Fire Alarm Systems | D9072 Four‑Output NAC Module D9072 Four‑Output NAC Module ▶ Connection points for four programmable NACs ▶ NAC supervision and detection of open circuit and ground fault conditions ▶ DIP switch programmable device address The D9072 Four‑output NAC Module provides connection points for four notification appliance circuits (NACs) while supervising and detecting open circuit and ground fault conditions. Trouble conditions on the NACs are shown on the control panel text display. Each of the four NACs can be programmed for On, Off, Double Knock, Delay or Steady/ Steady Delay Mode. The D9072 operates in the RS‑485 peripheral circuit that connects to a fire alarm control panel (FACP) through the D9051 RS‑485 Bus Module. Each NAC output on the D9072 provides up to 1 A of power; however, the total current allowed for all outputs must not exceed 3 A. Certifications and Approvals Region Certification USA UL UOXX: Control Unit Accessories, System (UL864, 9th edition) CSFM 7165-1615: 138 and 7170-1615: 146 NYC-MEA 26-02-E, Vol. III Installation/Configuration Notes Compatibility Information The following products are compatible with the D9072 Four‑output NAC Module: Functions Address Setting Each D9072 has a bank of DIP switches for setting the device address. Category Product ID Product Description Control Panels: D8024 Analog FACP D10024A Analog FACP Modules: D9051 RS‑485 bus module NAC Devices: Refer to the Analog Panels Compatible Devices Technogram (P/N: 73‑07674‑000) for a list of compatible notification appliances. Power Supplies: D9142F 24 V auxiliary power supply Mounting Considerations The D9072 can be conveniently mounted in an approved fire‑rated enclosure such as the D4103R or D8109. www.boschsecurity.com 2 | D9072 Four‑Output NAC Module Wiring Considerations Parts Included RS‑485 Circuit Connections Make a two‑wire connection from the input terminals on the terminal block labeled D9072 485 TERMINALS back to the FACP's RS‑485 peripheral circuit (connects to the FACP through a D9051 RS‑485 Bus Module). Make a two‑wire connection from the D9072 485 TERMINALS terminal block's output terminals to the next RS‑485 device in the circuit. The unused output terminals of the last device in the RS‑485 peripheral circuit are connected with an EOL resistor. Two 150 Ω, 0.25 W EOL resistors come with each D9051 RS‑485 Bus Module. Quant. Component 1 Four‑output NAC module 4 EOL resistors (2.2 kΩ, 1 W) 1 Hardware pack 1 Literature pack Note Relative Humidity Other RS‑485 compatible devices can be mixed on the RS‑485 bus. Only fifteen D9072 modules can be supported on a single system. Technical Specifications Environmental Considerations Notification Appliance Circuit (NAC) Connections Module Design Connect up to four NAC modules to the D9072 SOUNDERS terminal block. Each NAC is a Class B circuit terminated with a 2.2 kΩ EOL resistor (supplied). All NACs are supervised for open or short circuits. A fault in a NAC results in local annunciation by the D9072 LEDs. This trouble condition is also annunciated at the FACP. Dimensions (H x W): External Trouble Input Connections A pair of terminals for monitoring normally-closed contacts, typically trouble outputs on auxiliary power supplies, is at the right end of the SOUNDERS terminal block. An open circuit at these terminals results in LED annunciation at the module and a text display on the FACP’s LCD display. These terminals can be used to monitor any supervisory point, or to supervise an auxiliary power source such as a D9142F 24 VDC Auxiliary Power Supply. Note If these terminals are not connected, through closed contacts or a jumper, the control panel displays a fault message. Power Connections An auxiliary power supply (24 VDC to 28 VDC), such as the D9142F, is required to power the D9072. The terminal block for DC power to the module is located at the right of the 485 TERMINALS terminal block. A 3.15 A fuse protects the FACP against incoming power surges. Americas: Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us Europe, Middle East, Africa: Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com © Bosch Security Systems Inc. 2010 | Data subject to change without notice T1372088587 | Cur: en-US, V5, 4 Jul 2010 85% non‑condensing at +104°F (+40°C) Temperature (operat- +32°F to +120°F (0°C to +49°C) ing): 5.4 in. x 7.6 in. (14 cm x 19.2 cm) Outputs (NAC) Current (per circuit): 1 A per output maximum Current (total): 3 A maximum Number of Circuits: Four programmable supervised NACs EOL Resistors 2.2 kΩ, 1 W Power Requirements Current Idle: 120 mA Total: 220 mA (four circuits) + notification appliance load Voltage Range: 21 VDC to 32 VDC Ordering Information D9072 Four‑Output NAC Module Provides connection points for four NACs while supervising and detecting open circuit and ground fault conditions D9072 Accessories D8109 Fire Enclosure Red steel enclosure measuring 40.6 cm x 40.6 cm x 8.9 cm (16 in. x 16 in. x 3.5 in). UL Listed. Includes a lock and key set. D8109 D9013 Analog Modules Mounting Bracket Compatible enclosures: D8109 UL Approved Fire Enclosure (red), D8109G Fire Enclosure (gray), D8109L Louvered Enclosure (red) D9013 Asia-Pacific: Represented by Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.com