Station Posts - End Fittings At lower voltages, corona rings may be considered for areas of high local contamination, and/or with altitudes > 3300 feet. Crimped End Fittings All end fittings are attached using a crimping process to achieve the required tensile strength. Class 100 IAA 100 XH Corona rings for 2 ½ and 3 ½ inch insulators will be included in proposals where MPS considers them necessary. Class 200 IAA 200 XV The user is ultimately responsible for the proper application of corona rings. Class 20 IPP 20 XG 0.67” 0.63” Ø 6.4” Ø 3.1” Ø 6.7” Ø 15.4” 0.67” Ø 3.1” Type P Type A Type A 4 Tapped Holes 1/2” - 13 UNC on 3” Dia. B.C. 4 Tapped Holes 5/8” - 11 UNC, 0.9” Deep on 5” Dia. B.C. 4 Tapped Holes 5/8” - 11 UNC, 1.2” Deep on 5” Dia. B.C. Ø 8.66” Iron end fitting; outer surfaces galvanized for corrosion protection FRP Fiberglass reinforced epoxy resin core Impenetrable Injection-molded SILICONE rubber covering and weathersheds End Fitting joined to core by compression process © Copyright 2010 MacLean Power Systems Issued: May 2010 Supercedes: n/a Adapter Plate 4 x 3/4 - 10 Tapped Holes on 7” Dia. B.C. Adapter plates To comply with ANSI standards on 7” B.C.D. fittings, MPS has adopted the use of 1” adapter plates (5”-7”) shown here. The top adapter plate, when needed, has integral slotted holes to facilitate alignment during erection of bus supports. The use of adapter plates increases the height of insulators by 1” or 2”. For retrofitting, it is possible to adjust the total height to original TR value. Contact factory for details. Standards Complies with ANSI and IEEE standards + IEC tests. Seismically validated and tested per IEEE 693. Recommended for most applications with B.I.L. ≥ 900 kV. IN-62 11411 Addison Avenue, Franklin Park, IL 60131 T: 847.455.0014 F: 847.455.0029 www.macleanpower.com