Electronic Timers

advertisement
Electronic
Timers
Data Sheets and Selection Guide
Valid as of 1 March 2012
Electronic Timers
Introduction & Selection Guide
INTRODUCTION
The Brodersen timer programme includes both multifunction and singlefunction timers. The selection guide below will help to select the right
application.
Brodersen multifunction timers combine a range of timing functions which
are easily selected on the front of the timer. The time range is also
selectable on the front and the timer will work at any voltage from 10.5265V AC or DC
In addition to the multifunction timers, Brodersen also manufacture a
singlefunction timer. All timers are available in versions for DIN rail or 11pole plug-in mounting.
The compact design, the ease of adjustment and the consistent quality
of the entire range of Brodersen timers are the hallmarks of a truly unique
product.
Release delay - true off
On pulse
Off pulse
On-off pulse
Symmetrical recycler
Asymmetrical recycler
One shot, asymmetrical
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
W: 27 mm x H: 75 mm
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Housing
Remote timer start
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Transistor output
0.1sec-3min.
0.1sec-10min.
0.1sec.-30min.
1.5-60sec.
0.6sec.-60min.
0.6min.-60hrs.
Output relay, SPDT
Release delay
Output relay, DPDT
Function
On delay
Time range and
adjustment
Output
Potentiometer, front
SELECTION GUIDE
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Multi-/singlefunction
Multifunction
M
M
M
S
M
M
M
M
M
M
M
M
Type
XMW
XM
XMW
XW
XF
XMW
XM
XW
XW
XW
XMW
XM
XT
Page
8
4
8
6
14
8
4
6
6
6
8
4
10
M
XOT
12
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
Electronic Timers
Introduction & Selection Guide
PROVEN TECHNOLOGY
You will find Brodersen timers in equipment, control panels and machines all over the world. Over the last decade more than 1 million timers
has been installed in various applications. And we are still one of the largest manufactures of electronic timers. That is what we call “Proven
Techology”.
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
3
Electronic Timers
On Delay • On Pulse • Symmetrical Recycler
XM
DESCRIPTION
OPERATION
Multifunction timer with 4 functions and 4 time ranges. The function
and the time range are selectable via 2 front mounted rotary switches.
Time ranges: 0.6-6sec, 6-60sec, 0.6-6min, 6-60min. The time is
adjustable on the timer front.
The timer can directly be connected to the supply voltage in the range
of 10.5-265V AC/DC.
Single or double relay output with LED indication of energized relay.
Intermittent flashing of LED indicating timing period (over 6 sec.).
Versions available for DIN rail or 11-pole plug-in mounting.
The function is selected via the rotary switch on the timer front. The
switch may only be operated, when the supply voltage is disconnected.
On delay.
The timing period starts when supply voltage is connected. When the
preset time has elapsed, the relay is energized.
The relay is de-energized when the supply voltage is disconnected.
If the supply voltage is disconnected before the preset time has
elapsed, the timer resets.
Supply
T
T
LED
On pulse.
When supply voltage is connected, the relay is energized and the timing
period starts. When the preset time has elapsed, the relay is deenergized.
If the supply voltage is disconnected before the preset time has
elapsed, the relay will be de-energized and the timer resets.
Supply
T
T
LED
Symmetrical recycler with pause or pulse start.
Depending on the setting of the function switch, the timer starts with e.g
a pause period, when supply voltage is connected. When the pause
period has elapsed, the relay energizes. The relay remains energized
during the pulse period. The sequence is repeated until the supply
voltage is disconnected.
The duration of the pause and pulse periods is equal.
VERSIONS/ORDERING CODES
Type:
On delay.
On pulse.
Symmetrical recycler.
XM-
Supply
S
1
T
T
T
T
LED
XM
Mounting:
11-pole plug-in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT.
1
2
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
4
Time ranges:
0.6-6sec, 6-60sec, 0.6-6min. 6-60min.
Full linearity between the ranges is provided i.e. an adjustment
made to a specific time in seconds will give the same time in minutes
just by operating the range switch.
Supply voltage above 50V.
The installation (all terminals) must be carried out according to the
safety regulations! The control input and the supply input must be
connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
regulations.
Timer accuracy:
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
A1 15 26 28
6
5
7
4
8
9
3
2
16 18 25 A2
1
Supply
+/L
10
11
XT
SPDT or DPDT. 1)
D1/S1: Max. 8A/240V AC 2)
Min. 10mA/24VDC
D2/S2: Max. 5A/240V AC 2)
Min. 100mA/24VDC
Contact material:
D1/S1: AgNi 0,15
D2/S2: AgCdO
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate time:
Max. 50msec.
Release time:
Max. 20msec.
Output relay:
Load (cosϕ=1):
XMW
Max. 100msec.
Supply
-/N
+/L
-/N
MECHANICAL DIMENSIONS
10
27
10
47
SXM
Mounting:
S1/S2:
D1/D2:
XOT
Reset time:
Supply voltage below 50V.
The output relay may NOT be used for voltages above 50V unless the
entire supply circuit is made according to the safety regulations.
XM
WIRING DIAGRAMS
XW
TECHNICAL DATA
INTRO...
Electronic Timers
On Delay • On Pulse • Symmetrical Recycler XM
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
SXT
75
45
Terminals:
Max. conductor size 4 mm2.
(D1/D2 only)
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
Supply voltage:
24-265V AC
10.5-265V DC
Mains frequency:
40-440Hz.
Consumption:
0.5-3VA.
Cable lengths:
Supply voltage:
Max. 50 m.
OUTPUT LOAD DIAGRAMS, X TIMERS.
Protection:
S1/S2:
D1/D2:
IP40.
IP20.
Fig. 1
2kV AC according to EN 60950 class I.
6
53.5
1,0
TXT
TXW
6
Fig. 2
Reduction factor
for inductive load
10
0,9
0,8
DC load characteristics
5
XI
Isolation:
Supply to relay
contacts:
53.5
I [A] DC
Conforming to EN 50081-1/EN 50082-2.
Reduction factor
EMC:
13
2
0,7
1
0,6
0,5
0,5
Housing:
Black Noryl SE-1.
Weight:
Typically 80 g.
0,4
0,2
0,2
0,4
0,6
0,8
1,0
cosϕ
0,1
0
50
100
150
200
XB
Ambient temperature: -20 to +55°C.
250 300
U [V] DC
X types SPDT.
X types DPDT
XIW
XWI
&
TX types SPDT and DPDT
NOTES/REMARKS
XIW
XF
1) Double output relay available in S2/D2 versions.
2) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and 2.
When inductive loads are switched, it is recommended to use a RCnetwork, see accessories in price list, to protect the relay contacts.
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
5
Electronic Timers
Release Delay • On Pulse • Off Pulse • On-Off Pulse XW
DESCRIPTION
Multifunction timer with 5 functions and 4 time ranges. The function
and the time range are selectable via 2 front mounted rotary
switches.
Time ranges: 0.6-6sec, 6-60sec, 0.6-6min, 6-60min. The time is
adjustable on the timer front.
The timer can directly be connected to the supply voltage in the
range of 10.5-265V AC/DC.
Single or double relay output with LED indication of energized relay.
Intermittent flashing of LED indicating timing period (over 6 sec.).
Versions available for DIN rail or 11-pole plug-in mounting.
VERSIONS/ORDERING CODES
On pulse - without control switch.
A jumper must be connected between 5 and 7 (B1 and B2).
When supply voltage is connected, the relay is energized and the
timing period starts. The relay de-energizes when the preset time
has elapsed.
Supply
T
T
LED
On pulse - with control switch.
The timer must be connected to the supply voltage permanently.
When the control switch is closed, the output relay is energized and
the timing period starts. When the preset time has elapsed, the relay
de-energizes.
To energize the relay again, the control switch must be opened and
closed again, after the relay is de-energized.
Supply
Type:
Release delay.
On pulse - without control switch.
On pulse - with control switch.
Off pulse.
On-off pulse.
XW -
S
1
T
XW
Mounting:
11-pole plug in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT 1).
1
2
T
LED
Off pulse.
The timer must be connected to the supply voltage permanently.
When the control switch is opened after having been closed, the
relay is energized and the timing period starts. When the preset time
has elapsed, the relay de-energizes.
Supply
T
T
LED
OPERATION
The function is selected via the rotary switch on the timer front. The
switch may only be operated, when the supply voltage is disconnected.
Release delay.
The timer must be connected to the supply voltage permanently.
When the switch is closed, the output relay is energized. When the
switch is opened again, the timing period starts.
The relay de-energizes when the preset time has elapsed.
On-off pulse.
The timer must be connected to supply voltage permanently.
When the control switch is opened or closed, the relay is energized
and the timing period starts. When the preset time has elapsed, the
relay de-energizes.
During the timing period the control switch cannot change the status
of the relay.
Supply
T
T
T
LED
Supply
T
T
LED
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
6
Electronic Timers
Release Delay • On Pulse • Off Pulse • On-Off Pulse XW
TECHNICAL DATA
WIRING DIAGRAMS
Time ranges:
0.6-6sec, 6-60sec, 0.6-6min. 6-60min.
Full linearity between the ranges is provided i.e. an adjustment
made to a specific time in seconds will give the same time in
minutes just by operating the range switch.
Supply voltage above 50V.
The installation (all terminals) must be carried out according to the
safety regulations! The control input and the supply input must be
connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
regulations.
Timer accuracy:
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
Start pulse:
Min. 30msec.
Reset time:
Max. 100msec.
Input current
(control switch):
3-5mA (max. 0.2A peak).
Supply voltage below 50V.
The output relay may NOT be used for voltages above 50V unless the
entire supply circuit is made according to the safety regulations.
Release delay. On pulse - with control switch. Off pulse. On-Off
pulse.
Alternative 1
SPDT or DPDT. 1)
D1/S1: Max. 8A/240V AC 4)
Min. 10mA/24VDC
S2:
Max. 5A/240V AC 4)
Min. 100mA/24VDC
Contact material:
D1/S1: AgNi 0,15
S2: AgCdO
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time:
Min. 100,000 operations at max. load.
Operate and
release time:
Max. 20msec.
Output relay:
Load (cosϕ=1):
Alternative 2
A1 15 B1 B2
6
5
7
4
16 18
Supply
+/L
11
+/L
+/L
9
10
1
11
Supply
-/N
+/L
-/N
note 1-3
A1 15 B1 B2
6
5
7
8
9
3
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
Terminals: (D1 only) Max. conductor size 4 mm2.
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
8
2
A2
Supply
-/N
4
Mounting:
S1/S2:
D1:
16 18
Supply
-/N
7
3
10
1
6
5
4
9
2
A2
A1 15 B1 B2
8
3
16 18
A2
2
11
Supply
Supply
+/L
10
1
-/N
+/L
-/N
note 1-3
24-265V AC
10.5-265V DC
Mains frequency:
40-440Hz.
Consumption:
0.5-3VA.
Cable lengths:
Supply voltage:
Control switch:
Max. 50 m.
Max. 50 m.
Protection:
S1/S2:
D1:
IP40.
IP20.
EMC:
Conforming to EN 50081-1/EN 50082-2.
Isolation:
Supply to relay
contacts:
2kV AC according to EN 60950 class I.
MECHANICAL DIMENSIONS
10
13
Black Noryl SE-1.
Weight:
Typically 80 g.
NOTES/REMARKS
1) Double output relay only available in S2 versions.
2) Terminals 2 and 7 (A1 & B2) are internally connected.
3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the
supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage.
4) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and 2.
When inductive loads are switched, it is recommended to use a RCnetwork, see tmer price list, to protect the relay contacts.
53.5
6
53.5
Fig. 1
6
1,0
Fig. 2
Reduction factor
for inductive load
10
I [A] DC
Housing:
27
OUTPUT LOAD DIAGRAMS
Reduction factor
Ambient temperature:-20 to +55°C.
10
47
75
45
Supply voltage:
0,9
0,8
2
0,7
1
0,6
0,5
0,5
0,2
0,4
DC load characteristics
5
0,2
0,4
0,6
0,8
1,0
cosϕ
0,1
0
50
100
150
200
250
300
U [V] DC
X types SPDT.
X types DPDT
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
7
Electronic Timers
On Delay • Release delay • On Pulse • Symmetrical Recycler XMW
DESCRIPTION
Multifunction timer with 5 functions and 4 time ranges. The function
and the time range are selectable via 2 front mounted rotary
switches.
The time ranges cover 0.6sec.-60min. or 0.6min.-60hrs. The time is
adjustable on the timer front.
The timer can directly be connected to the supply voltage in the
range of 10.5-265V AC/DC.
Single or double relay output with LED indication of energized relay.
Intermittent flashing of LED indicating timing period (over 6 sec.).
Versions available for DIN rail or 11-pole plug-in mounting.
Release delay.
The timer must be connected to supply voltage permanently.
When the switch is closed, the output relay is energized. When the
switch is opened again, the timing period starts.
The relay de-energizes when the preset time has elapsed.
Supply
T
T
LED
On pulse - without control switch.
A jumper must be connected between 5 and 7 (B1 and B2).
When supply voltage is connected, the relay is energized and the
timing period starts. The relay de-energizes when the preset time
has elapsed.
VERSIONS/ORDERING CODES
Type:
XMWOn delay.
Release delay.
On pulse - without control switch.
XMW
On pulse - with control switch.
Symmetrical recycler with pause start.
Mounting:
11-pole plug-in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT 1).
1
2
Timing range:
0.6sec.-60min.
0.6min.-60hrs.
H
S
1
H
OPERATION
The function is selected via the rotary switch on the timer front. The
switch may only be operated, when the supply voltage is disconnected.
On delay.
The timing period starts when supply voltage is connected. When
the preset time has elapsed, the relay is energized.
The relay is de-energized when the supply voltage is disconnected.
Supply
T
T
LED
On pulse - with control switch.
The timer must be connected to supply voltage permanently.
When the control switch is closed, the output relay is energized and
the timing period starts. When the preset time has elapsed, the relay
de-energizes.
To energize the relay again, the control switch must be opened and
closed again, after the relay is de-energized.
Supply
T
T
LED
Symmetrical recycler with pause start.
When supply voltage is connected and the pause period has
elapsed, the relay energizes. The relay remains energized during
the pulse period. The sequence is repeated until the supply voltage
is disconnected.
The duration of the pause and pulse periods is equal.
Supply
T
T
T
T
LED
Supply
TECHNICAL DATA
T
LED
T
Time ranges:
Code Time ranges
0.6-6sec. 6-60sec. 0.6-6min. 6-60min.
H
0.6-6min. 6-60min. 0.6-6hrs. 6-60hrs.
Full linearity between the ranges is provided i.e. an adjustment
made to a specific time in seconds will give the same time in
minutes just by operating the range switch.
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
8
Electronic Timers
On Delay • Release Delay • On Pulse • Symmetrical Recycler XMW
Timer accuracy:
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
Start pulse:
Min. 30msec.
Reset time:
Max. 100msec.
Input current
(control switch):
3-5mA (max. 0.2A peak).
SPDT or DPDT. 1)
D1/S1: Max. 8A/240V AC 5)
Min. 10mA/24VDC
S2:
Max. 5A/240V AC 5)
Min. 100mA/24VDC
Contact material:
D1/S1: AgNi 0,15
S2:
AgCdO
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate time:
Max. 50msec.
Release time:
Max. 20msec.
Output relay:
Load (cosϕ=1):
Mounting:
S1/S2:
D1:
WIRING DIAGRAMS
Supply voltage above 50V.
The installation (all terminals) must be carried out according to the
safety regulations! The control input and the supply input must be
connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
regulations.
Supply voltage below 50V.
The output relay may NOT be used for voltages above 50V unless
the entire supply circuit is made according to the safety regulations.
On delay. Symmetrical recycler.
A1 15 B1 B2
6
5
7
4
8
9
3
16 18
2
A2
10
1
Supply
+/L
11
Supply
+/L
-/N
-/N
note 1-4
Release delay. On pulse - with control switch.
Alternative 1
Alternative 2
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
A1 15 B1 B2
Terminals: (D1 only) Max. conductor size 4 mm2.
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
Supply voltage:
24-265V AC
10.5-265V DC
6
5
9
2
A2
10
Supply
+/L
+/L
40-440Hz.
Consumption:
0.5-3VA.
8
9
2
A2
10
1
Supply
-/N
note 1-4
Mains frequency:
16 18
Supply
-/N
7
3
11
1
6
5
4
8
3
16 18
A1 15 B1 B2
7
4
+/L
11
Supply
-/N
+/L
-/N
note 1-4
On pulse - without control switch.
Cable lengths:
Supply voltage:
Control switch:
A1 15 B1 B2
Max. 50 m.
Max. 50 m.
IP40.
IP20.
EMC:
Conforming to EN 50081-1/EN 50082-2.
7
8
9
3
16 18
Protection:
S1/S2:
D1:
6
5
4
1
Supply
+/L
10
2
A2
11
Supply
-/N
+/L
-/N
note 1-4
MECHANICAL DIMENSIONS
27
10
47
10
2kV AC according to EN 60950 class I.
75
45
Isolation:
Supply to relay
contacts:
Ambient temperature:-20 to +55°C.
Black Noryl SE-1.
Weight:
Typically 80 g.
13
NOTES/REMARKS
53.5
6
6
OUTPUT LOAD DIAGRAMS
Fig. 1
Reduction factor
1) Double output relay only available in S2 versions.
2) Terminals 2 and 7 (A1 & B2) are internally connected.
3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the
supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage.
4) Terminals 5 and 6 are internally connected.
5) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and
2. When inductive loads are switched, it is recommended to use a
RC-network, see timer price list , to protect the relay contacts.
53.5
1,0
Fig. 2
Reduction factor
for inductive load
10
I [A] DC
Housing:
0,9
0,8
5
2
0,7
1
0,6
0,5
0,5
0,4
DC load characteristics
0,2
0,4
0,6
0,8
1,0
cosϕ
0,2
0,1
0
50
100
150
200
250 300
U [V] DC
X types SPDT.
X types DPDT
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
9
Electronic Timers
Asymmetrical Recycler
XT
DESCRIPTION
OPERATION
Asymmetrical recycler with 2 functions and 4 time ranges. The
function is selected by mounting a jumper and the time range is
selectable via the front mounted rotary switch.
The pulse and pause time ranges cover 0.6sec.-60min. or 0.6min.60hrs. Pulse and pause time are individually adjustable on the timer
front.The timer can directly be connected to the supply voltage in the
range of 10.5-265V AC/DC.
Single or double relay output with LED indication of energized relay.
Intermittent flashing of LED indicating timing period (over 6 sec.).
Versions available for DIN rail or 11-pole plug-in mounting.
Asymmetrical recycler with pause start.
When supply voltage is connected and the pause time has elapsed,
the output relay is energized. The relay remains energized through
the pulse period. The sequence is repeated until the supply voltage
is disconnected.
When the supply voltage is disconnected, the timer resets.
Supply
T1
T2
T1
LED
Asymmetrical recycler with pulse start.
By connecting terminals 5 and 7 (B1 and B2) the recycler starts with
a pulse i.e. the relay is energized when supply voltage is applied.
Supply
T1
T2
T1
T2
LED
Please note that the function: Pause start/pulse start is determined
at power up. If the terminals 5 and 7 (B1 and B2) are connected or
disconnected after power up, it will not change function.
VERSIONS/ORDERING CODES
Type:
Asymmetrical recycler.
XT
-
S
1
.
LH
XT
Mounting:
11 pole plug-in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT 1).
1
2
Timing range (pause/pulse):
0.6sec-60min./0.6sec-60min.
0.6sec-60min./0.6min-60hours. LH
0.6min-60hours. /0.6sec-60min. HL
0.6min-60hours. /0.6min-60hours.HH
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
10
Electronic Timers
Asymmetrical Recycler XT
TECHNICAL DATA
WIRING DIAGRAMS
Time ranges:
Supply voltage above 50V.
The installation (all terminals) must be carried out according to the
safety regulations! The control input and the supply input must be
connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
regulations.
Code Time ranges
0.6-6sec.6-60sec.0.6-6min. 6-60min.
H
0.6-6min. 6-60min.0.6-6hrs. 6-60hrs.
Full linearity between the ranges is provided i.e. an adjustment
made to a specific time in seconds will give the same time in
minutes just by operating the range switch.
Timer accuracy:
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
Reset time:
Supply voltage below 50V.
The output relay may NOT be used for voltages above 50V unless
the entire supply circuit is made according to the safety regulations.
Pause start
Max. 100msec.
SPDT or DPDT. 1)
D1/S1: Max. 8A/240V AC 3)
Min. 10mA/24VDC
S2 :
Max. 5A/240V AC 3)
Min. 100mA/24VDC
Contact material:
D1/S1: AgNi 0,15
S2:
AgCdO
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate time:
Max. 50msec.
Release time:
Max. 20msec.
A1 15 B1 B2
6
5
A1 15 B1 B2
7
9
3
16 18
2
A2
+/L
16 18
11
+/L
-/N
8
9
2
A2
+/L
note 1, 2
10
1
Supply
Supply
-/N
7
3
10
1
Supply
6
5
4
8
4
Output relay:
Load (cosϕ=1):
Mounting:
S1/S2:
D1:
Pulse start
11
Supply
-/N
+/L
-/N
note 1, 2
MECHANICAL DIMENSIONS
10
27
10
47
75
45
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
Terminals: (D1 only) Max. conductor size 4 mm2.
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
Supply voltage:
24-265V AC
10.5-265V DC
Mains frequency:
40-440Hz.
Consumption:
0.5-3VA.
13
53.5
6
53.5
6
OUTPUT LOAD DIAGRAMS
Cable lengths:
Supply voltage:
Max. 50 m.
Fig. 1
EMC:
Conforming to EN 50081-1/EN 50082-2.
Isolation:
Supply to relay
contacts:
2kV AC according to EN 60950 class I.
Reduction factor
IP40.
IP20.
1,0
Reduction factor
for inductive load
10
0,9
0,8
DC load characteristics
5
2
0,7
1
0,6
0,5
0,5
0,4
Ambient temperature:-20 to +55°C.
Fig. 2
I [A] DC
Protection:
S1/S2:
D1:
0,2
0,2
0,4
0,6
0,8
1,0
cosϕ
0,1
0
50
100
150
200
250 300
U [V] DC
X types SPDT.
Housing:
Black Noryl SE-1.
Weight:
Typically 80 g.
X types DPDT
NOTES/REMARKS
1) Double output relay only available in S2 versions.
2) Terminals 2 & 7 (A1 & B2) are internally connected.
3) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and
2. When inductive loads are switched, it is recommended to use a
RC-network, see timer price list, to protect the relay contacts.
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
11
Electronic Timers
One Shot XOT
DESCRIPTION
OPERATION
One shot asymmetrical timer with 4 time ranges.
The time range is selectable via the front mounted rotary switch.
The pulse and pause time ranges cover 0.6sec.-60min. or 0.6min.60hrs. Pulse and pause time are individually adjustable on the timer
front.The timer can directly be connected to the supply voltage in the
range of 10.5-265V AC/DC.
Single or double relay output with LED indication of energized relay.
Intermittent flashing of LED indicating timing period (over 6 sec.).
Versions available for DIN rail or 11-pole plug-in mounting.
One-shot asymmetrical without control switch.
A jumper must be connected between 5 and 7 (B1 and B2).
When supply voltage is connected and the pause time has elapsed,
the output relay is energized. The relay remains energized through
the pulse period and de-energize when the puls period has elapsed.
This is one time sequenze (one shot).
Supply
T1
T2
T1
LED
One-shot asymmetrical with control switch.
The timer must be connected to supply permanently.
When the switch is closed, the pause timing period starts. When the
preset pause time has elapsed, the output relay is energized. The
relay remains energized through the pulse period and de-energize
when the puls period has elapsed.
To start a one-shot sequenze again, the control switch must be
opened and closed again, after the relay is de-energized.
Supply
T1
T2
T1
T2
LED
VERSIONS/ORDERING CODES
Type:
One shot asymmetrical.
XOT-
S
1
.
LH
XOT
Mounting:
11 pole plug-in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT 1).
1
2
Timing range (pause/pulse):
0.6sec-60min./0.6sec-60min.
0.6sec-60min./0.6min-60hours. LH
0.6min-60hours. /0.6sec-60min. HL
0.6min-60hours. /0.6min-60hours.HH
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
12
Electronic Timers
One Shot XOT
TECHNICAL DATA
WIRING DIAGRAMS
Time ranges:
Supply voltage above 50V.
The installation (all terminals) must be carried out according to the
safety regulations! The control input and the supply input must be
connected to the same circuit (phase and main switch). The output
relay may only be used in circuits made according to the safety
regulations.
Code Time ranges
0.6-6sec.6-60sec.0.6-6min. 6-60min.
H
0.6-6min. 6-60min.0.6-6hrs. 6-60hrs.
Full linearity between the ranges is provided i.e. an adjustment
made to a specific time in seconds will give the same time in
minutes just by operating the range switch.
Timer accuracy:
Repeating accuracy: ± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
Reset time:
Max. 100msec.
SPDT or DPDT. 1)
D1/S1: Max. 8A/240V AC 5)
Min. 10mA/24VDC
S2 :
Max. 5A/240V AC 5)
Min. 100mA/24VDC
Contact material:
D1/S1: AgNi 0,15
S2:
AgCdO
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate time:
Max. 50msec.
Release time:
Max. 20msec.
Supply voltage below 50V.
The output relay may NOT be used for voltages above 50V unless
the entire supply circuit is made according to the safety regulations.
Function - with control switch.
Alternative 1
Output relay:
Load (cosϕ=1):
Alternative 2
A1 15 B1 B2
16 18
11
16 18
+/L
9
+/L
10
1
Supply
-/N
Note 1-4
8
2
A2
Supply
-/N
7
3
10
1
6
5
4
9
Supply
+/L
A1 15 B1 B2
8
2
A2
11
Supply
-/N
+/L
-/N
Note 1-4
Function - Without control switch.
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
6
5
7
4
8
9
3
16 18
Terminals: (D1 only) Max. conductor size 4 mm2.
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
7
3
A1 15 B1 B2
Mounting:
S1/S2:
D1:
6
5
4
A2
2
Supply
+/L
10
1
11
Supply
-/N
+/L
-/N
Supply voltage:
24-265V AC
10.5-265V DC
Note 1-4
Mains frequency:
40-440Hz.
MECHANICAL DIMENSIONS
Consumption:
0.5-3VA.
Cable lengths:
Supply voltage:
Max. 50 m.
Protection:
S1/S2:
D1:
IP40.
IP20.
EMC:
Conforming to EN 50081-1/EN 50082-2.
10
10
27
75
45
47
13
Isolation:
Supply to relay
contacts:
53.5
6
53.5
6
2kV AC according to EN 60950 class I.
OUTPUT LOAD DIAGRAMS
Ambient temperature:-20 to +55°C.
NOTES/REMARKS
1) Double output relay only available in S2 versions.
2) Terminals 2 and 7 (A1 & B2) are internally connected.
3) Terminals 5 and 7 (B1 & B2) are not galvanically isolated from the
supply terminals 2 and 10 (A1 & A2), the control switch must therefore be approved for the actual supply voltage.
4) Terminals 5 and 6 are internally connected.
5) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and
2. When inductive loads are switched, it is recommended to use a
RC-network, see timer price list, to protect the relay contacts.
1,0
Fig. 2
Reduction factor
for inductive load
10
0,9
0,8
2
0,7
1
0,6
0,5
0,5
0,4
DC load characteristics
5
0,2
0,2
0,4
0,6
0,8
1,0
cosϕ
0,1
0
50
100
150
200
250 300
U [V] DC
X types SPDT.
X types DPDT
XIW
XF
Typically 80 g.
Fig. 1
I [A] DC
Weight:
Black Noryl SE-1.
Reduction factor
Housing:
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
13
Electronic Timers
Release Delay - True Off XF
DESCRIPTION
OPERATION
Timer with release delay function, the timer operates without auxiliary supply voltage during the timing period.
Fixed time ranges: 0.1-3sec, 1-30sec. or 0.1-3min. The time is
adjustable on the timer front.
The timer is available in different versions for AC and DC supply
voltage.
Single or double relay output with LED indication of energized relay.
Versions available for DIN rail or 11-pole plug-in mounting.
Release delay - true off.
When supply voltage is connected, the output relay is energized.
When the supply voltage is disconnected, the timing period starts
and the output relay remains energized until the preset time has
elapsed.
Supply
T
T
VERSIONS/ORDERING CODES
Type:
Release delay - true off. XF
Mounting:
11-pole plug-in.
DIN rail.
S
D
Output relay:
SPDT.
DPDT.
1
2
Supply voltage:
24V AC/DC
48V AC/DC
110/120V AC
220/240V AC
380V AC
024
048
115
230
380
Timing ranges:
0.1-3sec.
1-30sec.
0.1-3min.
1
2
3
XF
-
S
1
230
1
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com
14
Electronic Timers
Release Delay - True Off XF
TECHNICAL DATA
Time ranges:
WIRING DIAGRAMS
0.1-3sec, 1-30sec, 0.1-3min.
A1 15 26 28
Timer accuracy:
Repeating accuracy:± 0.5% at constant conditions.
Setting accuracy:
± 10%.
Temperature drift:
Max. 0.15% per °C.
Min. 100msec.
Reset time:
Max. 100msec.
2)
7
8
9
3
2
16 18 25 A2
+/L
10
1
Supply
Start time:
6
5
4
11
Supply
-/N
+/L
-/N
note 1
SPDT or DPDT. 1)
D1/S1: Max. 8A/24V AC 3)
Min.10mA/240V DC
D2/S2: Max. 5A/240V AC 3)
Min.100mA/24V DC
Contact material:
AgNi 0,15.
Frequency:
Max. 1000 operations per hour at max. load.
Mechanical life time: Min. 10 x 106 operations.
Electrical life time: Min. 100,000 operations at max. load.
Operate and
release time:
Max. 20msec.
Output relay:
Load (cosϕ=1):
10
27
10
47
75
45
Mounting:
S1/S2:
D1/D2:
MECHANICAL DIMENSIONS
11-pole plug-in.
Directly on DIN rail TS35 (EN50022).
Terminals:
Max. conductor size 4 mm2.
(D1/D2 only)
Screw type terminals with self-lifting clamps shrouded in accordance to VDE0106 (finger and back of hand protection).
Supply voltage:
24V AC/DC (20-28V),
48V AC/DC (40-56V),
110/120V AC/DC (95-135V),
220/240V AC (195-265V),
380V (340-420V).
13
53.5
6
53.5
OUTPUT LOAD DIAGRAMS
Consumption:
0.7-1VA 2).
Cable lengths:
Supply voltage:
Max. 50 m.
Protection:
S1/S2:
D1/D2:
IP40.
IP20.
EMC:
Conforming to EN 50081-1/EN 50082-2.
1,0
Fig. 2
Reduction factor
for inductive load
10
I [A] DC
40-60Hz.
Reduction factor
Fig.1
Mains frequency:
6
0,9
0,8
DC load characteristics
5
2
0,7
1
0,6
0,5
0,5
0,4
0,2
0,2
0,4
0,6
0,8
1,0
cosϕ
0,1
0
50
100
150
200
250 300
U [V] DC
X types SPDT.
X types DPDT
Isolation:
Supply to relay
contacts:
2kV AC according to EN 60950 class I.
Ambient temperature:-20 to +55°C.
Housing:
Black Noryl SE-1.
Weight:
Typically 80 g.
NOTES/REMARKS
1) Double output relay available in S2/D2 versions.
2) The supply voltage must be applied for minimum 100 msec. or the
output relay will remain activated after the preset time has elapsed.
The power supply must be able to supply an in-rush current of minimum 300mA during the 100msec. start time.
3) When inductive or DC loads are switched the load capacity of the
output relay is reduced, see the output load diagrams on fig. 1 and
2. When inductive loads are switched, it is recommended to use a
RC-network, see timer price list, to protect the relay contacts.
Brodersen A/S - Islevdalvej 187 - DK-2610 Roedovre - Tel: +45 45 35 26 27 - Fax: +45 45 35 26 29
E-mail: sales@brodersen.com - www.brodersen.com