Table of Contents CENTERLINE® Motor Control Centers 400 Amp Disconnect Switch Removal and Installation Instructions Frame Mounted (Bolt-in) Units Disconnect Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Disconnect Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Plug-in (Withdrawable) Units Disconnect Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Disconnect Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch Disconnect Switch Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Disconnect Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 i Publication 2100-IN053A-EN-P - June 2003 ii CENTERLINE® Motor Control Centers 400 Amp Disconnect Switch Removal and Installation Instructions Publication 2100-IN053A-EN-P - June 2003 Instructions Frame Mounted (Bolt-in) Units Disconnect Switch Removal ATTENTION ! ATTENTION ! De-energize all power sources to the motor control center (MCC) before replacing the disconnect switch. Verify that all power is OFF, per NFPA 70E - Standards for Electrical Safety Requirements. Failure to de-energize all power sources can result in severe injury or death. To prevent personal injury or damage to equipment, be sure the unit handle operator is in the OFF/O position before replacing the disconnect switch. NOTE: Torque values shown are nominal. A torque of ±10% of the nominal value is acceptable. 1. Open the section door. Remove the line terminal guard from the line side of the disconnect switch. See Figure 1. Figure 1 Example of the Line Terminal Guard. Line Terminal Guard 1 Publication 2100-IN053A-EN-P - June 2003 2 Frame Mounted (Bolt-in) Units ATTENTION ! Ensure that no voltage is present on the line side of the disconnect switch per NFPA 70E - Standards for Electrical Safety Requirements before proceeding. 2. For fused disconnect switches, label the line side power wires for proper installation later. 3. For unfused disconnect switches, label the line side and load side power wires to ensure they will be reinstalled properly. 4. For fused disconnect switches, photograph or sketch the position of the fuse holder parts for reference in Step 12. See Figure 2. Figure 2 Remove and fit to new switch (only 1 type of fuse holder is shown) Photograph or sketch part position 5. For fused disconnect switches, remove power fuses from the fuse holders. Then remove the fuse holders from the existing disconnect switch terminals, for later installation onto the replacement disconnect switch. See Figure 2. 6. For fused disconnect switches, remove the labeled power wires from the line side disconnect switch terminals 7. For unfused disconnect switches, remove the labeled power wires from the line side and load side disconnect switch terminals. 8. If present, remove the control auxiliary block from the left side of the disconnect switch. See Figure 3. Publication 2100-IN053A-EN-P - June 2003 Frame Mounted (Bolt-in) Units 3 Figure 3 Control Auxiliary Block 9. Support the disconnect switch and then remove the four (4) screws used to mount the disconnect switch. The disconnect switch should be loose and now removable. See Figure 4. Screws may be either hex-head bolt or a slotted torx head bolt. NOTE: Figure 4 shows a plug-in unit, not a frame mounted unit. Figure 4 illustrates the disconnect switch mounting screw locations. Figure 4 Mounting Screws Mounting Screws Publication 2100-IN053A-EN-P - June 2003 4 Frame Mounted (Bolt-in) Units 10. Verify both the replacement disconnect switch and the handle operator are in the OFF/O position. See Figure 5. Disconnect Switch Installation ATTENTION ! Ensure that no voltage is present on all power wires from Steps 2 and 3, per NFPA 70E - Standards for Electrical Safety Requirements, before proceeding. 11. Install the replacement disconnect switch in the same location as the original disconnect switch (removed in Step 9), using the hardware supplied with the replacement kit. Torque mounting screws to 150 lb-in. (17 Nm). After mounting the disconnect switch, the disconnect switch’s crossbar and mechanism parts should be in the positions shown in Figure 5. Figure 5 Crossbar in the OFF/O position When the disconnect switch crossbar is in the OFF/O position, all 3 movable blades must be fully visible When both the handle and disconnect switch are in the OFF/ O position the crossbar so it meets the mechanism (as shown) sm ni r a s ba h ros ec C M Mechanism Place the handle in the OFF/O position 12. Refer to the photograph or sketch of the fuse holder parts (See Step 4), mount the fuse holders on the replacement disconnect switch terminals. Torque the fuse holder’s mounting hardware to the disconnect switch terminals. See Table A. Publication 2100-IN053A-EN-P - June 2003 Frame Mounted (Bolt-in) Units 5 Table A Torque Requirements for Fuse Holder Mounting Hardware Disconnect Size Required Torque 200 Amp Holder 20 lb-in. (2.2 Nm) 400 Amp Holder 30 lb-in. (3.4 Nm) 600 Amp Holder 45 lb-in. (5.0 Nm) 600 Amp Bolt-In Fuse “L” Bracket 45 lb-in. (5.0 Nm) 13. Install the labeled line side power wires, removed in Steps 6 and 7, to the line side of the replacement disconnect switch. Ensure they are installed in the same location and orientation as on the original disconnect switch. Maintain a minimum 1 inch air gap between lugs of opposite phases. Torque line side power wire connections to 240 lb-in. (27 Nm). 14. If present, install the control auxiliary block removed in Step 8 on the left side of the disconnect switch (See Figure 3). Torque the mounting hardware to 11 lb-in. (1.3 Nm). 15. Install the new line terminal guard supplied with replacement kit. See Figure 1. 16. For fused disconnect switches, install the power fuses removed in Step 5. Torque the fuse clamps. See Table B. Table B Torque Requirements for Fuse Clamps Disconnect Size Required Torque 200 Amp Clamp 30 lb-in. (3.4 Nm) 400 Amp Clamp 45 lb-in. (5.0 Nm) 600 Amp Clamp 45 lb-in (5.0 Nm) 600 Amp Bolt-In Fuse “L” Bracket 540 lb-in (61 Nm) 200 Amp HRCII - C 200 lb-in (23 Nm) 400 Amp HRCII - C 396 lb-in (45 Nm) 500 Amp Type 170M SCR Fuse(1) 192 lb-in (22 Nm) (1) Used in Bulletin 2162N and 2162P, 150-250HP, Rollout Variable Frequency Drive Units 17. For unfused disconnect switches, install the labeled load side power wires, removed in Step 7, to the load side of the replacement disconnect switch. Ensure they are installed in the same location and orientation as on the original disconnect switch. Maintain a minimum 1 inch air gap between lugs of opposite phases. Torque the load side power wire connections to 240 lb-in (27 Nm). 18. Replace any additional equipment that was removed for installation. Publication 2100-IN053A-EN-P - June 2003 6 Frame Mounted (Bolt-in) Units 19. Close the section door. With power removed from the MCC, use the unit handle to cycle the disconnect switch to ON/I. Open the section door and verify the unit handle, mechanism, and disconnect switch work properly. 20. Close the section door. With power removed from the MCC, use the unit handle to cycle the disconnect switch to OFF/O. Open the section door and verify the unit handle, mechanism, and disconnect switch work properly. 21. With power removed from the MCC, verify all the wiring is correctly installed. 22. Before closing the enclosure and/or the individual units, remove all tools, metal clips, scrap wire and other debris from the MCC interior. If there is an accumulation of dust or dirt, clean out by using a brush, vacuum cleaner or clean, lint-free rags. Do not use compressed air, because it will redistribute contaminants onto other surfaces. 23. Ensure the handle and disconnect switch are in the OFF/O positions. Close doors and re-energize equipment in accordance with Motor Control Center Instruction Manual, publication 2100-5.0, and NFPA 70E, Standards for Electrical Safety Requirements. Publication 2100-IN053A-EN-P - June 2003 Plug-in (Withdrawable) Units Disconnect Switch Removal ATTENTION ! ATTENTION ! ATTENTION ! Turn OFF all power to the unit before removal or installation. Verify all power is OFF, per NFPA 70E Standards for Electrical Safety Requirements. To prevent personal injury or damage to equipment, make sure the unit handle operator is in the OFF/O position before removing the unit. If unit is not removed (withdrawn) from the MCC, follow the instructions on pages 1 - 6, for a Frame Mounted (Bolt-in) Unit. NOTE: Torque values shown are nominal. A torque of ±10% of the nominal value is acceptable. 1. Remove the plug-in unit from the MCC. If unit is not removed (withdrawn) from the MCC, follow the instructions for a Frame Mounted (Bolt-In) Unit, see pages 1 - 6. 2. Remove the top plate from the unit. See Figure 6. 7 Publication 2100-IN053A-EN-P - June 2003 8 Plug-in (Withdrawable) Units Figure 6 Top Plate Line Terminal Guard 3. Remove the line terminal guard from the line side of the disconnect switch. 4. For fused disconnect switches, label the line side power wires to ensure they will be reinstalled properly. 5. For unfused disconnect switches, label the line side and load side power wires to ensure they will be reinstalled properly. 6. For fused disconnect switches, photograph or sketch the position of the fuse holder parts for reference in Step 15. See Figure 8. 7. For fused disconnect switches, remove power fuses from the fuse holders. 8. For fused disconnect switches, remove the labeled power wires from the line side disconnect switch terminals. 9. For unfused disconnect switches, remove the labeled power wires from the line and load side of the disconnect switch terminals. 10. If present, remove the control auxiliary block from the left side of the disconnect switch. See Figure 7. Publication 2100-IN053A-EN-P - June 2003 Plug-in (Withdrawable) Units 9 Figure 7 Control Auxiliary Block 11. For fused disconnect switches, remove the fuse holders from the existing disconnect switch terminals, for later installation on the replacement disconnect switch. See Figure 8. Figure 8 Remove and fit to new switch (only 1 type of fuse holder is shown) Photograph or sketch part position 12. Support the disconnect switch and then remove the four (4) screws used to mount the disconnect switch. The disconnect switch should be loose from the unit and removable. See Figure 9. Screws may be either hex head bolts or slotted torx head bolts. Publication 2100-IN053A-EN-P - June 2003 10 Plug-in (Withdrawable) Units NOTE: Figure 9 is only meant to illustrate the disconnect switch mounting screw locations. Figure 9 Mounting Screws Mounting Screws 13. Ensure both the replacement disconnect switch and the handle operator are in OFF/O position. See Figure 10. Disconnect Switch Installation ATTENTION In ! Ensure that no voltage is present on all power wires (from Step 4 and 5), per NFPA 70E - Standards for Electrical Safety Requirements, before proceeding. 14. Install the replacement disconnect switch in the same location as the original disconnect switch, removed in Step 12, using hardware supplied with the replacement kit. Torque the mounting screws to 150 lb-in. (17 Nm). After mounting the disconnect switch, the switch’s crossbar and mechanism parts should be in position, as show in Figure 10. Publication 2100-IN053A-EN-P - June 2003 Plug-in (Withdrawable) Units 11 Figure 10 Crossbar in the OFF/O position When the disconnect switch crossbar is in the OFF/O position, all 3 movable blades must be fully visible When both the handle and disconnect switch are in the OFF/O position the crossbar so it meets the mechanism (as shown) M ism ar an h ssb ec Cro Mechanism Place the handle in the OFF/O position 15. Refer to the photograph or sketch of the fuse holder parts (from Step 6), mount the fuse holders onto the replacement disconnect switch terminals. Torque the fuse holder’s mounting hardware to disconnect switch terminals, see Table C. Table C Torque Requirements for Fuse Holder Mounting Hardware Disconnect Size Required Torque 200 Amp Holder 20 lb-in. (2.2 Nm) 400 Amp Holder 30 lb-in. (3.4 Nm) 600 Amp Holder 45 lb-in. (5.0 Nm) 600 Amp Bolt-In Fuse “L” Bracket 45 lb-in. (5.0 Nm) 16. For fused disconnect switches install the labeled line side power wires, removed in Step 8, to the line side of the replacement disconnect switch. Ensure they are installed in the same location and orientation as on the original disconnect switch. Maintain a minimum 1 inch air gap between lugs of opposite phases. Torque line side power wire connections to 240 lb-in. (27 Nm). Publication 2100-IN053A-EN-P - June 2003 12 Plug-in (Withdrawable) Units 17. For unfused disconnect switches, install the labeled line side and load side power wires, removed in Step 9, to the line side and load side of the replacement disconnect switch. Ensure they are installed in the same location and orientation as on the original disconnect switch. Maintain a minimum 1 inch air gap between lugs of opposite phases. Torque line side power wire connections to 240 lb-in. (27 Nm). 18. If present, install the control auxiliary block removed in Step 10 on the left side of the disconnect switch. Torque the mounting hardware to 11 lb-in. (1.3 Nm). See Figure 7. 19. Install the new line terminal guard supplied with replacement kit. See Figure 6. 20. For fused disconnect switches, install the power fuses removed in Step 7. Torque fuse clamps, see Table D. Table D Torque Requirements for Fuse Clamps Disconnect Size Required Torque 200 Amp Clamp 30 lb-in. (3.4 Nm) 400 Amp Clamp 45 lb-in. (5.0 Nm) 600 Amp Clamp 45 lb-in. (5.0 Nm) 600 Amp Bolt-In Fuse “L” Bracket 540 lb-in. (61 Nm) 200 Amp HRCII - C 200 lb-in. (23 Nm) 400 Amp HRCII - C 396 lb-in. (45 Nm) 500 Amp Type 170M SCR Fuse(1) 192 lb-in. (22 Nm) (1) Used in Bulletin. 2162N and 2162P, 150 - 250HP, Rollout Variable Frequency Drive Units 21. Perform continuity check between all stab assemblies mounted on the back of the respective unit to ensure the power wires are connected appropriately. 22. Replace unit top plate (if removed in Step 2). See Figure 6. 23. Replace any additional equipment that was removed for installation. 24. Verify that all wiring is correctly installed. 25. Use the unit handle to cycle the disconnect switch to ON/I. Verify the unit handle, mechanism, and disconnect switch work properly. 26. Use the unit handle to cycle the disconnect switch to OFF/O. Verify the handle, mechanism, and disconnect switch work properly. Publication 2100-IN053A-EN-P - June 2003 Plug-in (Withdrawable) Units 13 27. With the unit handle in the OFF/O position, and with all three movable blades of the disconnect switch in the open and visible position, replace the unit in MCC and secure. 28. Before closing the enclosure and/or the individual units, remove all tools, metal clips, scrap wire and other debris from the MCC interior. If there is an accumulation of dust or dirt, clean out by using a brush, vacuum cleaner or clean, lint-free rags. Do not use compressed air, because it will redistribute contaminants onto other surfaces. 29. Ensure the handle and disconnect switch are in the OFF/O positions. Close the doors and re-energize equipment in accordance with Motor Control Center Instruction Manual, publication 2100-5.0, and per NFPA 70E, Standards for Electrical Safety Requirements. Publication 2100-IN053A-EN-P - June 2003 14 Plug-in (Withdrawable) Units Publication 2100-IN053A-EN-P - June 2003 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch Disconnect Switch Removal ATTENTION ! ATTENTION ! De-energize all power sources to the enclosure before replacing the disconnect switch, per NFPA 70E - Standards for Electrical Safety Requirements. Failure to de-energize all power sources can result in severe injury or death. To prevent personal injury or damage to equipment, be sure the enclosure’s handle operator is in the OFF/O position before replacing the disconnect switch. NOTE: Torque values shown are nominal. A torque of ±10% of the nominal value is acceptable. 1. Open the enclosure door. Remove the line terminal guard from the line side of the disconnect switch. See Figure 11. Figure 11 Line Terminal Guard 15 Publication 2100-IN053A-EN-P - June 2003 16 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch ATTENTION ! Ensure that no voltage is present on the line side of the disconnect switch per NFPA 70E - Standards for Electrical Safety Requirements before proceeding. 2. Label the line side and the load side power wires to ensure they will be reinstalled properly. 3. Remove the labeled power wire lugs from the line and load side of the disconnect switch terminals. 4. If present, remove the control auxiliary block from left side of disconnect switch. See Figure 12. Figure 12 Control Auxiliary Block 5. Support the disconnect switch and remove the four (4) screws used to mount the disconnect switch. The disconnect switch should be loose from the enclosure and removable. See Figure 13. Screws may be either hex head bolts or slotted torx head bolts. Publication 2100-IN053A-EN-P - June 2003 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch 17 NOTE: Figure 13 shows a disconnect switch in an MCC unit, not an enclosed disconnect switch. Figure 13 is only meant to illustrate the disconnect switch mounting screw locations. Figure 13 Mounting Screws Mounting Screws 6. Ensure both the replacement disconnect switch and the handle operator are in the OFF/O position. Disconnect Switch Installation ATTENTION In ! Ensure that no voltage is present on the labeled line side power wires, per NFPA 70E - Standards for Electrical Safety Requirements, before proceeding. 7. Using the hardware supplied, install the replacement disconnect switch in the same location as the original disconnect switch, removed in Step 5. Torque the mounting screws to 150 lb-in (17 Nm). Once the disconnect switch is mounted, the switch’s crossbar and mechanism parts should be in the positions shown in Figure 14. Publication 2100-IN053A-EN-P - June 2003 18 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch Figure 14 Crossbar in the OFF/O position When disconnect switch crossbar is in the OFF/O position, all 3 movable blades must be fully visible When both the handle and disconnect switch are in the OFF/O position the crossbar so it meets the mechanism (as shown) ism an h bar ec M Cross Mechanism Place the handle in the OFF/O position 8. Install the labeled line and load side power wire lugs, removed in Step 3, to the replacement disconnect switch's power terminals. Ensure they are installed in same location and orientation as on the original disconnect switch. Maintain a minimum 1 inch air gap between lugs of opposite phases. NOTE: See Figure 15 for screw identification. Flat washers and lock washers are NOT used with the power wire lug retaining screws (hex head cap screw). Torque the power wire lug retaining screw connections to 240 lb-in (27 Nm). Publication 2100-IN053A-EN-P - June 2003 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch 19 Figure 15 Load Side of Disconnect Switch - line and load side lug connections are similar Power wire lug retaining screw (hex head cap screw) Power wire retaining screw (hex socket set screw) Power wire lugs (load side shown) for 400A enclosed disconnect switch 9. Torque the power wire retaining screw (hex socket set screw) to 275 lb-in (31 Nm). See Figure 15. 10. Re-torque the 6 power wire lug terminal screw connections, from Step 8, to 240 lb-in (27 Nm). See Figure 15. Maintain a minimum 1 inch air gap between lugs of opposite phases. 11. If present, install the control auxiliary block, removed in Step 4, on left side of the disconnect switch. Torque the mounting hardware to 11 lb-in (1.3 Nm). See Figure 12. 12. Install the new line terminal guard supplied with the replacement kit. See Figure 11. 13. Replace any additional equipment that was removed for installation. 14. Close the enclosure door. With all power still removed from the enclosure, use the handle to cycle the disconnect switch to ON/I. Open the enclosure door and verify the handle, mechanism, and disconnect switch work properly. 15. Close the enclosure door. With all power still removed from the enclosure, use the handle to cycle the disconnect switch to OFF/O. Open the enclosure door and verify the handle, mechanism, and disconnect switch work properly. Publication 2100-IN053A-EN-P - June 2003 20 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch 16. With power OFF/O, verify all wiring is correctly installed. Before closing the enclosure, remove all tools, metal clips, scrap wire and other debris from the enclosure interior. If there is an accumulation of dust or dirt, clean out by using a brush, vacuum cleaner or clean, lint-free rags. Do not use compressed air, because it will redistribute contaminants onto other surfaces. 17. Ensure the handle and disconnect switch are in the OFF/O positions. Close and secure the enclosure door. Re-energize equipment in accordance with NFPA 70E, Standards for Electrical Safety Requirements. Publication 2100-IN053A-EN-P - June 2003 Bulletin 1494F and Bulletin 2294F - Enclosed Disconnect Switch 21 Notes: Publication 2100-IN053A-EN-P - June 2003 Publication 2100-IN053A-EN-P - June 2003 22 © 2003 Rockwell International Corporation. Printed in the U.S.A.