Fire damper ETPS-EI TECHNICAL DATA 1 Fire damper ETPS-EI EI 60 S / EI 120 S Figure 1 ER1 Figure 2 ER3 The rectangular fire damper ETPS-EI is available both as motorized and with fuse. The damper casing is manufactured from hot-galvanised steel sheet and the blade from heat-insulating material. All of the dampers are delivered with flange joint. CE marking of the damper is based on product standard EN 15650:2010 and fire resistance tests performed according to EN 1366-2. The damper meets the requirements of fire class EI 60 S (solid walls and ceilings min 100 mm and lightweight partition walls min 120 mm) and EI 120 S (solid walls min 100 mm and ceilings min 115 mm; structural lengths 400 and 500 mm). Note! New fire classes with renewed construction start from 1.9.2012. ETPS-EI is available in three different structural lengths: standard length is 500 mm, lengths of 400 mm and 355 mm are also available. A factory-made installation frame ER1 made of calcium silicate and equipped with an expanding fire seal (Figure 1) is available for gypsum plate wall mounting. With ER1, the fire damper can be installed in a quick and tight manner in compliance with the type approval, without needing to seal the damper after installation. ER1 may also be used to facilitate damper installation into building elements made of rock material. If the fire damper is to be installed onto a fire-separating shaft or other location where the structural length of the damper must be as short as possible, the shortest model of 355 mm is recommended for use. In cases like these, the damper is always installed using installation frame ER2 or ER3 (Figure 2). The installation frame ER2 or ER3 may be installed as early as in the wall construction phase, whereby the fire damper can be inserted into the frame at a later stage, at the same time as the ventilation ducts are being mounted. The leverage of ETPS-EI is fully enclosed to protect it from the airflow – a property that enables maintenance-free operation. In addition, standard damper equipment includes two inspection doors. To special order, the damper can also be converted into a motorized model by replacing the whole actuator panel. ETPS-EI is also available in epoxy resin coating for use in cleanrooms and other facilities where good corrosion resistance is required. In this version, the blade is protected with stainless steel sheet. For use in potentially explosive atmospheres, ETPS-EI is available in an ATEX version. Fläkt Woods EN 2013.05 15 Product data Sizes B x H 200 x 200…1500 x 800 mm CE marking ETPS-EI MPA No. 0761-CPD-0240 Fire class according to EN 13501-3 EI 90 (ve i ↔ o) S EI 90 (ho i ↔ o) S EI 120 (ve i ↔ o) S EI 120 (ho i ↔ o) S Tested according to EN 1366-2. When closed, the fire damper fulfils the requirements of tightness class 2 according to EN 1751. The damper casing fulfils the requirements of tightness class B according to EN 1751. Pressure drop across a closed damper may amount to 2500 Pa, which complies with pressure class B. Product code example Fire damper ETPS-EI-1500800A30 Width: 1500 = 1500 mm Height: 800 = 800 mm Structural length: A = 500 mm Actuator: 3 = 24V AC/DC motor with heat detector Installation frame: 0 = no frame All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Technical data - pressure drop, sound data Pressure drop and sound power level ΔPs (Pa) Height (mm) v (m/s) Sound power level correction by octave bands OCTAVE BAND (Hz) 125 250 500 1000 CORRECTION Koct 6 1 -3 -6 2000 4000 8000 -9 -15 -22 TOLERANCE +/- 6 3 3 3 3 6 6 Lwoct = LWA + Koct Wiring diagram for damper motor Descriptions v Lwokt LwA Koct Dps Power supply AC 230 V AC 24 V T ~ DC 24 V flow velocity(m/s) sound power level in the duct (dB) sound power level(dB) correction(dB) static pressure drop(Pa) Status data of limit switches 1 2 S1 S3 S4 S2 S5 S6 M < 5° < 80° M Thermal trip (T) Tf1 Tf2 Tf3 LED Fläkt Woods EN 2013.05 16 All rights reserved. Fire damper ETPS-EI TECHNICAL DATA Dimensions ETPS-EI Structural lengths 500 and 400 mm Dimensions ETPS-EI Structural length 355 mm The bottom figure represents installation frame ER1 available as accessory. The damper is always installed using installation frame ER2 or ER3. Fläkt Woods EN 2013.05 17 All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Dimensions and weights Dimensions H K K355 K400 200 - 16 - K500 - 250 - 41 - - 300 - 66 17 - 350 - 91 42 - 375 - 103 54 - 400 - 116 67 - 450 - 141 92 - 500 - 166 117 17 550 - 191 142 42 600 7 216 167 67 650 32 241 192 92 700 57 266 217 117 750 82 291 242 142 800 107 316 267 167 Weights (Structural length 500 mm, model with fuse. Motorized model + 3 kg) H B 200 250 300 350 400 450 500 550 600 650 700 750 800 200 10 11 12 13 14 15 15 16 17 18 19 19 20 250 11 12 13 14 15 16 17 17 18 19 20 21 22 300 12 13 14 15 16 17 18 19 20 21 22 22 23 350 13 14 15 16 17 18 19 20 21 22 23 24 25 400 14 15 16 17 18 19 20 21 22 23 24 26 27 450 15 16 17 18 19 20 21 23 24 25 26 27 28 500 15 17 18 19 20 21 23 24 25 26 27 29 30 550 16 17 19 20 21 23 24 25 26 28 29 30 31 600 17 18 20 21 22 24 25 26 28 29 30 32 33 650 18 19 21 22 23 25 26 28 29 30 32 33 35 700 19 20 22 23 24 26 27 29 30 32 33 35 36 750 19 21 22 24 26 27 29 30 32 33 35 36 38 800 20 22 23 25 27 28 30 31 33 35 36 38 39 850 21 23 24 26 28 29 31 33 34 36 38 39 41 900 22 24 25 27 29 30 32 34 36 37 39 41 42 950 23 25 26 28 30 32 33 35 37 39 41 42 44 1000 24 25 27 29 31 33 35 36 38 40 42 44 46 1050 24 26 28 30 32 34 36 38 40 42 43 45 47 1100 25 27 29 31 33 35 37 39 41 43 45 47 49 1150 26 28 30 32 34 36 38 40 42 44 46 48 50 1200 27 29 31 33 35 37 39 42 44 46 48 50 52 1250 28 30 32 34 36 38 41 43 45 47 49 51 54 1300 28 31 33 35 37 40 42 44 46 49 51 53 55 1400 30 32 35 37 40 42 44 47 49 51 54 56 58 1500 32 34 37 39 42 44 47 49 52 54 57 59 62 * Note! Special sizes available at 10 mm intervals (BxH). Fläkt Woods EN 2013.05 18 All rights reserved. Fire damper ETPS-EI TECHNICAL DATA Accessories Extension piece FLRW-aaaa-bbb Reducer flange/slip joint FORW-aaaa-bbb 180 mm Protective grille (B x H) FNRW-aaaa-bbb B+78xH+78 7 Installation frame for gypsum plate wall ER1 Installation frame FBRW-aaaa-bbb See page 11 120 10 Installation frame for solid wall or intermediate floor ER2 B+65xH+65 Support profile FURW-aaaa See page 23 135 Installation frame for gypsum plate wall ER3 Reducer rectangular/circular FDRW-800 105 8 220 B+78xH+78 880 880 00 Ø8 135 Fläkt Woods EN 2013.05 19 All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Product code Description Accessories Fläkt Woods CE marked fire damper ETPS-EI which is suitable for installation into building elements of fire class EI 60 / EI 90 / EI 120 made of rock material, or gypsum plate walls of fire class EI 60 / EI 90. The damper is installed according to the mounting instructions provided by the manufacturer. Reducer flange / slip joint Width 200 – 1500 (mm) Height 200 – 800 (mm) Protective grille FNRW-aaaa-bbb Width 200 – 1500 (mm) Height 200 – 800 (mm) Product code Fire damper FORW-aaaa-bbb ETPS-EI-aaaabbbCde Extension piece FLRW-aaaa-bbb The structural length is always 180 mm Width 200 – 1500 mm (aaaa) Height 200 – 800 mm (bbb) Width 200 – 1500 (mm) Height 200 – 800 (mm) Structural length (C) A = 500 mm, standard B = 400 mm C = 355 mm (Installation requires installation frame ER2 or ER3. Fire class EI 60 / EI 90.) Installation frame FBRW-aaaa-bbb Width 200 – 1500 (mm) Height 200 – 800 (mm) Actuator (d) 1 = fuse + 70°C with microswitch 2 = fuse + 70°C with two microswitches 3 = 24 V AC/DC motor with heat detector 5 = 230V AC motor with heat detector Support profile Installation frame (e) 0 = no frame 1 = ER1, for gypsum plate wall 2 = ER2, for solid wall or intermediate floor 3 = ER3, for gypsum plate wall Round connection Ø800 (mm) available for size 800 – 800 FURW-aaaa Width 200 – 1500 (mm) Height 200 – 800 (mm) Reducer rectangular / round Control system FDRW-800 FICO-128 / FICO-2 See separate brochure. Order example: ETPS-EI-1500800A30 size 1500 x 800 mm, length 500 mm, 24 V motor with heat detector, no frame ETPS-EI-0800800B11 size 800 x 800 mm, length 400 mm, fuse with micro­ switch, ER1 frame Accessories for damper with fuse Microswitch Microswitch with one closing and opening switch pair (standard) E-a. a = switch installation location 1 = closed (always the case with dampers with fuse) 2 = open 3 = both open and closed Spare parts Fuse 70° C (spare part) ETPS-99-01 Fuse 90° C (spare part) ETPS-99-02 Fläkt Woods EN 2013.05 20 All rights reserved. Fire damper ETPS-EI TECHNICAL DATA Installation in building elements of rock material Complete installation, operation and maintenance instructions can be found on the Fläkt Woods home page www.flaktwoods.fi. Installation instructions, along with an installation certificate, are also delivered with every fire damper. For additional information, contact the nearest Fläkt Woods sales representative. Installation of fire damper into building elements (walls or intermediate floors) made of rock material (concrete, lightweight concrete or brick) and having fire class EI 60 / EI 90. Damper length 355 mm, installation frame ER2. Installation of fire damper into building elements (walls or intermediate floors) made of rock material (concrete, lightweight concrete or brick) and having fire class EI 60 / EI 90 / EI 120. Damper length 400 mm or 500 mm. ER2 n mi 0 10 mm 0 10 in mm m Building element of rock material. Element penetration min. (B+80 mm) x (H+80 mm). Element penetration min. (B+80 mm) x (H+80 mm). Two adjoining fire dampers. Fläkt Woods EN 2013.05 21 All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Installation into building elements made of gypsum plate or similar material Complete installation, operation and maintenance instructions can be found on the Fläkt Woods home page www.flaktwoods.fi. Installation instructions, along with an installation certificate, are also delivered with every fire damper. For additional information, contact the nearest Fläkt Woods sales representative. Installation of fire damper equipped with installation frame ER1, into building elements made of gypsum plate or similar material. Fire class of building element EI 60 / EI 90, damper length 400 mm or 500 mm. Installation of fire damper with no frame into building elements made of gypsum plate or similar material. Fire class of building element EI 60 / EI 90, damper length 400 mm or 500 mm. ER 1 0 12 in mm 0 12 in m mm m The dimensions of the building element penetration must be fitted to the outer dimensions of ER1, which are: (B + 78 mm) x (H + 78 mm). Installation principle without installation frame ER1. Installation of short fire damper (355 mm), equipped with installation frame ER3, into building elements made of gypsum plate or similar material. Fire class of building element EI 60 / EI 90. ER 1 n mi 0 12 mm 0 2 n1 mi mm The dimensions of the building element penetration must be fitted to the outer dimensions of ER3, which are: (B + 78 mm) x (H + 78 mm). Fläkt Woods EN 2013.05 22 All rights reserved. Fire damper ETPS-EI TECHNICAL DATA Installation outside building element Complete installation, operation and maintenance instructions can be found on the Fläkt Woods home page www.flaktwoods.fi. Installation instructions, along with an installation certificate, are also delivered with every fire damper. For additional information, contact the nearest Fläkt Woods sales representative. Installation of fire damper outside building element. Fire class of construction element EI 60 / EI 90, damper length 500 mm or 400 mm. Fixing frame FBRW Support profile FURW Support profile FURW Installation outside building element. Fläkt Woods EN 2013.05 Installation onto outer surface of building element, using fixing frame FBRW. 23 All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Microswitch – wiring diagram ‘Damper closed’ microswitch (standard version) Alternative microswitch location ‘damper open’ Brown White Green ‘Damper closed’ microswitch (E-closed, standard version) Damper closed Damper open Brown Brown White White Green Green ‘Damper open’ microswitch (E-open) Damper closed Fläkt Woods Damper open Brown Brown White White Green Green EN 2013.05 24 All rights reserved. Fire damper ETPS-EI TECHNICAL DATA Replacing the fuse Note! When replacing the fuse, use caution with special attention to the spring-loaded blade. B. E. D. C. A. A. Fixing screw B. Locking screw C. Fuse applicator D. New fuse E. Old fuse cartridge 1. Unscrew the fixing screws (4xM8) and remove the actuator from the damper. Fläkt Woods EN 2013.05 2. Loosen the fuse locking screw by turning it in the ‘open’ direction. 25 3. Use the slot at the end of the fuse mechanism to turn the mechanism clockwise to the next notch: the fuse is released by the spring load. All rights reserved. TECHNICAL DATA Fire damper ETPS-EI Replacing the fuse, cont. 4. Pull out the fuse mechanism and push out the old fuse cartridge through the actuator. 5. To install the new fuse, place it onto the spring mechanism. 6. Turn the fuse mechanism into place and secure it by turning the locking screw in the ‘close’ direction. 7. Before fixing the actuator, open the damper blade (the notch in the shaft indicates the blade position). 8. Set the actuator open and fix it to the damper with the fixing screws. 9. To check the operation, trigger the actuator by pressing the red test button (the damper should close). Reset the damper. Fläkt Woods EN 2013.05 26 All rights reserved.