Motivation
Steady State G enerator O verexcited C apability (GOEC)
Generator Distance Phase Backup Protection (Relay 21)
Coordination between Relay 21 and GOEC
Overexcitation thermal capability and Overexcitation limiter (OEL)
System Under Study and Simulation Results
Conclusions
2
“Performance of generation protection during major system disturbances”
Due to generator protection misoperations during recent blackouts :
1996 outages in the Western U.S.
2003 U.S. East Coast blackout
2007 Saskatchewan mid west disturbance
As a result the need for better coordination of generator protection with generator capability and control has come to light.
Therefore, NERC has mandated several tests and is asking users to verify the coordination between generator protection and control.
3
Armature current limit (2)
Field current limit
(1)
Stator end core
limit (3)
4
Q
A MVAR into System
Field Limit
GOEC B
Stator Limit
MW into System
Gas
E
GUEC
D
C
Stator End
Core Limit
P
Steam
F MVAR into generator
GOEC: G enerator o verexcited c apabilit y
GUEC: G enerator u nderexcited c apabi lity
Hydro
5
Generator distance phase backup protection (Relay 21)
A- Condition of operation:
- Within generator capability limits.
- It detects system phase faults external to generator zone.
C.B
Transmission system
Impedance
plane
Main C.B
Trip zone
Block zone
21
Generator Zone
Relay connection Relay Characteristic
B- Mode of operation:
-Always monitoring.
Delay time from the fault occurrence to trip the unit out of service.
6
Generator distance phase backup protection (Relay 21) (cont.)
C- Setting criteria:
•
120% of the longest line with in-feeds.
•
50 to 67% of the generator load impedance (Z load
) at the rated power factor angle (RPFA) of the generator.
•
80 to 90% of the generator load impedance at the maximum torque angle (MTA) of the relay setting (typically 85) (Z
GCC
).
•
A proper time delay for the relay should be set with appropriate margin for proper coordination with transmission lines backup protection.
7
MVA
GOEC
Transformation of P-Q to R-X plot
8
In response to system voltage drops caused by high reactive power requirements, switching manipulations or faults, the generator field winding is allowed for short time overexcitation levels .
IEEE/ANSI C50.13
9
OEL operation
during a system disturbance.
10
G
21
Hydro
Generator
A
230 kV, 300 km
B
Infinite
Bus
Different cases are considered:
(fault location, fault type, and generator loading)
11
Coordination between Relay 21 and GOEC for the generator under study
•
•
•
PPFA : R ated P ower F actor A ngle (19.95
0 )
•
MTA : M aximum T orque A ngle (85 0
)
•
Z
21
Z
: Relay 21 characteristic
GCC
Time delay of 2 second
(23.25 Ω at 85 is considered
0 )
: Maximum permissible limit (25.955 Ω at 85 0 )
12
Disturbance 1, OEL response
Generator terminal voltage and field current transient time responses as well as Relay (21) trip signal during and after
Disturbance 1.
13
Disturbance 1, Relay 21
Impedance measured by Relay 21 during and after Disturbance 1
14
Disturbance 2, OEL response
Field current transient time response as well as Relay (21) trip signal during and after Disturbance 2.
15
Disturbance 2, Relay 21
Impedance measured by
Relay 21 during and after Disturbance 2
16
Impedance measured by Relay 21 with reduced setting during and after
Disturbances 1, 2
17
• The current setting of Relay (21) for generator thermal backup protection restricts the overexcitation thermal capability of the generator
• Such a restriction does not allow the generator to supply its maximum reactive power during system disturbances.
• The paper highlights the need for revising the setting of the Relay
(21) through in-depth dynamic stability studies in order to allow the generator to fulfill the system requirements during major disturbances to ensure adequate level of voltage stability
In this regard, the paper proposes the reduction of Relay (21) reach
18