NOTE: TERMINAL L1 MUST BE POWERED BEFORE TERMINAL 12 120V. 50/60HZ. FUSED POWER SUPPLY. L1 L2 UV FORM 6642 VBT GROUP M3101 PROTECTOFIER SINGLE BURNER, AUTOMATIC OPERATION,INCLUDES TIMER FOR PURGE AND IGNITION TRIAL. 7 9 X FLAME RELAY (F) COIL IS ENERGIZED WHEN FLAME IS ESTABLISHED AND DETECTED. FLAME-PAK ELECT. NETWORK G LS * 13 12 CTP1 F 8 4 C 9 N.O. HELD CLOSED 2 12 X X 1 3 F 13 D.C.ua TEST JACK CTP-U300A AUTOMATIC TIMOFIER 4 E ACF SS100A FLAME PAK C-CHECK RELAY ACF F-FLAME RELAY 3 X SEE INTERCONNECTION DIAGRAM BELOW. 8 C 13 LOCKOUT SWITCH 4 AH TIMER MOTOR NO CONNECTIONS 7 C NOTE: TIMER CAMS (CTP) SHOWN IN ZERO TIME POSITION. CTP2 AND CTP3 CLOSE AT END OF PURGE FOR IGNITION. * 1 F 6 9 F 2 DIAGRAM F 11 F C 5 3 6 CTP 1 TIMER 11 9 5 CTP3 INTERNAL WIRING EXTERNAL WIRING WIRING 2 7 - SAFETY INTLK.SERIES CIRCUIT. FUEL AND AIR PRESS.SWS., VENT.FANS,ETC.AS REQ'D. 12 ALARM HORN 10 5 2 ACF C 4 CTP2 10 (CHECK) 1 3 IGN.TRANS. IT SPARK IGNITOR 3 6 PV PILOT VALVE(S) N.C. 3 8 MAIN VALVE(S) MV N.C. 8 FLAME ON (NEON LIGHT) NOTE: TERMINAL L1 MUST BE POWERED BEFORE TERMINAL 12 120V. 50/60HZ. FUSED POWER SUPLY SINGLE BURNER PROTECTOFIER (FORM 6642 VBT GROUP M3101) LOCKOUT SWITCH L1 L2 * NOTES: FLAME WIRE TO BE NO. 14 TYPE TW. 600V. INSULATED WIRE OR EQUAL. FLAME WIRE MUST NOT BE IN SAME CONDUITS WITH POWER WIRING. IGNITION CABLE MUST BE RUN IN SEPARATE CONDUIT TO SPARK ELECTRODE. (DO NOT MIX WITH 115V.WIRING.) ALL WIRING AND EQUIPMENT EXTERNAL TO PROTECTOFIER TO BE FURNISHED BY OTHERS UNLESS OTHERWISE SPECIFIED. INSTALLATION, OPERATION AND MAINTENANCE SHALL CONFORM WITH NATIONAL FIRE PROTECTION ASSOCIATION STANDARDS, NATIONAL AND LOCAL CODES AND AUTHORITIES HAVING JURISDICTION. ANY MODIFICATION VOIDS APPROVAL. LS D.C.TEST JACK L1 L2 3 4 5 6 7 8 9 10 11 12 13 G TRANS. UV ACF PURGE(MIN.) FLAME WIRE PURPLE IGN.(SEC.) MIN. A SEC. ACF (FLAME) OPERATING SIGNAL FROM P-C II OR UV FLAME ROD YELLOW E G TIMER ALARM HORN AH IGN.TRANS. IT SPARK IGNITOR IGN.CABLE PROTECTION CONTROLS, INC. SKOKIE, ILLINOIS MAIN VALVE(S) WIRING DIAGRAM FOR: PROTECTOFIER FORM 6642VBT GROUP M3101 JOB NO. E (CHECK) GAS PILOT P-C II ULTRAVIOLET SCANNER (IF USED) RANGE FLAME PAK U300A AUTOMATIC TIMOFIER FLAME ELECTRODE ASSY. (IF USED) BURNER U300A AUTOMATIC TIMOFIER TIMING ua REVISED DRAWING NO. 10-03 X-244 PILOT VALVE(S) INTERCONNECTION DIAGRAM MV N.C. PV N.C.