25-kV Apparatus Bushings - Elliott Industries, Inc.

advertisement
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
Page 1
2015
Grounded Metal
Equipment Plate
Equipment
Connection
Bus Bar or
Other Component
Grounded Metal
Equipment Plate
15 kV or 25 kV
Separable Insulated
Connector (elbow)
Equipment
Connection
Bus Bar or
Other Component
Power
Cable
Power
Cable
For 15-kV and 25-kV Connectors (Elbows)
Elliott “A” Series (clamp-in) apparatus bushings are used to
construct air-insulated equipment that connects to the utility’s
underground shielded cable system with IEEE Standard
separable insulated connectors (i.e. elbows). Integral shielding
prevents “edge-of-hole” corona discharge. The live side of the
bushing is provided with unique square-edge skirts to resist
flashover when contaminated and wet. The large diameter
live end terminal pad (with female threads) provides for direct
contact of current-carrying parts and eliminates exposed sharp
threads, which could induce destructive corona discharge. In
addition to IEEE Standard 386 design tests, Elliott bushings
are design tested for thermal cycle withstand from +200° to
-200° F to assure long field life. Every bushing is production
tested “in-air” mounted in a grounded steel plate with an
insulated protective plug (or cap) installed on the interface to
accurately simulate operating conditions.
ELRIM Cycloaliphatic Epoxy Provides:
Nontracking, self-scouring, nonweathering performance
Superior dielectric strength, dielectric loss and power factor
Choice of shapes allows design innovation
Mechanical and thermal toughness
Shatter-free arc flashover performance
Oil resistant
Elliott Design Provides:
Precision molded interfaces per IEEE Standard 386
Integral shielding to prevent destructive corona discharge
Square-edge skirts resist contamination - wet or dry
Generous dry arcing (strike) distance
Large diameter live end terminal pad with female threads
for direct contact of current-carrying parts
and improved corona performance
Thermal cycle withstand from +200° to -200° F for long life
High Strength - field proven performance since 1975
Ratings and Dimensions of Bushing Wells & Bushings
Voltage
Class
kV
Continuous
Current
Amps
1101-225A2
Bushing Well
25
1201-625A2
Bushing
1201-625A2F
Bushing
Catalog
Number
Withstand Test Voltage
Kilovolts
Minimum
Leakage
Inches
Minimum
Strike
Inches
Impulse
1.2 x 50
One Min.
Dry
10 Sec.
Dew
200
125
40
26
17
8.5
25
600
125
40
26
21
10
25
600
125
40
26
21
10
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
RTE®
Clamp Ring
#1991-CRAR Clamp Ring Adapter
and Bushing Well to replace
RTE® 8.3 kV Safebreak Bushing
(Page 7)
Page 2
Existing RTE®
Mounting Hole
200 Amp 15 kV or 25 kV
Elbow and Insert
2015
0.375"–16 Bolt
Bus Bar or
Other Component
#1900-CR4S
Clamp Ring
200 Amp Bushing Well
(Page 3)
Small "A" Series
Mounting Hole
#1900-CR4S
Clamp Ring
600 Amp Bushing
(Page 4)
Large "A" Series
Mounting Hole
0.625"–11 Bolt
Bus Bar or
Other Component
#1902-CR4-A2F
Clamp Ring
600 Amp Bushing Special Flange
(Page 5)
A2F Special
Mounting Hole
600 or 1250 Amp
15 kV or 25 kV Elbow
Elliott “A2” Bushings are advanced design clamp-in
bushings typically used to construct air-insulated
pad-mounted switchgear. Elliott “A2” bushings fit older-style
equipment constructed with clamp-in bushings and may
be used to upgrade or replace failed bushings on existing
equipment in the field. For new switchgear designs, we
suggest our higher performance “B” series bushings, which
offer superior electrical performance, higher mechanical
strength and numerous design advantages.
200 Amp Bushing Well - The #1101-225A2 bushing well is
a small-shank design that can be used to replace older Elliott
(and other manufacturer’s) clamp-in bushings using the
existing mounting hole and clamp ring. The #1101-225A2
bushing well can also be used to replace the discontinued
RTE® porcelain Safebreak Bushing when used with the
Elliott #1991-CRAR clamp ring adapter.
600 Amp Bushing - The #1201-625A2 bushing is a
large-shank design that uses the same mounting bolt
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
pattern and clamp ring as the small-shank bushing, but
requires a larger mounting hole. The #1201-625A2F is the
same bushing, with a special flange that allows the use of a
sealing gasket for in-oil application. It uses the same size
mounting hole as the #1201-625A2, but requires a different
mounting bolt pattern and clamp ring.
Index Slots - Elliott “A2” bushings feature a keying hole or
slots on the live end. Fuse clips and hinge kits are available
that bolt directly to the bushing conductor and key in the slots
to prevent rotation.
Conductor Connection - Female threads in the live end of
the conductor allow the attachment of live parts of almost any
thickness. The bolted connection of current-carrying parts
does not depend on current transfer through the fastener’s
thread-to-thread contact. Additional advantages of the bolted
connection are higher clamping pressure and elimination of
exposed sharp threads that could initiate corona.
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
Page 3
2015
200 Amp Bushing Well #1101-225A2
1.125”
8.625”
0.75” Dia. Copper Conductor
Threaded 0.375”–16 x 1” Deep
0.150”
3.75”
2.5”
0.75”
200 Amp
Bushing Well Interface
8.3 kV and 15.2 kV per
IEEE Standard 386
Conductive
Shielding
Voltage Class.................................................. 25 kV
Leakage Distance, Inches................................................ 17
Phase-to-Ground Voltage................................ 15.2 kV
Dry Arcing Distance, Inches............................................. 8.5
BIL................................................................... 125 kV
Mechanical - Strength Rating, Pounds
AC Withstand - 1 Min. Dry............................... 40 kV
Cantilever, Ultimate 2.5 inches past end.................. >250
10 Sec. Dew......................... 26 kV
Tensile, Pounds........................................................ >2,500
DC Withstand - 15 Min. Dry............................. 78 kV
Torsion, Inches-Pounds (bolt breaks)...................... >700
Corona Extinction Level - Minimum................ 19 kV
Compression, Pounds.............................................. 20,000
Continuous Current......................................... 200 Amps
Conductor (live end) Thread Size ................................... 0.375”–16 x 1”
Momentary - RMS, Sym., 0.17 sec................. 10,000 Amps
Net Weight, Pounds (kg) ................................................. 2.94 (1.34)
RMS, Sym., 3 sec...................... 3,500 Amps The #1101-225A2 bushing well is a small-shank design that can be used to replace older Elliott (and other manufacturer’s)
clamp-in bushing wells using the existing mounting hole and clamp ring. The #1101-225A2 bushing well can also be used to
replace the discontinued RTE® porcelain Safebreak Bushing when used with the #1991-CRAR clamp ring adapter (page 7).
Typical Specifications - 200 Amp 15-kV and 25-kV Bushing Wells
Bushings shall be Elliott #1101-225A2, 25 kV Class
(15.2 kV to ground) Air-Insulated Bushing Wells, 125 kV
BIL, per IEEE Standard 386 Fig. 3 (200 A Bushing Well
Interface 8.3 kV, 15.2 kV, and 21.1 kV) for use with
either 8.3/14.4 kV or 15.2/26.3 kV separable insulated
connectors (Elastimold®, Eaton's Cooper Power Systems
or other approved equal). The bushing wells shall be
pressure-molded cycloaliphatic epoxy with a 0.75-inch
diameter copper conductor on the “air-insulated” side that
is drilled and tapped 0.375-inch–16UNC x 1-inch deep to
provide direct connection of the bus and/or live parts. Integral
shielding shall be provided to eliminate partial discharge
caused by off-center mounting and mounting holes that may
have sharp edges or burrs. Bushing wells shall mount in
a 2.75-inch diameter opening and bolt or clamp in place
to allow field replacement with standard tools. To assure
adequate strength for apparatus support, the bushing well
shall withstand a minimum cantilever loading of 150 pounds
for five minutes without damage. The bushing well interface
shall be free of all voids, holes and heat sinks to assure proper
mating with separable insulated connectors. Each bushing
well shall be tested in free air, mounted in a grounded steel
plate not less than 10 inches x 10 inches and with a bushing
well plug (Eaton's Cooper Power Systems #IBWP225 or
equal) installed in the well interface to accurately simulate
operating conditions (gas or liquid dielectric in the interface
shall not be acceptable for this test). Each bushing shall
meet the requirements for 25 kV devices in accordance with
IEEE Standard 386 (latest revision), including 100 percent
production testing.
Mounting Hole for #1101-225A2
Clamp Ring #1900-CR4S
4.25” Dia.
Bolt
Circle
4.5”
2.75”
Dia.
1.5”
1.5”
1.5”
1.5”
1.5”
3.125”
Dia.
4.5”
1.5”
0.3125”–18 x 1.25” Studs with
Elliott #1900-CR4S Clamp Ring
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
0.1054”
0.375” Dia.
Holes
1509 Hamilton Road
Phone 318-746-3296
1.5”
1.5”
0.5” Radius
All Corners
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
600 Amp Bushing #1201-625A2
4.625”
10.125”
0.563”
Page 4
2015
1.25” Dia. Tin-Plated
Aluminum Conductor
Tapped 0.625”–11 x 1” Deep
(both ends of conductor)
0.150”
4.5”
3.25”
2.5”
1.25”
600 Amp
Deadbreak Interface No. 1
8.3 kV and 15.2 kV per
IEEE Standard 386
Conductive
Shielding
Voltage Class.................................................. 25 kV
Leakage Distance, Inches................................................ 21
Phase-to-Ground Voltage................................ 15.2 kV
Dry Arcing Distance, Inches............................................. 10
BIL................................................................... 125 kV
Mechanical - Strength Rating, Pounds
AC Withstand - 1 Min. Dry............................... 40 kV
Cantilever, Ultimate 2.5 inches past end.................. >350
DC Withstand- 15 Min. Dry.............................. 78 kV
Tensile, Pounds........................................................ >2,500
10 Sec. Dew......................... 26 kV
Torsion, Inches-Pounds (bolt breaks)...................... >3,500
Corona Extinction Level - Minimum................ 19 kV
Compression, Pounds.............................................. 20,000
Continuous Current......................................... 600 Amps
Conductor (live end) Thread Size.................................... 0.625”–11 x 1”
Momentary - RMS, Sym., 0.17 sec................. 25,000 Amps
Net Weight, Pounds (kg).................................................. 6.01 (2.73)
RMS, Sym., 3 sec...................... 10,000 Amps The #1201-625A2 bushing is a large-shank design that uses the same mounting bolt pattern and clamp ring as the small-shank
bushing, but requires a larger mounting hole. The #1201-625A2F bushing (page 5) is the same basic design, except it features
a special flange to allow the use of a sealing gasket for in-oil application.
Typical Specifications - 600 Amp 15-kV and 25-kV Bushings
Bushings shall be Elliott #1201-625A2, 25 kV Class
(15.2 kV to ground) Air-Insulated Bushings, 125 kV BIL,
per IEEE Standard 386 Fig. 11 (600 A Deadbreak Interface
No. 1, 8.3 kV and 15.2 kV) for use with either 8.3/14.4 kV or
15.2/26.3 kV separable insulated connectors (Elastimold®,
Eaton's Cooper Power Systems or other approved equal).
The bushings shall be pressure-molded cycloaliphatic
epoxy with a 1.25-inch diameter tin-plated aluminum
conductor on the “air-insulated” side that is drilled and
tapped 0.625-inch–11UNC x 1-inch deep to provide direct
connection of the bus and/or live parts. Integral shielding
shall be provided to eliminate partial discharge caused by
off-center mounting and mounting holes that may have sharp
edges or burrs. Bushings shall mount in a 3.5-inch diameter
opening and bolt or clamp in place to allow field replacement
with standard tools. To assure adequate strength for
apparatus support, the bushing shall withstand a minimum
cantilever loading of 200 pounds for five minutes without
damage. The bushing interface shall be free of all voids,
holes and heat sinks to assure proper mating with separable
insulated connectors. Each bushing shall be tested in free
air, mounted in a grounded steel plate not less than 10 inches
x 10 inches and with an insulated protective cap (Eaton's
Cooper Power Systems #DPC625 or equal) installed on the
interface to accurately simulate operating conditions (gas
or liquid dielectric on the interface shall not be acceptable
for this test). Each bushing shall meet the requirements for
25 kV devices in accordance with IEEE Standard 386 (latest
revision), including 100 percent production testing.
Mounting Hole For #1201-625A2
Clamp Ring #1900-CR4S
4.25” Dia.
Bolt
Circle
3.5”
Dia.
1.5”
1.5”
1.5”
1.5”
1.5”
3.125”
Dia.
0.1054”
4.5”
1.5”
0.3125”–18 x 1.25” Studs with
Elliott #1900-CR4S Clamp Ring
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
4.5”
0.375” Dia.
Holes
1509 Hamilton Road
Phone 318-746-3296
1.5”
1.5”
0.5” Radius
All Corners
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
600 Amp Bushing #1201-625A2F
4.625”
10.125”
0.563”
Page 5
2015
1.25” Dia. Tin-Plated
Aluminum Conductor
Tapped 0.625”–11 x 1” Deep
(both ends of conductor)
0.150”
4.5”
3.25”
2.5”
1.25”
600 Amp
Deadbreak Interface No. 1
8.3 kV and 15.2 kV per
IEEE Standard 386
Conductive
Shielding
Voltage Class.................................................. 25 kV
Leakage Distance, Inches................................................ 21
Phase-to-Ground Voltage................................ 15.2 kV
Dry Arcing Distance, Inches............................................. 10
BIL................................................................... 125 kV
Mechanical - Strength Rating, Pounds
AC Withstand - 1 Min. Dry............................... 40 kV
Cantilever, Ultimate 2.5 inches past end.................. >350
10 Sec. Dew......................... 26 kV
Tensile, Pounds........................................................ >2,500
DC Withstand - 15 Min. Dry............................. 78 kV
Torsion, Inches-Pounds (bolt breaks)...................... >3,500
Corona Extinction Level - Minimum................ 19 kV
Compression, Pounds.............................................. 20,000
Continuous Current......................................... 600 Amps
Conductor (live end) Thread Size.................................... 0.625”–11 x 1”
Momentary - RMS, Sym., 0.17 sec................. 25,000 Amps
Net Weight, Pounds (kg).................................................. 6.2 (2.82)
RMS, Sym., 3 sec...................... 10,000 Amps The #1201-625A2F bushing is a large-shank design that is similar to the #1201-625A2 (page 4), except it features a special
flange to allow the use of a sealing gasket for in-oil application. The #1201-625A2F bushing uses the same mounting hole as the
#1201-625A2, but requires a different mounting bolt pattern and clamp ring.
Typical Specifications - 600 Amp 15-kV and 25-kV Bushings
Bushings shall be Elliott #1201-625A2F, 25 kV Class
(15.2 kV to ground) Air-Insulated Bushings, 125 kV BIL,
per IEEE Standard 386 Fig. 11 (600 A Deadbreak Interface
No. 1, 8.3 kV and 15.2 kV) for use with either 8.3/14.4 kV or
15.2/26.3 kV separable insulated connectors (Elastimold®,
Eaton's Cooper Power Systems or other approved equal).
The bushings shall be pressure-molded cycloaliphatic
epoxy with a 1.25-inch diameter tin-plated aluminum
conductor on the “air-insulated” side that is drilled and
tapped 0.625-inch–11UNC x 1-inch deep to provide direct
connection of the bus and/or live parts. Integral shielding
shall be provided to eliminate partial discharge caused by
off-center mounting and mounting holes that may have sharp
edges or burrs. Bushings shall mount in a 3.5-inch diameter
opening and bolt or clamp in place to allow field replacement
with standard tools. To assure adequate strength for
apparatus support, the bushing shall withstand a minimum
cantilever loading of 200 pounds for five minutes without
damage. The bushing interface shall be free of all voids,
holes and heat sinks to assure proper mating with separable
insulated connectors. Each bushing shall be tested in free
air, mounted in a grounded steel plate not less than 10 inches
x 10 inches and with an insulated protective cap (Eaton's
Cooper Power Systems #DPC625 or equal) installed on the
interface to accurately simulate operating conditions (gas
or liquid dielectric on the interface shall not be acceptable
for this test). Each bushing shall meet the requirements for
25 kV devices in accordance with IEEE Standard 386 (latest
revision), including 100 percent production testing.
Mounting Hole For #1201-625A2F
Clamp Ring #1902-CR4-A2F
3.5”
Dia.
5.125” Dia.
Bolt
Circle
1.8125”
1.8125”
1.8125”
1.8125”
1.8125”
3.25”
Dia.
1.8125”
0.3125”–16 x 1.5” Studs with
Elliott #1902-CR4-A2F Clamp Ring
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
4.5”
0.375” Dia.
Holes
1509 Hamilton Road
Phone 318-746-3296
1.8125” 1.8125”
0.25”
4.5”
0.5” Radius
All Corners
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
25-kV Apparatus Bushings
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
Bushing Well
Plug or Cap
Production Tests
Every bushing is production tested in free air,
mounted in an 11-gauge grounded steel plate
not less than 10 inches x 10 inches, with an
insulating protective plug (or cap) installed on
the interface to accurately simulate operating
conditions.
Each bushing must meet or
exceed the requirements for 15.2/26.3 kV
devices in accordance with the test values of
IEEE Standard 386 (latest revision) for partial
discharge (corona) and AC voltage withstand
when tested in this manner.
Descriptive
Bulletin
1125-200
Page 6
2015
Test Configuration
High Voltage
Electrode
Grounded Steel
Test Plate
Installation Instructions
Elliott “A” Series Apparatus Bushings clamp in place utilizing
the mounting hole and hardware shown below. All mounting
hardware is located on the elbow side of the equipment
mounting plate to eliminate the possibility of reduced
phase-to-ground clearance.
Every Elliott Bushing is tested at the factory, mounted
in a grounded steel plate. A greased bushing well plug
(or insulating protective cap) is installed on the interface
to accurately simulate operating conditions. To prevent
contamination of the silicone grease, it is important to keep
the shipping cap in place until you are ready to install the
bushing insert (or elbow). Should the grease become
contaminated, thoroughly clean the interface and reapply
silicone grease before installing the bushing insert (or elbow).
NOTE: The shipping cap on the bushing well (or bushing)
should be left in place to prevent contamination of
the interface.
4.25” Dia.
Bolt
Circle
4.25” Dia.
Bolt
Circle
2.75”
Dia.
3.5”
Dia.
1. The bushing installs from the elbow side.
2. A clamp ring is placed on the bushing.
3. Lock washers and lock nuts are installed on the studs
(or bolts). The nuts should be tightened in a uniform
manner (rather than one-by-one in a random sequence).
Do not apply more than 90 inch-pounds torque to each
nut. The studs should be left unpainted to provide a
connection from the shielding to the grounded mounting
plate. If the bushing is mounted on an ungrounded
or insulated plate (such as fiberglass), a ground strap
should be attached to one of the mounting studs.
IMPORTANT:
Do not energize this bushing with only the shipping
cap in place. To do so would lead to failure of the
bushing and create a hazard to operating personnel.
This product is designed to be used only when it is
mated with an appropriate 15 kV or 25 kV Class bushing
insert (and/or elbow) conforming to the latest revision of
IEEE Standard 386. The bushing insert (and/or elbow)
should be installed in accordance with the instructions
supplied by the connector manufacturer.
5.125” Dia.
Bolt
Circle
0.3125"–18 x 1.25"
Weld Studs
1.5”
1.5”
1.8125”
1.5”
1.5”
1.8125”
1.5” 1.5”
1.5” 1.5”
Mounting Hole
For #1101-225A2
Mounting Hole
For #1201-625A2
Mounting Hole
For #1201-625A2F
0.3125”–18 x 1.25” Studs with
Elliott #1900-CR4S Clamp Ring
0.3125”–16 x 1.5” Studs with
Elliott #1902-CR4-A2F Clamp Ring
0.3125”–18 x 1.25” Studs with
Elliott #1900-CR4S Clamp Ring
1.8125”
1.8125”
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
Equipment Plate
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Descriptive
Bulletin
25-kV Apparatus Bushings
1125-200
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
Page 7
2015
Replace existing RTE® 8.3-kV Safebreak Bushing with an
Elliott Bushing Well and #1991-CRAR Clamp Ring Adapter
#2700250A01
RTE® Clamp Ring
#2600779C03
RTE® Safebreak Bushing
2.625" Dia.
0.375"–16 x 1"
Stud
0.125"
Equipment Plate
7”
The #1991-CRAR Clamp Ring Adapter permits a
#1101-225A2 Elliott Bushing Well to be mounted, with
an RTE® Clamp Ring, in equipment originally equipped
with the discontinued RTE® 8.3 kV porcelain Safebreak
Bushing. The clamp ring is located on the elbow
side of the equipment mounting plate to eliminate the
possibility of reduced phase-to-ground clearance. The
#1991-CRAR Clamp Ring Adapter comes complete
with the bolts, nuts and washers shown below.
1.5”
8.5”
#1991-CRAR
Elliott Clamp Ring
Adapter
IMPORTANT:
Do not energize this bushing with only the shipping
cap in place. To do so would lead to failure of the
bushing and create a hazard to operating personnel.
This product is designed to be used only when it
0.75" Dia.
is mated with an appropriate 15 kV or 25 kV Class
Copper Conductor
bushing insert conforming to the latest revision of IEEE
Tapped 0.375"–16 x 1" Deep
Standard 386. The bushing insert should be installed
#1101-225A2
in accordance with the instructions supplied by the
Elliott Bushing Well
connector manufacturer.
2.625" Dia.
0.375"–16 x 1.75"
S.S. Hex Bolt, Flat Washer,
Lock Washer and Hex Nut
#2700250A01
RTE® Clamp Ring
(from existing equipment)
Replacement Instructions
NOTE: The shipping cap on the bushing
well should be left in place to prevent
contamination of the interface.
1. The existing RTE® bushing is removed,
keeping the RTE® clamp ring for re-use.
2. The bushing well installs from the elbow
side for easy installation.
3. The clamp ring adapter and RTE® clamp
ring are placed on the bushing.
4. Flat washers, lock washers and nuts are
installed on the bolts. The nuts should
be tightened in a uniform manner rather
than one-by-one in a random sequence.
Do not apply more than 90 inch-pounds
torque to each nut.
0.375" S.S.
Lockwasher
#2700250A01
RTE® Clamp Ring
(from existing
equipment)
0.375"–16
S.S. Hex Nut
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
0.4375" Dia. Holes
(in equipment plate)
1509 Hamilton Road
Phone 318-746-3296
#1991-CRAR
Adapter
0.375"–16 x 1.75"
S.S. Bolt
#1101-225A2
Elliott Bushing
Well
0.375" S.S.
Flat Washer
Equipment
Plate
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
25-kV Apparatus Bushings
“A” Series (clamp-in) for Elbow to Air-Insulated Service
200 Amp and 600 Amp
Descriptive
Bulletin
1125-200
Page 8
2015
If you do not find the design
you need
PLEASE CONTACT
our REPRESENTATIVE or the FACTORY
Elastimold® is a registered trademark of ABB Asea Brown Boveri Ltd.
Elliott Molding and Components
A Division of Elliott Industries, Inc.
© Copyright 2015
1509 Hamilton Road
Phone 318-746-3296
RTE® is a registered trademark of Eaton in the U.S. and other countries.
Bossier City, LoUiSiAna 71111
Fax 318-741-1127
sales@elliott-industries.com
www.elliott-industries.com
Download