2457CS Series Catalog Page

advertisement
FIRE ALARM EQUIPMENT
Chime/Strobe
2457CS Series
FEATURES
> Low current draw synchronous
strobe
The Edwards 2457CS series is an audible/visual signal designed for
> Control modules not required
that is often preferred over the harsh noise of bells and horns. It is
> Red or white flame resistant
housing
often used in low ambient noise areas.
> Strobe available in 15, 30, 15/75,
and 110 candela models
all units operate at the same time and at a rate of one flash per
second.
> Chime may be pulsed up to 6
times per second
The 2457CS is designed for indoor wall or ceiling mounting. For
flush mounting use a 4" (102mm) square box with a depth of 2 1/8"
> Engineered thermoplastic
housing UL flame rated 94V-0
(54mm).
AGENCY APPROVALS
for installations that operate in conjunction with an installed fire
> Strobe - UL 1971 Listed for the
hearing impaired
alarm panel and detection devices.
> Strobe - UL 1638 Listed for
Private Mode Signaling
> Chime - UL 464 Listed for Private
Mode Signaling
use with life safety control equipment. The chime has a gentle tone
The strobes employ a unique microprocessor design that assures
The 2457CS chime/strobe is an audible/visual signaling appliance
ACCESSORIES
Cat. No.
Description
2459-SMB-R
2459-SMB-W
Surface mount box, red
Surface mount box, white
12-46
D-04
> CSFM Listed
90 Fieldstone Court |
Ph: 203.699.3300 |
Cheshire, CT 06410
Fx: 203.699.3108
www.edwards-signals.com
© Copyright 2004 Edwards
FIRE ALARM EQUIPMENT
TECHNICAL INFORMATION
5 1/2"
(140mm)
5 1/2"
(140mm)
5/8"
(16mm)
Catalog Number
2457CS-15-(†)
Operating Voltage
2457CS-15/75-(†)
2457CS-110-(†)
Chime: 20 to 24V DC Continuous or Pulsed up to 6 times per second
Strobe: 20 to 31V DC Continuous
Chime Current 4,1
Chime Output
2457CS-30-(†)
12 mA @ 24V DC / 12mA @ 24V DC FWR
886 Hz (+/- 70 Hz) Anechoic: 91 dBA Peak @ 24V DC
Reverberant: 70 dBA @ 24V DC, 64 dBA at minimum volume @ 20 to 24V DC
UL 1638 Strobe
Flash Output
Not UL 1638 Rated
30 cd
75 cd
110 cd
UL 1971 Strobe
Flash Output
15 cd
(Wall Mount Only)
30 cd Wall
15 cd Ceiling
15 cd Wall
15 cd Ceiling
110 cd Wall
60 cd Ceiling
Mean Operating
Current 1, 2
70 mA @ 24V DC
83 mA @ 20V DC
89 mA @ 24V DC
107 mA @ 20V DC
96 mA @ 24V DC
115 mA @ 20V DC
197 mA @ 24V DC
241 mA @ 20V DC
Peak Operating Current 2
156 mA @ 24V DC
189 mA @ 24V DC
204 mA @ 24V DC
338 mA @ 24V DC
Average Operating
Current FWR 3
58 mA @ 24V DC
69 mA @ 20V DC
75 mA @ 24V DC
91 mA @ 20V DC
79 mA @ 24V DC
97 mA @ 20V DC
338 mA @ 24V DC
202 mA @ 20V DC
Peak Operating
Current FWR 3
356 mA @ 24V DC
402 mA @ 24V DC
446 mA @ 24V DC
788 mA @ 24V DC
Operating Environment
Strobe Flash Rate
Synchronization Modules
Strobe Lens
Wire Connection
Lens Markings
Faceplate Material
85% relative humidity at 86°F (30°C); 32°F to 120°F (0° to 49°C) variable ambient temperature, indoor
Synchronized at one flash per second. External control module necessary to meet
UL 1971 synchronization requirements of 10 milliseconds over a two-hour period.
EG1M, EG1-RM
Clear Lexan
Terminals, Polarized Input, #12 AWG
Red "FIRE" Vertical Both Sides (Wall Mount)
Textured Color-Impregnated Noryl (Exceeds 94V-0 UL Flammability Rating)
90 Fieldstone Court |
Ph: 203.699.3300 |
Cheshire, CT 06410
Fx: 203.699.3108
www.edwards-signals.com
12-47
© Copyright 2004 Edwards
D-04
† Insert "R" for Red or "W" for white.
Note 1: Use the mean current rating to establish the maximum number of strobes, wire gauge and standby power requirements. 2400 Series uses 24V DC. Fire Shield uses 24V DC FWR.
Note 2: From a FILTERED DC source.
Note 3: From an UNFILTERED (Full Wave Rectified) DC source.
Note 4: When chime and strobe are connected in parallel to the same circuit the currents for each must be added together.
Download