
347V ballasts available
TVE
Performance
™
| 10%
Specifications
•
Continuous, flicker-free dimming
from 100% to 10%
•
Lighting management dimming from
100% to 10% relative light output
•
0-10V control
•
No visible flicker
•
Lamps turn on at any dimmed level
without flashing to full brightness
•
Total Harmonic Distortion (THD) less than 20%
•
Power factor greater than .95
•
Low harmonic distortion
•
Ballast factor greater than .85
•
100% performance tested
•
Frequency of operation greater than 25 kHz
•
Ultra-quiet operation
•
Inaudible in 27 dBA ambient environment
•
Designed and assembled in the USA
•
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
Inrush current limiting circuitry built-in
(maximum of 7 amps for 120V,
3 amps for 277V and 347V)
•
Internal fusing
•
Minimum lamp starting temperature 10°C (50°F)
•
Maximum ballast case temperature 75°C (167°F)
0-10V control
For the full offering of TVE dimming ballast controls by Lutron, please see page 41.
Hot
120/277/347VAC
60Hz Feed
Control*
Hot
Neutral
Control (+)
Control (–)
Dimming Ballast
Neutral
* Based on control being used, wiring method may differ.
|
Lutron 21
Lutron
®
| 10% lighting management dimming
EcoSystem
™
EcoSystem devices employ revolutionary
technology allowing each device to listen, think,
decide and remember. EcoSystem fluorescent
lighting control solutions create fluorescent lighting
control systems with a simple building block
architecture of EcoSystem fluorescent dimming
ballasts, EcoSystem sensors, and EcoSystem
controls, free from interfaces and power packs.
EcoSystem fluorescent solutions redefine
fluorescent lighting control as easy to design,
easy to install, easy to maintain and cost effective.
For the complete listing of EcoSystem
ballasts by Lutron, please see
pages 30 and 31.
•
Dims T8 linear and U-bent, T5 linear, and
T5-HO linear lamps
•
Slim-profile design –just 1" high x 1.18" wide
•
Color-matched for Lutron sensors and controls
|
22 Lutron
•
Dims T8 linear and U-bent lamps
•
Low-power design
•
Color-keyed push-in connectors
with or without leads
EcoSystem
™
Performance
| 10%
Specifications
•
Continuous, flicker-free dimming
from 100% to 10%
•
Lighting management dimming from 100% to 10%
relative light output
•
Models available for T5, T5-HO, and T8 lamps
•
No visible flicker
•
Multi-input digital control
•
Total Harmonic Distortion (THD) less than 20%
•
Lamps turn on at any dimmed level without
flashing to full brightness
•
Power factor greater than .95
•
Ballast factor greater than .85 for T8 lamps
•
Low harmonic distortion
•
Ballast factor equal to 1.0 for T5 and T5-HO lamps
•
Miswire protection
•
Frequency of operation greater than 42 kHz
•
Slim-profile and standard designs available
•
Inaudible in 27 dBA ambient environment
•
Meets FCC Part 18 Non-Consumer
requirements for EMI/RFI emissions
•
•
100% performance tested
Inrush current limiting circuitry built-in
(maximum of 7 amps for 120V
and 3 amps at 277V)
•
Ultra-quiet operation
•
Internal fusing
•
Designed and assembled in the USA
•
Minimum lamp starting temperature 10°C (50°F)
•
5-year warranty (limited) with field service
commissioning (3-year warranty standard)
•
Maximum ballast case temperature 75°C (167°F)
Multi-input digital control
For the full offering of EcoSystem dimming ballast controls by Lutron, please see page 41.
Hot
Neutral
Dimming
Ballast
E1*
E2*
* To other ballasts and bus supply
Sensors
|
Lutron 23
Lutron
®
, Compact SE , Eco-10
| Hi-lume
120 volt 3-wire dimming ballasts
®
™
™
For the latest
model numbers:
www.lutron.com/ballasts
Eco-10
Ballast
Current2
– Amps
––
E 3 T514 C 120 1
.17
C3
––
E 3 T514 C 120 2
.32
1
C3
––
E 3 T521 C 120 1
.25
(34")
2
3
C
––
E 3 T521 C 120 2
.43
28W
1
C3
––
ECO-T528-120-1
.30
(45”)
2
C3
––
ECO-T528-120-2
.55
24W
1
C3
FDB-T524-120-1
ECO-T524-120-1
.26
(21.5")
2
3
C
FDB-T524-120-2
ECO-T524-120-2
.45
39W
1
C3
FDB-T539-120-1
ECO-T5H39-120-1
.38
(33.4")
2
3
C
FDB-T539-120-2
ECO-T5H39-120-2
.76
54W
1
C3
FDB-T554-120-1
ECO-T554-120-1
.58
(45”)
2
3
C
FDB-T554-120-2
ECO-T554-120-2
1.1
17W
1
F
FDB-2427-120-1
ECO-T817-120-1
.19
and U-Bent (24")
2
F
FDB-2427-120-2
ECO-T817-120-2
.31
3
F
FDB-2427-120-3
ECO-T817-120-3
.43
25W
1
F
FDB-3627-120-1
ECO-T825-120-1
.24
(36")
2
F
FDB-3627-120-2
ECO-T825-120-2
.43
3
F
FDB-3627-120-3
––
.62
32W
1
F
FDB-4827-120-1
––
.30
(48")
1
D
––
ECO-T832-120-1-L .34
1
D
––
ECO-T832-120-1-T .34
2
F
FDB-4827-120-2
––
2
D
––
ECO-T832-120-2-L .53
2
D
––
ECO-T832-120-2-T .53
3
F
FDB-4827-120-3
ECO-T832-120-3
.82
40W
1
F
FDB-6027-120-1
––
.36
(60")
2
F
FDB-6027-120-2
––
.64
Lamp
Type
Lamps
Lamp
per
Watts
Case
(Length) Ballast Type1
T5 Linear
14W
1
C3
(22")
2
21W
5/8" Dia
T5-HO
Linear
5/8" Dia
T8 Linear
1" Dia
1% Dimming
Hi-lume
10% Dimming
5% Dimming
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.
3 Standard with terminals. Leaded options available. Please consult factory.
|
24 Lutron
.57
For the latest
model numbers:
www.lutron.com/ballasts
Lamp
Type
Lamps
Lamp
Case
per
Watts
1
(Length) Ballast Type
T4 4-Pin
18W
1% Dimming
5% Dimming
10% Dimming
Hi-lume
Compact SE
Eco-10
Ballast
Current2
– Amps
1
A3
––
FDB-T418-120-1-S ––
.20
2
B3
––
FDB-T418-120-2-S ––
.42
1
A3
––
FDB-T426-120-1-S ––
.26
2
B3
––
FDB-T426-120-2-S ––
.50
1
A3
––
FDB-T418-120-1-S ––
.20
2
B
3
––
FDB-T418-120-2-S ––
.42
1
A3
HL3-T426-120-1-S FDB-T426-120-1-S ––
.26
2
3
B
––
FDB-T426-120-2-S ––
.50
1
A3
HL3-T432-120-1-S FDB-T432-120-1-S ––
.31
2
B
3
––
FDB-T432-120-2-S ––
.59
1
B3
––
FDB-T442-120-1-S ––
.39
2
B
3
––
FDB-T442-120-2-S ––
.67
T5
36/39W 1
F
––
FDB-1643-120-1
ECO-T539-120-1
.33
Twin-Tube
(16")
2
F
––
FDB-1643-120-2
ECO-T539-120-2
.58
3
F
––
FDB-1643-120-3
ECO-T539-120-3
.85
40W
1
F
––
FDB-2227-120-1
ECO-T540-120-1
.33
(22")
2
F
––
FDB-2227-120-2
ECO-T540-120-2
.61
3
F
––
FDB-2227-120-3
ECO-T540-120-3
.88
50W
1
F
––
FDB-2243-120-1
ECO-T550-120-1
.38
(22")
2
F
––
FDB-2243-120-2
ECO-T550-120-2
.69
Quad-Tube
26W
1/2" Dia
T4 4-Pin
18W
Triple-Tube
26W
1/2" Dia
32W
42W
5/8" Dia
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.
3 Mounting studs standard. Delete suffix -S if mounting studs not desired.
|
Lutron 25
Lutron
®
|
Hi-lume , Compact SE , Eco-10
277 volt 3-wire dimming ballasts
®
™
™
NEW!
For the latest
model numbers:
www.lutron.com/ballasts
Eco-10
Ballast
Current2
– Amps
––
E 3 T514 C 277 1
.08
C3
––
E 3 T514 C 277 2
.14
1
C3
––
E 3 T521 C 277 1
.11
(34")
2
3
C
––
E 3 T521 C 277 2
.19
28W
1
C3
––
ECO-T528-277-1
.14
(45”)
2
C3
––
ECO-T528-277-2
.25
24W
1
C3
FDB-T524-277-1
ECO-T524-277-1
.13
(21.5")
2
3
C
FDB-T524-277-2
ECO-T524-277-2
.20
39W
1
C3
FDB-T539-277-1
ECO-T5H39-277-1
.17
(33.4")
2
3
C
FDB-T539-277-2
ECO-T5H39-277-2
.31
54W
1
C3
FDB-T554-277-1
ECO-T554-277-1
.25
(45”)
2
3
C
FDB-T554-277-2
ECO-T554-277-2
.45
17W
1
F
FDB-2427-277-1
ECO-T817-277-1
.08
and U-Bent (24")
2
F
FDB-2427-277-2
ECO-T817-277-2
.15
3
F
FDB-2427-277-3
ECO-T817-277-3
.20
25W
1
F
FDB-3627-277-1
ECO-T825-277-1
.12
(36")
2
F
FDB-3627-277-2
ECO-T825-277-2
.19
3
F
FDB-3627-277-3
––
.28
32W
1
F
FDB-4827-277-1
ECO-T832-277-1
.14 /.15 4
(48")
1
D
––
ECO-T832-277-1-L .14
1
D
––
ECO-T832-277-1-T .14
2
F
FDB-4827-277-2
ECO-T832-277-2
2
D
––
ECO-T832-277-2-L .23
2
D
––
ECO-T832-277-2-T .23
3
F
FDB-4827-277-3
ECO-T832-277-3
.35
40W
1
F
FDB-6027-277-1
––
.16
(60")
2
F
FDB-6027-277-2
––
.30
Lamp
Type
Lamps
Lamp
per
Watts
Case
(Length) Ballast Type1
T5 Linear
14W
1
C3
(22")
2
21W
5/8" Dia
T5-HO
Linear
5/8" Dia
T8 Linear
1" Dia
1% Dimming
Hi-lume
10% Dimming
5% Dimming
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.
3 Standard with terminals. Leaded options available. Please consult factory.
4 Eco-10 ballast current.
|
26 Lutron
.25 /.22 4
For the latest
model numbers:
www.lutron.com/ballasts
Lamp
Type
Lamps
Lamp
Case
per
Watts
1
(Length) Ballast Type
T4 4-Pin
18W
1% Dimming
5% Dimming
10% Dimming
Hi-lume
Compact SE
Eco-10
Ballast
Current2
– Amps
1
A3
––
FDB-T418-277-1-S ––
.08
2
B3
––
FDB-T418-277-2-S ––
.17
1
3
A
––
FDB-T426-277-1-S ––
.12
2
B3
––
FDB-T426-277-2-S ––
.21
1
A3
––
FDB-T418-277-1-S ––
.08
2
B
3
––
FDB-T418-277-2-S ––
.17
1
A3
HL3-T426-277-1-S FDB-T426-277-1-S ––
.12
2
3
B
––
FDB-T426-277-2-S ––
.21
1
A3
HL3-T432-277-1-S FDB-T432-277-1-S ––
.13
2
B
3
––
FDB-T432-277-2-S ––
.24
1
B3
––
FDB-T442-277-1-S ––
.16
2
B
3
––
FDB-T442-277-2-S ––
.29
T5
36/39W 1
F
––
FDB-1643-277-1
ECO-T539-277-1
.14
Twin-Tube
(16")
2
F
––
FDB-1643-277-2
ECO-T539-277-2
.25
3
F
––
FDB-1643-277-3
ECO-T539-277-3
.35
40W
1
F
––
FDB-2227-277-1
ECO-T540-277-1
.14
(22")
2
F
––
FDB-2227-277-2
ECO-T540-277-2
.25
3
F
––
FDB-2227-277-3
ECO-T540-277-3
.38
50W
1
F
––
FDB-2243-277-1
ECO-T550-277-1
.17
(22")
2
F
––
FDB-2243-277-2
ECO-T550-277-2
.32
Quad-Tube
26W
1/2" Dia
T4 4-Pin
18W
Triple-Tube
26W
1/2" Dia
32W
42W
5/8" Dia
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.
3 Mounting studs standard. Delete suffix -S if mounting studs not desired.
|
Lutron 27
Lutron
®
120 volt
| Tu-Wire
2-wire dimming ballasts
®
For the latest
model numbers:
www.lutron.com/ballasts
5% Dimming
Lamp
Type
Lamps
Lamp
per
Watts
(Length) Ballast
Case
Type1
T8 Linear
32W
1
C3
2W-T832-120-1
.37
and U-Bent (48")
2
C3
2W-T832-120-2
.70
Tu-Wire
10% Dimming
Contact Lutron
for other
lamp lengths.
1" Dia
T4 4-Pin
1% Dimming
Ballast
Current2
– Amps
18W
2
B4
2W-T418-120-2-S
.41
26W
1
A4
2W-T426-120-1-S5
.27
2
4
B
2W-T426-120-2-S
.53
18W
2
B4
2W-T418-120-2-S
.41
26W
1
A4
2W-T426-120-1-S5
.27
2
4
B
2W-T426-120-2-S
.53
1
A4
2W-T432-120-1-S5
.33
2
B4
2W-T432-120-2-S
.58
Quad-Tube
1/2" Dia
T4 4-Pin
Triple-Tube
1/2" Dia
32W
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.
3 Standard with terminals. Leaded options available. Please consult factory.
4 Mounting studs standard. Delete suffix -S if mounting studs not desired.
5 One-lamp T4 models meet FCC Part 18 consumer requirements for residential use (FCC ID: JPZB001).
|
28 Lutron
Lutron
®
|
TVE 120/277/347 volt
0-10V dimming ballasts
For the latest
model numbers:
www.lutron.com/ballasts
™
10% Dimming Ballast
Lamp
Type
Lamps
Lamp
per
Watts
(Length) Ballast
Case
Type1
T8 Linear
17W
1
TVE
Current2
– Amps
F
TVE-T817-120-1
.14
1
F
TVE-T825-120-1
.24
32W
1
F
TVE-T832-120-1
.34
(48")
1
F
TVE-T832-277-1
.15
1
F
TVE-T832-347-1
.11
2
F
TVE-T832-120-2
.55
2
F
TVE-T832-277-2
.25
2
F
TVE-T832-347-2
.19
3
F
TVE-T832-120-3
.80
3
F
TVE-T832-277-3
.35
1% Dimming
5% Dimming
and U-Bent (24")
25W
1" Dia
(36")
T5
40W
2
F
TVE-T540-120-2
.61
Twin-Tube
(22")
2
F
TVE-T540-277-2
.25
5/8" Dia
1 For case type information, see pages 32 and 33.
2 To calculate ballast input power, use the following formula:
Watts = Ballast Current x Ballast Voltage (included in model number).
|
Lutron 29
Lutron
®
|
EcoSystem 120 volt multi-input
digital addressable dimming ballasts
TM
Lamps
per
Case
(Length) Ballast Type1
10% Dimming
T8 Linear
17W
1
and U-Bent
(24")
Lamp
Watts
NEW!
For the latest
model numbers:
www.lutron.com/ballasts
System
Efficacy2
(Im/W)
EcoSystem
Ballast
Current Ballast
– Amps Factor
Input
Power
J
EC5 T817 J 120 1
.158
.85
19
4.47
1105
58
2
J
EC5 T817 J 120 2
.292
.85
35
2.43
2210
63
25W
1
J
EC5 T825 J 120 1
.208
.85
25
3.40
1615
65
(36")
2
J
EC5 T825 J 120 2
.383
.85
46
1.85
3230
70
32W
(48")
1
2
J
J
EC5 T832 J 120 1
EC5 T832 J 120 2
.250
.475
.85
.85
30
57
2.83
1.49
2550
5100
85
89
14W
1
J
EC5 T514 J 120 1
.158
1.00
19
5.26
1350
71
(22")
2
J
EC5 T514 J 120 2
.283
1.00
34
2.94
2700
79
21W
1
J
EC5 T521 J 120 1
.217
1.00
26
3.85
2100
81
(34")
2
J
EC5 T521 J 120 2
.404
1.00
48.5
2.06
4200
87
28W
1
J
EC5 T528 J 120 1
.275
1.00
33
3.03
2900
88
(45")
2
J
EC5 T528 J 120 2
.525
1.00
63
1.59
5800
92
T5 -HO
24W
1
J
EC5 T524 J 120 1
.226
1.00
27
3.70
2000
74
Linear
(21.5") 2
J
EC5 T524 J 120 2
.434
1.00
52
1.92
4000
77
High
39W
1
J
EC5 T539 J 120 1
.359
1.00
43
2.33
3500
81
Output
(33.4") 2
J
EC5 T539 J 120 2
.695
1.00
83
1.20
7000
84
54W
1
J
EC5 T554 J 120 1
.500
1.00
60
1.67
5000
83
(45")
2
J
EC5 T554 J 120 2
1.00
1.00
120
0.83
10000
83
Lamp
Type
1" Dia
T5 Linear
5/8" Dia
5/8" Dia
Ballast
Efficacy System
Lumens2
Factor
Use EcoSystem ballast module (C5-BMF-2A) to integrate any Lutron Eco-10TM or
Hi-lume® phase-control ballast into the EcoSystem bus.
Switched Hot,
Dimmed Hot
and Neutral
Sensors
3
E1*
BMF
Dimming Ballast
3
E2*
Hot
Neutral
1 For case type information, see pages 32 and 33.
2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
3 To other ballasts and bus supply.
|
30 Lutron
Lutron
®
|
EcoSystem 277 volt
digital addressable dimming ballasts
TM
Lamp
Watts
NEW!
For the latest
model numbers:
www.lutron.com/ballasts
Ballast
Efficacy System
Factor
Lumens2
Lamps
Case
per
(Length) Ballast Type1
10% Dimming
EcoSystem
Ballast
Current Ballast
– Amps Factor
17W
1
J
EC5 T817 J 277 1
.075
.85
19
4.47
1105
58
and U-Bent (24")
2
J
EC5 T817 J 277 2
.126
.85
35
2.43
2210
63
25W
1
J
EC5 T825 J 277 1
.095
.85
25
3.40
1615
65
(36")
2
J
EC5 T825 J 277 2
.166
.85
46
1.85
3230
70
32W
1
J
EC5 T832 J 277 1
.108
.85
30
2.83
2550
85
(48")
2
J
EC5 T832 J 277 2
.206
.85
57
1.49
5100
89
2
G
EC5 T832 G 277 2L .216
.85
57
1.49
5100
89
3
G
EC5 T832 G 277 3L .320
.85
86
0.99
7632
89
14W
1
J
EC5 T514 J 277 1
.078
1.00
19
5.26
1350
71
(22")
2
J
EC5 T514 J 277 2
.123
1.00
34
2.94
2700
79
21W
1
J
EC5 T521 J 277 1
.094
1.00
26
3.85
2100
81
(34")
2
J
EC5 T521 J 277 2
.175
1.00
48.5
2.06
4200
87
28W
1
J
EC5 T528 J 277 1
.119
1.00
33
3.03
2900
88
(45”)
2
J
EC5 T528 J 277 2
.227
1.00
63
1.59
5800
92
T5 -HO
24W
1
J
EC5 T524 J 277 1
.100
1.00
27
3.70
2000
74
Linear
(21.5") 2
J
EC5 T524 J 277 2
.191
1.00
52
1.92
4000
77
High
39W
1
J
EC5 T539 J 277 1
.158
1.00
43
2.33
3500
81
Output
(33.4") 2
J
EC5 T539 J 277 2
.306
1.00
83
1.20
7000
84
54W
1
J
EC5 T554 J 277 1
.217
1.00
60
1.67
5000
83
(45")
2
J
EC5 T554 J 277 2
.433
1.00
120
0.83
10000
83
Lamp
Type
T8 Linear
1" Dia
T5 Linear
5/8" Dia
5/8" Dia
Input
Power
System
Efficacy2
(Im/W)
1 For case type information, see pages 32 and 33.
2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specific data.
|
Lutron 31
Lutron
®
| ballast case dimensions
A
8-32 Threaded Stud
0.29" (.736mm)
A
F
G
B
C
I
H
E
8-32 Threaded Stud
0.29" (.736mm)
A
B
G
F
G
H
I
D
B
A
B
C
D
E
F
C
A
B
C
D
E
I
F
G
H
I
H
D
E
A
B
C
D
E
C or J
A
B
C
F
E
G
D
F
G
Note: Dotted area for sensor attachment
applies for EcoSystem™ J can only.
|
32 Lutron
4.20" (107mm)
1.00" (25mm)
3.00" (76mm)
4.90" (124mm)
4.60" (117mm) C-C
(mounting centers)
2.00" (51mm)
1.08" (27mm)
1.60" (41mm)
1.39" (35mm)
6.00" (152mm)
1.00" (25mm)
3.00" (76mm)
6.75" (171mm)
6.50" (165mm) C-C
(mounting centers)
2.00" (51mm)
1.16" (29mm)
1.60" (41mm)
1.39" (35mm)
16.12" (409mm)
1.00" (25mm)
1.18" (30mm)
18.00" (457mm)
17.70" (450mm)
C-C (mounting
centers)
6.82" (173mm)
(J only)
0.394"(10mm)
(J only)
D
A
B
C
A
7.13" (181mm)
B
1.00" (25mm)
C
1.58" (40mm)
D
9.50" (241mm)
E
8.91" (226mm)
Slot mounting centers
E
D
Optional lamp wires
are 36" (0.90m)
Optional power
and control wires
are 18" (0.45m)
F
A
B
C
E
D
Lamp wires
are 36" (0.90m)
Power and control
wires are 18" (0.45m)
G
A
B
C
E
D
Lamp wires
are 36" (0.90m)
Power and control
wires are 18" (0.45m)
Proper ballast mounting is critical in providing effective grounding and for
managing ballast heat. Please refer to the Lutron Fluorescent Dimming
Systems Technical Guide (P/N 366-606) for detailed information.
If using 4-hole mount,
mounting centers are 9.00"
(229mm) X 1.06" (27mm).
A
8.30" (211mm)
B
1.50" (38mm)
C
2.38" (60.5mm)
D
9.50" (241mm)
E
8.91" (226mm)
Slot mounting centers
If using 4-hole mount,
mounting centers are 9.21"
(234mm) X 1.70" (43mm).
A
7.13" (181mm)
B
1.00" (25mm)
C
2.38" (60.5mm)
D
9.50" (241mm)
E
8.91" (226mm)
Slot mounting centers
If using 4-hole mount,
mounting centers are 9.00"
(229mm) X 1.06" (27mm).
|
Lutron 33
Lutron
®
| fluorescent dimming controls
Wallbox dimmers
NovaTa®
Classic, thin-profile
linear-slide dimmer
Wireless remote controls
Nova®
Contractor’s choice in
linear-slide dimmers
•
•
PerSONNA®
Personal control of one or more overhead
fluorescent fixtures in open office areas
Dim lights to eliminate computer screen
glare and reflections
See the Lutron Commercial Wallbox Catalog
(P/N 367-572) for detailed information.
Vareo®
Diva®
Elegant thin-profile
TapSwitch™ dimmer
Designer dimmer
that matches your
paddle switches
•
Skylark®
Ariadni®
Original designer-style
slide dimmer
Dimmer that matches
your toggle switches
See the Lutron Commercial Wallbox Catalog
(P/N 367-572) for detailed information.
|
34 Lutron
RadioTouch™
Wireless control
of multiple lighting zones
•
Occupant sensing,
motorized shade and
A/V equipment control optional
•
Ideal for retrofit applications
See the Lutron Commercial Wallbox Catalog
(P/N 367-572) for detailed information.
Preset scene control
•
Entire building lighting
management system
Spacer System™
Up to five preset scenes
•
Easy upgrade for enclosed
offices and conference rooms
•
Dims multiple sources
See the Lutron Commercial Wallbox
Catalog (P/N 367-572) for
detailed information.
•
•
•
GRAFIK Eye®
Create and recall 4-16 room
lighting scenes
•
Optional accessories for wireless
remote control, remote scene
selection, and more
•
Controls multiple sources
See the Lutron Commercial Systems Technical
Guide (P/N 367-573) for detailed information.
Digital microWATT™
The industry’s first lighting automation system,
capable of automatic or manual adjustment
of any fluorescent or incandescent lighting
Employs integral switching and dimming,
real-time monitoring and measurement,
occupant sensing, daylight sensing,
and load shedding, all accessed through
web-based software
See the Lutron Commercial Systems Technical
Guide (P/N 367-573) for detailed information.
|
Lutron 35
Lutron
®
| EcoSystem
TM
components
Ballasts
Sensors/Receivers
EcoSystem Daylight
Sensor with IR Receiver
EcoSystem T8 Digital Ballast
•
Automatically dim the lights when the available
daylight is high and brighten the light when the
available daylight is low in order to maintain a
specific light level in the space
•
Integrated IR receiver for
EcoSystem programming
•
1 daylight sensor can control multiple fixtures
or groups of fixtures differently
EcoSystem T5 Digital Ballast
•
Smooth and continuous dimming from
100% to 10%
•
Provides power for one occupancy sensor,
one daylight sensor, and one personal control
input (infrared receiver or wallstation)
•
Communicates status and sensor inputs over
the EcoSystem bus
20VDC Occupancy Sensor
Modules
EcoSystem Ballast Module
Fixture-mounted (BMF)
•
Allows integration of any Lutron Eco-10™
or Hi-lume® phase-control ballast into
the EcoSystem
•
Provides power for one occupancy sensor,
one daylight sensor, and one personal control
input (infrared receiver or wallstation)
•
Use an ultrasonic sensor for small movement
detection when fans or other automated
systems are not present
•
Use an infrared sensor for occupant detection
when “line of sight” is available from the sensor
•
Use a dual-tech sensor for a combination of
both technologies
EcoSystem IR Receiver
|
36 Lutron
•
Can control individual or grouped
EcoSystem ballasts or modules
•
Flashing LED response to indicate
signal reception
Controls
EcoSystem™ 1-Button Wallstation
and IR Receiver
•
Allows user to manually control any of the
fixtures on the bus for simple on/off,
raise/lower
Support components
EcoSystem Programmer
•
Handles programming changes for all
sensors, ballasts, and modules
•
Transmits to any IR receiver, daylight
sensor, or EcoSystem wallstation
•
Simple user interface allows programming
without training or guidebook
EcoSystem 4-Button Wallstation
and IR Receiver
•
Allows occupants to save and recall different
lighting scenes in multi-purpose rooms
EcoSystem Remote Control
and IR Receiver
•
EcoSystem Bus Supply
•
Required for two or more ballasts (or
modules) to work together
•
Powers the communication bus and is
capable of supporting up to 64 ballasts
or modules
See the Lutron EcoSystem Technical Guide
(P/N 367-1028) for detailed information.
For personal control of lighting
|
Lutron 37
Lutron
®
| select your fluorescent dimming controls
3-wire controls for Hi-lume , Compact SE and Eco-10 ballasts
®
™
™
Control Family
Description
Ballast
Voltage
Control
Model Number
Control
Capacity
NovaTa®
Thin Profile
Slide-To-Off
Dimmer
single
single
single
single
pole
pole
pole, 3-way, preset
pole, 3-way, preset
120V
277V
120V
277V
NTF-10NTF-10-277NTF-103PNTF-103P-277-
16A
8A
8A
6A
Nova®
Standard Profile
Slide-To-Off
Dimmer
single
single
single
single
pole
pole
pole, 3-way, preset
pole, 3-way, preset
120V
277V
120V
277V
NF-10NF-10-277NF-103PNF-103P-277-
16A
8A
8A
6A
Vareo®
Tapswitch/
Preset Slide
Dimmer
single pole, 3-way
120V
VF-10-
8A1
Diva®
Paddle Switch/
Preset Slide
Dimmer
single pole, 3-way
single pole, 3-way
120V
277V
DVF-103PDVF-103P-277-
8A
6A
Skylark®
Rocker Switch/
Preset Slide
Dimmer
single
single
single
single
pole
pole
pole, 3-way
pole, 3-way
120V
277V
120V
277V
SF-10PSF-12P-277SF-103PSF-12P-277-3-
8A
6A
8A
6A
Ariadni®
Toggle Switch/
Preset Slide
Dimmer
single pole, 3-way
single pole, 3-way
120V
277V
AYF-103PAYF-103P-277-
8A
6A
1 Not to exceed 20 Lutron 3-wire dimming ballasts.
2 Wallbox transmitter may be powered by 120 or 277V.
3 Also requires SPS-AD- or SPS-AD-277- for multi-location dimming (10 maximum).
4 Insert 2, 3, 4, or 6 (number of zones); requires GRX-FDBI interface for 120V ballasts;
requires HP-2 for 277V ballasts.
5 For sensors, central monitoring software, etc., contact Lutron.
|
38 Lutron
Ballast
Voltage
Control
Model Number
Control
Capacity
Control Family
Description
PerSONNA®
Wireless
Fluorescent
Remote Control
individual dimmer/receiver
system dimmer/receiver
remote control
120/277V
120/277V
PN-IR
PNS-IR-277
PN-HT-GR
20 ballasts
20 ballasts
RadioTouch™
Wireless
Multi-Zone
Control
controller
wallbox transmitter
tabletop transmitter
120/277V
RTA-RX-FRTA-WX-2
RTA-TX-
16A
Spacer System™
Wireless Preset
Scene Control
single pole
single pole
multi-location
multi-location
remote control
120V
277V
120V
277V
SPSF-6ASPSF-6A-277SPSF-6AM-3
SPSF-6AM-277-3
SPS-4IT-RP
6A1
6A1
6A1
6A1
GRAFIK Eye®
Multi-Scene
Preset Control
control unit
120/277V
GRX-310_4
16A
per zone
Digital
microWATT™
Lighting
Automation
System
controller5
remote control (optional)
GRX-IT-WH
120/277V
DMW-LZC1
16A
1 Not to exceed 20 Lutron 3-wire dimming ballasts.
2 Wallbox transmitter may be powered by 120 or 277V.
3 Also requires SPS-AD- or SPS-AD-277- for multi-location dimming (10 maximum).
4 Insert 2, 3, 4, or 6 (number of zones); requires GRX-FDBI interface for 120V ballasts;
requires HP-2 for 277V ballasts.
5 For sensors, central monitoring software, etc., contact Lutron.
|
Lutron 39
Lutron
®
| select your fluorescent dimming controls
2-wire controls for Tu-Wire ballasts
®
|
40 Lutron
Control Family
Description
Ballast
Voltage
Control
Model Number
Control
Capacity
NovaTa®
Thin Profile
Slide-To-Off
Dimmer
single pole
120V
NTFTU-5A-
5A1
Nova®
Standard Profile
Slide-To-Off
Dimmer
single pole
120V
NFTU-5A-
5A1
Diva®
Paddle Switch/
Preset Slide
Dimmer
single pole, 3-way
120V
DVFTU-5A3P-
5A1
Skylark®
Rocker Switch/
Preset Slide
Dimmer
single pole, 3-way
120V
SFTU-5A3P-
5A1
RadioTouch™
Wireless
Multi-Zone
Control
controller
wallbox transmitter
tabletop transmitter
120V
RTA-RX-F-2
RTA-WX-3
RTA-TX-
16A
Spacer System™
Wireless Preset
Scene Control
single pole
remote control
120V
SPSFTU-5ASPS-4IT-RP
5A1
GRAFIK Eye®
Multi-Scene
Preset Control
control unit
120V
GRX-310_4
6.7A
per zone
Digital
microWATT™
Lighting
Automation
System
controller5
remote control (optional)
GRX-IT
120V
DMW-LZC12
16A
1 Minimum capacity: 2 ballasts.
2 Requires FDI-FTU-16A-120 interface.
3 Wallbox transmitter may be powered by 120 or 277V.
4 Insert 2, 3, 4, or 6 (number of zones).
5 For sensors, central monitoring software, etc., contact Lutron.
6 Requires relay pack to switch power to ballasts. Please consult factory.
7 Insert 02, 03, 04, 06, 08, 16, or 24 (number of zones); 347V requires XP Panel with TVM.
8 Insert 2, 3, 4, or 6 (number of zones); requires GRX-TVI interface.
0-10V controls for TVE ballasts
™
Control Family
Description
Ballast
Voltage
Control
Model Number
Control
Capacity
NovaTa®
Thin Profile
Slide-To-Off
Dimmer
single pole
120/277/347V
NTFTV-6
Up to 60 ballasts
or Relay Pack
Capacity
Nova
Standard Profile
Slide-To-Off
Dimmer
single pole
120/277/347V
NFTV-6
Up to 60 ballasts
or Relay Pack
Capacity
RadioTouch
Wireless
Multi-Zone
Control
controller
347V
controller
120/277V
wallbox transmitter
tabletop transmitter
RTA-RX-F-347
RTA-RX-FRTA-WX-3
RTA-TX-
8A/40 ballasts
16A
GRAFIK Eye
Multi-Scene
Preset Control
control unit
control unit
remote control
(optional)
GRX-41_ _7
GRX-310_8
16A/100 ballasts
16A
GRX-IT
347V
120/277V
multi-input digital controls for EcoSystem ballasts
™
Control Family
Description
Control Model Number
EcoSystem Daylight Sensor
with IR Receiver
sensor
C-SR-M1-WH
EcoSystem IR Receiver
for Personal Control
IR receiver
C-R-M1-WH
EcoSystem
Occupancy Sensor
sensor
LOS-_ _ _ (Please visit
www.lutron.com/occsensors for full line)
EcoSystem 1-Button
with Raise/Lower
wall control
CC-1BRL-WH
EcoSystem 4-Button
with Raise/Lower
wall control
CC-4BRL-WH
1 Minimum capacity: 2 ballasts.
2 Requires FDI-FTU-16A-120 interface.
3 Wallbox transmitter may be powered by 120 or 277V.
4 Insert 2, 3, 4, or 6 (number of zones).
5 For sensors, central monitoring software, etc., contact Lutron.
6 Requires relay pack to switch power to ballasts. Please consult factory.
7 Insert 02, 03, 04, 06, 08, 16, or 24 (number of zones); 347V requires XP Panel with TVM.
8 Insert 2, 3, 4, or 6 (number of zones); requires GRX-TVI interface.
|
Lutron 41
www.lutron.com
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299
World Headquarters 1.610.282.3800
I
I
I
I
I
I
I
Barcelona Beijing Berlin Guangzhou Hong Kong London Madrid Mexico City
I
I
I
I
I
I
I
Milan Paris Rome Sao Paulo Shanghai Singapore Tokyo
Technical Support Center 1.800.523.9466
Customer Service 1.888.LUTRON1
Cover photograph © Peter Aaron/Esto. Architect: Davis Brody Bond Architects.
Lighting design: Fisher Marantz Stone.
© 01/2007 Lutron Electronics Co., Inc.
| Made and printed in the U.S.A. | P/N 366-002