B50 CS, SWA - General Cable Australia

advertisement
INSTRUMENTATION
PROCON
B50 CS SWA
Overall Screened
APPLICATION
Suitable for the interconnection of:
Electrical measuring devices to instrument panel.
Instrument to instrument.
Electrical sensing devices to control cabinets.
Control cabinets to supervisory consoles and panels.
Telemeters to recorders and annunciators.
Suitable for glanding.
Armoured version offers additional mechanical protection.
COLOUR CODE
Wire 1 – White with number mark
Wire 2 – Black with number mark
STANDARD
AS/NZS 1125
AS/CA S008
IEC 60332-3 Cat.A, IEC 60332-1
IS Circuits to AS/NZS 60079.14
AS/NZS 3808
CONDUCTOR
Annealed Copper (20 AWG)
INSULATION
PVC V-90HT
SCREEN
Aluminium/Polyester tape with
7/0.25mm Tinned Copper Drain Wire
BEDDING
Flame Retardant PVC Black
ARMOUR
Galvanised Steel Wire
SHEATH
Flame Retardant PVC Black
(Intrinsically Safe blue PVC Sheath
available on request)
TECHNICAL SPECIFICATIONS
ITEM
NUMBER
24660016
24775016
24860016
29080016
29150016
29160016
29211016
29215016
29220016
29227016
29235016
TYPE
CONDUCTOR
NUMBER
OF PAIRS
B5002 CS SWA
B5004 CS SWA
B5006 CS SWA
B5008 CS SWA
B5010 CS SWA
B5012 CS SWA
B5016 CS SWA
B5020 CS SWA
B5024 CS SWA
B5036 CS SWA
B5050 CS SWA
2
4
6
8
10
12
16
20
24
36
50
mm
2
APPROX.
MASS
(kg/km)
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
(a) Based on a steel strength of 100 N/mm2.
Australia/Instrumentation/B5x/B50/B50 CS SWA │ VERSION:
(No./mm)
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
7/0.30
220
300
390
560
640
700
850
1130
1280
1540
1960
NOMINAL DIAMETER
OVER
BEDDING
OVER
ARMOUR
mm
mm
8.5
9.7
11.8
12.6
14.2
15.0
16.8
18.4
19.9
23.5
26.2
10.3
11.5
13.6
13.1
16.7
17.5
19.3
21.6
23.1
26.7
29.4
OVERALL
MINIMUM INSTALLED
BENDING RADIUS
MAXIMUM PULLING
TENSION (a)
mm
mm
kN
12.6
14.2
16.0
17.5
19.1
20.0
21.8
24.4
26.1
29.8
33.1
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
12 x OD
1.6
2.0
2.4
3.8
4.2
4.5
5.2
7.2
7.8
8.7
10.1
TECHNICAL SPECIFICATIONS
ELECTRICAL CHARACTERISTICS
PROPERTY
VALUE
UNITS
DC Conductor Resistance @ 20°C
Maximum Continuous Current Rating
Maximum Recommended Voltage
Capacitance of Pairs
B5001 CS – B5002 CS
B5004 CS onwards
Inductance @ 1kHz
L/R Ratio
38.4
3.2
110/150
Ω/km
Amps
VRMS/VDC
145
120
0.9
13
pF/m
pF/m
mH/km
µH/Ω
NOTE:
•
•
•
•
All cables are subject during manufacture to in-process spark testing at 4kV AC
All cables are tested between each conductor and screens earthed at 3kV DC
These cables are not to be regarded as power cables or for the direct connection of equipment to mains power supplies.
Values are nominal unless otherwise specified.
GENERAL CABLE AUSTRALIA PTY LTD
Level 1, 591-595 Blackburn Road
Notting Hill VIC 3168
Locked Bag 220, Clayton VIC 3168, Australia
Phone:
FAX:
EMAIL:
1300 363 282
1300 363 382
sales@generalcable.com.au
Australia/Instrumentation/B5x/B50/B50 CS SWA │ VERSION: B50 CS SWA v250615
Download