GT5Y Miniature Electronic Timers - Carlton

advertisement
GT5Y Miniature Electronic Timers
Four Selectable Time Ranges
Delayed Output 4PDT/3A or DPDT/5A
• Three operation modes: ON Delay, Interval ON, and Cycle
• Repeat error: ±0.2% maximum
• Miniature size
• LED indicators for output and power
• Complies with safety standards.
UL/c-UL listed. EN compliant.
220V AC/
30V DC, 5A
ON
Delay
4PDT
DPDT
Interval
ON
220V AC/
30V DC, 3A
220V AC/
30V DC, 5A
4PDT
220V AC/
30V DC, 3A
DPDT
220V AC/
30V DC, 5A
4PDT
220V AC/
30V DC, 3A
Cycle
1S/10S/1M/10M
1S/10S/1M/10M
Operating
Voltage
Type No.
100 to 120V AC
12V DC
24V DC
100 to 120V AC
24V DC
GT5Y-2SN1A100
GT5Y-2SN3A100
GT5Y-2SN6A100
GT5Y-2SN1A200
GT5Y-2SN3A200
GT5Y-2SN6A200
GT5Y-2SN1D12
GT5Y-2SN3D12
GT5Y-2SN6D12
GT5Y-2SN1D24
GT5Y-2SN3D24
GT5Y-2SN6D24
GT5Y-4SN1A100
GT5Y-4SN3A100
GT5Y-4SN6A100
GT5Y-4SN1A200
GT5Y-4SN3A200
GT5Y-4SN6A200
GT5Y-4SN3D12
GT5Y-4SN1D24
GT5Y-4SN3D24
GT5Y-4SN6D24
GT5Y-2SV1A100
GT5Y-2SV1D12
GT5Y-2SV1D24
GT5Y-4SV1A100
GT5Y-4SV1D24
100 to 120V AC
GT5Y-2SF1A100
200 to 240V AC
24V DC
GT5Y-4SF1A200
GT5Y-4SF1D24
100 to 120V AC
200 to 240V AC
12V DC
24V DC
100 to 120V AC
200 to 240V AC
12V DC
24V DC
Note: S and M of the time range indicate second, and minute respectively.
Accessories
Both SY4S-05C and SM2S-05C are UL recognized, CSA certified, and TÜV approved. Others
are UL recognized and CSA certified, except for SY4S-05A and SM2S-05A.
When ordering, specify the ordering Type No.
Item
DIN
Rail
Mount
Socket
Type No.
Socket
Hold-Down
Spring
Panel/
PC
Board
Mount
Socket
Socket
Hold-Down
Spring
SY4S-05A
SY4S-05C
SY4S-05D
SY4S-05DF
SM2S-05A
SM2S-05C
SM2S-05D
SM2S-05DF
SFA-202
SFA-511
SY4S-51
SY4S-61
SM2S-51
SM2S-61
SFA-302
Ordering
Type No.
SY4S-05A
SY4S-05C
SY4S-05D
SY4S-05DF
SM2S-05A
SM2S-05C
SM2S-05D
SM2S-05DF
SFA202PN20
SFA511PN20
SY4S-51
SY4S-61
SM2S-51
SM2S-61
SFA302PN20
Package
Quantity
1
1
1
1
1
1
1
1
10 sets
(20 pcs)
20
1
1
1
1
10 sets
(20 pcs)
Remarks
For 4PDT contact
For 4PDT contact
For 4PDT contact
For 4PDT contact
For DPDT contact
For DPDT contact
For DPDT contact
For DPDT contact
For SY4S-05A, SM2S-05A (2 pcs/set)
For SY4S-05D, SY4S-05DF,
SM2S-05D, SM2S-05DF
For 4DPT contact, Solder Terminal
For 4DPT contact, PC Board Terminal
For DPDT contact, Solder Terminal
For DPDT contact, PC Board Terminal
For SY4S-51, SY4S-61, SM2S-51,
SM2S-61 (2 pcs/set)
Code
Scale
1S
10S
1M
10M
3S
30S
3M
30M
6S
60S
6M
60M
0 to 10
0 to 10
0 to 10
0 to 10
0 to 3
0 to 3
0 to 3
0 to 3
0 to 6
0 to 6
0 to 6
0 to 6
Time Range
Indication
× 0.1
S
×1
S
× 0.1
M
×1
M
×1
S
× 10
S
×1
M
× 10
M
×1
S
× 10
S
×1
M
× 10
M
Time Range
0.1 sec to 1 sec
0.2 sec to 10 sec
1.2 sec to 1 min
12 sec to 10 min
0.1 sec to 3 sec
0.5 sec to 30 sec
3 sec to 3 min
30 sec to 30 min
0.1 sec to 6 sec
1 sec to 60 sec
6 sec to 6 min
1 min to 60 min
Contact Ratings
Type No.
Contact
Configuration
GT5Y-4
GT5Y-2
4PDT
DPDT
Resistive
Load
220V AC, 3A
30V DC, 3A
220V AC, 5A
30V DC, 5A
Inductive
Load
cosø=0.3
L/R=7ms
220V AC, 0.8A
30V DC, 1.5A
220V AC, 2A
30V DC, 2.5A
250V AC/125V DC
250V AC/125V DC
3A
5A (Note)
Maximum Switching
Voltage
Maximum Switching
Current
Maximum Switching
Frequency
1800 operations/hour
1800 operations/hour
Resistive
Load
AC: 660VA
DC: 90W
AC: 1100VA
DC: 150W
Inductive
Load
cosø= 0.3
L/R=7ms
AC: 176VA
DC: 45W
AC: 440VA
DC: 75W
5V DC, 10mA
(reference value)
24V DC, 5mA
(reference value)
5V DC, 20mA
(reference value)
24V DC, 10mA
(reference value)
Minimum Applicable
Load
External Protection
Element
Electrical
Mechanical
Fuse 250V 3A
Fuse 250V 5A
200,000 operations
minimum
(220V AC, 3A)
50 million operations
minimum
500,000 operations
minimum
(220V AC, 5A)
50 million operations
minimum
Note: See Operating Temperature - Maximum Switching
Current Characteristics.
Operating Temperature Maximum Switching Current
Characteristics
Check the derating curve described below when
mounting more than two GT5Y-2 timers and SM2S05∗ sockets.
Mounting
Direction
Derating Curve
Switching Current
DPDT
Output
Rated Load
Contact
Time Ranges
Allowable
Contact Power
Operation
Mode
Package Quantity: 1
Time Ranges
(4 ranges
selectable)
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
3S/30S/3M/30M
1S/10S/1M/10M
3S/30S/3M/30M
6S/60S/6M/60M
Life
Type List
SM2S-05A, C
Sockets
5A
SM2S-05D, DF
Sockets
2.5A
40ºC
50ºC
Operating Temperature
1086
GT5Y Miniature Electronic Timers
General Specifications
Type
Operation Type
Pollution Degree
Overvoltage Category
A200
Rated
A100
Operational
D24
Voltage
D12
A200
A100
Voltage
Range
D24
D12
Reset Voltage
Operating Temperature
Storage/Transportation Temperature
Operating Humidity
Operation Charts and Internal Connections
GT5Y-oSN
GT5Y-oSV
GT5Y-oSF
ON Delay
Interval
Cycle
2 (IEC60664-1)
III (IEC60664-1)
200 to 240V AC (50/60Hz)
100 to 120V AC (50/60Hz)
24V DC
12V DC
170 to 264V AC (50/60Hz)
85 to 132V AC (50/60Hz)
21.6 to 26.4V DC
10.8 to 13.2V DC
Rated Voltage × 20% minimum
-10 to +50°C (no freezing and condensation)
35 to 85% RH (no condensation)
0 to 2000m (operation)
0 to 3000m (transportation)
100 ms maximum
±0.2%, ±20 ms maximum
±0.5%, ±20 ms maximum
±3% maximum
±10% maximum
100 MΩ minimum (500V DC megger)
Between power and output terminals: 2000V AC, 1 minute
Between contacts of different poles: 2000V AC, 1 minute
Between contacts of the same pole: 1000V AC, 1 minute
10 to 55 Hz, amplitude 0.75 mm, 2 hours each in 3 directions
Operating extremes: 98 m/s2,
Damage limits: 490 m/s2, 3 shocks each in 6 directions
IP40 (timer), IP20 (socket) (IEC60529)
1.6 VA (200V AC/60Hz)
1.4 VA (100V AC/60Hz)
1.0W
0.9W
27.5H × 21.0W × 58.6D mm
50g
Reset Time
Repeat Error
Voltage Error
Temperature Error
Setting Error
Insulation Resistance
Dielectric Strength
Vibration Resistance
Shock Resistance
Degree of Protection
A200
Power
A100
Consumption
D24
(approx.)
D12
Dimensions
Weight (approx.)
Note: See Operating Temperature – Maximum Switching Current Characteristics.
• Electrical Life Curves
5000
AC Load
Life (× 10,000 operations)
Life (× 10,000 operations)
1000
110V AC Resis. Load
220V AC Resis. Load
110V AC Induc. Load
220V AC Induc. Load
100
50
10
0
1
2
Operation
Display
Lights
1-9, 3-11, 2-10, 4-12 (NC)
ON Delay
5-9, 7-11, 6-10, 8-12 (NO)
Display
Units
POWER Indicator
Safety
Products
OUT Indicator
3
4
500
1-9, 3-11, 2-10, 4-12 (NC)
Interval
ON
0
1
2
3
4
Comm.
Terminals
5-9, 7-11, 6-10, 8-12 (NO)
POWER Indicator
AS-Interface
OUT Indicator
Relays &
Timers
Set Time
T
T
Terminal No.
13-14 (POWER)
Sockets
1-9, 3-11, 2-10, 4-12 (NC)
Cycle
5-9, 7-11, 6-10, 8-12 (NO)
Circuit
Protectors
POWER Indicator
Power
Supplies
OUT Indicator
(Internal Connections)
• GT5Y-4
• GT5Y-4
PLCs &
SmartRelay
Operator
Interfaces
50
10
5
Terminal
Blocks
100
Sensors
Control
Stations
GT5Y-2
5
Load Current (A)
Load Current (A)
Set Time
Terminal No.
13-14 (POWER)
30V DC Resis. Load
30V DC Induc. Load
100V DC Resis. Load
100V DC Induc. Load
1000
See page 1112 for SM2S-05A, SM2S-05C, SM2S-05D,
SM2S-05DF.
Dimensions
(When using DIN Rail Mount Socket)
Explosion
Protection
(When using DIN rail)
BAA, BAP: 87.6 max. (Note 4)
• GT5Y-4
See page 1113 for SY4S-05A, SY4S-05C, SY4S-05D, SY4S-05DF.
83.6 max. (Note 3)
References
(When using DIN rail)
BAA, BAP: 87.6 max. (Note 2)
27.5
83.6 max. (Note 1)
6
52.6
58.6
6.4
HoldDown
Spring
DIN
Rail
18.5
21
6
52.6
58.6
6.4
25
DIN
Rail
3
18.5
25
3
27.5
21
HoldDown
Spring
Flush
Silhouette
Control
Units
Set Time
Terminal No.
13-14 (POWER)
DC Load
GT5Y-2
GT5Y-4
GT5Y-2
GT5Y-4
500
Item
-30 to +80°C (no freezing and condensation)
Altitude
5000
Operation
Mode
Note 3: SM2S-05A: 83.6 max., SM2S-05C: 83.6 max., SM2S-05D: 88.6
max., SM2S-05DF: 88.6 max.
Note 4: SM2S-05A: 87.8 max., SM2S-05C: 87.8 max., SM2S-05DN: 92.8
max., SY4S-05DF: 92.8 max.
Note 1: SY4S-05A: 83.6 max., SY4S-05C: 83.6 max., SY4S-05D: 88.6
max., SY4S-05DF: 88.6 max.
Note 2: SY4S-05A: 87.8 max., SY4S-05C: 87.8 max., SY4S-05D: 92.8
max., SY4S-05DF: 92.8 max.
1087
GT5P Miniature Electronic Timers
Economic Efficiency Focused
Delayed Output SPDT/5A
• Three operation modes: ON Delay, Cycle, and One Shot
• Repeat error: ±0.2% maximum
• Complies with safety standards
UL recognized, CSA certified, TÜV approved, EN compliant
ON Delay
Cycle
One Shot
Contact
SPDT
SPDT
SPDT
Package Quantity: 1
Output
24V DC/
120V AC, 5A
240V AC, 3A
24V DC/
120V AC, 5A
240V AC, 3A
24V DC/
120V AC, 5A
240V AC, 3A
Time
Range
3S
10S
30S
60S
3M
6M
10M
1S
6S
10S
30S
60S
3M
6M
10M
1S
6S
10S
60S
6M
10M
10S
30S
60S
10M
3S
10S
3S
10S
3S
10S
3S
10S
3S
3S
10S
3S
10S
Operating
Voltage
100 to 120V AC
200 to 240V AC
24V AC/DC
12V DC
100 to 120V AC
200 to 240V AC
24V AC/DC
12V DC
100 to 120V AC
200 to 240V AC
24V AC/DC
Type No.
(Order No.)
GT5P-N3SA100
GT5P-N10SA100
GT5P-N30SA100
GT5P-N60SA100
GT5P-N3MA100
GT5P-N6MA100
GT5P-N10MA100
GT5P-N1SA200
GT5P-N6SA200
GT5P-N10SA200
GT5P-N30SA200
GT5P-N60SA200
GT5P-N3MA200
GT5P-N6MA200
GT5P-N10MA200
GT5P-N1SAD24
GT5P-N6SAD24
GT5P-N10SAD24
GT5P-N60SAD24
GT5P-N6MAD24
GT5P-N10MAD24
GT5P-N10SD12
GT5P-N30SD12
GT5P-N60SD12
GT5P-N10MD12
GT5P-F3SA100
GT5P-F10SA100
GT5P-F3SA200
GT5P-F10SA200
GT5P-F3SAD24
GT5P-F10SAD24
GT5P-F3SD12
GT5P-F10SD12
GT5P-P3SA100
GT5P-P3SA200
GT5P-P10SA200
GT5P-P3SAD24
GT5P-P10SAD24
Time Ranges
Code
1S
3S
6S
10S
30S
60S
3M
6M
10M
Time Range
0.1 sec to 1 sec
0.1 sec to 3 sec
0.1 sec to 6 sec
0.2 sec to 10 sec
0.5 sec to 30 sec
1 sec to 60 sec
3 sec to 3 min
6 sec to 6 min
10 sec to 10 min
Contact Ratings
Contact Configuration
Maximum Switching
Voltage
Maximum Switching
Current
Maximum Switching
Power
SPDT
Rated Load
Operation
Mode
120V AC / 24V DC, 5A
240V AC, 3A
Life
Type No.
Resistive Load
Inductive Load
cosø = 0.3 - 0.4
L/R = 15 ms
Electrical
Mechanical
250V AC, 150V DC
5A
AC: 960VA
DC: 120W
240V AC, 0.8A
120V AC, 1.4A
24V DC, 1.7A
100,000 operations minimum
(rated resistive load)
20,000,000 operations
minimum
Minimum Applicable Load: 5V DC 10 mA (reference value)
Note: S and M of time range indicate second and minute respectively.
Accessories
Item
DIN Rail Mount
Socket
Socket
Hold-Down Spring
Panel Mount
Socket
1088
w/Solder Terminals
w/Wire Wrap Terminals
Type No.
SR2P-06A
SR2P-05A
SR2P-05C
SFA-202
SFA-203
SR2P-511
SR2P-70
Ordering Type No.
SR2P-06A
SR2P-05A
SR2P-05C
SFA-202PN20
SFA-203PN20
SR2P-511
SR2P-70
Package Quantity
1
1
1
10 sets (20 pcs)
10 sets (20 pcs)
1
1
Remarks
UL/CSA/TÜV
For SR2P-06A (2 pcs/set)
For SR2P-05A (2 pcs/set)
UL/CSA
GT5P Miniature Electronic Timers
General Specifications
Type
Operation Type
Pollution Degree
A200
Rated
A100
Operational
AD24
Voltage
D12
A200
A100
Voltage
Range
AD24
D12
Operating Temperature
Storage/Transportation Temperature
Operating Humidity
Operation
Mode
Reset Time
Repeat Error
Voltage Error
Temperature Error
Setting Error
Insulation Resistance
Dielectric Strength
Vibration Resistance
Shock Resistance
A200
A100
AD24
D12
Dimensions
Weight (approx.)
Operation
Set Time
Display
Lights
On Delay
6-8 (NO)
Display
Units
POWER Indicator
OUT Indicator
Safety
Products
Set Time
T
T
Terminal No.
2-7 (POWER)
Terminal
Blocks
5-8 (NC)
Comm.
Terminals
Cycle
6-8 (NO)
POWER Indicator
AS-Interface
OUT Indicator
Relays &
Timers
Terminal No.
13-14 (POWER)
50ms minimum
3-4 (Start Input)
One Shot
Sockets
5-8 (NC)
Circuit
Protectors
6-8 (NO)
Power
Supplies
POWER Indicator
100
70
50
OUT Indicator
30
24V
DC R
120V
20
240V
10
AC R
AC R
7
5
120
24V
esis.
load
esis.
esis
load
. loa
d
(Internal Connections)
ON Delay/Cycle
6
5
7(~)/( + )
PLCs &
SmartRelay
One Shot
6
5
DC
24
τ=
VA
0V
15
Cc
ms
AC
os
ø=
co
sø
0.4
=0
.4
3
2
Flush
Silhouette
Control
Units
5-8 (NC)
• Electrical Life Curves
Life ( ×10,000 operations)
Item
Terminal No.
2-7 (POWER)
–30 to +70°C (no freezing)
35 to 85% RH (no condensation)
0 to 2000m (operation)
0 to 3000m (transportation)
100 ms maximum
±0.2%, ±10 ms maximum
±0.5%, ±20 ms maximum
±3% maximum
±10% maximum
100 MΩ minimum (500V DC megger)
Between power and output terminals: 2000V AC, 1 minute
Between contacts of different poles: 2000V AC, 1 minute
Between contacts of the same pole: 750V AC, 1 minute
10 to 55Hz, amplitude 0.75 mm, 2 hours each in 3 directions
Operating extremes: 98 m/s2,
Damage limits: 490 m/s2
3.9 VA (60Hz)
5.6 VA (60Hz)
2.3 VA (60Hz)
2.9 VA (60Hz)
1.3 VA (60Hz)/0.5W
1.2 VA (60Hz)/0.5W
0.6W
0.6W
36H × 29W × 81.5D mm
49g
Altitude
Power
Consumption
(approx.)
Operation Charts and Internal Connections
GT5P-N
GT5P-F
GT5P-P
ON Delay
Cycle
One Shot
2 (IEC60664-1)
200 to 240V AC (50/60Hz)
100 to 120V AC (50/60Hz)
24V AC (50Hz/60Hz)/24V DC
12V DC
170 to 264V AC (50/60Hz)
85 to 132V AC (50/60Hz)
20.4 to 26.4V AC (50/60Hz)/21.6 to 26.4V DC
10.8 to 13.2V DC
–10 to +50°C (no freezing)
7(~)/( + )
4
Operator
Interfaces
3
Sensors
1
0
1
2
3
4
Load Current (A)
5
8
2(~)/(-)
8
2(~)/(-)
Control
Stations
Dimensions
(When using DIN Rail Mount Socket)
• SR2P-05A
For SR2P-05C, see page 1109.
Explosion
Protection
• SR2P-06B
References
Note 1: SR2P-05C: 99.5 max.
Note 2: SR2P-05C: 103.5 max.
1089
GT5Y/GT5P Miniature Electronic Timers [Common]
Dimensions / Mounting Hole Layout (for Panel/PC Board Mount Socket)
1. GT5Y-4
• Panel Mount Socket (SY4S-51)
2. GT5Y-2
• Panel Mount Socket (SM2S-51)
• PC Board Mount Socket (SY4S-61)
• PC Board Mount Socket (SM2S-61)
3. GT5P
• Solder Terminal (SR2P-511)
• Wire Wrap Terminal (SR2P-70)
Installation of Hold-Down Springs
• DIN Rail Mount Socket
• Panel/PC Board Mount Socket
The SFA-302 Hold-Down Springs can be installed to the
SY4S-51, SY4S-61, SM2S-51, and SM2S-61 sockets.
Hold-down springs cannot be installed to SR2P-511 and
SR2P-70 panel mount sockets.
Note: Once installed into sockets, the hold-down springs cannot
be removed.
1090
GT5Y/GT5P Miniature Electronic Timers [Common]
!
Safety Precautions
• Be sure to turn off power before mounting, removal, wiring, maintenance and inspection. Otherwise, electric shock or fire could
occur.
• Be sure to use timers within rated specification values. Otherwise,
electric shock or fire may occur.
• Be sure to use wires to meet voltage and current requirements
and tighten M3.5 terminal screws to a tightening torque of 1.0 to
1.3 N•m. Be sure to solder the terminals correctly. Loose terminal screws or incomplete soldering may cause abnormal heat and
fire.
Flush
Silhouette
Control
Units
Display
Lights
Instructions
Time Range Setting
Contact Protection
Display
Units
The time range is calibrated at its maximum time scale, therefore
it is desirable to use the timer at a setting as close to its maximum
time scale as possible for accurate time delay. For a more accurate
time delay, adjust the control knob by measuring the operating time
with a watch before application.
On the GT5Y timers, a desired time range can be selected using
the time range selectors on the side surface. Turn the multiplier and
time unit selectors using a flat screwdriver until they click.
Switching an inductive load generates a counter-electromotive force
in the coil. The counter emf will cause arcing, which may shorten the
contact life. Application of a protection circuit is recommended for
contact protection.
Safety
Products
Terminal
Blocks
Rest Time
When turning power off after time-out, allow a rest time of 0.1 sec,
and during operation, 1 sec at least.
Control knob
Power
Time range indication window
Since DC types are designed to operate on DC power containing
10% or less ripple, insert a smoothing circuit when using a rectified
AC power to operate DC type timers.
Time range selector
Continuous Energizing
Continuous energizing for a long period of time may damage the
electrical characteristics of the timer because of internal heating.
Use an additional relay to the output circuit and refrain from continuous energizing of the timer.
Comm.
Terminals
AS-Interface
Relays &
Timers
Sockets
Circuit
Protectors
Dielectric Strength Test
Timing Accuracy
Timing accuracies are calculated from the following formulas:
• Repeat Error
=±
1
Max. measured value - Min. measured value
× 100 (%)
×
2
Maximum scale value
• Voltage Error
=±
Tv - Tr
Tv: Average of measured values at voltage V
× 100 (%)
Tr
Tr: Average of measured values at the raged voltage
• Temperature Error
=±
Tt - T20
Tt: Average of measured values at t°C
× 100 (%)
T20
T20: Average of measured values at 20°C
• Setting Error
=
Average of measured values - Set value
× 100 (%)
Maximum scale value
Use of External Input (GT5P-P Only)
1. Do not apply voltage to external input terminals 3 and 4. Be sure
not to connect external inputs to other terminals because the
internal circuit may be damaged.
2. Use reliable mechanical contacts capable of switching approximately 22V DC, 1 mA to close input terminals 3 and 4.
(Closed: 1 kΩ maximum, Open: 100 kΩ minimum) The input
terminals should not be connected to a ground wire of other devices.
3. Do not install input lines in parallel with high-voltage or motor
lines. Use shielded wires or separate conduit for input lines, and
make the input lines as short as possible.
Load Current
The rated current of the contact (or control output) should not be exceeded. Especially for inductive, capacitive, and incandescent lamp
loads, the inrush current as large as a few to several tens times the
rated current may cause welded contacts and other troubles. The
amount of inrush current as well as steady-state current must be
taken into consideration.
When performing an insulation resistance or dielectric strength test
on control panels containing timers, make sure that the dielectric
strength of the timer is not exceeded. In case the dielectric strength
is exceeded, remove the timers from the panels.
Power
Supplies
PLCs &
SmartRelay
Operating Environment
• Temperature and Humidity
Use the timer within the operating temperature and operating humidity ranges and prevent freezing and condensation. After storing below the operation temperature, leave the timer at room temperature for a sufficient period of time before use.
• Environment
Prevent a corrosive gas such as sulfurous or ammonia gas, organic solvents (alcohol, benzine, thinner, etc.), strong alkaline
substances or strong acids from touching to the timer, and do not
use the timer in such an environment. Keep the timer from water
splashes or steam.
• Vibration and Shock
Since excessive vibrations or shocks cause the output contacts
to open, the timer should be used within the operating extremes
of vibration and shock resistance. Use of hold-down springs is
recommended for secure mounting on sockets.
Others
• Use a mechanical-contact switch or relay to supply power to the
time.
• When driving the timer using a solid-state output device such as
two-wire proximity switch, photoelectric switch or solid-state relay
directly, malfunction may be caused by a leakage current from the
solid-state device. Be sure to check thoroughly before using.
• Since AC types (such as A100 and A200) comprise a capacitive
load, the SSR dielectric strength should be two or more times as
large as the power voltage when switching the timer power using
an SSR.
• To make a sequence circuit by connecting timer and relay, check
the timer operation sufficiently in consideration of the reset time
of the timer.
1091
Operator
Interfaces
Sensors
Control
Stations
Explosion
Protection
References
GT5Y/GT5P Miniature Electronic Timers [Common]
Installation/Removal of Hold-Down Springs
1092
Installation/Removal of Hold-Down Springs
Download