MV Network Management MERLIN GERIN Easergy Range

advertisement
MV Network Management
Fault tracking, monitoring and control
MERLIN GERIN Easergy Range
Fault Passage Indicator for underground MV Network
Easergy Flair 279 - Flair 219
Application
The Fault Passage Indicators Flair 279 and Flair 219 are dedicated to underground MV
networks with direct, resistive or isolated with restriction earthing.
Flair 279 : MV/LV substation with a 220Vac power supply
Flair 219 : Distribution MV/MV substation without power supply
Description
Flair 279 and Flair 219 boxes are made of polycarbonat ABS including a lead locking.
b Detection system is fully configurable on site by means of dip-switches.
v Fault current setting (earth fault and phase fault)
v Fault current time duration
v Light indication duration
v Reset mode
b Lithium battery for :
v Detector and outdoor light power supply (Flair 219)
v Power supply backup (Flair 279)
b TEST and RESET function
v By push button on the box
b Light indication
v Fault current : LED on the box and outdoor flashing light
v LV supply presence : LED on the box (Flair 279)
b Terminal block : Power supply, current transformers
b SCADA link : Dry contact
b Phase to earth and phase to
phase fault detection and
indication
b On site configuration (fault
setting, duration, reset mode)
b Bardin genuine technology
Sensors
b The detectors allow three types of sensors mounting :
v Type A mounting : 3 phase CT for phase to earth fault >20A and phase fault
v Type B mounting : 2 phase CT and one single core CT for earth fault setting
>5A (Flair 279).
v Type C mounting : one single core CT for earth fault detection only
b Sensors
v MF1 CT self-locking for phase current measurement (cable < Æ 60mm)
v Encapsulated waterproof for phase current measurement (cable < Æ 45mm)
v Single core waterproof CT, for earth fault current measurement (cable < Æ 146mm)
MF1 CT
Encapsulated CT
Waterproof CTW
Light indication
b Standard box
Outdoor mounting
b Discret lamp box
b Light
Mounted inside the
substation, with a 30 cm
optical fiber light guide
Mounted on thin plate
(door or metallic
enclosure)
Get more with world’s Power & Control specialist
Characteristics
Flair 279
Flair 219
4 kV to 36 kV
50 Hz and 60 Hz
Direct - resistive - isolated
MV/LV
4 kV to 36 kV
50 Hz and 60 Hz
Direct - resistive - isolated
MV/MV
Earth fault setting : Type A mounting
20-25-30-35-40-50-60-70-80
100-120-140-160
Earth fault setting: Type B mounting and single CT
5-10-15-20-25-30-35-40-5060-70-80-100-120-140-160
Phase fault setting : Type A and B mounting
225-450-575-700
20-30-40-50-60-70-80-90
100-110-120-130-140-150160
10-20-30-35-40-50-60-7080-90-100-110-120-130140-160
225-450-700-1200
50-100-200-350
50-100-200-300
On voltage recovery
2-4
Push button
On current recovery *
1-2-4-8-16-24-32-96
Push button
7
3s (0 to 2h) - 5s (2 to 4 h)
400
7
from 2 to 8s
800
230 Vac (±10%)
Insulation 10 kV
> 10
Without
-15 to +70
IP 21 (54 as an option)
-15 to +70
IP 21 (54 as an option)
250 x 160 x 65
0,8
250 x 160 x 65
0,8
IEC 68-2-6
IEC 68-2-29
IEC 1000-4
IEC 1000-6/10
IEC 1000-4-2 / 8 kV
IEC 68-2-6
IEC 68-2-29
IEC 1000-4
IEC 1000-6/10
IEC 1000-4-2 / 8 kV
Application
Network
Frequency
Neutral system
Substation
Earth bread
mounting
Fault detection
Type A mounting
Temporisation
Fault duration (ms)
Reset
3s delay after power recovery
Long duration delay (h)
Manually on the box
Outdoor light indication
Total light flow (Lm)
Flashing period (s)
Standard flashing capacity (h)
Power supply
External power supply
Lithium battery : standard life duration (years)
Type B mounting (except 219)
> 10
Environment
Operational temperature (°C)
Protection
Mechanical characteristics
Dimension (mm) H x L x D
Net weight (kg)
Norme
Mechanical tests
Electrical tests
Type C mounting
* except single core mounting
References
59956
59958
59963
59964
Flair 279A
Flair 279B
Flair 219A
Flair 279 type A and C
Flair 279 type B
Flair 219 type A and C
59959
59967
59967
BVE
LED
BVD
Standard ourdoor lamp box
Light
Discreet lamp box
MF1
CTW
CTR
Standard CT
CTW waterproof CT
Encapsulated CT
59962
FCA
Type A bundle type A
59965
59966
BAT 279
BAT 219
Flair 279 spare battery
Flair 219 spare battery
Bundle
Kits
The kits include
KFlair 279A - xxx
KFlair 279AR - xxx
KFlair 279B - xxx
KFlair 279C - xxx
Detector
Flair 279A
Flair 279A
Flair 279B
Flair 279A
KFlair 219A - xxx
KFlair 219AR - xxx
KFlair 219C - xxx
Flair 219A
Flair 219A
Flair 219A
Number of CT
MF1
CTR
CTW
3
3
2
1
1
3
BVE
59969
xxx = lamp
BVD
LED
59971
59977
59974
59976
59978
3
1
ENMED300020EN
the bundle
Schneider Electric
Industries SA
Postal address
F - 38050 Grenoble Cedex 9
Tél : +33 (0)4 76 57 60 60
As standards, specifications and design change from time to
time, always ask for confirmation of the information given in
this publication.