Electronic Timers Data Sheets and Selection Guide Valid as of 1 March 2012 Electronic Timers Introduction & Selection Guide INTRODUCTION The Brodersen timer programme includes both multifunction and singlefunction timers. The selection guide below will help to select the right application. Brodersen multifunction timers combine a range of timing functions which are easily selected on the front of the timer. The time range is also selectable on the front and the timer will work at any voltage from 10.5265V AC or DC In addition to the multifunction timers, Brodersen also manufacture a singlefunction timer. All timers are available in versions for DIN rail or 11pole plug-in mounting. The compact design, the ease of adjustment and the consistent quality of the entire range of Brodersen timers are the hallmarks of a truly unique product. Release delay - true off On pulse Off pulse On-off pulse Symmetrical recycler Asymmetrical recycler One shot, asymmetrical • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • W: 27 mm x H: 75 mm • • • • • • • • • • • • • • Housing Remote timer start • • • • • • • • • • • • • • Transistor output 0.1sec-3min. 0.1sec-10min. 0.1sec.-30min. 1.5-60sec. 0.6sec.-60min. 0.6min.-60hrs. Output relay, SPDT Release delay Output relay, DPDT Function On delay Time range and adjustment Output Potentiometer, front SELECTION GUIDE • • • • • • • • • • • • • • Multi-/singlefunction Multifunction M M M S M M M M M M M M Type XMW XM XMW XW XF XMW XM XW XW XW XMW XM XT Page 8 4 8 6 14 8 4 6 6 6 8 4 10 M XOT 12 Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com Electronic Timers Introduction & Selection Guide PROVEN TECHNOLOGY You will find Brodersen timers in equipment, control panels and machines all over the world. Over the last decade more than 1 million timers has been installed in various applications. And we are still one of the largest manufactures of electronic timers. That is what we call “Proven Techology”. Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 3 Electronic Timers On Delay • On Pulse • Symmetrical Recycler XM DESCRIPTION OPERATION Multifunction timer with 4 functions and 4 time ranges. The function and the time range are selectable via 2 front mounted rotary switches. Time ranges: 0.6-6sec, 6-60sec, 0.6-6min, 6-60min. The time is adjustable on the timer front. The timer can directly be connected to the supply voltage in the range of 10.5-265V AC/DC. Single or double relay output with LED indication of energized relay. Intermittent flashing of LED indicating timing period (over 6 sec.). Versions available for DIN rail or 11-pole plug-in mounting. The function is selected via the rotary switch on the timer front. The switch may only be operated, when the supply voltage is disconnected. On delay. The timing period starts when supply voltage is connected. When the preset time has elapsed, the relay is energized. The relay is de-energized when the supply voltage is disconnected. If the supply voltage is disconnected before the preset time has elapsed, the timer resets. Supply T T LED On pulse. When supply voltage is connected, the relay is energized and the timing period starts. When the preset time has elapsed, the relay is deenergized. If the supply voltage is disconnected before the preset time has elapsed, the relay will be de-energized and the timer resets. Supply T T LED Symmetrical recycler with pause or pulse start. Depending on the setting of the function switch, the timer starts with e.g a pause period, when supply voltage is connected. When the pause period has elapsed, the relay energizes. The relay remains energized during the pulse period. The sequence is repeated until the supply voltage is disconnected. The duration of the pause and pulse periods is equal. VERSIONS/ORDERING CODES Type: On delay. On pulse. Symmetrical recycler. XM- Supply S 1 T T T T LED XM Mounting: 11-pole plug-in. DIN rail. S D Output relay: SPDT. DPDT. 1 2 Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 4 Time ranges: 0.6-6sec, 6-60sec, 0.6-6min. 6-60min. Full linearity between the ranges is provided i.e. an adjustment made to a specific time in seconds will give the same time in minutes just by operating the range switch. Supply voltage above 50V. The installation (all terminals) must be carried out according to the safety regulations! The control input and the supply input must be connected to the same circuit (phase and main switch). The output relay may only be used in circuits made according to the safety regulations. Timer accuracy: Repeating accuracy: ± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. A1 15 26 28 6 5 7 4 8 9 3 2 16 18 25 A2 1 Supply +/L 10 11 XT SPDT or DPDT. 1) D1/S1: Max. 8A/240V AC 2) Min. 10mA/24VDC D2/S2: Max. 5A/240V AC 2) Min. 100mA/24VDC Contact material: D1/S1: AgNi 0,15 D2/S2: AgCdO Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate time: Max. 50msec. Release time: Max. 20msec. Output relay: Load (cosϕ=1): XMW Max. 100msec. Supply -/N +/L -/N MECHANICAL DIMENSIONS 10 27 10 47 SXM Mounting: S1/S2: D1/D2: XOT Reset time: Supply voltage below 50V. The output relay may NOT be used for voltages above 50V unless the entire supply circuit is made according to the safety regulations. XM WIRING DIAGRAMS XW TECHNICAL DATA INTRO... Electronic Timers On Delay • On Pulse • Symmetrical Recycler XM 11-pole plug-in. Directly on DIN rail TS35 (EN50022). SXT 75 45 Terminals: Max. conductor size 4 mm2. (D1/D2 only) Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). Supply voltage: 24-265V AC 10.5-265V DC Mains frequency: 40-440Hz. Consumption: 0.5-3VA. Cable lengths: Supply voltage: Max. 50 m. OUTPUT LOAD DIAGRAMS, X TIMERS. Protection: S1/S2: D1/D2: IP40. IP20. Fig. 1 2kV AC according to EN 60950 class I. 6 53.5 1,0 TXT TXW 6 Fig. 2 Reduction factor for inductive load 10 0,9 0,8 DC load characteristics 5 XI Isolation: Supply to relay contacts: 53.5 I [A] DC Conforming to EN 50081-1/EN 50082-2. Reduction factor EMC: 13 2 0,7 1 0,6 0,5 0,5 Housing: Black Noryl SE-1. Weight: Typically 80 g. 0,4 0,2 0,2 0,4 0,6 0,8 1,0 cosϕ 0,1 0 50 100 150 200 XB Ambient temperature: -20 to +55°C. 250 300 U [V] DC X types SPDT. X types DPDT XIW XWI & TX types SPDT and DPDT NOTES/REMARKS XIW XF 1) Double output relay available in S2/D2 versions. 2) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RCnetwork, see accessories in price list, to protect the relay contacts. Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 5 Electronic Timers Release Delay • On Pulse • Off Pulse • On-Off Pulse XW DESCRIPTION Multifunction timer with 5 functions and 4 time ranges. The function and the time range are selectable via 2 front mounted rotary switches. Time ranges: 0.6-6sec, 6-60sec, 0.6-6min, 6-60min. The time is adjustable on the timer front. The timer can directly be connected to the supply voltage in the range of 10.5-265V AC/DC. Single or double relay output with LED indication of energized relay. Intermittent flashing of LED indicating timing period (over 6 sec.). Versions available for DIN rail or 11-pole plug-in mounting. VERSIONS/ORDERING CODES On pulse - without control switch. A jumper must be connected between 5 and 7 (B1 and B2). When supply voltage is connected, the relay is energized and the timing period starts. The relay de-energizes when the preset time has elapsed. Supply T T LED On pulse - with control switch. The timer must be connected to the supply voltage permanently. When the control switch is closed, the output relay is energized and the timing period starts. When the preset time has elapsed, the relay de-energizes. To energize the relay again, the control switch must be opened and closed again, after the relay is de-energized. Supply Type: Release delay. On pulse - without control switch. On pulse - with control switch. Off pulse. On-off pulse. XW - S 1 T XW Mounting: 11-pole plug in. DIN rail. S D Output relay: SPDT. DPDT 1). 1 2 T LED Off pulse. The timer must be connected to the supply voltage permanently. When the control switch is opened after having been closed, the relay is energized and the timing period starts. When the preset time has elapsed, the relay de-energizes. Supply T T LED OPERATION The function is selected via the rotary switch on the timer front. The switch may only be operated, when the supply voltage is disconnected. Release delay. The timer must be connected to the supply voltage permanently. When the switch is closed, the output relay is energized. When the switch is opened again, the timing period starts. The relay de-energizes when the preset time has elapsed. On-off pulse. The timer must be connected to supply voltage permanently. When the control switch is opened or closed, the relay is energized and the timing period starts. When the preset time has elapsed, the relay de-energizes. During the timing period the control switch cannot change the status of the relay. Supply T T T LED Supply T T LED Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 6 Electronic Timers Release Delay • On Pulse • Off Pulse • On-Off Pulse XW TECHNICAL DATA WIRING DIAGRAMS Time ranges: 0.6-6sec, 6-60sec, 0.6-6min. 6-60min. Full linearity between the ranges is provided i.e. an adjustment made to a specific time in seconds will give the same time in minutes just by operating the range switch. Supply voltage above 50V. The installation (all terminals) must be carried out according to the safety regulations! The control input and the supply input must be connected to the same circuit (phase and main switch). The output relay may only be used in circuits made according to the safety regulations. Timer accuracy: Repeating accuracy: ± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. Start pulse: Min. 30msec. Reset time: Max. 100msec. Input current (control switch): 3-5mA (max. 0.2A peak). Supply voltage below 50V. The output relay may NOT be used for voltages above 50V unless the entire supply circuit is made according to the safety regulations. Release delay. On pulse - with control switch. Off pulse. On-Off pulse. Alternative 1 SPDT or DPDT. 1) D1/S1: Max. 8A/240V AC 4) Min. 10mA/24VDC S2: Max. 5A/240V AC 4) Min. 100mA/24VDC Contact material: D1/S1: AgNi 0,15 S2: AgCdO Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate and release time: Max. 20msec. Output relay: Load (cosϕ=1): Alternative 2 A1 15 B1 B2 6 5 7 4 16 18 Supply +/L 11 +/L +/L 9 10 1 11 Supply -/N +/L -/N note 1-3 A1 15 B1 B2 6 5 7 8 9 3 11-pole plug-in. Directly on DIN rail TS35 (EN50022). Terminals: (D1 only) Max. conductor size 4 mm2. Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). 8 2 A2 Supply -/N 4 Mounting: S1/S2: D1: 16 18 Supply -/N 7 3 10 1 6 5 4 9 2 A2 A1 15 B1 B2 8 3 16 18 A2 2 11 Supply Supply +/L 10 1 -/N +/L -/N note 1-3 24-265V AC 10.5-265V DC Mains frequency: 40-440Hz. Consumption: 0.5-3VA. Cable lengths: Supply voltage: Control switch: Max. 50 m. Max. 50 m. Protection: S1/S2: D1: IP40. IP20. EMC: Conforming to EN 50081-1/EN 50082-2. Isolation: Supply to relay contacts: 2kV AC according to EN 60950 class I. MECHANICAL DIMENSIONS 10 13 Black Noryl SE-1. Weight: Typically 80 g. NOTES/REMARKS 1) Double output relay only available in S2 versions. 2) Terminals 2 and 7 (A1 & B2) are internally connected. 3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage. 4) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RCnetwork, see tmer price list, to protect the relay contacts. 53.5 6 53.5 Fig. 1 6 1,0 Fig. 2 Reduction factor for inductive load 10 I [A] DC Housing: 27 OUTPUT LOAD DIAGRAMS Reduction factor Ambient temperature:-20 to +55°C. 10 47 75 45 Supply voltage: 0,9 0,8 2 0,7 1 0,6 0,5 0,5 0,2 0,4 DC load characteristics 5 0,2 0,4 0,6 0,8 1,0 cosϕ 0,1 0 50 100 150 200 250 300 U [V] DC X types SPDT. X types DPDT Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 7 Electronic Timers On Delay • Release delay • On Pulse • Symmetrical Recycler XMW DESCRIPTION Multifunction timer with 5 functions and 4 time ranges. The function and the time range are selectable via 2 front mounted rotary switches. The time ranges cover 0.6sec.-60min. or 0.6min.-60hrs. The time is adjustable on the timer front. The timer can directly be connected to the supply voltage in the range of 10.5-265V AC/DC. Single or double relay output with LED indication of energized relay. Intermittent flashing of LED indicating timing period (over 6 sec.). Versions available for DIN rail or 11-pole plug-in mounting. Release delay. The timer must be connected to supply voltage permanently. When the switch is closed, the output relay is energized. When the switch is opened again, the timing period starts. The relay de-energizes when the preset time has elapsed. Supply T T LED On pulse - without control switch. A jumper must be connected between 5 and 7 (B1 and B2). When supply voltage is connected, the relay is energized and the timing period starts. The relay de-energizes when the preset time has elapsed. VERSIONS/ORDERING CODES Type: XMWOn delay. Release delay. On pulse - without control switch. XMW On pulse - with control switch. Symmetrical recycler with pause start. Mounting: 11-pole plug-in. DIN rail. S D Output relay: SPDT. DPDT 1). 1 2 Timing range: 0.6sec.-60min. 0.6min.-60hrs. H S 1 H OPERATION The function is selected via the rotary switch on the timer front. The switch may only be operated, when the supply voltage is disconnected. On delay. The timing period starts when supply voltage is connected. When the preset time has elapsed, the relay is energized. The relay is de-energized when the supply voltage is disconnected. Supply T T LED On pulse - with control switch. The timer must be connected to supply voltage permanently. When the control switch is closed, the output relay is energized and the timing period starts. When the preset time has elapsed, the relay de-energizes. To energize the relay again, the control switch must be opened and closed again, after the relay is de-energized. Supply T T LED Symmetrical recycler with pause start. When supply voltage is connected and the pause period has elapsed, the relay energizes. The relay remains energized during the pulse period. The sequence is repeated until the supply voltage is disconnected. The duration of the pause and pulse periods is equal. Supply T T T T LED Supply TECHNICAL DATA T LED T Time ranges: Code Time ranges 0.6-6sec. 6-60sec. 0.6-6min. 6-60min. H 0.6-6min. 6-60min. 0.6-6hrs. 6-60hrs. Full linearity between the ranges is provided i.e. an adjustment made to a specific time in seconds will give the same time in minutes just by operating the range switch. Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 8 Electronic Timers On Delay • Release Delay • On Pulse • Symmetrical Recycler XMW Timer accuracy: Repeating accuracy: ± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. Start pulse: Min. 30msec. Reset time: Max. 100msec. Input current (control switch): 3-5mA (max. 0.2A peak). SPDT or DPDT. 1) D1/S1: Max. 8A/240V AC 5) Min. 10mA/24VDC S2: Max. 5A/240V AC 5) Min. 100mA/24VDC Contact material: D1/S1: AgNi 0,15 S2: AgCdO Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate time: Max. 50msec. Release time: Max. 20msec. Output relay: Load (cosϕ=1): Mounting: S1/S2: D1: WIRING DIAGRAMS Supply voltage above 50V. The installation (all terminals) must be carried out according to the safety regulations! The control input and the supply input must be connected to the same circuit (phase and main switch). The output relay may only be used in circuits made according to the safety regulations. Supply voltage below 50V. The output relay may NOT be used for voltages above 50V unless the entire supply circuit is made according to the safety regulations. On delay. Symmetrical recycler. A1 15 B1 B2 6 5 7 4 8 9 3 16 18 2 A2 10 1 Supply +/L 11 Supply +/L -/N -/N note 1-4 Release delay. On pulse - with control switch. Alternative 1 Alternative 2 11-pole plug-in. Directly on DIN rail TS35 (EN50022). A1 15 B1 B2 Terminals: (D1 only) Max. conductor size 4 mm2. Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). Supply voltage: 24-265V AC 10.5-265V DC 6 5 9 2 A2 10 Supply +/L +/L 40-440Hz. Consumption: 0.5-3VA. 8 9 2 A2 10 1 Supply -/N note 1-4 Mains frequency: 16 18 Supply -/N 7 3 11 1 6 5 4 8 3 16 18 A1 15 B1 B2 7 4 +/L 11 Supply -/N +/L -/N note 1-4 On pulse - without control switch. Cable lengths: Supply voltage: Control switch: A1 15 B1 B2 Max. 50 m. Max. 50 m. IP40. IP20. EMC: Conforming to EN 50081-1/EN 50082-2. 7 8 9 3 16 18 Protection: S1/S2: D1: 6 5 4 1 Supply +/L 10 2 A2 11 Supply -/N +/L -/N note 1-4 MECHANICAL DIMENSIONS 27 10 47 10 2kV AC according to EN 60950 class I. 75 45 Isolation: Supply to relay contacts: Ambient temperature:-20 to +55°C. Black Noryl SE-1. Weight: Typically 80 g. 13 NOTES/REMARKS 53.5 6 6 OUTPUT LOAD DIAGRAMS Fig. 1 Reduction factor 1) Double output relay only available in S2 versions. 2) Terminals 2 and 7 (A1 & B2) are internally connected. 3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage. 4) Terminals 5 and 6 are internally connected. 5) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RC-network, see timer price list , to protect the relay contacts. 53.5 1,0 Fig. 2 Reduction factor for inductive load 10 I [A] DC Housing: 0,9 0,8 5 2 0,7 1 0,6 0,5 0,5 0,4 DC load characteristics 0,2 0,4 0,6 0,8 1,0 cosϕ 0,2 0,1 0 50 100 150 200 250 300 U [V] DC X types SPDT. X types DPDT Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 9 Electronic Timers Asymmetrical Recycler XT DESCRIPTION OPERATION Asymmetrical recycler with 2 functions and 4 time ranges. The function is selected by mounting a jumper and the time range is selectable via the front mounted rotary switch. The pulse and pause time ranges cover 0.6sec.-60min. or 0.6min.60hrs. Pulse and pause time are individually adjustable on the timer front.The timer can directly be connected to the supply voltage in the range of 10.5-265V AC/DC. Single or double relay output with LED indication of energized relay. Intermittent flashing of LED indicating timing period (over 6 sec.). Versions available for DIN rail or 11-pole plug-in mounting. Asymmetrical recycler with pause start. When supply voltage is connected and the pause time has elapsed, the output relay is energized. The relay remains energized through the pulse period. The sequence is repeated until the supply voltage is disconnected. When the supply voltage is disconnected, the timer resets. Supply T1 T2 T1 LED Asymmetrical recycler with pulse start. By connecting terminals 5 and 7 (B1 and B2) the recycler starts with a pulse i.e. the relay is energized when supply voltage is applied. Supply T1 T2 T1 T2 LED Please note that the function: Pause start/pulse start is determined at power up. If the terminals 5 and 7 (B1 and B2) are connected or disconnected after power up, it will not change function. VERSIONS/ORDERING CODES Type: Asymmetrical recycler. XT - S 1 . LH XT Mounting: 11 pole plug-in. DIN rail. S D Output relay: SPDT. DPDT 1). 1 2 Timing range (pause/pulse): 0.6sec-60min./0.6sec-60min. 0.6sec-60min./0.6min-60hours. LH 0.6min-60hours. /0.6sec-60min. HL 0.6min-60hours. /0.6min-60hours.HH Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 10 Electronic Timers Asymmetrical Recycler XT TECHNICAL DATA WIRING DIAGRAMS Time ranges: Supply voltage above 50V. The installation (all terminals) must be carried out according to the safety regulations! The control input and the supply input must be connected to the same circuit (phase and main switch). The output relay may only be used in circuits made according to the safety regulations. Code Time ranges 0.6-6sec.6-60sec.0.6-6min. 6-60min. H 0.6-6min. 6-60min.0.6-6hrs. 6-60hrs. Full linearity between the ranges is provided i.e. an adjustment made to a specific time in seconds will give the same time in minutes just by operating the range switch. Timer accuracy: Repeating accuracy: ± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. Reset time: Supply voltage below 50V. The output relay may NOT be used for voltages above 50V unless the entire supply circuit is made according to the safety regulations. Pause start Max. 100msec. SPDT or DPDT. 1) D1/S1: Max. 8A/240V AC 3) Min. 10mA/24VDC S2 : Max. 5A/240V AC 3) Min. 100mA/24VDC Contact material: D1/S1: AgNi 0,15 S2: AgCdO Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate time: Max. 50msec. Release time: Max. 20msec. A1 15 B1 B2 6 5 A1 15 B1 B2 7 9 3 16 18 2 A2 +/L 16 18 11 +/L -/N 8 9 2 A2 +/L note 1, 2 10 1 Supply Supply -/N 7 3 10 1 Supply 6 5 4 8 4 Output relay: Load (cosϕ=1): Mounting: S1/S2: D1: Pulse start 11 Supply -/N +/L -/N note 1, 2 MECHANICAL DIMENSIONS 10 27 10 47 75 45 11-pole plug-in. Directly on DIN rail TS35 (EN50022). Terminals: (D1 only) Max. conductor size 4 mm2. Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). Supply voltage: 24-265V AC 10.5-265V DC Mains frequency: 40-440Hz. Consumption: 0.5-3VA. 13 53.5 6 53.5 6 OUTPUT LOAD DIAGRAMS Cable lengths: Supply voltage: Max. 50 m. Fig. 1 EMC: Conforming to EN 50081-1/EN 50082-2. Isolation: Supply to relay contacts: 2kV AC according to EN 60950 class I. Reduction factor IP40. IP20. 1,0 Reduction factor for inductive load 10 0,9 0,8 DC load characteristics 5 2 0,7 1 0,6 0,5 0,5 0,4 Ambient temperature:-20 to +55°C. Fig. 2 I [A] DC Protection: S1/S2: D1: 0,2 0,2 0,4 0,6 0,8 1,0 cosϕ 0,1 0 50 100 150 200 250 300 U [V] DC X types SPDT. Housing: Black Noryl SE-1. Weight: Typically 80 g. X types DPDT NOTES/REMARKS 1) Double output relay only available in S2 versions. 2) Terminals 2 & 7 (A1 & B2) are internally connected. 3) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RC-network, see timer price list, to protect the relay contacts. Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 11 Electronic Timers One Shot XOT DESCRIPTION OPERATION One shot asymmetrical timer with 4 time ranges. The time range is selectable via the front mounted rotary switch. The pulse and pause time ranges cover 0.6sec.-60min. or 0.6min.60hrs. Pulse and pause time are individually adjustable on the timer front.The timer can directly be connected to the supply voltage in the range of 10.5-265V AC/DC. Single or double relay output with LED indication of energized relay. Intermittent flashing of LED indicating timing period (over 6 sec.). Versions available for DIN rail or 11-pole plug-in mounting. One-shot asymmetrical without control switch. A jumper must be connected between 5 and 7 (B1 and B2). When supply voltage is connected and the pause time has elapsed, the output relay is energized. The relay remains energized through the pulse period and de-energize when the puls period has elapsed. This is one time sequenze (one shot). Supply T1 T2 T1 LED One-shot asymmetrical with control switch. The timer must be connected to supply permanently. When the switch is closed, the pause timing period starts. When the preset pause time has elapsed, the output relay is energized. The relay remains energized through the pulse period and de-energize when the puls period has elapsed. To start a one-shot sequenze again, the control switch must be opened and closed again, after the relay is de-energized. Supply T1 T2 T1 T2 LED VERSIONS/ORDERING CODES Type: One shot asymmetrical. XOT- S 1 . LH XOT Mounting: 11 pole plug-in. DIN rail. S D Output relay: SPDT. DPDT 1). 1 2 Timing range (pause/pulse): 0.6sec-60min./0.6sec-60min. 0.6sec-60min./0.6min-60hours. LH 0.6min-60hours. /0.6sec-60min. HL 0.6min-60hours. /0.6min-60hours.HH Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 12 Electronic Timers One Shot XOT TECHNICAL DATA WIRING DIAGRAMS Time ranges: Supply voltage above 50V. The installation (all terminals) must be carried out according to the safety regulations! The control input and the supply input must be connected to the same circuit (phase and main switch). The output relay may only be used in circuits made according to the safety regulations. Code Time ranges 0.6-6sec.6-60sec.0.6-6min. 6-60min. H 0.6-6min. 6-60min.0.6-6hrs. 6-60hrs. Full linearity between the ranges is provided i.e. an adjustment made to a specific time in seconds will give the same time in minutes just by operating the range switch. Timer accuracy: Repeating accuracy: ± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. Reset time: Max. 100msec. SPDT or DPDT. 1) D1/S1: Max. 8A/240V AC 5) Min. 10mA/24VDC S2 : Max. 5A/240V AC 5) Min. 100mA/24VDC Contact material: D1/S1: AgNi 0,15 S2: AgCdO Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate time: Max. 50msec. Release time: Max. 20msec. Supply voltage below 50V. The output relay may NOT be used for voltages above 50V unless the entire supply circuit is made according to the safety regulations. Function - with control switch. Alternative 1 Output relay: Load (cosϕ=1): Alternative 2 A1 15 B1 B2 16 18 11 16 18 +/L 9 +/L 10 1 Supply -/N Note 1-4 8 2 A2 Supply -/N 7 3 10 1 6 5 4 9 Supply +/L A1 15 B1 B2 8 2 A2 11 Supply -/N +/L -/N Note 1-4 Function - Without control switch. 11-pole plug-in. Directly on DIN rail TS35 (EN50022). 6 5 7 4 8 9 3 16 18 Terminals: (D1 only) Max. conductor size 4 mm2. Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). 7 3 A1 15 B1 B2 Mounting: S1/S2: D1: 6 5 4 A2 2 Supply +/L 10 1 11 Supply -/N +/L -/N Supply voltage: 24-265V AC 10.5-265V DC Note 1-4 Mains frequency: 40-440Hz. MECHANICAL DIMENSIONS Consumption: 0.5-3VA. Cable lengths: Supply voltage: Max. 50 m. Protection: S1/S2: D1: IP40. IP20. EMC: Conforming to EN 50081-1/EN 50082-2. 10 10 27 75 45 47 13 Isolation: Supply to relay contacts: 53.5 6 53.5 6 2kV AC according to EN 60950 class I. OUTPUT LOAD DIAGRAMS Ambient temperature:-20 to +55°C. NOTES/REMARKS 1) Double output relay only available in S2 versions. 2) Terminals 2 and 7 (A1 & B2) are internally connected. 3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage. 4) Terminals 5 and 6 are internally connected. 5) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RC-network, see timer price list, to protect the relay contacts. 1,0 Fig. 2 Reduction factor for inductive load 10 0,9 0,8 2 0,7 1 0,6 0,5 0,5 0,4 DC load characteristics 5 0,2 0,2 0,4 0,6 0,8 1,0 cosϕ 0,1 0 50 100 150 200 250 300 U [V] DC X types SPDT. X types DPDT XIW XF Typically 80 g. Fig. 1 I [A] DC Weight: Black Noryl SE-1. Reduction factor Housing: Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 13 Electronic Timers Release Delay - True Off XF DESCRIPTION OPERATION Timer with release delay function, the timer operates without auxiliary supply voltage during the timing period. Fixed time ranges: 0.1-3sec, 1-30sec. or 0.1-3min. The time is adjustable on the timer front. The timer is available in different versions for AC and DC supply voltage. Single or double relay output with LED indication of energized relay. Versions available for DIN rail or 11-pole plug-in mounting. Release delay - true off. When supply voltage is connected, the output relay is energized. When the supply voltage is disconnected, the timing period starts and the output relay remains energized until the preset time has elapsed. Supply T T VERSIONS/ORDERING CODES Type: Release delay - true off. XF Mounting: 11-pole plug-in. DIN rail. S D Output relay: SPDT. DPDT. 1 2 Supply voltage: 24V AC/DC 48V AC/DC 110/120V AC 220/240V AC 380V AC 024 048 115 230 380 Timing ranges: 0.1-3sec. 1-30sec. 0.1-3min. 1 2 3 XF - S 1 230 1 Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 14 Electronic Timers Release Delay - True Off XF TECHNICAL DATA Time ranges: WIRING DIAGRAMS 0.1-3sec, 1-30sec, 0.1-3min. A1 15 26 28 Timer accuracy: Repeating accuracy:± 0.5% at constant conditions. Setting accuracy: ± 10%. Temperature drift: Max. 0.15% per °C. Min. 100msec. Reset time: Max. 100msec. 2) 7 8 9 3 2 16 18 25 A2 +/L 10 1 Supply Start time: 6 5 4 11 Supply -/N +/L -/N note 1 SPDT or DPDT. 1) D1/S1: Max. 8A/24V AC 3) Min.10mA/240V DC D2/S2: Max. 5A/240V AC 3) Min.100mA/24V DC Contact material: AgNi 0,15. Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical life time: Min. 100,000 operations at max. load. Operate and release time: Max. 20msec. Output relay: Load (cosϕ=1): 10 27 10 47 75 45 Mounting: S1/S2: D1/D2: MECHANICAL DIMENSIONS 11-pole plug-in. Directly on DIN rail TS35 (EN50022). Terminals: Max. conductor size 4 mm2. (D1/D2 only) Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection). Supply voltage: 24V AC/DC (20-28V), 48V AC/DC (40-56V), 110/120V AC/DC (95-135V), 220/240V AC (195-265V), 380V (340-420V). 13 53.5 6 53.5 OUTPUT LOAD DIAGRAMS Consumption: 0.7-1VA 2). Cable lengths: Supply voltage: Max. 50 m. Protection: S1/S2: D1/D2: IP40. IP20. EMC: Conforming to EN 50081-1/EN 50082-2. 1,0 Fig. 2 Reduction factor for inductive load 10 I [A] DC 40-60Hz. Reduction factor Fig.1 Mains frequency: 6 0,9 0,8 DC load characteristics 5 2 0,7 1 0,6 0,5 0,5 0,4 0,2 0,2 0,4 0,6 0,8 1,0 cosϕ 0,1 0 50 100 150 200 250 300 U [V] DC X types SPDT. X types DPDT Isolation: Supply to relay contacts: 2kV AC according to EN 60950 class I. Ambient temperature:-20 to +55°C. Housing: Black Noryl SE-1. Weight: Typically 80 g. NOTES/REMARKS 1) Double output relay available in S2/D2 versions. 2) The supply voltage must be applied for minimum 100 msec. or the output relay will remain activated after the preset time has elapsed. The power supply must be able to supply an in-rush current of minimum 300mA during the 100msec. start time. 3) When inductive or DC loads are switched the load capacity of the output relay is reduced, see the output load diagrams on fig. 1 and 2. When inductive loads are switched, it is recommended to use a RC-network, see timer price list, to protect the relay contacts. Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29 E-mail: sales@brodersen.com - www.brodersen.com 15