QO® Load Centers 3Ш, Main Lugs, Main Circuit Breaker

QO® Load Centers
3Ø, Main Lugs, Main Circuit Breaker
Class 1130 / Refer to Catalog 1100CT0501
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
Table 1.22:
3Ø4W 208Y/120 Vac, 3Ø4W 240/120 Vac Delta and 3Ø3W 240 Vac Delta, UL Listed.
(Order QO, QO-GFI, QO-AFI, QO-PL branch circuit breakers from pages 1-2 and 1-3.)
Mains
Rating
LOAD CENTERS
I
N
D
O
O
R
Max.
Number
of 1P QO
circuit
breakers
$ Price
(Interior,
Box and
Cover)
Indoor Cover with Door
(Order Separately)
Load Center
Box and Interior
Cat. No.
Flush
Cat. No.
$ Price
Surface
Cat. No.
Main
Wire Size
AWG/kcmil
$ Price
Fixed Mains—Factory-installed Main Lugs—Copper Bus—65 kA Short Circuit Current Rating a
60 A
3
71.00
QO403L60NF/S
71.00
Cover Included With Load Center
12
246.10
QO312L125Gh
221.00
QOC16UF
QOC16US
25.10 i
125 A
20
339.10
QO320L125Gh
314.00
QOC24UF
QOC24US
25.10 i
24
385.10
QO324L125Gh
360.00
QOC24UF
QOC24US
25.10 i
18
353.00
QO318L200Gh
295.00
QOC30UF
QOC30US
58.00 i
200 A
30
471.00
QO330L200Gh
413.00
QOC30UF
QOC30US
58.00 i
225 A
42
635.00
QO342L225Gh
561.00
QOC42UF
QOC42US
74.00 i
Equipment
Ground Bar Kit
(Order Separately)
Box No.
See
Pages
1-16,
1-17
$ Pricej
Al
Cu
Cat. No.
—
10–6
6–2/0
6–2/0
PK4GTA
Factory-incl.g
Factory-incl.g
Factory-incl.g
Factory-incl.f
Factory-incl.f
Factory-incl.f
7.20
—
—
—
—
—
—
13
6
7
7
9
9
11
PK15GTA
PK18GTA
PK18GTA
PK23GTA
PK18GTA
PK23GTA
PK23GTA
11.40
12.50
12.50
14.20
12.50
14.20
14.20
9
12
12
12
12
12
12
6–250
6–250
6–300
Convertible Mains—Factory-installed QDL Main Circuit Breaker—Copper Bus—25 kA Short Circuit Current Rating b
100 A
27
705.00
QO327M100c
647.00
QOC30UF
QOC30US
58.00 i
4–2/0
125 A
30
1287.00 QO330MQ125dh
1226.00 QOC342MQF QOC342MQS
61.00
4–300
30
1287.00 QO330MQ150dh
1226.00 QOC342MQF QOC342MQS
61.00
150 A
4–300
42
1412.00 QO342MQ150dh
1351.00 QOC342MQF QOC342MQS
61.00
30
1287.00 QO330MQ200dh
1226.00 QOC342MQF QOC342MQS
61.00
200 A
4–300
42
1412.00 QO342MQ200dh
1351.00 QOC342MQF QOC342MQS
61.00
225 A
42
1412.00 QO342MQ225dh
1351.00 QOC342MQF QOC342MQS
61.00
4–300
6–300
4–2/0
4–300
4–300
4–300
4–300
Fixed Mains—Factory-installed Main Lugs—Copper Bus—65 kA Short Circuit Current Ratingae
60 A
3
118.00
QO403L60NRB
118.00
—
10–6
PK4GTA
7.20
10R
12
323.00 QO312L125GRB
323.00
Factory Incl.g
—
3R
125 A
6–2/0
6–2/0
20
419.00 QO320L125GRB
419.00
Factory Incl.g
—
4R
R
Cover Included
18
412.00 QO318L200GRB
412.00
Factory Incl.f
—
6R
A
200 A
6–250
6–250
I
30
559.00 QO330L200GRB
559.00
Factory Incl.f
—
6R
N
225 A
42
996.00 QO342L225GRB
996.00
6–300
6–300
Factory Incl.f
—
8R
P
R Convertible Mains—Factory-installed QDL Main Circuit Breaker—Copper Bus—25 kA Short Circuit Current Ratingb e
O
100 A
27
790.00 QO327M100RBc
790.00
4–2/0
4–2/0
PK15GTA
11.40
6R
O
125 A
30
1431.00 QO330MQ125RBd
1431.00
4–300
4–300
PK18GTA
12.50
14R
F
150 A
30
1431.00 QO330MQ150RBd
1431.00
4–300
4–300
PK18GTA
12.50
14R
Cover Included
30
1431.00 QO330MQ200RBd
1431.00
PK18GTA
12.50
14R
200 A
4–300
4–300
42
1555.00 QO342MQ200RBd
1555.00
PK23GTA
14.20
14R
225 A
42
1555.00 QO342MQ225RBd
1555.00
4–300
4–300
PK23GTA
14.20
14R
Above listings through 200 A mains rating meet Federal Specification W-P-115C as Type 1, Class 2.
a
UL short circuit current rating depends on lowest interrupting rating of circuit breaker installed.
b
25 kA short circuit current rating maximum with Square D Type QDL main circuit breaker, or 22 kA SCCR maximum with back-fed Type QO-VH main circuit breaker, feeding QO 10 k AIR
branch circuit breakers.
c
Includes factory-installed back fed QO3100VH main circuit breaker.
d
65 kA Short Circuit Current Rating maximum with field-installed Square D type QGL 65 k AIR minimum main circuit breaker feeding QO and Q1 10 k AIR minimum branch circuit breakers.
e
Side hinge door device allow 1-1/4 in. on left side for door to open.
f
PK23GTA and LK100AN.
g
PK15GTA.
h
Certified to IEC 60439-1 for use on 415Y/240 Vac 3Ø4W, 3,000 SCCR when QODX... branch circuit breakers are used and 10,000 SCCR when QO...VS branch circuit breakers are used.
CE marked.
i
DE3A Discount Schedule
j
DE2 Discount Schedule
Table 1.23:
3Ø Main Circuit Breakers
Field-installable alternate main circuit breakers for QO 3Ø main circuit breaker load centers rated 70–225 A. Do not exceed the
load center main rating.
k
Amperage
25 k AIR
65 k AIR
100 k AIRk
70 A
QDL32070
QGL32070
QJL32070
80 A
QDL32080
QGL32080
QJL32080
90 A
QDL32090
QGL32090
QJL32090
100 A
QDL32100
QGL32100
QJL32100
110 A
QDL32110
QGL32110
QJL32110
125 A
QDL32125
QGL32125
QJL32125
150 A
QDL32150
QGL32150
QJL32150
175 A
QDL32175
QGL32175
QJL32175
200 A
QDL32200
QGL32200
QJL32200
225 A
QDL32225
QGL32225
QJL32225
$ Price (DE2)
1189.00
1628.00
1864.00
When these 3P circuit breakers are used as the main circuit breaker of a 3Ø load center, the maximum AIR
rating is 65 kA at 240 Vac and 100 kA at 208 Vac.
Table 1.24:
3Ø Main Lug Kits
Field-installable main lugs for convertible 3Ø main circuit breaker load centers.
QO342MQ200
1-8
QO312L125G
Main Lug
Amperage Rating
125 A
225 A
DE3
DE3A
DE2
Cat. No.
QOL3125
QOL3225
Discount
Schedule
$ Price
44.90
105.00
Lug Wire Size
AWG/kcmil
6–2/0 Cu/Al
6–300 Cu/Al
© 2007 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
QO® Load Centers
Special Applications
www.us.schneider-electric.com
Class 1130 / Refer to Catalog 1100CT0501
FOR CURRENT INFORMATION
QO Special Application (Order QO, QOT, QO-EPD, QO-GFI and QO-AFI Branch Circuit Breakers from pages 1-2 and 1-3.)
Short Circuit
Current
Rating
Spaces
Max. 1P
Circuits a
Cat. No.
0
2
QO2L30TTSd
QO24L50TTSe
Manufactured Housing:
1Ø2W 120 Vac—Main Lugs Only—CSA Certified
30 Ac
10 kA
2
2
4
50 A
10 kA
2
I
N
D
O
O
R
Load Center b
Box, Interior, and Cover
Max. Tandem
Circuit
Breakers
Equipment Ground Bar Kit
(Order Separately)
$ Price
Cat. No.
33.90
52.00
$ Price
Factory-installed
1Ø2W 120 Vac—Main Circuit Breaker—CSA Certified
30 A
10 kA
3
5
2
QO35FM30TTF/S
55.00
Factory-installed
1Ø3W 120/240 Vac—Main Lugs Only—CSA Certified
70 A
10 kA
2
4
2
QO24L70TSe
52.00
10 kA
6
12
6
QO612L100TF/Sg
57.00
Factory
10 kA
6
12
6
QO612L100DTF/Sg
67.00
Installed
100 A
10 kA
8
16
8
QO816L100TF/Sg
91.00
10 kA
8
16
8
QO816L100DTF/Sg
106.00
Generator Panel: 1Ø3W 120/240 Vac—Factory-installed Main Circuit Breakers with Mechanical Interlock
30 A
10 kA
4
8
4
QO48M30DSGP
375.00
PK7GTA
7.80
60 A
10 kA
4
8
4
QO48M60DSGP
375.00
PK7GTA
7.80
Generator Panel – Use With Automatic Transfer Switchk—1Ø3W 120/240 Vac—Factory/Field-installed Main Circuit Breaker
New!
150 A
22 kA
38
42
42
QO13842MX150
899.00
PK23GTA
14.20
200 A
22 kA
38
42
42
QO13842MX200
999.00
PK23GTA
14.20
22 kA
38
42
42
QO13842MX225
1099.00
PK23GTA
14.20
225 A
22 kA
38
42
42
QO13842UX225m
799.00
PK23GTA
14.20
QOC38MXUF (Cover)
99.00
150 A
22 kA
14
28
28
QO11428MX150FTRBl
899.00
PK23GTA
14.20
22 kA
14
28
28
QO11428MX200FTRBl
999.00
PK23GTA
14.20
200 A
22 kA
14
28
28
QO11428UX200FTRBml
799.00
PK23GTA
14.20
Load Center with Cover: 1Ø3W 120/240 Vac—UL Listed Complete QO Load Center—Box, Interior & Combination Cover in One Package
Main Wire Size
AWG/kcmil
Al
Cu
Box No.
See
Page 1-16
12–10
—
14–10
14–6
1
2
f
12–3
LOAD CENTERS
Mains
Rating
3
14–4
2
4
4
4
4
14–8
8–2
14–8
8–2
4
4
4–250
4–250
4–250
4–250
4–250
4–250
4–250
4–250
12
12
12
12
4–250
4–250
4–250
4–250
4–250
4–250
7R
7R
7R
4–1
1
Table 1.25:
Convertible Mains—Factory-Installed Main Lugs hi—QOM1 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-5)—Copper Bus
65 kA
12
0
QO112L125GC
125.00
PK12GTA Incl.
6–2/0
6
12
125 A
65 kA
12
24
12
QO11224L125GC
166.00
PK15GTA Incl.
6–2/0
6
20
65 kA
20
0
QO120L125GC
189.00
PK15GTA Incl.
6–2/0
7
Convertible Mains—Factory-Installed Main Lugs hi—QOM2 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-5)—Copper Bus
150 A
65 kA
30
30
0
QO130L150TC
301.00 PK23GTA & LK100AN Installed
6–250
9
200 A
65 kA
30
40
10
QO13040L200GC
383.00 PK23GTA & LK100AN Incl.
6–250
9
Convertible Mains—Factory-Installed Main Circuit Breaker—
QOM1 Main Frame Size—Convertible to Main Lugs (See page 1-6) or Lower Amperage Main Circuit Breaker (See page 1-5)—Copper Bus j
22 kA
12
12
0
QO112M100C
234.00
PK9GTA
8.90
4–1/0
5
22 kA
12
20
8
QO11220M100C
275.00
PK15GTA
11.40
4–1/0
5
100 A
22 kA
16
16
0
QO116M100C
263.00
PK12GTA
10.50
4–1/0
6
22 kA
20
20
0
QO120M100C
297.00
PK15GTA
11.40
4–1/0
6
Convertible Mains—Factory-Installed Main Circuit Breaker—
QOM2 Main Frame Size—Convertible to Main Lugs (See page 1-6) or Lower Amperage Main Circuit Breaker (See page 1-5)—Copper Bus j
22 kA
20
30
10
QO12030M150C
562.00
PK18GTA
12.50
4–250
9
150 A
22 kA
30
30
0
QO130M150C
580.00
PK18GTA
12.50
4–250
9
22 kA
20
40
20
QO12040M200C
562.00
PK23GTA
14.20
4–250
9
22 kA
30
30
0
QO130M200C
597.00
PK18GTA
12.50
4–250
9
200 A
22 kA
30
40
10
QO13040M200C
649.00
PK23GTA
14.20
4–250
9
22 kA
40
40
0
QO140M200C
758.00
PK23GTA
14.20
4–250
10
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
a
Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers.
b
Order F for flush device or S for surface device.
c
Mains rating 25 A when Al wire is used.
d
Will not accept Qwik-Gard® QO-GFI circuit breaker.
e
Use 10 AWG maximum size wire for GFI circuit breakers.
f
Main circuit breaker is a field-installed standard QO single pole circuit breaker. Order separately from page 1-2.
g
70 A max. branch circuit breaker and 70 A max. back fed main circuit breaker.
h
UL short circuit current rating depends on lowest interrupting rating of circuit breaker installed.
i
UL Listed 5000 A short circuit current rating for corner grounded Delta systems. Use QO-H circuit breakers only.
j
22 k AIR main circuit breaker UL Listed for use ahead of QO, QOT and QO-PL 10 k AIR branch circuit breakers to permit their application on systems with up to 22,000 A available fault current.
k
One main circuit breaker is included with panel. NEMA 1 indoor device requires cover ordered separately. Alternate source main circuit breaker (QO 125 A max) ordered separately. Automatic
Transfer switch and Generator for secondary power source are ordered through a Kohler authorized dealer or contractor.
l
Device is rated NEMA 3R and can be used for indoor or outdoor applications.
m
Universal mains—no factory installed main circuit breaker or main lugs. QOM2 frame size—field install 22 k AIR main circuit breaker or main lugs (see page 1-5 or 1-6).
Table 1.26:
Auxiliary Gutter
UL Listed for use with standard 1Ø and 3Ø load centers for riser applicationsn. For auxiliary gutter-load center compatibility, see Catalog 1100CT0501
n
o
Table 1.27:
Cat. No.
$ Price
Cover
SDAG26
225.00
Flush
One tap kit required for each riser wire.
When used with B300 bolt-on hubs.
Conduit Riser Size
1-3/4, 2, 2-1/2 or o3
Width
13.50
Height
26.12
Depth
3.75
Tap Kits 120/240 Vac—UL Listed For Use With Auxiliary Gutters SDAG26
Cat. N0.
$ Price
Use With Auxiliary
Gutter Cat. No.
SDGT30020
SDGT300300
54.00
80.00
SDAG26
SDAG26
SDGT300C10C
33.10
SDAG26
SDGT300C300C
46.90
SDAG26
QOGL20 Grounding Terminals
27.10
SDAG26
© 2007 Schneider Electric
All Rights Reserved
Riser Wire
Lug Type
Mechanical (Included)
Mechanical (Included)
Anderson VCEL030516H1
(Not included)
Anderson VCEL030516H1
(Not included)
Mechanical (Included)
DE3A
Discount
Schedule
Tap Off Wire
Al/Cu Wire Size
(2) 6 AWG–300 kcmil
(2) 6 AWG–300 kcmil
(2) 4 AWG–300 kcmil
(2) 4 AWG–300 kcmil
(2) 6–2/0 AWG
Lug Type
Mechanical (Included)
Mechanical (Included)
Anderson VCEL02114S1
(Not Included)
Anderson VCEL030516H1
(Not included)
—
Al/Cu Wire Size
(1) 6–2/0 AWG
(1) 6 AWG–300 kcmil
(1) 8–1/0 AWG
(1) 4 AWG–300 kcmil
—
1-9
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
QO® and Homeline® Load
Centers
Load Center Value Pack
Class 1130, 1170 / Refer to Catalog 1100CT0501
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
Load Center Value Pack
LOAD CENTERS
Mains
Rating
1Ø3W—120/240 Vac—UL Listed—Convertible Mains—Factory-installed Main Circuit Breaker
Complete Load Center (Box, Interior and Cover) and Selected Branch Circuit Breakers
Spaces
Table 1.28:
Max.
1P
Circuitsa
Max.
Tandem
Circuit
Breakers
Equipment
Ground Bar Kit
(Order Separately)
Load Center
Box, Interior, Cover and Branch Circuit Breakers
Cat. No.
Included Load Center/Circuit Breakers
$ Price
QO—Copper Bus—Order extra QO, QOT, QO-EPD, QO-GFI, QO-AFI branch circuit breakers from pages 1-2 and 1-3.
Main Circuit Breaker
100 A
32
32
0
QOVP2
(1) QO132M100C, (5) QO120
200 A
30
40
10
QOVP1
(1) QO13040M200C, (5) QO120
200 A
30
40
10
QOVP10
(1) QO13040M200C, (10) QO120
Homeline—Order extra HOM, HOMT, HOM-GFI, HOM-AFI branch circuit breakers from page 1-13.
Main Lugs
125 A
12
24
12
HOMVPL2 (1) HOM1224L125TC, (5) HOM120
200 A
30
40
10
HOMVPL1 (1) HOM3040L200TC, (6) HOM115, (6) HOM120, (1) HOM230, (1) HOM250
Main Circuit Breaker
100 A
20
20
0
HOMVP4
(1) HOM20M100C, (5) HOM115
100 A
20
20
0
HOMVP5
(1) HOM20M100C, (5) HOM120
150 A
30
30
0
HOMVP12 (1) HOM30M150C, (5) HOM120, (1) HOM230
200 A
20
40
20
HOMVP16 (1) HOM2040M200TC, (5) HOM120, (1) HOM230
200 A
30
40
10
HOMVP1
(1) HOM3040M200TC, (5) HOM120, (1) HOM230
200 A
30
40
10
HOMVP2
(1) HOM3040M200TC, (5) HOM115, (1) HOM230
200 A
30
40
10
HOMVP9
(1) HOM3040M200TC, (6) HOM115, (6) HOM120, (1) HOM230, (1) HOM250
200 A
30
40
10
HOMVP14 (1) HOM3040M200TC, (12) HOM120, (1) HOM230, (1) HOM250
200 A
40
40
0
HOMVP15 (1) HOM40M200C, (10) HOM120
I
N
D
O
O
R
R
A
I
N
P
R
O
O
F
Cat. No.
559.00
735.00
885.00
PK18GTA
PK23GTA
PK23GTA
235.00
641.00
Included
Included
352.00
352.00
655.00
643.00
722.00
722.00
885.00
885.00
897.00
PK15GTA
PK15GTA
PK23GTA
Included
Included
Included
Included
Included
PK23GTA
835.00
PK23GTA
Main
Box No.
Wire Size
See
AWG/kcmil Pages
Al/Cu
1-16, 1-17
$ Price
12.50
14.20
14.20
4–2/0
4–250
4–250
8
9
9
6–2/0
4–250
6
10
11.40
11.40
14.20
—
—
—
—
—
14.20
4–2/0
4–2/0
4–250
4–250
4–250
4–250
4–250
4–250
4–250
8
8
10
9
10
10
10
10
12
14.20
4–250
6R
—
—
Homeline—Order extra HOM, HOMT, HOM-GFI, HOM-AFI branch circuit breakers from page 1-13.
Main Circuit Breaker
200 A
20
40
20
HOMVPRB1 (1) HOM2040M200RB, (6) HOM115, (6) HOM120, (1) HOM230, (1) HOM250
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
a
Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers.
Riser Panels
Table 1.29:
1Ø3W 120/240 Vac—Offset Interior Wide Gutter—30 A Maximum Branch Circuit Breaker on left side of interior bc
New!
Mains
Rating
Spaces
Max.
Single
Pole
Circuitsd
Max.
Tandem
Circuit
Breakers
Load Center Box and Interior
Cat. No.
Load Center Cover
$ Price
Cat. No.
$ Price
Equipment
Ground Bar Kit
(Order Separately)
Cat. No.
Convertible Mains—Factory-installed Main Lugs—65 kA Short Circuit Current Rating
QOM1 Main Frame Size—Convertible to Main Circuit Breaker (See page 1-5) when used with QOC cover below—Copper Bus
125 A
12
24
12
QO11224L125WG
225.00 QOC20UFWG
35.00
PK15GTA
125 A
20
30
10
QO12030L125WG
310.00 QOC20UFWG
35.00
PK15GTA
I
N Convertible Mains—Factory-installed Main Lugs—65 kA Short Circuit Current Rating
D
O QOM2 Main Frame Size–Convertible to Main Circuit Breaker (See page 1-5) when used with QOC cover below–Copper Bus
O
200 A
30
40
10
QO13040L200WG
467.00 QOC30UFWG
68.00
PK23GTA
R
Convertible Mains—Factory-installed Main Circuit Breaker—22 kA Short Circuit Current Rating
QOM2 Main Frame Size–Convertible to Main Lugs (See page 1-6)—Copper Bus
QO124M200WG125
200 A
24
24
0
455.00 QOC30UFWG
68.00
PK23GTA
e
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
b
UL short circuit current rating depends on lowest interrupting rating of circuit breaker installed.
c
UL Listed 5000 A short circuit current rating for corner grounded Delta systems. Use QO-H circuit breakers only.
d
Maximum single pole branch circuits utilizing QO and/or QOT circuit breakers.
e
Comes with 125 A main circuit breaker factory installed.
Main
Wire Size
AWG/kcmil
$ Price
Al
Cu
Box No.
See
Page 1-16
11.40
11.40
6–2/0
6–2/0
14
14
14.20
4–250
23
14.20
4–250
23
Panelboard-style Covers for Riser Panels
Mono-Flat® Front available for riser panels as an alternative to standard load center cover listed above. Provides a low-profile, aesthetically
pleasing solution for high-traffic areas in upscale multi-family applications. Deadfront included. Lock kit not provided. Cannot be used when panel
has been converted to main breaker panel. f
f
1-10
Mains Rating of Load Center
Cat. No.
125 A
NQC20FWG
200 A
NQC30FWG
Order catalog number PK4FL for field installable lock kit.
$ Price
78.00
120.00
DE3A
Discount
Schedule
© 2007 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
Load Center Accessories
QO Load Center Accessories
www.us.schneider-electric.com
Class 1130 / Refer to Catalog 1100CT0501
FOR CURRENT INFORMATION
QO Load Center Accessories
Cat. No.
$ Price Schedule
PK2MB
4.80
DE3A
PK3MB
PK5RK
9.80
9.80
DE3A
DE3A
PK4MB2LA
9.80
DE3A
PK4MB2HA
9.80
DE3A
QO2DTI
16.60
DE2E
QO2DTIM
42.00
DE2E
PK4DTIM4LA
68.00
DE3A
PK4DTIM4HA
68.00
DE3A
PK4DTIM4LAL
68.00
DE3A
QOCRBGK1
70.00
DE3A
QOCGK2
70.00
DE3A
QORBGK2
70.00
DE3A
QO1SE
SDSA1175
SDSA3650
QO2175SB
HOM2175SB
2.40
61.00
165.00
106.00
106.00
DE3A
DE1B
DE1B
DE1B
DE1B
QOSAMK
7.60
DE3A
LSDL
.36
DE5
PSDS
.50
DE5
LOAD CENTERS
Description
Secures circuit breaker to interior when used as a back-fed main. For QO612L100F/S, RB,
QO612L100DF/S, QO816L100F/S, RB, QO816L100DF/S and QO148L125GF/S, GRB load centers
Secures 3P circuit breaker without accessories to left side of interior when used as a back-fed main. For 3Ø load centers
Secures circuit breaker to interior when used as a back-fed main for 2P QO 150–200 A circuit breakers.
Retaining Kit
Secures ONE circuit breaker with or without electrical accessories to right side of interior when used as a back-fed main.
For 1Ø 100–125 ampere convertible main load centers. Series S01 and S02.
Secures ONE circuit breaker with or without electrical accessories to right side of interior when used as a back-fed main.
For 1Ø 150–225 ampere convertible main load centers. Series S01 and S02.
For interlocking the handles of two 2P or one 2P and one 1P QO and Q1 circuit breakers mounted
side-by-side so that only one circuit breaker can be “ON’’ at a time
QO2DTI mechanical interlock attachment with retaining kits for securing two adjacent back-fed circuit breakers in dual
power supply applications. Can be used with (2) 2P or (1) 2P and (1) 1P QO circuit breakers in QO816L100 load centers.
Secures two 2P circuit breakers to right side of interior when used as back-fed mains, a QO2DTI Kit included for
Manual Transfer Equipment Kit
back-up power supply applications. For 1Ø 100–125 ampere convertible main load centers. Series S01 and S02.
Secures two 2P circuit breakers to right side of interior when used as back-fed mains, a QO2DTI Kit included for
back-up power supply applications. For 1Ø 150–225 ampere convertible main load centers. Series S01 and S02.
Secures two 2P circuit breakers to left side of interior when used as back-fed mains, a QO2DTI Kit included for
back-up power supply applications. For 1Ø 100–125 ampere convertible main load centers. Series S01 and S02.
For use on “G” and “S” Series NEMA 1 and “G”, “S1” and “S2” Series NEMA 3R load centers. Interlocks a
New!
QOM1 2P main circuit breaker of a load center (100–125 A) with a QO 2P (15–125 A) branch circuit breaker. Includes
a retaining kit.
Generator Circuit Breaker
For use on “G” and “S” Series NEMA 1 and “G” and “S1” Series NEMA 3R load centers. Interlocks a QOM2 2P main
Interlock Kit
circuit breaker of a load center (150–225 A) with a QO 2P (15–125 A) branch circuit breaker. Includes a retaining kit.
For use on “S2” Series NEMA 3R load centers. Interlocks a QOM2 2P main circuit breaker of a load center
(150–225 A) with a QO 2P (15–125 A) branch circuit breaker. Includes a retaining kit.
Cover Sealing Strap: Provides means of sealing trim mounting screws on QO load center covers
For use on 1Ø3W, 150 Vac maximum
For use on 3Ø4W, 650 Vac maximum
Surge Arresters:
QO Surgebreaker CULUS Listed Secondary Surge Arrester 150 Vac line-to-ground maximum.
Homeline Surgebreaker CULUS Listed Secondary Surge Arrester 150 Vac line-to-ground maximum.
Miscellaneous
Surge Arrester
UL Listed for mounting SDSA1175 surge arrester into ground bar mounting holes on 1Ø convertible main circuit breaker
Mounting Kit:
load centers
Replacement Cover 1 through 42 numbered universal replacement directory label for load center covers
Directory Label:
Circuit Identification Circuit identification stickers for use on cover directory labels to identify branch circuits
Stickers:
1
Table 1.30:
PK2MB
QOSAMK
QO2DTI
6
OFF
1
ON
ON
4
3
2
ON
OFF
5
ON
OFF
OFF
PK3MB
QO2DTI Installed
QOCGK2 Installed
PK4DTIM4HA
© 2007 Schneider Electric
All Rights Reserved
DE1B
DE2E
DE3A
DE5
Discount
Schedule
1-11
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
QO® and Homeline® Accessories and Voltage testers
Load Center Accessories
Class 1130, 6610 / Refer to Catalog 1100CT0501
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
Table 1.31:
QO Load Center Accessories
LOAD CENTERS
Description
Cat. No.
Fills opening in covers if twistout is removed in error
QOFP
Fills main circuit breaker opening in convertible load center covers100–125 A
QOM1FP
Filler Plates
Fills main circuit breaker opening in convertible load center covers150–225 A
QOM2FP
Fills main circuit breaker opening in 3Ø load center covers (S01 and S02 Series)
KFP
Fills main circuit breaker opening in “Q” style 3Ø load center covers (S03 Series)
Q2FP
Use with convertible mains, 1Ø and 3Ø 100–225 A, and fixed mains, 3Ø 125–225 A indoor load centers
PK6FLa
Lock Kits
Use with 300 and 400 ampere indoor load centers
PK4FL
Field-installed for 12– 2 Al or 14–4 Cu AWG wire
LK70AN
Field-installed for 6–2/0 Al/Cu AWG wire
LK100AN
Neutral / Ground Lugs
Field-installed for 14–2/0 Al/Cu AWG wire
LK125AN
Field-installed for 2–3/0 Al/Cu AWG wire
LK150AN
Field-installed for 4 AWG to 300 kcmil Al/Cu wire. Use in Series S, 150–225 A QO or HOM load center
LK225AN
Standard PK15GTA with a 1–4/0 Al/Cu Lug
PK15GTAL
Standard PK18GTA with a 1–4/0 Al/Cu Lug
PK18GTAL
Ground Bar Kits
Standard PK23GTA with a 1–4/0 Al/Cu Lug
PK23GTAL
Insulator Kit for PK7GTA through PK27GTA
PKGTAB
For padlocking main circuit breakers in convertible load centers OFF..........50–125 A, QOM1 Frame Size
QOM1PA
Handle Padlock Attachment:
For padlocking main circuit breakers in convertible load centers OFF..........100–225 A, QOM2 Frame Size
QOM2PA
a
QO612L100DF/S, QO816L100DF/S, QO612L100DFCU/SCU, QO816L100DFCU/SCU and QO403L60NF/S DO NOT have provisions for field-installed lock.
$ Price Schedule
2.40 DE3A
13.50 DE3A
13.50 DE3A
13.50 DE3A
13.50 DE3A
62.00 DE3A
60.00
PE1A
6.70 DE3A
7.20 DE3A
14.70 DE3A
21.60 DE3A
22.10 DE3A
23.30 DE3A
25.20 DE3A
27.10 DE3A
29.20 DE3A
7.30 DE2E
7.30 DE2E
QOFP
PKGTAB
PK4FL
PK6FL
Table 1.32:
Homeline Load Center Accessories
Description
Handle Padlock Attachment:
50–125 A
100–225 A
For padlocking main circuit breakers in convertible load center, “OFF”
Fills opening in covers if twistout is removed in error
Filler Plates
Field-installed for 14–2 AWG Al or 14–4 AWG Cu wire
Field-installed for 6–2/0 AWG Al/Cu wire
Field-installed for 14–2/0 AWG Al/Cu wire
Field-installed for 4 AWG–300 kcmil Al/Cu wire. Use in Series S, 150–225 A QO or HOM load center
Secures circuit breaker to interior when used as a back-fed main.
For HOM612L100F/S, RB and HOM48L125GC, GRB load centers.
Secures ONE circuit breaker right side of interior when used as a back-fed main.
For 100–125 A convertible main load centers, Series S01 and S02
Secures ONE circuit breaker right side of interior when used as a back-fed main.
For 150–225 A convertible main load centers, Series S01 and S02
Secures circuit breaker to interior when used as a back-fed main.
For 2P 150–200 A circuit breakers
Neutral Lugs
Retaining Kit
Miscellaneous
New!
Generator Circuit
Breaker Interlock Kit
100–125 A
150–225 A
Fills main circuit breaker opening in convertible load centers
Cat. No.
QOM1PA
QOM2PA
HOMFP
QOM1FP
QOM2FP
LK70AN
LK100AN
LK125AN
LK225AN
$ Price Schedule
7.30 DE2E
7.30 DE2E
2.10 DE3C
13.50 DE3A
13.50 DE3A
6.70 DE3B
7.20 DE3B
14.70 DE3B
22.10 DE3A
HOM1RK
4.30
DE3C
HOM4RK2LA
9.80
DE3C
HOM4RK2HA
9.80
DE3C
HOM5RK
9.80
DE3C
DE3A
Lock Kit
Use with convertible indoor load center covers (Series S-1)
PK6FL
62.00
Replacement Cover
Directory Label
1 through 42 numbered universal replacement directory label for load center covers
LSDL
.36
DE5
PSDS
.50
DE5
Circuit Identification
Circuit identification stickers for use on cover directory labels to identify branch circuits
Stickers:
For use on “S” Series NEMA 1 and “S1” and “S2” Series NEMA 3R load centers. Interlocks a QOM1 2P main
circuit breaker of a load center (100–125 A) with a Homeline 2P (15–125 A) branch circuit breaker.
For use on “S” Series NEMA 1 and “S1” Series NEMA 3R load centers. Interlocks a QOM2 2P main circuit breaker
of a load center (150–225 A) with a Homeline 2P (15–125 A) branch circuit breaker.
For use on “S2” Series NEMA 3R load centers. Interlocks a QOM2 2P main circuit breaker of a load center
(150–225 A) with a Homeline 2P (15–125 A) branch circuit breaker.
HOMCRBGK1
70.00
DE3D
HOMCGK2
70.00
DE3D
HOMRBGK2
70.00
DE3D
Table 1.33:
Voltage Testers
Solenoid Type with polarity indication and slotted receptacles for holding prods. UL and CSA Listed.
Description
The
Type
Voltage Tester 120-240-480-600 Vac 50/60 Hz; 120-240-600 Vdc
Same as VT-1 except with fused leads
Deluxe Simulated Leather Carrying Case
Replacement Polarity Indication Cap b
Replacement Leads b
Fused Replacement Leads b
b
Wiggy® Voltage Tester
1-12
$ Price Schedule
6610VT1
67.00
DE3B
6610VT1S
74.00
DE3B
6610L2
39.30
DE3B
6610PC1
8.00
DE3B
6610P1
25.70
DE3B
6610P1S
35.50
DE3B
IMPORTANT: Will fit only Class 6610 Series A testers and Catalog Number 5008, Series B testers. Will not fit 5008 Pre-Series B testers. Leads must
be replaced as a unit. Replacement of individual lead components must not be attempted.
DE2E
DE3A
DE3B
DE3C
DE3D
DE3E
DE5
PE1A
Discount
Schedule
© 2007 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
www.us.schneider-electric.com
Homeline® Circuit
Breakers
Plug-On Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
FOR CURRENT INFORMATION
Table 1.34:
HOM 2P
2 Spaces Required
HOM2200BB
Branch
Circuit Breaker
4 Spaces Required
HOM
Ampere
Rating
AIR
15 A
20 A
25 A
30 A
35 A
40 A
45 A
50 A
60 A
70 A
80 A
90 A
100 A
110 A
125 A
150 A
175 A
200 A
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
10 kA
1P—120/240 Vac
Cat. No.
HOM115 ab
HOM120 ab
HOM125 b
HOM130 b
—
HOM140 b
—
HOM150 b
—
—
—
—
—
—
—
—
—
—
New!
HOM 1P AFI
(Arc Fault Circuit
Interrupter)
1 Space Required
1P—120/240 Vac
Amperes
Cat. No.
HOM115HMb
HOM120HMb
Circuit Breaker Type
Arc-fault Circuit
Interrupter
Combination Arc-fault
Circuit interrupter
—
—
—
Poles 120
Cat. No.
Vac
1
HOM115AFIb
1
HOM120AFIb
1
HOM115CAFIb
1
HOM120CAFIb
150.00
150.00
150.00
150.00
AIR
10 kA
10 kA
10 kA
10 kA
10 kA
Table 1.38:
1 Space Required
Cat. No.
HOM115GFI
HOM120GFI
—
—
—
2 Spaces Required
$ Price
141.00
141.00
—
—
—
Cat. No.
HOM215GFI
HOM220GFI
HOM230GFI
HOM240GFI
HOM250GFI
$ Price
275.00
275.00
275.00
275.00
275.00
HOM-EPD—10 k AIR
Homeline Equipment Protection Device—Circuit Breakers with 30 mA
Equipment Ground Fault Protection (UL Listed)
15 A
20 A
25 A
30 A
40 A
50 A
2P—120/240 Vac
Common Trip
1P—120 Vac
Cat. No.
HOM115EPD
HOM120EPD
—
—
—
—
$ Price
249.00
249.00
—
—
—
—
DE3D
Cat. No.
HOM215EPD
HOM220EPD
HOM225EPD
HOM230EPD
HOM240EPD
HOM250EPD
DE3C
DE2E
$ Price
440.00
440.00
440.00
440.00
440.00
440.00
Discount
Schedule
AIR
1P Tandem—120/240 Vac (One Space
Required)
Cat. No.
$ Price
15 and 15 A
10 kA
HOMT1515 b
34.90
15 and 20 A
10 kA
HOMT1520 b
34.90
20 and 20 A
10 kA
HOMT2020 b
34.90
30 and 15 A
10 kA
HOMT3015 b
34.90
30 and 20 A
10 kA
HOMT3020 b
34.90
a
UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac
fluorescent lighting loads.
b
UL Listed as HACR type for use with air conditioning, heating and
refrigeration equipment having motor group combinations and marked
for use with HACR type circuit breakers.
Table 1.40:
HOMT Quad Tandem Circuit Breakers
Ampere Ratingd
AIR
2P Tandem—120/240 Vac (Two Spaces
Required)
1P
2P
Cat. No.
$ Price
(2) 15 A
15 A
10 kA
HOMT1515215 b
80.00
(2) 15 A
20 A
10 kA
HOMT1515220 b
80.00
(2) 15 A
25 A
10 kA
HOMT1515225 b
80.00
(2) 15 A
30 A
10 kA
HOMT1515230 b
80.00
(2) 15 A
40 A
10 kA
HOMT1515240 b
80.00
(2) 15 A
50 A
10 kA
HOMT1515250 b
80.00
(2) 20 A
20 A
10 kA
HOMT2020220 b
80.00
(2) 20 A
25 A
10 kA
HOMT2020225 b
80.00
(2) 20 A
30 A
10 kA
HOMT2020230 b
80.00
(2) 20 A
40 A
10 kA
HOMT2020240 b
80.00
(2) 20 A
50 A
10 kA
HOMT2020250 b
80.00
Note: Typical catalog number (e.g. HOMT 1515230) represents two 1P, outer
poles (two 15 A 1P CBs) and one 2P inner circuit breaker with common
trip (one 30 A 2P CB).
Circuit Breaker Wire Sizese
Wire Size (AWG/kcmil)
Breaker Type
Ampere
Rating
Aluminum
HOM
1P
15–30 A
14–8 AWG
HOM
2P
$ Price
2P—120/240 Vac
Common Trip
1P—120 Vac
Amperes
© 2007 Schneider Electric
All Rights Reserved
Ampere
Rating
15 A
20 A
15 A
20 A
Ampere Rating d
Table 1.41:
2Ps
$ Price
18.40
18.40
HOM-GFI circuit breakers provide overload and short
circuit protection, combined with Class A ground fault
protection. Class A denotes a ground fault circuit
interrupter that will trip when a fault current to ground is 6
milliamperes or more.
Table 1.37:
HOM-GFI
15 A
20 A
30 A
40 A
50 A
HOM 2P GFI
(With Ground Fault
Circuit Interrupter)
2 Spaces Required
$ Price
40.30
40.30
40.30
40.30
40.30
40.30
40.30
40.30
40.30
82.00
112.00
112.00
112.00
246.00
246.00
285.00
285.00
285.00
Homeline Arc Fault Circuit Interrupters—Provide overload
and short circuit protection, plus arc fault protection in
accordance with UL 1699.
Table 1.36:
HOM-AFI
Ampere
Rating
HOM 1P GFI
(With Ground Fault
Circuit Interrupter)
1 Space Required
Cat. No.
HOM215b
HOM220b
HOM225b
HOM230b
HOM235b
HOM240b
HOM245b
HOM250b
HOM260b
HOM270b
HOM280b
HOM290b
HOM2100 b
HOM2110 b
HOM2125 b
HOM2150BB bc
HOM2175BB bc
HOM2200BB bc
High magnetic trip circuit breakers are recommended for
applications where high initial inrush current may occur.
Table 1.35:
HOM-HM
15 A
20 A
HOMT Quad Circuit
Breaker
2 Space Required
2P—120/240 Vac Common Trip
$ Price
17.50
17.50
17.50
17.50
—
17.50
—
17.50
—
—
—
—
—
—
—
—
—
—
HOMT Tandem Circuit Breakers
HOMT and Quad
Quad Only
HOM-GFI - 1P
HOM-GFI - 2P
Table 1.42:
LOAD CENTERS
HOM 1P
1 Space Required
Table 1.39:
1
The Square D Homeline circuit breakers are in a 1 in. wide
format for 1-pole circuit breakers. They are designed to
plug into Homeline load centers that are available from 4 to
42 circuits.
The Square D exclusive Qwik-Open® mechanism, with a
trip reaction within 1/60th of a second, is standard on all
15 A and 20 A circuit breakers.
40–50 A
8–2 AWG
15–30 A
14–8 AWG
35–70 A
80–125 A
150–200 A
15–30 A
40–50 A
15–20 A
15–50 A
8–2 AWG
4–2/0 AWG
4 AWG–300 kcmil
14–8 AWG
6–12 AWG
14–10 AWG
12–4 AWG
Copper
14–8 AWG or
(2) 14–10 AWG
8–2 AWG
14–8 AWG or
(2) 14–10 AWG
8–2 AWG
4–2/0 AWG
4 AWG–300 kcmil
14–8 AWG
6–14 AWG
14–10 AWG
14–6 AWG
Accessories
Description
Cat. No.
$ Price
Handle Attachments
Handle Tie: Converts any two adjacent 120/240 Vac
HOM1HTg
2.30
single HOM circuit breakers to independent trip 2P
Handle Tie: Converts any two adjacent 120/240 Vac
1P side-by-side HOMT circuit breakers to independent HOMTHTg
2.50
trip 2P
Handle Clamp: Clamp for holding HOM 1P handle in
QO1LOh
2.50
the ON or OFF position
Handle Blocking Device: Attaches to standard HOM 2P
circuit breakers for holding the handle in the OFF
HOM2HBDg
7.10
position
Handle Padlock Attachment: For padlocking 1P
HOM1PAg
2.60
Standard HOM breakers in the ON or OFF position.
15–70 A HOM2PALAg
6.60
Handle Padlock Attachment: For
padlocking 2P Standard HOM circuit
80–125 A HOM2PAHAg
6.60
breakers in ON or OFF position
150–200 A HOM2PAVHAg
33.60
Handle Padlock Attachment: For padlocking center
HOMQPA
6.60
poles of Homeline Quad breakers in the OFF position.
Handle Padlock Attachment: For
50–125 A QOM1PAfh
7.20
padlocking main
circuit breakers in convertible load center 100–225 A QOM2PAfh
7.20
in OFF position
Sub-Feed Lugs
125 A 2P plug-on—2 spaces required
HOML2125
31.70
225 A 2P plug-on—4 spaces required
HOML2225c
197.00
c
Requires four spaces (1 AWG–300 kcmil Al/Cu). Use only in 1Ø panel
rated 150 A or greater.
d
15–20 A tandem or quad tandem circuit breakers are suitable for use
with 60oC or 75oC conductors. 25–50 A tandem or quad tandem circuit
breakers are suitable for use with 75oC conductors only.
e
15–30 A circuit breakers are suitable for use with 60oC or 75oC
conductors. 40–125 A circuit breakers are suitable for use with 75oC
conductors.
f
50–125 A QOM1 frame size; 100–225 A QOM2 frame size.
g
DE3C Discount Schedule
h
DE2E Discount Schedule
1-13
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
Homeline®
Load Centers
Indoor, 1Ø, Main Lug, Main Circuit Breaker
Class 1170 / Refer to Catalog 1100CT0501
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
Table 1.43:
Mains
Rating
1Ø3W—120/240 Vac—UL Listed—10 kA Short Circuit Current Rating
Spaces
Max.
Single
Pole
Circuits a
Max.
Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover b
Main Wire Size
AWG/kcmil
$ Price
(DE3C)
Cat. No.
Al
Cu
Equipment Ground Bar Kit
(Order Separately)
Cat. No.
$ Price
(DE3A)
Box No.
See
Page 1-16
LOAD CENTERS
Main Lugs—Order HOM, HOMT, HOMGFI and HOMAFI Circuit Breakers from page 1-13
Factory-installed Fixed Main Lugs
70 A
2
4
2
HOM24L70F/Sdc
100 A
6
12
6
HOM612L100F/Sce
125 A
4
8
4
HOM48L125GC
Convertible Mains—Factory-installed Main Lugs
QOM1 Main Frame Size—Convertible to 22 k AIR Main Circuit Breaker (See page 1-15)
8
16
8
HOM816L125C
8
16
8
HOM816L125TC
12
12
0
HOM12L125C
12
24
12
HOM1224L125TC
125 A
16
24
8
HOM1624L125C
20
20
0
HOM20L125C
20
24
4
HOM2024L125TC
24
24
0
HOM24L125TC
Convertible Mains—Factory-installed Main Lugs
QOM2 Main Frame Size—Convertible to 22 k AIR Main Circuit Breaker (See page 1-15)
30
30
0
HOM30L150C
150 A
30
30
0
HOM30L150TC
16
32
16
HOM1632L200TC
200 A
16
32
16
HOM1632L200TCFTf
20
40
20
HOM2040L200TC
30
30
0
HOM30L200C
30
30
0
HOM30L200TC
200 A
30
40
10
HOM3040L200TC
40
40
0
HOM40L200C
40
40
0
HOM40L200TC
225 A
42
42
0
HOM42L225C
I
N
D
O
O
R
39.20
52.00
57.00
12–3
14–4
8–1
12–2/0
88.00
100.00
116.00
136.00
173.00
158.00
192.00
229.00
250.00
264.00
238.00
383.00
278.00
280.00
309.00
319.00
412.00
447.00
488.00
14–2/0
6–2/0
PK3GTA1
7.60
PK7GTA
7.80
PK7GTA Factory-included
PK15GTA
Factory-installed
PK15GTA
Factory-installed
PK15GTA
PK15GTA
Factory-installed
Factory-installed
11.40
—
11.40
—
11.40
11.40
—
—
6–250
6–250
PK23GTA
Factory-installed
—
6–250
Factory-installed
—
6–250
6–250
PK23GTA
Factory-installed
Factory-installed
PK23GTA
Factory-installed
PK23GTA
14.20
14.20
—
—
14.20
—
14.20
2
4
21
6
6
6
6
8
8
8
8
10
10
9
10
9
10
10
10
12
12
12
Main Circuit Breaker—22 kA Short Circuit Current Rating
Convertible Mains—Factory-installed Main Circuit Breaker
QOM1 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See page 1-15)
8
16
8
HOM816M100C
210.00
8
16
8
HOM816M100TC
222.00
12
12
0
HOM12M100C
196.00
100 A
12
24
12
HOM1224M100TC
256.00
20
20
0
HOM20M100C
264.00
24
24
0
HOM24M100C
342.00
30
30
0
HOM30M100C
448.00
12
24
12
HOM1224M125C
404.00
12
24
12
HOM1224M125TC
413.00
125 A
24
24
0
HOM24M125C
473.00
30
30
0
HOM30M125C
541.00
Convertible Mains—Factory-installed Main Circuit Breaker
QOM2 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See page 1-15)
16
32
16
HOM1632M150TC
424.00
20
30
10
HOM2030M150TC
500.00
150 A
30
30
0
HOM30M150C
517.00
12
24
12
HOM1224M200TC
381.00
16
32
16
HOM1632M200TC
450.00
20
40
20
HOM2040M200C
474.00
20
40
20
HOM2040M200TC
509.00
200 A
30
30
0
HOM30M200C
532.00
30
40
10
HOM3040M200TC
594.00
40
40
0
HOM40M200C
679.00
42
42
0
HOM42M200C
729.00
225 A
42
42
0
HOM42M225C
744.00
6–1
6–1
4–2/0
4–2/0
4–2/0
4–2/0
4–2/0
4–2/0
4–250
4–250
4–250
PK15GTA
Factory-installed
PK15GTA
Factory-installed
PK15GTA
PK15GTA
PK23GTA
PK15GTA
Factory-installed
PK15GTA
PK23GTA
Factory-installed
Factory-installed
PK23GTA
Factory-installed
Factory-installed
PK23GTA
Factory-installed
PK23GTA
Factory-installed
PK23GTA
PK23GTA
PK23GTA
11.40
—
11.40
—
11.40
11.40
14.20
11.40
—
11.40
14.20
—
—
14.20
—
—
14.20
—
14.20
—
14.20
14.20
14.20
5
5
6
6
8
8
10
6
6
8
10
9
9
10
9
9
9
9
10
10
12
12
12
Universal Mains—No Factory-installed Main Circuit Breaker or Main Lugs
QOM2 Main Frame Size—Field-install 22 k AIR Main Circuit Breaker or Main Lugs (See page 1-15)
16
32
16
HOM1632U200TC
195.00
200 A
20
40
20
HOM2040U200TC
238.00
4–250
30
40
10
HOM3040U200TC
353.00
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
a
Maximum single pole branch circuits utilizing HOM and/or HOMT circuit breakers.
b
C at end of catalog number indicates combination flush/surface cover included with device.
c
F/S at end of catalog number indicates to order F for flush device or S for surface device. The cover does not have a door.
d
HOM-GFI branch circuit breaker is limited to number 10 maximum wire.
e
70 A maximum branch circuit breaker, 100 A maximum back feed main circuit breaker.
f
Supplied with feed-thru lugs.
1-14
DE3A
DE3C
Discount
Schedule
Factory-installed
Factory-installed
Factory-installed
—
—
—
9
9
10
© 2007 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
www.us.schneider-electric.com
Homeline®
Load Centers
Rainproof, 1Ø, Main Lug, Main Circuit Breakers
Class 1170 / Refer to Catalog 1100CT0501
FOR CURRENT INFORMATION
Table 1.44:
1Ø3W 120/240 Vac UL Listed Load Centers
Mains
Rating
Spaces
Max. Single
Pole
Circuits a
Max. Tandem
Circuit
Breakers
Load Center
Box, Interior and Cover
Cat. No. (DE3C)
Main Wire Size
AWG/kcmil
$ Price
Al
Cu
Equipment Ground Bar Kit
(Order Separately)
Cat. No. (DE3A)
$ Price
Box No.
See
Page 1-17
Main Circuit Breaker (Order HOM, HOMT, HOMGFI and HOMAFI Circuit Breakers from Page 1-13), 22 kA Short Circuit Current Rating
Convertible Mains with Factory-Installed Main Circuit Breaker, QOM1 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See Below) d
16
8
HOM816M100RB
286.00
PK15GTA
11.40
8
12
12
0
HOM12M100RB
277.00
PK15GTA
11.40
100 A
4–2/0
20
20
0
HOM20M100RB
354.00
PK15GTA
11.40
24
24
0
HOM24M100RB
404.00
PK15GTA
11.40
125 A
24
24
0
HOM24M125RB
572.00
4–2/0
PK15GTA
11.40
1R
2R
15R
3R
3R
3R
4R
5R
6R
7R
14R
1
R
A
I
N
P
R
O
O
F
Factory-installed Fixed Main Lugs, 10 kA Short Circuit Current Rating
70 A
2
4
2
HOM24L70RBb
74.00
12–3
14–4
PK4GTA
7.20
100 A
6
12
6
HOM612L100RBf
86.00
8–1
PK7GTA
7.80
125 A
4
8
4
HOM48L125GRB
91.00
12–2/0
14–2/0
PK7GTA Factory-included
Convertible Mains with Factory-installed Main Lugs c, QOM1 Main Frame Size—Convertible to 22 k AIR Main Circuit Breaker (See Below)
8
16
8
HOM816L125RB
165.00
PK15GTA
11.40
12
12
0
HOM12L125RB
156.00
PK15GTA
11.40
125 A
6–2/0
12
24
12
HOM1224L125RB
185.00
PK15GTA
11.40
20
20
0
HOM20L125RB
255.00
PK15GTA
11.40
Convertible Mains with Factory-installed Main Lugs c, QOM2 Main Frame Size—Convertible to 22 k AIR Main Circuit Breaker (See Below)
12
12
0
HOM12L200RB
282.00
PK23GTA
14.20
20
40
20
HOM2040L200RB
373.00
PK23GTA
14.20
200 A
6–250
30
30
0
HOM30L200RB
391.00
PK23GTA
14.20
40
40
0
HOM40L200RB
607.00
PK23GTA
14.20
LOAD CENTERS
Main Lugs (Order HOM, HOMT, HOMGFI and HOMAFI Circuit Breakers from Page 1-13), 10 kA Short Circuit Current Rating
3R
3R
4R
6R
6R
Convertible Mains with Factory-installed Main Circuit Breaker, QOM2 Main Frame Size—Convertible to Main Lugs or Lower Amperage Main Circuit Breaker (See Below)
150 A
30
30
0
HOM30M150RB
685.00
4–250
PK23GTA
14.20
7R
20
40
20
HOM2040M200RB
581.00
PK23GTA
14.20
6R
30
30
0
HOM30M200RB
669.00
PK23GTA
14.20
7R
200 A
4–250
30
40
10
HOM3040M200RB
768.00
PK23GTA
14.20
7R
40
40
0
HOM40M200RB
851.00
PK23GTA
14.20
14R
16
24
8
HOM1624M225RB
788.00
PK15GTA
11.40
7R
225 A
4–250
42
42
0
HOM42M225RB
882.00
PK23GTA
14.20
14R
Convertible Mains with Factory-installed Main Circuit Breaker with Feed-thru Lugs c
150 A
8
16
8
HOM816M150FTRB
523.00
4–250
PK15GTAL
23.30
6R
200 A e
8
16
8
HOM816M200FTRB
523.00
4–250
PK15GTAL
23.30
6R
Universal Main with Feed-thru Lugs—No Factory-installed Main Circuit Breaker or Main Lugs c
QOM2 Main Frame Size—Field-install 22 k AIR Main Circuit Breaker or Main Lugs (See Kits Below)
200 A
8
16
8
HOM816U200FTRB
297.00
4–250
PK15GTAL
23.30
6R
Above listings through 200 A mains rating meet Federal Specification W-P-115c as Type 1, Class 2.
a
Maximum single pole branch circuits utilizing HOM and/or HOMT circuit breakers.
b
HOM-GFI branch circuit breaker is limited to number 10 maximum wire.
c
Side hinge door device allow 1-1/4 in. on left side for door to open.
d
22 k AIR main circuit breaker UL Listed for use ahead of HOM and HOMT 10 k AIR branch circuit breakers to permit their application on systems with up to 22 kA available fault current.
e
Rated 200 A when using copper wire. Reference NEC® Table 310.15(B)(6) when using Al wire.
f
70 A maximum branch circuit breaker, 100 A maximum back feed main circuit breaker.
R
A
I
N
P
R
O
O
F
Field-installable Kits
Table 1.45:
Main Lug Kit
QOL125
QOL225
© 2007 Schneider Electric
All Rights Reserved
Field-installable Mains, Convertible Load Centers Only
Main g
Use On Convertible Load
$ Price
Lug Wire Size j
Cat. No.
Ampere Rating
Center With Mains Rating
(DE3A)
AWG/kcmil
125 A
100–125 A
QOL125
29.40
6–2/0 Al or Cu
Main Lug h
—
225 A
150–225 A
QOL225
69.00
6–300 Al or Cu
50 A
100–125 A
QOM50VH
93.00
60 A
100–125 A
QOM60VH
93.00
70 A
100–125 A
QOM70VH
93.00
80 A
100–125 A
QOM80VH
134.00
QOM1
12–2/0 Al or Cu
90 A
100–125 A
QOM90VH
134.00
100 A
100–125 A
QOM100VH
134.00
110 A
125 A
QOM110VH
312.00
Main Circuit
Breaker i
125 A
125 A
QOM125VH
312.00
100 A
150–225 A
QOM2100VH
312.00
125 A
150–225 A
QOM2125VH
312.00
150 A
150–225 A
QOM2150VH
312.00
QOM2k
4–300 Al or Cu
175 A
200–225 A
QOM2175VH
312.00
200 A
200–225 A
QOM2200VH
312.00
225 A
225 A
QOM2225VH
312.00
g
Do not exceed the load center mains rating.
h
If main circuit breaker knockout has been removed from the load center’s trim, order appropriate filler plate from page 1-12.
i
22 k AIR main circuit breaker UL Listed for use ahead of HOM and HOMT 10 k AIR branch circuit breakers to permit their application on systems with
up to 22 kA available fault current.
j
Wire range listed for main device kits is the wire range of that device. To find out maximum wire size permitted in a particular load center per UL, see
pages 1-5 through 1-10 under Main Wire Size.
k
Add suffix 1021 for 120, 208, 240 Vac shunt trip. Add $126.00.
Field-installable
Main Type
Frame Size
DE3A
DE3C
Discount
Schedule
1-15
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
QO® and Homeline®
Load Centers
Indoor Load Centers–Dimensions, Knockouts
Class 1130, 1170 / Refer to Catalog 1100CT0501
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
A
Indoor Knockout Information and Enclosure Dimensions
A,B,C,D
A,B,C
A,B,C
A
A,B,C
A
Table 1.46:
Enclosure Dimensions
A,B,C
Dimensions
A
LOAD CENTERS
A
A,B
A
B,C,D,E
B,C,D,E
C,D,E,F,G
A A,B
B,C,D,E
C,D,E,F
B,C,D,E
A,B
A
A
B,C,D,E
B,C,D,E
A,B,C,D
B,C,D,E
Table 1.47:
C,D,E,F,G
C,D,E,F,G
mm
171
236
236
319
379
455
531
661
758
858
965
1000
in.
3.00
3.19
3.19
3.80
3.75
3.75
3.75
3.75
3.75
3.75
3.75
3.75
W
Box
No.
mm
76
81
81
97
95
95
95
95
95
95
95
95
in.
5.88
14.25
20.00
20.00
20.00
5.88
7.56
9.62
8.88
8.55
14.25
13
14
15
16
17
18
19
20
21
22
23
H
mm
149
362
508
508
508
149
192
244
226
217
362
in.
13.12
20.92
50.00
68.00
53.00
16.12
23.12
26.12
14.80
23.92
29.86
D
mm
333
531
1270
1727
1346
409
587
663
376
608
758
in.
3.38
3.75
5.75
5.75
5.75
3.38
4.25
4.75
3.80
3.95
3.75
mm
86
95
146
146
146
86
108
121
97
100
95
Knockout Information
Knockouts
A A,B
A
B
C
Conduit
Size
1/2
3/4
1
C,D,E,F,G
D
E
1-1/4 1-1/2
F
G
H
I
2
2-1/2
3
3-1/2
C,D,E,F,G
B,C,D,E
C,D,E,F
A A,B
D,E,F,G
C,D,E,F
B,C,D,E
C,D,E,F
A A,B
D
in.
6.72
9.30
9.30
12.57
14.92
17.92
20.92
26.04
29.86
33.78
37.98
39.37
Symbol
B,C,D,E
B,C,D,E
B,C,D,E
mm
97
122
122
226
362
362
362
362
362
362
362
362
Box 5
Box 4
Dimensions
H
in.
3.81
4.81
4.81
8.88
14.25
14.25
14.25
14.25
14.25
14.25
14.25
14.25
1
2
3
4
5
6
7
8
9
10
11
12
Box 3
Box 2
Box 1
B,C,D,E
A
A,B
W
Box
No.
B,C,D,E
C,D,E,F
A A,B
B,C,D,E
D,E,F,G
B,C
C,D,E,F,G
D,E,F,G
A A,B
B,C,D,E
D,E,F,G
B,C
A,B
B,C,D,E
C,D,E,F
A,B
A,B
A
A,B
A
A
A
A,B,C,D
A,B,C,D
Box 6
B,C,D,E
C,D,E,F
C,D,E,F,G
D,E,F,G
B,C,D,E
Box 7
C,D,E,F,G
D,E,F,G
Box 10
A A,B
C,D,E,F
D,E,F,G
A,B
B,C
B,C
A,B,C,D
C,D,E,F
D,E,F,G
Box 9
Box 8
B,C,D,E
B,C,D,E
A A,B
B,C,D,E
D,E,F,G
A,B,C,D
C,D,E,F
D,E,F,G
A,B,C,D
D,E,F,G,H
D,E,F,G,H,I
C,D,E,F
A,B,C
A
A,B
D,E,F,G
A,B
B,C,D,E
A,B
C,D,E,F
C,D,E,F
A,B,C,D
A
A,B
A
A
A,B,C,D
C,D,E,F
D,E,F,G
A,B,C,D
B,C,D,E
A,B,C,D
B,C,D,E
C,D,E,F
Box 14
Box 13
Box 12
Box 11
Box 15, 16, 17
A,B,C
A
C,D,E,F
D,E,F,G
B,C
C,D,E,F E,F,G,H
C,D,E,F
A,B,C,D
D,E,F,G
A,B
D,E,F,G
D,E,F,G
A,B
B,C,D,E
D,E,F,G
A
B,C,D,E
A,B
B,C,D,E
B,C,D,E
A
A
A,B
B,C,D,E
B,C,D,E
C,D,E,F
Box 18
1-16
Box 19
Box 20
Box 21
A,B,C,D
C,D,E,F
D,E,F,G
B,C,D,E
Box 22
Box 23
© 2007 Schneider Electric
All Rights Reserved
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com
QO® and Homeline®
Load Centers
www.us.schneider-electric.com
Rainproof—Dimensions, Knockouts, Bolt-on Hubs
Class 1130, 1170 / Refer to Catalog 1100CT0501
FOR CURRENT INFORMATION
2 1 2" Hub Maximum
2 1 2" Hub Maximum
Table 1.48:
Enclosure Dimensions
Dimensions
W
A
A,B
A,B,C,D
Box
Box 1NM
1NM
B,C,D,E A
B,C,D,E
Box 1R
B,C,D,E
A,B
Box 2R
2 1 2" Hub Maximum
2 1 2" Hub Maximum
C,D,E,F,G
C,D,E,F,G
C,D,E,F
A,B,C
A A,B C,D,E,F,G
C,D,E,F
Box 3R, 4R
C,D,E,F
2 1 2" Hub Maximum
A,B,C
A A,B C,D,E,F,G
C,D,E,F
a
Table 1.49:
Box 5R
mm
99
102
108
115
115
115
115
115
115
99
105
121
140
105
115
108
106
LOAD CENTERS
B,C
B,C
A,B
A,B
D
in.
3.90
4.00
4.27
4.52
4.52
4.52
4.52
4.52
4.52
3.88
4.12
4.75
5.50
4.12
4.52
4.27
4.16
1
H
in.
mm
in.
mm
1NM
6.52
166
8.79
223
1Ra
4.88
124
9.38
238
2R
8.88
226
12.65
321
3R
14.75
375
18.92
481
4R
14.75
375
22.06
560
5R
14.75
375
26.04
661
6R
14.75
375
29.86
758
7R
14.75
375
33.78
858
8R
14.75
375
37.98
965
9R
4.56
116
6.50
165
10R
6.92
176
13.18
335
11R
7.56
192
23.24
590
12R
9.62
244
26.24
666
13R
6.92
176
16.18
411
14R
14.75
375
39.37
1000
15R
8.88
226
14.80
376
16R
8.55
217
24.75
629
HOME250SPA and QO260NATR top endwall has no hub opening.
Box No.
Knockout Information
Knockouts
C,D,E,F,G
Symbol
A
B
C
Conduit Size
1/2 in.
3/4 in.
1 in.
D
E
1-1/4 in. 1-1/2 in.
F
G
H
2 in.
2-1/2 in.
3 in.
2 1 2" Hub Maximum
2 1 2" Hub Maximum
2 1 2" Hub Maximum
A,B,C
C,D,E,F
A,B,C
A A,B C,D,E,F,G
C,D,E,F
Box 9R
Box 6R, 7R, 8R
2 1 2" Hub Maximum
2 1 2" Hub Maximum
B,C,D,E
D,E,F,G
B,C,D,E
A,B
Box 15R
Box 12R
2 1 2" Hub Maximum
C,D,E,F,G
C,D,E,F
B,C,D,E
A
E,F
E,F,G,H
B,C,D,E
A,B,C,D
B,C,D,E
Box 10R, 13R
D,E,F,G
Box 11R
A,B
C,D,E,F
A,B,C
A A,B C,D,E,F,G
C,D,E,F
C,D,E,F
Box 16R
Box 14R
Bolt-On Hubs
Square D equipment with “R’’ or “RB’’ suffix, designated NEMA 3R rainproof construction,
utilizes bolt-on hubs listed below. “RB’’ devices will accept 3⁄ 4" through 2-1⁄ 2" bolt-on
hubs without the use of reducers. Off-center conduit thread openings and elongated
mounting holes provide quick and easy adjustment to eliminate costly conduit offsets and
bends. Catalog suffix “R’’ devices require 3" through 4" field cut opening. Hubs are
suitable for use with conduit having ANSI standard taper pipe thread.
Table 1.50:
3/4 in.
1 in.
1-1/4 in.
1-1/2 in.
2 in.
2-1/2 in.
Hub Cat. No.
B075
B100
B125
B150
B200
B250
b
$ Price
22.20
22.20
22.20
22.20
40.90
68.00
Closing cap (Cat. No. BCAP) is provided factory-installed on each device having “RB’’ suffix.
Price if ordered separately; $2.50
Table 1.51:
“RB’’ Hub
Bolt-On Hubs UL Listed for Mounting in Field-Cut Opening
Conduit Size
3 in.
3-1/2 in.
4 in.
Hub Cat. No.
B300
B350
B400
$ Price
© 2007 Schneider Electric
All Rights Reserved
Bolt-On Hubs UL Listed for “RB” Devicesb
Conduit Size
DE1A
124.00
Discount
Schedule
200.00
Designed for mounting in field cut opening.
Includes gasket and four mounting bolts and nuts.
245.00
1-17