Operating Instructions GB Pressure gauges Model 232.XX.063 per

advertisement
Pressure gauges Model 232.XX.063
per directive 94/9/EC (ATEX)
with alarm contacts Model 831
II 2 GD c
Contents
1.
2.
3.
4.
5.
6.
7.
8.
Safety instructions
Description
Technical data and intended use
Alarm contacts
Commissioning
Maintenance and servicing / cleaning
Repairs
Disposal
Enclosure 1: Declaration of conformity
for Models 232.XX.63 with
alarm contacts Model 831
11133104.02 05/2014 D/GB
Operating
Instructions GB
Enclosure 2: EC-type examination certificate
(Ex approval for gases and dust) for slottype proximity sensors Si2-K08-Y1X
(WIKA-Model 831)
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg/Germany
Tel.
+49 9372 132-0
Fax +49 9372 132-406
info@wika.de
www.wika.de
1. Safety instructions
!
Caution
The appropriate national safety regulations (e.g. VDE 0100 / EN 60 079-14 /
EN 837-2) must be observed when installing, putting into operation and
running these instruments.
T Do not work on gauge while under voltage
T Serious injuries and/or damage can occur should the appropriate regulations not be
observed
T Only appropriately qualified persons should work on these instruments
2. Description
T Nominal size 63 mm
T The pressure gauges measure the pressure by means of resilient bourdon tube measuring
elements
T The measuring features are in accordance with the standards EN 837-1
T In addition the case and bezel ring as well as the pressurised components of models
232.3X also meet the requirements of this standard on safety pattern pressure gauges
with solid baffle wall (code S3).
The built-in electrical alarm contacts are non-contact slot-type inductive proximity sensors,
which are supplied from control units with circuits that are certified to be intrinsically safe.
When the adjustable set points are reached, their output circuits will be opened or closed.
The connection values of the switches are in accordance with EN 60 947-5-6 ("NAMUR").
3. Technical data and intended use
Working pressure
Steady:
Fluctuating:
Short time:
full scale value
0.9 × full scale value
1.1 × full scale value
Pressure connection
T According to the general technical regulations for pressure gauges, respectively
(e.g. EN 837-2 "Selection and installation recommendations for pressure gauges").
When screw-fitting the gauges the force required for sealing must not be applied through the
case but, using a suitable tool, only through the spanner flats provided for this purpose at the
square of the connector.
Installation with
open-ended spanner
Temperature effect
When temperature of the pressure element deviates from reference temperature (+20 °C):
max. ±0.4 %/10 K of true scale value
IP Ingress protection
Enveloping case IP 54 resp. IP 65 as special feature (EN 60 529 / IEC 60 529)
Materials
Wetted parts:
Movement:
Dial and pointer:
Case, bezel ring:
Window:
Stainless steel
Stainless steel
Aluminium
Stainless steel
Polycarbonate
Installation
T Nominal position per EN 837-1 / 9.6.7 Figure 9: 90° (
)
T Pressure connection: lower mount (LM) or back mount (BM)
T In order to ensure that with models 232.3X pressure can be safely and reliably vented
through the case back, a distance of at least 25 mm has to remain free behind the case!
T In order to avoid any additional heating, the instruments must not be exposed to direct
solar irradiation while in operation!
Permissible vibratory stress at the mounting location
T As a matter of principle the instruments should only be mounted at locations without
vibratory stresses
T Where required, a decoupling from the mounting location can be achieved e.g. by a
flexible connecting line from the measuring point to the pressure gauge and mounting via
a measuring instrument bracket.
T If this is not possible, the following limits must not be exceeded:
Frequency range < 150 Hz
Acceleration < 0.5 g (5 m/s2)
Operating Temperature
Ambient: -25 ... +60 °C
Attention: Footnote 1) under table 1 must be absolutely taken into account!
Medium: see table 1
Attention! With gaseous substances the temperature may increase as a result of the
compression temperature. In such cases the pressure change rate has to be slowed down
resp. the permissible medium temperature has to be reduced.
Table 1: Permissible medium temperature (only mechanical part)
Ignition temperature of
the ambient atmosphere
(temperature class)
Permissible maximum medium
temperature (in the pressure system)
T6
T5
T4
T3
T2
T3
+70 °C
+85 °C
+120 °C
+185 °C
+200 °C
+200 °C
( > 85 °C)
( > 100 °C)
( > 135 °C)
( > 200 °C)
( > 300 °C)
( > 450 °C)
1) The permissible upper ambient temperature for the electrical components is determined by the
electrical connection values and the ignition temperature of the ambient gases, vapours and dusts.
Therefore the maximum permissible ambient temperatures specified in the EC-type examination
certificates for slot-type sensors and SN sensors must be observed as well. The lower of these two
values is to be considered the maximum permissible ambient temperature!
4. Alarm contacts
EC-type examination certificates
The proximity sensors are in accordance with EC-type examination certificate
KEMA 01 ATEX 1264 X.
The built-in sensor type is stated on the product label of the pressure gauge.
Contact function index
The contact function of the switch is identified by the indices 1 or 2.
831.1 = NO - normally open, contact makes (clockwise pointer motion)
831.2 = NC - normally closed, contact breaks (clockwise pointer motion)
Wiring details
T The electrical connections should be made by qualified electricians
T Cable outlet 2 m length, conductor cross section 0.14 mm2, flying leads
T The terminal assignment is stated on the connection plate at the pressure gauge
!
Caution
T The instruments are to be included in the equipotential bonding of the
plant!
The permissible limits of the intrinsically safe supply circuits:
Ui = 15 V
Ii = 60 mA
Pi = 100 mW for temperature class T6 resp. 150 mW for temperature class T4
Suitable switch amplifiers are e.g.:
Model designation of the manufacturer
Fa. Pepperl & Fuchs
EC-type examination
certificate
WIKAModel
KFD2-SR2-Ex1
KFD2-SR2 Ex2
KHA6-SR2-Ex1
KHA6-SR2-Ex2
PTB 00 ATEX 2080
PTB 00 ATEX 2080
PTB 99 ATEX 2141
PTB 99 ATEX 2141
904.31
904.32
904.28
904.29
Electromagnetic compatibility
EMC according to EN 60 947-5-2.
The instruments are to be protected against strong electromagnetic fields.
To adjust red set pointers
The red set pointers for the alarm contacts are adjustable over the adjustment lock in the
window with the aid of the adjustment key (included in delivery).
Red set
pointers
Adjustment lock
The red set pointers for the alarm contacts are adjustable over the full range of the
instrument. Switching points shall be set in the ranges between 10 % und 90 % of the
scale to ensure switching accuracy and long life of the mechanical measuring system.
5. Commissioning
During the commissioning process pressure peaks must be absolutely avoided. Open the
shut-off valves slowly.
6. Maintenance and servicing / cleaning
The instruments require no maintenance or servicing.
The indicator and switching function should be checked once or twice every 12 months. The
instrument must be disconnected from the process to check with a pressure testing device.
The instruments should be cleaned with a damp cloth moistened with soap solution.
Remainder of the pressure medium in dismounted pressure gauges may be hazardous or
toxic. This should be considered when handling and storing the removed pressure gauges.
7. Repairs
Repairs are to be only carried out by the manufacturer or appropriately trained personnel.
For further details see WIKA data sheet PM 02.02, PM 02.04 or PM 02.11.
8. Disposal
Dispose of instrument components and packaging materials in accordance with the
respective waste treatment and disposal regulations of the region or country to which the
instrument is supplied.
Enclosure 2
The gauges are marked with
Die Geräte werden gekennzeichnet mit
Armin Hawlik
Leiter Logistikzentrum 2
Manager Production and Logistics
Klingenberg, 08.07.2005
Werner Hünerth
Leiter Qualitätssicherung
Quality Assurance Manager
WIKA
Alexander Wiegand GmbH & Co. KG
Geschäftsbereich Prozessinstrumentierung / Division Process Instrumentation
II 1 G EEx ia IIC T4 ... T6
II 1 D T95°C
The built-in alarm contacts 831 are EC-type-certified.
Numbers of certificates and marking
Die eingebauten Grenzsignalgeber 831 sind EGbaumustergeprüft. Die Nummern der Prüfbescheinigungen und die Kennzeichnung
KEMA 01 ATEX 1264 X
Applied standards:
EN 13463-1 General requirements
EN 13463-5 Constructional safety 'c'
Angewandte Normen:
EN 13463-1 Allgemeine Bestimmungen
EN 13463-5 Konstruktive Sicherheit 'c'
II 2 GD c
The dossier is retained
under file nr. 8000550026
at the notified body No. 0032
TÜV NORD CERT
Am TÜV 1
D-30519 Hannover
Datenblätter / data sheets
PM 02.04
PM 02.11
PM 02.02
Die Unterlagen werden aufbewahrt
unter der Aktennummer 8000550026
bei der benannten Stelle Nr. 0032
TÜV NORD CERT
Am TÜV 1
D-30519 Hannover
WIKA-Typen / WIKA models
232.30.063
232.35.063
232.50.063
Directive 94 / 9 / EC (ATEX)
Declaration of Conformity
We declare under our sole responsibility that the
products mentioned below, i.e. bourdon tube pressure
gauges, according to the current data sheets
correspond with the directive and were subjected to
the conformity assessment procedure
'Internal Control of Production'.
Konformitätserklärung
Richtlinie 94 / 9 / EG (ATEX)
Wir erklären in alleiniger Verantwortung, dass
nachstehend genannte Produkte, Druckmessgeräte
mit Rohrfeder, gemäß gültigen Datenblättern mit der
Richtlinie übereinstimmen und dem Konformitätsbewertungsverfahren
'Interne Fertigungskontrolle'
unterzogen wurden.
Enclosure 1