Liquid Level Control

advertisement
Presentation,
description
1
Zelio Control-modular measurement
and control relays
1
Level control relays RM35 L
Presentation
105685
Level control relays RM35 LM33MW and RM35 LV14MW control one or two levels,
with fill or empty function:
2 RM35 LM33MW: control by resistive level probe,
2 RM35 LV14MW: control by discrete sensor.
Settings are protected by a sealable cover.
Control status is indicated by a LED.
The relays are designed for clip-on mounting on 4 rail
Applications
These devices monitor the levels of conductive liquid or non-conductive material.
They control the actuation of pumps or valves to regulate levels. They are also
suitable for protecting submersible pumps against dry running, or protecting tanks
from "overflow". They can also be used to control dosing of liquids in mixing
processes and to protect heating elements in the event of non immersion.
They have a transparent, hinged cover on their front panel to avoid any accidental
alteration of the settings. This cover can be directly sealed.
RM35 L111MW
2
5
5
5
5
5
Application examples for RM35 LM33MW:
spring, town, industrial and sea water,
metallic salt, acid or base solutions,
liquid fertilizers,
non concentrated alcohol (< 40 %),
liquids in the food-processing industry: milk, beer, coffee, etc.
2
5
5
5
5
Application examples for RM35 LV14MW:
chemically pure water,
fuels, liquid gasses (inflammable),
oil, concentrated alcohol (> 40 %),
ethylene, glycol, paraffin, varnish and paints.
Description
RM35 LM33MW
A1 A2
Min Max C
Tt
Un
1
2
3
4
R
1 Configuration: selection of operating
mode:
/
and of sensitivity
range. LS, St, HS.
2 Sensitivity adjustment potentiometer. %
3 Switch for selecting the number of levels.
4 Time delay adjustment potentiometer. Tt
5 Spring for clip-on mounting on 35 mm
4 rail.
12 11 14 22 21 24
5
RM35 LV14MW
12V12V Min Max 0V
Tt
1
2
3
Un
1 Configuration: selection of operating
mode:
/
and of sensor type
PNP, NPN.
2 Time delay adjustment potentiometer. Tt
3 Switch for selecting the number of levels.
4 Spring for clip-on mounting on 35 mm
4 rail.
R
A1 A2
12 11 14
4
Tt Yellow LED: indicates timing status.
Un Green LED: indicates that supply to the relay is on.
R Yellow LED: indicates relay output state.
Operation:
pages 53 to 55
52
Characteristics:
pages 56 and 57
References, dimensions :
page 57
Operation
1
Zelio Control-modular measurement
and control relays
Level control relays RM35 L
Operating principle
Control relays RM35 LM and RM35 LV are designed to control levels of:
2 Conductive liquid for RM35 LM,
2 Any other material for RM35 LV.
Relay RM35 LM measures the levels by means of resistive probes.
Relay RM35 LM controls the levels of conductive liquids.
The operating principle is based on measurement of the apparent resistance of the
liquid between two submerged probes. When this value is less than the threshold
setting on the front panel of the device, the relay changes state. To avoid electrolytic
phenomena, an a.c. current runs across the probes. A selector switch on the front
panel allows selection of the required function and sensitivity range. Control of one
single level can be achieved by using the 2nd selector switch.
In this case, the Max level probe stays up in the air and an adjustable time delay
avoids any wave effect.
Relay RM35 LV measures the levels by means of discrete sensors.
These two products activate their output relay when a tank is either emptying or
filling.
A green LED indicates that the supply is ON.
A yellow LED indicates the state of the output relay.
A yellow LED indicates that timing is in progress.
The green and yellow LEDs flash to indicate an unacceptable setting position.
Level control relay: RM35 LM33MW
Configuration
A selector switch on the front panel allows selection of the required sensitivity range
and of the empty or fill function.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.
2 Control of two levels
5 empty function
Function diagram
2 Fill/Empty function
level: 2, function:
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
The output relay stays open until the liquid reaches the Max. level probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. level, the
contact opens to stop the emptying process.
Supply Un
Max. level
Min. level
Relays
11-12/11-14
21-22/21-24
Relays
11-12/11-14
21-22/21-24
Note: When two levels are controlled, the anti-wave time delay function is not active.
5 fill function
level: 2, function:
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
The output relay stays energised until the liquid reaches the Max. level probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. level, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.
Presentation, description :
page 52
Characteristics:
pages 56 and 57
References, dimensions :
page 57
53
1
Operation (continued)
1
Zelio Control-modular measurement
and control relays
Level control relays RM35 L
Level control relay: RM35 LM33MW (continued)
Configuration (continued)
2 Control of one level, empty function
5 level: 1 - on delay functions:
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
Function diagrams
2 Empty function T on
Supply Un
Level
Relays
When the liquid level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level drops back down to the probe.
If the liquid drops back down to below the set level before the end of the time delay,
the relay does not energise.
11-12/11-14
21-22/21-24
Tt
Tt
Tt
2 Empty function T off
5 level: 1 - off delay functions:
-
Supply Un
Level
Relays
11-12/11-14
21-22/21-24
Tt
Tt
Tt
Tt
-
Supply Un
Level
Tt
Tt
2 Fill function T off
5 level: 1 - off delay functions:
-
Supply Un
Level
11-12/11-14
21-22/21-24
Tt
Presentation, description :
page 52
54
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
liquid level rises back up to the probe.
If the liquid rises back up to above the set level before the end of the time delay
period, the relay does not energise.
11-12/11-14
21-22/21-24
Tt
Relays
When the liquid level rises above the probe, the relay instantly energises and stays
energised until the liquid again reaches the probe level for a time Tt set on the front
panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.
2 Control of one level, fill function
5 level: 1 - on delay functions:
2 Fill function T on
Relays
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
Tt
Characteristics:
pages 56 and 57
Tt
LS (Low Sensitivity: 250 Ω…5 kΩ),
St (Standard Sensitivity: 5 kΩ…100 kΩ),
HS (High Sensitivity: 50 kΩ…1 MΩ).
When the liquid level drops below the probe, the relay instantly energises and stays
energised until the liquid level again reaches the probe level and stays above it for
a time greater than the time delay period Tt set on the front panel.
If the liquid drops back down to below the set level before the end of the time delay
period, the relay stays energised.
References, dimensions :
page 57
1
Operation (continued)
1
Zelio Control-modular measurement
and control relays
Level control relays RM35 L
Level control relay: RM35 LV14MW
Configuration
A selector switch on the front panel allows selection of the function (empty or fill) and
the type of sensor.
A second switch allows selection of the number of levels (1 or 2) and the type of time
delay in the case of 1 level mode.
The configuration of these switches is taken into account on energisation.
If the switch is set to an unacceptable position, the product detects a fault, the output
relay stays open and the LEDs flash to signal the position error.
If the switch position is changed while the device is operating, all the LEDs flash, but
the product continues to operate normally with the function selected at the time of
energisation preceding the change of position.
The LED's return to their normal state if the switch is returned to the original position
selected prior to the last energisation.
2 Control of two levels
Function diagram
56Fill/Empty function
5 empty function. Level: 2
The output relay stays open until the material level reaches the Max. probe. As soon
as the Max. level is reached, the contact closes and then allows emptying of the tank
(valve opens, pump starts, ...). When the level drops below the Min. probe, the
contact opens to stop the emptying process.
Supply Un
Max. level
Min. level
Relays
11-12/11-14
Relays
11-12/11-14
5 fill function. Level: 2
The output relay stays energised until the material level reaches the Max. probe. As
soon as the Max. level is reached, the contact opens and the pump stops. When the
level drops below the Min. probe, the contact closes again and pumping re-starts to
raise the level.
Note: When two levels are controlled, the anti-wave time delay function is not active.
2 Control of one level, empty function
Function diagrams
56Empty function T on
5 level: 1 - on delay
When the material level rises above the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level drops back down to the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.
Supply Un
Level
Relays
11-12/11-14
Tt
Tt
Tt
56Empty function T off
5 level: 1 - off delay
When the material level rises above the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays below it
for a time greater than the time delay value Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.
Supply Un
Level
Relays
11-12/11-14
Tt
Tt
Tt
Tt
2 Control of one level, fill function
56Fill function T on
5 level: 1 - on delay
When the material level drops below the probe for a time greater than the time delay
value Tt set on the front panel, the relay is energised and stays energised until the
material level again reaches the probe.
If the level rises above the probe before the end of the time delay period, the relay
does not energise.
Supply Un
Level
Relays
11-12/11-14
Tt
Tt
Tt
5 Fill function T off
5 level: 1 - off delay
When the material level drops below the probe, the relay instantly energises and
stays energised until the material level again reaches the probe and stays above it
for a time greater than the time delay period Tt set on the front panel.
If the level drops back down to below the probe before the end of the time delay
period, the relay stays energised.
Supply Un
Level
Relays
11-12/11-14
Tt
Presentation, description :
page 52
Tt
Characteristics:
pages 56 and 57
Tt
References, dimensions :
page 57
55
1
Characteristics
1
Zelio Control-modular measurement
and control relays
Level control relays RM35 L
Environment characteristics
Conforming to standards
Product certifications
Marking
Ambient air temperature
around the device
Storage
Operation
Permissible relative humidity
Vibration resistance
Shock resistance
Degree of protection
Conforming to IEC 60529
Conforming to IEC 60068-2-30
Conforming to IEC 60068-2-6
Conforming to IEC 60068-2-6
Casing
Terminals
2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)
0.035 mm from 10…150 Hz
5 gn
IP 30
IP 20
Degree of pollution
Overvoltage category
Insulation resistance
Rated insulation voltage
Insulation test voltage
Conforming to
IEC 60664-1/60255-5
Conforming to IEC 60664-1
Conforming to IEC 60664-1
Conforming to 60664-1/60255-5
V
Conforming to IEC 60664-1
kV
Dielectric test
kV
Shock wave
3
III
> 500 MΩ,
500 V
250
2,
50 Hz, 1 min.
4 (1.2/50 µs)
Connection
Maximum c.s.a.
Conforming to IEC 60947-1
Solid cable without cable end
mm2
Flexible cable with cable end
mm2
Tightening torque
Housing material
Power ON indicator
Relay state indicator
Timing indicator
Mounting position
without derating
Mounting
Pending
°C
°C
Conforming to IEC 60947-1
In relation to normal
vertical mounting plane
Conforming to IEC/EN 60715
Immunity to microbreaks
1
2
1
1 conductor: 0.5…4 (AWG 20…AWG 11)
2 conductors: 0.5…2.5 (AWG 20…AWG 14)
1 conductor: 0.2…2.5 (AWG 24…AWG 12)
2 conductors: 0.2…1.5 (AWG 24…AWG 16)
0.6…1N.m / 5.3…8.8 Lbf.In
Self-extinguishing plastic
Green LED
Yellow LED
Yellow LED
Any position
On
Supply characteristics
Supply voltage Un
Operating range
Voltage limits
Of the power supply circuit
Frequency
Of the power supply circuit
Galvanic isolation, supply/measurement
Maximum power consumption at Un
NF EN 60255-6 and IEC 60255-6
UL, CSA, GL, C-Tick, GOST
: 73/23/EEC and EMC 89/336/EEC
- 40…+ 70
- 20…+ 50
V
V
VA
W
ms
4 rail
1/2 24…240
1/2 20.4…264
- 15 %, + 10 %
50/60 Hz ± 10 %
Yes
5
1.5
90,
100
13
2
1 2
Immunity to electromagnetic interference
Electromagnetic compatibility
Immunity NF EN 61000-6-2 2002 / IEC 61000-6-2
Emission NF EN 61000-6-4
NF EN 61000-6-3
IEC 61000-6-4
IEC 61000-6-3
Measurement circuit and input characteristics
Relay type
Measurement range
Sub-measurement range
Sensitivity adjustment
Setting accuracy
Measurement error with temperature variation
Maximum voltage at the probe terminals
Maximum current across the probes
Maximum probe cable length
Maximum capacity of probe cable
V
mA
m
nF
RM35 LM33MW
RM35 LV14MW
250 Ω…1 MΩ
–
250 Ω…5 kΩ
–
5 kΩ…100 kΩ
–
50 kΩ…1 MΩ
–
5…100 % of the range
–
± 10 % of the full scale / ± 20 % for the HS range
0.5 % / °C
12
<1
40
100
100
1 for LS, 2.2 for St and 4.7 pour HS
10
Delay on pick-up
ms
600
Presentation, description :
page 52
56
LS
St
HS
Operation:
pages 53 to 55
References, dimensions :
page 57
500
1
Characteristics (continued)
references,
dimensions,
schemes
Zelio Control-modular measurement
and control relays
1
Level control relays RM35 L
1
Time delay characteristics
Relay type
Time delay on crossing the threshold
Repeat accuracy (with constant parameters)
Reset time
RM35 LM33MW
0.1…5, 0 + 10 %
±2%
1.75
s
s
RM35 LV14MW
4 if 1 line broken /
1 if 2 lines broken
Output characteristics
Type of output
Contact type
Nominal current
Maximum switching voltage
Rated breaking capacity
Minimum breaking current
Maximum breaking current
Electrical durability
Mechanical durability
Maximum operating rate
Utilisation categories
2 C/O contacts
1 C/O contact
Cadmium-free
5
/ 250
1250
10/
5V
/ 5
1 x 105 operating cycles
30 x 106 operating cycles
360 operations/hour under full load
AC-12, AC-13, AC-14, AC-15, DC-12, DC-13
A
V
VA
mA
A
12
2
12
Conforming to IEC 60947-5-1
References
105686
12
Detection by
resistive probes
(see page 58)
1/2 24…240
Detection by
discrete sensors
(see page 60)
RM35 LV14MW
Dimensions
Schemes
RM35 LM33MW, RM35 LV14MW
RM35 LM33MW
Output
Reference
Weight
2 C/O
5A
RM35 LM33MW
kg
0.130
1 C/O
5A
RM35 LV14MW
0.130
RM35 LV14MW
35/1.38
14
22
NC 12V 12V Min Max
21
24
A2
12
11
14
12
A1
0V
11
A2
C
A1
11
11
A2
12
Min Max
12
A1
A2
14
2,8
0.11
90/3.54
A1
14
22
72/2.83
21
RM35 LM33MW
Supply
voltage
V
/ 24…240
24
105685
Function
76/2.99
72,5/2.85
mm/In.
Presentation, description :
page 52
Operation:
pages 53 to 55
Characteristics:
pages 56 and 57
57
References
1
Zelio Control-modular measurement
and control relays
1
Electrode holders and probes
Probes
Application
No.
Length
of
probes
Recommended
3
for drinks vending
machines and
where installation
space is limited
(Stainless steel)
1
Suitable for
boilers, pressure
vessels and under
high temperature
conditions (1)
(304 stainless
steel)
mm
1000
Operating
temperature
°C
80
kg/cm2
2
RM 79 696 044
kg
0.800
1000
200
25
RM 79 696 014
0.360
561034
Description
Protected probe
for mounting by suspension
RM 79 696 043
Description
Type of
installation
Liquid level
control probe
Suspended
by cable
Maximum
pressure
Reference
Weight
Material
Reference
Protective shell
PUC (S7)
Electrode : stainless
steel
RM 79 696 043
Weight
kg
0.150
Maximum operating
temperature
°C
100
Reference
Weight
Material
Reference
Stainless steel
isolated by ceramic
RM 79 696 006
kg
0.100
LA9 RM201
LA9 RM201
Electrode holders
561036
561035
Description
Electrode for use up to 350 °C
and 15 kg/cm2 (2)
Weight
kg
0.150
(1) 3/8" BSP mounting thread with hexagonal head. Use a 24 mm spanner for tightening.
(2) 3/8" BSP mounting thread.
RM 79 696 006
Dimensions :
page 59
58
Dimensions
1
Zelio Control-modular measurement
and control relays
Electrode holders and probes
Probes
RM 79 696 044
38,5
32
11
7 12
14
Ø 11
PF 1/2
3
26
100
Ø 27,5
RM 79 696 014
Ø6
G 3/8A
1000
60
60
RM 79 696 043
Ø 25
80
16
LA9 RM201
150
Electrode holder
29
13
5/32 whit
6,5
20,7
1/4 whit
84
46
9,5
Across flats
RM 79 696 006
3/8 tapered NPT
49
References :
page 58
59
1
References
1
Ultrasonic sensors
Osisonic®,
1
Optimum and Universal
564546
Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5
d.c. supply, solid-state output
Optimum sensors
Sensors
Ø 12
XX5212A1KAM8
5664547
532713
Ø 18
532243
Function
Output
Reference
NO
NO
0.15
NO
PNP/NPN
NPN
PNP
PNP/NPN
XX5 12A1KAM8
XX5 12A2NAM8
XX5 12A2PAM8
XX5 18A1KAM12
kg
0.011
0.011
0.011
0.033
Ø 18
0.50 (adjustable) NO
NPN
PNP
XX5 18A3NAM12
XX5 18A3PAM12
0.033
0.033
Ø 30
1 (adjustable)
NO
NO + NC
8 (adjustable)
NO + NC
PNP/NPN
NPN
PNP
NPN
PNP
XX6 30A1KAM12
XX6 30A1NCM12 (1)
XX6 30A1PCM12 (1)
XX6 30A3NCM12
XX6 30A3PCM12
0.091
0.091
0.091
0.110
0.110
XX5218A31AM12
Accessories
Teach mode pushbutton
Teach mode pushbutton
XX6230A1KAM12
Selection of detection window
Input: M12 female connector
Output: M12 male connector
XX6230A31CM12
564530
564533
For use with
sensors
XX5 18A3 7AM12
and XX7 V1A1 7AM12
M8
For use with
sensor
Ø 12
Type
Connection by
in-line IDC
Connection to
solder terminals
XZ2CC12FD140B
XXZ PB100
M12
Ø 18, Ø 30
Metal
clamping ring
Plastic
clamping ring
564534
Pre-wired
connectors
M8
For use with
sensor
Ø 12
Type
Straight
Elbowed
564535
XZ2CP1041L1
M12
Ø 18, Ø 30
XSZ B111
Straight
Elbowed
564532
Reference
XXZ PB100
Weight
kg
0.035
Cabling accessories (4-wire output) (3)
Connectors
Reference
Straight
Elbowed
Straight
Elbowed
Straight
Elbowed
Straight
Elbowed
Length
m
2
5
10
2
5
10
2
5
10
2
5
10
XZ CC8FDM40V
XZ CC8FCM40V
XZ CC8FDM40S
XZ CC8FCM40S
XZ CC12FDM40B
XZ CC12FCM40B
XZ CC12FDP40B
XZ CC12FCP40B
Reference
XZ CP0166L2
XZ CP0166L5
XZ CP0166L10
XZ CP0266L2
XZ CP0266L5
XZ CP0266L10
XZ CP1141L2
XZ CP1141L5
XZ CP1141L10
XZ CP1241L2
XZ CP1241L5
XZ CP1241L10
Weight
kg
0.010
0.010
0.010
0.010
0.020
0.020
0.020
0.020
Weight
kg
0.080
0.180
0.360
0.080
0.180
0.360
0.090
0.190
0.370
0.090
0.190
0.370
Fixing accessories
Description
Fixing clamps
XUZ A118
532517
Weight
Universal sensors
564531
XX5218A1KAM12
Sensing
distance (Sn)
m
0.05
0.10
XUZ 2001
90° fixing bracket
XUZ B20
3D fixing kit (2) M12 rod
Support for
M12 rod
Ball-joint
mounted
fixing bracket
3D fixing kit example
60
Reference
XSZ B112
XSZ B118
XXZ 12
XUZ A118
XXZ 30
XUZ 2001
XUZ 2003
Weight
kg
0.006
0.010
0.025
0.038
0.115
0.050
0.160
Ø 12
XUZ B2012
0.175
Ø 18
XUZ B2003
0.175
Ø 30
XUZ B2030
0.160
(1) Sensor available with stainless steel 303 case. To order, replace the 1st letter A by the letter S.
(2) To obtain a 3D fixing kit, order:
rod support XUZ 2003, M12 rod XUZ 2001 and ball-joint mounted fixing bracket XUZ B2011.
(3) For 3-wire cabling accessories, refer to the Global Detection catalogue.
XUZ 2003
Characteristics:
page 61
For use with
sensor
Ø 12
Ø 18
Ø 12
Ø 18
Ø 30
Ø 12, Ø 18 and Ø 30
Ø 12, Ø 18 and Ø 30
Dimensions:
page 62
Schemes:
page 63
Characteristics,
setting-up
Ultrasonic sensors
Osisonic®,
1
1
Optimum and Universal
Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5
d.c. supply, solid-state output
Sensor type
XX5
12A12222
Characteristics
XX5
12A22222
XX5
18A1 2222
XX5
18A32222
XX6
30A12222
XX6
30A32222
6
Product certifications
Conformity to standards
Connection
Sensing range
Nominal sensing distance (Sn)
Operating distance
IEC 60947-5-2, UL508 pending and CSA C22-2 n° 14 pending
M8 - 4-pin
M8 - 3-pin
M12 - 4-pin
6.4…51
6.4…102
19…152
51…508
51…991
203…8000
0.05
0.1
0.15
0.50
1
8
6.4…51
6.4…102
25…152
Adjustable using teach mode
Fixed
Fixed
Fixed
< 0.7
< 0.7
< 0.35
< 2.5
< 2.5
< 12.7
0…6.4
0…6.4
0…19
0…51
0…51
0…203
Connector
mm
m
mm
Differential travel
Blind zone (no object must pass through this zone whilst the
sensor is operating)
Transmission frequency
Repeat accuracy
Overall beam angle (see detection lobe)
Minimum size of object to be detected
Degree of protection
mm
mm
kHz
mm
500
± 0.7
11°
10°
8°
Cylinder Ø 2.5 mm or flat bar Cylinder
1 mm wide
Ø 1.6 mm
°C
°C
Case
Sensing face
Vibration resistance
To IEC 60068-2-6
Mechanical shock resistance
To IEC 60068-2-27
Resistance to electromagnetic interference
Electrostatic discharges
To IEC 61000-4-2
Radiated electromagnetic fields
To IEC 61000-4-3
Fast transients
To IEC 61000-4-4
LED indicators
Output state
- 40…+ 80
- 20…+ 65
0…+ 50
ULTEM®
Epoxy
Silicone
Amplitude ± 1 mm (f = 10…55 Hz)
30 gn, duration 11 ms, in all 3 axes
kV
V/m
kV
Setting-up assistance
First-up
Response
Recovery
75
± 2.54
16°
Cylinder
Ø 50.8 mm
up to a
sensing
distance of
4732 mm
- 20…+ 65
Valox®
Epoxy
0…+ 60
ULTEM®
Silicone
- 20…+ 60
Epoxy
8, level 4
10, level 3
1, level 3
Yellow LED, Yellow LED –
Yellow LED Yellow LED, Yellow LED,
rear
rear
rear
Green LED, Green LED –
Green LED –
–
rear
–
–
–
Dual colour Multicolour LED, rear
12…24 V with protection against reverse polarity
10…28 V
25
60
40
50
< 100 (PNP and NPN) with overload and short-circuit protection
< 1 (PNP and NPN)
125
125
80
40
10
2
20
20
350
100
720
800
2
3
3
10
20
200
2
3
3
10
20
200
± 10°
± 10°
± 10°
± 7°
± 7°
± 5°
Power on
Rated supply voltage
Voltage limits (including ripple)
Current consumption, no-load
Switching capacity
Voltage drop
Maximum switching frequency
Delays
200
± 0.9
10°
Cylinder
Ø 1.6 mm
up to a
sensing
distance of
635 mm
IP 65
IP 67
Conforming to IEC 60529
and IEC 60947-5-2
Storage temperature
Operating temperature
Materials
300
± 1.27
6°
Cylinder
Ø 2.5 mm
up to a
sensing
distance of
150 mm
2
2
V
V
mA
mA
V
Hz
ms
ms
ms
Deviation angle from 90° of the
object to be detected
Setting-up precautions
Minimum mounting distances
Side by side
e
e: respect the distances indicated on the
detection curves shown on page 63.
References:
page 60
Dimensions:
page 62
Face to face
e
e = 4 x Sn max.
Schemes:
page 63
61
Dimensions
1
Ultrasonic sensors
Osisonic®,
1
Optimum and Universal
Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5
d.c. supply, solid-state output
Dimensions
XX5 12A22AM8
XX5 18A37AM12
XX5 18A1KAM12
M18x1
M12x1
38
M18x1
43
51
50
XXZ PB100
XX6 30A32CM12
XX6 30A1KAM12
63
M12x1
M30x1,5
Ø43,2
M30x1,5
20
(1)
4,7
77,7
65
14,5
16
45
64,3
20
85
(1) Cable, length: 152.4 mm.
42,1
117,35
Accessories
XUZ A118
90° fixing bracket (Ø 18)
2,5
XXZ 12, XXZ 30
90° fixing bracket (Ø 12 and Ø 30)
G
Ø18,2
50
c1
10
Ø5
b
H
35
Ø1
=
28
=
15
=
16,5
XXZ
12
30
20
a
35
67
b
40
65
c
33
52
c1
18
25
e
2
3
H
31
51
G
18
35
G1
18
33
Ø
25
50
40
12
19
126
132
55
a1
a
1,9
3,5
(1)
Ø1
13
31
XUZ 2003
Support for M12 rod
b1
XUZ 2001
M12 rod
b2
b
XSZ B112, XSZ B118
Fixing clamps (Ø 12 and Ø 18)
38,3
Ø
a
c
6,5
=
10
6,5
G1
e
1
53
23
81,7
46,3
13
67
M4
M4
M3
76,5
62
40
67
40
33
Ø12,4
XUZ 2030
Ball-joint mounted fixing bracket (Ø 30)
6
42,2
Ø30,5
24,1
XUZ B2003
Ball-joint mounted fixing bracket (Ø 18)
5,7
36
Ø18,5
5,7
36
Ø
12
18
M12
19
b2
8.5
11.5
40
XSZ
a
a1
b
b1
B112
21.9
14.5
16
15.5
B118
26
15.7
22.3
20.1
(1) 2 elongated holes Ø 4 x 8.
XUZ B2012
Ball-joint mounted fixing bracket (Ø 12)
50
19
22,9
76,5
36
8
33
22,3
4
22,9
90,5
22,9
Curves,
schemes
Ultrasonic sensors
1
Osisonic®,
1
Optimum and Universal
Cylindrical plastic case, M12 x 1, M18 x 1, M30 x 1.5
d.c. supply, solid-state output
Detection curves
XX5 12A22NAM8
XX5 12A1KAM8
XX5 18A32AM12
XX5 18A1KAM12
mm
30
mm
30
mm
120
mm
300
20
20
80
200
10
40
100
-10
-40
-100
-80
-200
10
-10
-20
-20
-30
0
10
20
30
40 50 60
mm
-120
-30
0
2
4
6
8
10
cm
-300
0
50
100
150
200
mm
0 65 190 320 445 570
mm
XX6 30A12CM12
XX6 30A32CM12
mm
400
cm
400
300
300
200
200
100
100
-100
-100
-200
-200
-300
-300
-400
-400
Blind zone
0
20
40
60
0
80 100
cm
2
4
6
8m
Wiring schemes
M8 connector
XX5 12A1KAM8
4-wire type
2
4
1
NO outputs, PNP and NPN
NPN
PNP
NO outputs, PNP
1/BN
1/BN
NPN
4/BK
2/WH
4/BK
PNP
1
3/BU
2 PNP output
4 NPN output
NO outputs, NPN
4
1/BN
3
1 (+)
3 (-)
XX5 12A22
3-wire type
3
3/BU
4/BK
3/BU
(-) BU (Blue) (+) BN (Brown)
WH (White) BK (Black)
1 (+)
3 (-)
4 NPN or PNP output
(-) BU (Blue) (+) BN (Brown)
BK (Black)
NO outputs, PNP and NPN
XX5 18A32
3-wire type
NO outputs, NPN
M12 connector
XX5 18A1KAM12
4-wire type
4
3
4
1/BN
NPN
PNP
2
1
4
3
(-) BU (Blue) (+) BN (Brown)
WH (White) BK (Black)
NO outputs, PNP and NPN
3/BU
3
4
M12 male
connector
1
1
Sensor side
NC
NO
4
4/BK
3/BU
(-) BU (Blue) (+) BN (Brown)
BK (Black)
NO + NC outputs, PNP
1/BN
NPN
2/WH 4/BK
2/WH
NC
NO
4/BK
3/BU
(-) BU (Blue) (+) BN (Brown)
WH (White) BK (Black)
XX5 18A3
XXZ PB100
3
2
2
3/BU
3/BU
1 (+)
2 PNP output
(-) BU (Blue) (+) BN (Brown)
3 (-)
4 NPN output
WH (White) BK (Black)
XXZ PB100 (teach mode pushbutton for XX5 18A37AM12)
1
2
1 (+)
3 (-)
4 NPN or PNP output
XX6 30A22CM12
NO + NC outputs, NPN
1/BN
NPN
4/BK
2/WH
M12 female
connector
4/BK
PNP
1/BN
2
1
1/BN
NPN
1
NPN
PNP
NO outputs, PNP
1/BN
4/BK
2/WH
3/BU
1 (+)
2 PNP output
3 (-)
4 NPN output
XX6 30A1KAM12
4-wire type
3
1/BN
1/BN
4/BK
4/BK
NO
3
3
4
4
2/WH
1
3/BU
3/BU
Output
XXZ PB100
1 (+) BN (Brown) 2 WH (White)
3 (-) BU (Blue)
4 BK (Black)
63