Station Posts - End Fittings
At lower voltages, corona rings may be
considered for areas of high local
contamination, and/or with altitudes
> 3300 feet.
Crimped End Fittings
All end fittings are attached using a crimping
process to achieve the required tensile strength.
Class 100
IAA 100 XH
Corona rings for 2 ½ and 3 ½ inch
insulators will be included in proposals
where MPS considers them necessary.
Class 200
IAA 200 XV
The user is ultimately responsible for the
proper application of corona rings.
Class 20
IPP 20 XG
0.67”
0.63”
Ø 6.4”
Ø 3.1”
Ø 6.7”
Ø 15.4”
0.67”
Ø 3.1”
Type P
Type A
Type A
4 Tapped Holes
1/2” - 13 UNC
on 3” Dia. B.C.
4 Tapped Holes
5/8” - 11 UNC, 0.9” Deep
on 5” Dia. B.C.
4 Tapped Holes
5/8” - 11 UNC, 1.2”
Deep on 5” Dia. B.C.
Ø 8.66”
Iron end fitting; outer
surfaces galvanized for
corrosion protection
FRP
Fiberglass
reinforced
epoxy resin
core
Impenetrable
Injection-molded
SILICONE
rubber covering
and weathersheds
End Fitting
joined to core
by compression
process
© Copyright 2010 MacLean Power Systems
Issued: May 2010
Supercedes: n/a
Adapter Plate
4 x 3/4 - 10 Tapped
Holes on 7” Dia. B.C.
Adapter plates
To comply with ANSI standards on 7” B.C.D. fittings, MPS has adopted the use
of 1” adapter plates (5”-7”) shown here. The top adapter plate, when needed,
has integral slotted holes to facilitate alignment during erection of bus supports.
The use of adapter plates increases the height of insulators by 1” or 2”. For
retrofitting, it is possible to adjust the total height to original TR value. Contact
factory for details.
Standards
Complies with ANSI and IEEE standards + IEC tests. Seismically
validated and tested per IEEE 693.
Recommended for most applications with B.I.L. ≥ 900 kV.
IN-62