Learning Module 7: 101 Basic Series Low Voltage Power Circuit Breakers Low Voltage Power Circuit Breakers What You Will Learn We will step through each of these topics in detail: Introduction 6 What is a Low Voltage Power Circuit Breaker? Method Used to Make or Break Circuits Ratings Construction/Maintainability Trip Units Operating Mechanisms 8 8 8 9 9 9 Principles of Operation and Terminology Stored Energy Bus Control Voltage Drawout Behind Door Drawout Through Door Drawout Continuous Current Rating 100% Rated Interrupting Rating Short Time Rating Trip Free Current Sensor 10 11 11 11 11 13 14 14 14 14 14 15 15 Review 1 16 Design and Functional Considerations Frame or Chassis Primary Contacts Arc Extinguishers Operating Mechanism Integral Trip Unit Accessory Items 17 17 18 21 22 23 25 Review 2 28 Mounting Methods Fixed Circuit Breaker Drawout Circuit Breaker 29 29 29 Governing Standards ANSI UL IEC Closing Comments on Standards 30 31 31 31 31 Testing 32 Helping the Customer Standard Selection Factors ANSI Example IEC Example ANSI and IEC Example 33 33 34 36 36 Page 2 Low Voltage Power Circuit Breakers Special Selection Factors 37 Review 3 38 Advanced Low Voltage Power Circuit Breakers 39 Standards and Testing IEEE (Institute of Electrical and Electronic Engineers) NEMA (National Electrical Manufacturers Association) UL (Underwriters Laboratories Inc.) CSA (Canadian Standards Association) ANSI (American National Standards Institute) IEC (International Electrotechnical Commission) Standards Conclusion Low Voltage Power Circuit Breaker C37.50 Testing 40 41 41 42 42 42 44 44 45 Review 4 48 Construction Method 49 Ratings and Performance 50 Review 5 55 Operational Techniques Primary Opening and Closing Contacts Moving Contact Assembly Stationary Contact Assembly Operating Arm (Link) Magnum DS Primary Contact System Operating Mechanism Magnum DS Operating Mechanism Arc Chamber (Chutes) Magnum DS Arc Extinguishing Integral Trip Unit Programmable Protection and Coordination Circuit Breaker Coordination Circuit Breaker Coordination Example 56 56 57 57 58 58 62 63 64 65 66 67 67 68 Review 6 70 Protective Systems Long Delay Protection (L) Short Delay Protection (S) Instantaneous Protection (I) Ground Fault Protection (G) Overcurrent Protection Combinations Characteristic Curve Review Advance Warnings and Alarms System Diagnostics and Testing System Monitoring Power Quality Monitoring Energy Monitoring and Management Communications 72 73 73 74 74 74 75 75 75 76 76 76 76 Page 3 Low Voltage Power Circuit Breakers Applications Zone Selective Interlocking 76 77 Review 7 80 Meaning of Nameplate Ratings 81 Low Voltage Power Circuit Breaker Summary Standards and Testing Summary General Features Summary Magnum DS Summary 82 82 83 83 Review 8 85 Glossary 86 Review 1 Answers 88 Review 2 Answers 88 Review 3 Answers 88 Review 4 Answers 89 Review 5 Answers 89 Review 6 Answers 89 Review 7 Answers 89 Review 8 Answers 89 Page 4 Low Voltage Power Circuit Breakers Welcome Welcome to Module 7, which is about low voltage power circuit breakers. Figure 1. Molded Case Version of Low Voltage Power Circuit Breakers You will find the “Advanced Low Voltage Power Circuit Breakers” on page 39 to be an advanced discussion of the low voltage power circuit breaker. It is intended to be a continuation of the discussion of low voltage power circuit breakers and Module 5, “Fundamentals of Circuit Breakers.” It also addresses many of the same topics in a more detailed fashion. Because Eaton’s Cutler-Hammer Magnum DS Low Voltage Power Circuit Breaker is the latest and most advanced product in the industry, it will be the low voltage power circuit breaker used for most examples. Like the other modules in this series, this one presents small, manageable sections of new material followed by a series of questions about that material. Study the material carefully then answer the questions without referring back to what you’ve just read. You are the best judge of how well you grasp the material. Review the material as often as you think necessary. The most important thing is establishing a solid foundation to build on as you move from topic to topic and module to module. A Note on Font Styles Key points are in bold. Glossary items are italicized and underlined the first time they appear. Viewing the Glossary Printed versions have the glossary at the end of the module. You may also browse the Glossary by clicking on the Glossary bookmark in the left-hand margin. Page 5 Low Voltage Power Circuit Breakers Introduction There are both low voltage DC power circuit breakers and low voltage AC power circuit breakers. The interruption of direct current is distinctly different from the interruption of alternating current, and generally more difficult at comparable voltages and currents. Large quantities of low voltage AC power circuit breakers are used throughout industry in comparison to very small numbers of DC devices. For this reason and the fact that this is an introduction to low voltage power circuit breakers, only AC designs will be covered. Keep in mind, however, low voltage DC power circuit breakers do exist and are used in a number of specialty applications, such as rapid transit. Circuit Breakers are often classified by certain modifying words, such as low voltage power. Low voltage AC power is considered to be for applications at 1000 volts AC and below. For comparison reasons then, medium voltage AC power is considered to be for application above 1000 volts AC. In general, however, low voltage power circuit breakers are viewed as 600 volt circuit breakers applied at a number of different voltage levels, such as 240 or 480 volts. Sound confusing? Let’s try to clear it up a bit by taking a brief look at why a low voltage power circuit breaker might be used along with some background information. Why use a low voltage power circuit breaker over another type of low voltage circuit breaker? Most often the determination is made by the specific application. Let’s consider a number of the more prominent reasons why a low voltage power circuit breaker is ideally suited for certain applications. Keep these reasons in mind as you proceed through this module. You will learn about the features and requirements that support and further explain the following reasons for applying low voltage power circuit breakers: • Continuity of Service - Continuity of service allows for the maximum up time and minimum down time of equipment. A low voltage power circuit breaker has a significant Short Time Rating (also: “withstand rating”). This means that the low voltage power circuit breaker has the strength to withstand the stresses of a fault for up to 1/2 second or 30 cycles, instead of opening immediately. This ability to delay opening allows for a circuit breaker nearest the fault to clear the fault. This helps to prevent facility outages or a wide shutdown of facility equipment. • Maintainability - A low voltage power circuit breaker is designed to be maintained in the field. This extends the useful service life of the circuit breaker. Especially for heavy, repetitive duty applications, maintenance of the circuit breaker is quite an important feature. Low voltage power circuit breakers allow for the inspection and replacement of parts on site. • Safety - Low voltage power circuit breakers are tested as drawout devices in an enclosure. As such, four distinct circuit breaker positions relative to its enclosure are provided for maximum operator safety. The four drawout circuit breaker positions allow for the following uniquely different functions: Connected Position: The circuit breaker is fully connected and functional. Test Position: The circuit breaker’s primary connections are disconnected. Secondary connections are not disconnected and testing can be safely performed because the circuit breaker is not energized. This is not possible with a circuit breaker that is permanently mounted. Disconnect Position: Neither the primary nor secondary electrical connections of the circuit breaker are made. This position is often used as a storage position for the circuit breaker within its enclosure. Withdrawn Position: In this position, the circuit breaker has no electrical conPage 6 Low Voltage Power Circuit Breakers nections. It is far enough out of its enclosure, usually on some type of integral extension rails, to permit inspection and maintenance without turning the power off to an entire assembly of equipment. Reliability - Low voltage power circuit breakers are tested for and must be able to meet high electrical and mechanical endurance ratings. Electrical endurance is the number of operations at rated continuous current and maximum system voltage. Mechanical endurance is the number of operations with no voltage applied. Remote Operation and Reclosing - Low voltage power circuit breakers are designed for operation remotely. They have two-step Stored Energy mechanisms which permit circuit breakers to rapidly reclose after a fault. The twostep stored energy mechanism makes multiple charge-close operations possible, such as the operating sequence: charge-close-recharge-open-closeopen. Custom has led to using phrases such as low voltage power circuit breaker, low voltage metal-frame circuit breaker, low voltage air circuit breaker, and 600 volt power circuit breaker. Although these circuit breakers fall into the classification of 1000 volts and below, real world applications are usually 600 volts and below, thus the 600 volt reference. In general, such a device must be built and tested in accordance with a very specific set of standards, such as ANSI Standards. A low voltage power circuit breaker is a device with both an Interrupting Rating and a short time rating, where the short time rating is composed of two components: • Short Delay Current (expressed in kA) • Short Delay Time (expressed in cycles) This is the primary differentiating feature between a power circuit breaker and a molded case circuit breaker. The importance of this difference will be discussed a number of times later in this module. For many years, low voltage power circuit breakers were essentially an assembly of parts on a welded metal frame, thus the phrase metal-frame circuit breaker. Distinguishing one low voltage circuit breaker from another at that point was rather simple. If it was a metal-frame circuit breaker, it was probably a power circuit breaker. If the circuit breaker parts were enclosed by an insulating material, it was called a molded case circuit breaker (Figure 2). Figure 2. Metal-Frame Low Voltage Power Circuit Breaker Certain hybrid low voltage circuit breakers were later developed and quite successful in certain markets. These circuit breakers had their parts encased in an insulating material, not unlike a molded case circuit breaker. From a performance standpoint, however, they performed more like a power circuit breaker. They had several of the same physical attributes as the power circuit breaker, but were never able to achieve the short time ratings of a power circuit breaker or pass all the power circuit breaker test standards. Page 7 Low Voltage Power Circuit Breakers This type of circuit breaker, although not tested to all the same standards as a power circuit breaker, found its application niche to be similar to traditional power circuit breakers. This design became known as a low voltage insulated case circuit breaker (Figure 3). At that point, the line between frame material to identify the type of circuit breaker became blurred. All this said, the differentiating feature still remains the device’s ability to meet power circuit breaker test standards, not the frame’s type of construction. Figure 3. Low Voltage Insulated Case Circuit Breaker What is a Low Voltage Power Circuit Breaker? Like much other terminology in the industry, the designation low voltage power circuit breaker can be confusing at times. For now, let’s just say that the set or sets of standards a circuit breaker complies with determines whether or not the circuit breaker can be classified as a low voltage power circuit breaker. Applicable standards will be discussed later in this module. As you might imagine by now, there is a wide variety of low voltage power circuit breakers available in the market today. We will not concentrate on what circuit breakers are called. Instead, we will look at characteristics, features and governing standards. Then, no matter who the manufacturer or what a circuit breaker is called, you will be better prepared to discuss the subject. Low voltage power circuit breakers are considered rugged, long-lived, flexible and, to varying degrees, field-maintainable. Let’s briefly look as some of the areas that might set a low voltage power circuit breaker apart from other types of low voltage circuit breakers, such as: • Method used to make and break circuits • Ratings • Construction/Maintainability • Integral Trip Units • Operating Mechanisms • Testing Method Used to Make or Break Circuits Because they make and break power circuits in air using Arc Chutes, as opposed to Vacuum, SF6 or oil, they are considered Air Circuit Breakers. Ratings Low voltage power circuit breaker interrupting ratings and frame size designations can vary to some degree from one manufacturer to another or from one part of the world to another. One thing that is common to most power circuit breakers is the fact that they are rated for continuous operation at 100% of their current rating in their enclosure. What you see on the nameplate is what you get. There is Page 8 Low Voltage Power Circuit Breakers no derating necessary when enclosed, if they are applied as specified by the manufacturer. This is not the case with all types of low voltage circuit breakers when applied in an enclosure. Low voltage power circuit breakers also have a short time rating in addition to an interrupting rating making them naturally suited for selectivity and coordination with downstream devices. Downstream devices are devices, such as other circuit breakers, that are farther into the electrical system. You will recall from an earlier discussion, and it is worth mentioning again, that the short time rating is composed of two components - short delay current and short delay time, which are adjustable (programmable). As far as selectivity is concerned, let’s say it is the response to a set of circuit or system conditions, usually in terms of current, in a certain time frame. It is really the ability to withstand a certain level of current (kA) for a given time period (cycles) while a downstream device selectively takes care of the problem by interrupting. This is also known as discrimination. The degree of selectivity is usually limited by the sophistication of the trip unit and the physical ability of the circuit breaker to withstand the potentially large thermal and mechanical stresses created by a fault current. Construction/ Maintainability Low voltage power circuit breakers are essentially an assembly of parts on a metal frame or in an encased housing of insulating material. It is important to know that no set of standards dictates the type of frame construction for low voltage power circuit breakers. That decision is left in the hands of the manufacturer. You could look at it like the frame and body of a car holding all the other parts, like the motor, wheels, bumpers, seats and radio. This type of circuit breaker, to varying degrees, has the ability to be maintained in the field. Figure 4. The Frame of a Car is Like the Housing of a Low Voltage Power Circuit Breaker In addition, it is available in either a Fixed or Drawout configuration, with drawout being the most commonly used type. Trip Units Trip Units today used on low voltage power circuit breakers are almost universally of the solid state, microprocessor-based design. Years ago this same type circuit breaker used only electromechanical type trip units. Because this type of trip unit used with a low voltage power circuit breaker is almost non-existent, it is only mentioned briefly in this module. It is important to note that ANSI Standards require that the trip units on low voltage power circuit breakers be integrally mounted. Operating Mechanisms Low voltage power circuit breakers operate through two-step stored-energy spring mechanisms. The springs used to close the circuit breaker contacts, called closing springs, can be manually or electrically charged. The springs used to open the circuit breaker, called opening springs, are usually charged automatically when the breaker is closed. Because of the increased closing forces required and the closing speed, low voltage power circuit breakers use two-step, stored energy mechanisms. That is, the closing springs are charged and remain charged with the breaker open until a “close” button or some other type of release is activated to close the breaker. As mentioned in Module 5, the low voltage power circuit breaker is required by ANSI Page 9 Low Voltage Power Circuit Breakers Standards to provide an open-close-open duty cycle. This dictates the need for a two-step stored energy mechanism. In the Workplace Low voltage power circuit breakers are most commonly applied in switchgear assemblies like the one shown here. Figure 5. Typical Low Voltage Metal-Enclosed Assembly Frequently, low voltage power circuit breakers are used to control (and protect against overloads and short-circuits on) fans, pumps and lighting panels. An assembly such as this one could be used to serve the HVAC needs of a manufacturing facility. Because they are built to withstand such intense service conditions, low voltage power circuit breakers are ideal for industrial applications such as this. Principles of Operation and Terminology A low voltage power circuit breaker can be applied on any system within the interrupting rating of the circuit breaker. Low voltage power circuit breakers are ideally suited for applications where there is a requirement for the circuit breakers to be selective when faced with short-circuit conditions. In addition to our earlier discussion of selectivity, we could also say that “selective” means that the circuit breaker is capable of remaining closed for a certain period of time with a short-circuit present to allow the problem to be cleared up by a downstream device before the power circuit breakers open and the larger system is shut down (short time delay rating capacity). This is the area where short time delay ratings from 0 to 30 cycles play a key role. Obviously, it is assumed that the circuit breaker is applied properly and will not face short-circuit conditions beyond its capabilities. If it does see a condition beyond its short time rating, it will open instantaneously. Time will be taken here to introduce several additional principles and common terms associated with low voltage power circuit breakers and their application. This material will be especially helpful from a practical standpoint. These are the types of terms and topics encountered on the job when working with low voltage power circuit breakers and their assemblies. Principles and terms presented here are certainly not all inclusive. Even after this module is completed and you return to your work location, new terms will surface that should be part of your low voltage power circuit breaker vocabulary. The intent here is to provide a solid background on which to build. Page 10 Low Voltage Power Circuit Breakers Stored Energy Stored energy was briefly touched on earlier in this module and in Module 5. Because this is a phrase frequently heard with respect to circuit breakers, it deserves some elaboration. All low voltage power circuit breakers, whether manually or electrically operated, utilize two-step stored energy mechanisms. Stored energy mechanisms are needed to overcome inherent forces opposed to the closing process. They also make it possible to close the circuit breaker very quickly, 5 cycles or less time. Stored energy is energy held in waiting, ready to open or close the low voltage power circuit breaker in five cycles or less. Designs are such that the energy required to open a low voltage power circuit breaker is always available. On manually operated circuit breakers, closing springs are charged by hand. For electrically operated circuit breakers, springs are normally charged by a small electric motor, although they can also be charged manually if power is not available (Figure 6). Figure 6. Typical Low Voltage Metal Frame Power Circuit Breaker Being Manually Charged Bus Bus refers to a conductor or conductors, usually made of copper or aluminum bars. Bus bars carry current and serve as a common connection for two or more circuits (Figure 7). Figure 7. Rear View of Typical Low Voltage Switchgear Assembly Showing a Maze of Bus Bars Interconnected Control Voltage The Control Voltage (or secondary voltage), is usually secondary with respect to the voltage rating of the circuit in which the circuit breaker is applied. Control voltage is used to operate secondary devices. The voltage used to run the motor that charges a circuit breaker’s springs automatically is an example. Drawout A drawout circuit breaker refers to a circuit breaker that can be moved within a compartment from one defined position to another without manually disconnecting any connections or turning off the line side power. This is usually accomplished through the use of a mechanical levering device, some- Page 11 Low Voltage Power Circuit Breakers times in combination with the manual assistance of an operator. This is called racking the circuit breaker into or out of a position. The circuit breaker is first opened, and then automatic main disconnect devices on a drawout circuit breaker allow for the circuit breaker to connect or disconnect from the bus. These automatic main disconnect devices are often referred to as Finger Clusters. The phrase finger cluster comes from the fact that many designs utilize a number of conductive pieces (fingers) assembled into one cluster. The four typical defined positions are: • Connected • Test • Disconnect • Remove (Withdrawn) In the Connected position, the circuit breaker is into its compartment as far as it will go with both primary and secondary electrical connections made. The circuit breaker is now ready for normal operation (Figure 8). Figure 8. Connected Position In the Test position, the circuit breaker is farther out of its compartment with the primary electrical connections no longer made (Figure 9). Secondary electrical connections are still made in this position to provide the secondary power required to test the circuit breaker’s operation, including the trip unit. Figure 9. Test Position In the Disconnect position, the circuit breaker is even farther out of its compartment with the main Contacts open (Figure 10). Neither the primary nor secondary electrical connections are made. This is a typical compartment storage position for a circuit breaker not in use. Page 12 Low Voltage Power Circuit Breakers Figure 10. Disconnect Position In the Remove (or Withdrawn) position, the circuit breaker is out of the compartment on extension rails with the main contacts open and the closing springs discharged (Figure 11). There are neither primary nor secondary electrical connections. This is the typical last position for a circuit breaker to be in before it is physically removed from its rails to another location. Figure 11. Remove (Withdrawn) Position Behind Door Drawout This is related to the specific drawout breaker design (Figure 12). Behind the door drawout means that the breaker compartment door usually must be opened to Lever (or “rack”) the breaker from one position to another as just discussed under “Drawout.” The breaker normally has a Faceplate Shield (or “deadfront shield”) to protect the operator from dangerous voltages while the door is open. This type of design usually permits the breaker to be in any of three positions (Disconnect, Test, Connected) with the door closed. This design does not permit an individual to know the status of the circuit breaker or its trip unit without opening the compartment door. Page 13 Low Voltage Power Circuit Breakers Figure 12. Typical Behind the Door Drawout Type Low Voltage Metal-Frame Circuit Breaker Being Levered From One Position to Another Through Door Drawout This is also a drawout related circuit breaker design (Figure 13). Through the door drawout permits the operator to lever the circuit breaker from the “Connected” position to the “Test” position to the “Disconnect” position and vice versa without opening the compartment door. The door has a hole in it to accommodate protrusion through the door of some small portion of the circuit breaker as it reaches a position well to the front of the compartment. The operator is also protected by a deadfront shield, usually a combination of the door and the faceplate of the circuit breaker. The benefits associated with this design are that a full view of the circuit breaker front is given along with access to the racking (drawout) device without opening the compartment door. Figure 13. Three Typical Through-the-Door Drawout Positions of Low Voltage Power Circuit Breakers in its Compartment Continuous Current Rating The Continuous Current Rating of a circuit breaker is the maximum current rating the breaker is designed to carry on a continuous basis and remain within the applicable guidelines for the breaker. It is also referred to as the “Frame Rating” or the “Frame Size.” 100% Rated ANSI specifies that low voltage power circuit breakers are to be rated for continuous operation at 100% of their current ratings in their compartment. To meet these requirements, they are tested for operation within a specific enclosure and, therefore, do not need to be de-rated. Interrupting Rating The interrupting rating is the maximum short-circuit current that the circuit breaker can safely interrupt. ANSI prescribes its minimum preferred ratings for power circuit breakers to meet. Short Time Rating The short time rating of a low voltage power circuit breaker is the maximum value of current the circuit breaker is designed to handle safely for a short period of time (30 cycles or 0.5 seconds) in the closed position, without damage to the circuit breaker. This test is repeated twice for a total of one (1) second. The short time rating is usually equal to the 600 volt interrupting capacity. This attribute is one of the main features that differentiates a power circuit breaker from Page 14 Low Voltage Power Circuit Breakers other types of circuit breakers and allows for system selectivity. The short time rating was also discussed earlier in this module. Trip Free When a circuit breaker is in a Trip Free condition, it cannot, by design, be closed. Even when intentional efforts are made to close the circuit breaker and it is in a trip free condition, the main contacts will not touch and the circuit breaker will automatically return to the tripped position. This is an important safety feature specific to power circuit breakers. Current Sensor Sensor, as used with respect to a circuit breaker, is a common term for a current transformer which steps current down to useful levels for a specific purpose, such as providing an input to a trip unit (circuit breaker’s intelligence package). Page 15 Low Voltage Power Circuit Breakers Review 1 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. A power circuit breaker has either an interrupting rating or a short time rating. TRUE FALSE 2. While inside their compartments, most low voltage drawout power breakers can be in any of the following positions with compartment doors closed: a. Connected Position b. _______________ Position c. _______________ Position 3. Both manually and electrically operated low voltage power breakers use stored energy mechanisms for opening and closing. TRUE FALSE 4. The frame rating or the frame size of a low voltage power breaker refers to the _______________ ________________ rating of the breaker. 5. All low voltage power breakers that meet applicable ANSI Standards are capable of continuous operation at 100% of their current rating. TRUE FALSE 6. The _______________ _______________ Rating of a power breaker is one of the main features that differentiates a power breaker from other types of circuit breakers. 7. ANSI Standards requires low voltage power breakers to have integrally mounted trip units. TRUE FALSE 8. One reason a low voltage power breaker utilizes a two-step stored energy mechanism is so that it is able to provide an ______________________________-_______________ duty cycle. Page 16 Low Voltage Power Circuit Breakers Design and Functional Considerations In Module 5, you learned that all circuit breakers have a number of design and functional characteristics in common: • Compliance with Specific Standards • Set of Open/Close Contacts • Means to Open and Close the Contacts • Means to Extinguish an Arc • Means to Respond to Overcurrents/Commands • Method for Enclosing Circuit Breaker Components • Method For Mounting Circuit Breaker Specific methods used for mounting and using low voltage power circuit breakers will be covered in the next section. In this section, the concentration will be on how low voltage power circuit breaker operate to accomplish their tasks and what accessory items are available to enhance their capabilities. Basic low voltage power circuit breakers are generally composed of: • Frame or Chassis • Primary Contacts • Arc Extinguishers • Operating Mechanism • Integral Trip Unit • Accessory Items Let’s take a look at each. Frame or Chassis You will recall from Module 5 that all circuit breakers utilize some method to hold all the parts that make up a circuit breaker, usually called the frame or chassis. A low voltage power circuit breaker chassis today will be one of two types (Figure 14 and 15): • Open Type Metal-Frame (Older Designs) • Molded Frame of Engineered Thermoset Composite Resins (Newer Designs) Figure 14. Molded Frame Construction Page 17 Low Voltage Power Circuit Breakers Figure 15. Metal-Frame Construction The open type metal-frame has a number of pieces welded and/or bolted together on which the different circuit breaker components are assembled. Components have a tendency to be larger, heavier, and may need to be adjusted. In the Workplace The new Magnum DS power circuit breaker utilizes a rigid frame molded from engineered thermoset composite resins. Figure 16. Magnum DS Power Circuit Breaker Molding improves the structural rigidity of the frame, allowing for higher interrupting and short time ratings. Many individual circuit breaker parts are molded as integral assemblies. This improves the design by making it smaller and stronger with fewer individual parts, unlike the metal-frame approach. Primary Contacts Primary open/close contacts in a low voltage power circuit breaker provide a means for isolating or connecting a part of a circuit from or with the rest of the system. The design of the primary contacts is one of the most critical design considerations relative to the efficiency and overall effectiveness of any low voltage power circuit breaker. These contacts are used to carry or break the main continuous load current associated with the system in which the circuit breaker is applied. Each phase has an associated primary contact. A three-phase low voltage power circuit breaker, for example, would have three sets of primary contacts. Keep in mind that primary contacts come in a wide variety of designs and appearances. All designs do not use the same number of parts nor are all designs equally efficient. However, all designs act to provide the same general service. Low voltage power circuit breaker primary contacts usually have separate arcing and main current carrying parts. This does not mean that they are necessarily separate pieces. They could both be part of the same component piece, although the arcing and main contacts act as individual pieces and perform distinctly different functions. Page 18 Low Voltage Power Circuit Breakers In Module 5, the discharge of electric current crossing a gap between two contacts was discussed (Figure 17). This phenomenon, on a small scale, can occasionally be observed when pulling a plug from a wall socket. Figure 17. Electrical Current Crossing a Gap Arcing also occurs when opening and closing low voltage power circuit breakers under load, except to a much larger degree. The primary contact design challenge is to ensure that the arcing is dealt with first to protect the surface of the main contacts from arc damage. For this reason, primary contacts are mechanically designed such that on closing of the circuit breaker, the arcing contacts touch (make) before the main contacts. Also on opening of the circuit breaker, the main contacts part (break) before the arcing contacts. This construction ensures that arcing takes place on the heat resistant arcing contacts. Usually, primary contacts are replaceable on low voltage power circuit breakers, which can be needed in time if the operating duty of the breaker is severe enough. A primary contact assembly is composed of: • fixed (stationary) part • moving part A rigid insulating piece through a pushing or pulling motion is used to operate the moving part of the primary contact assembly. The fixed and moving main and arcing portions of the assembly can be in any number of configurations, some more efficient than others (Figures 18 and 19). Usually the designs for a particular type circuit breaker are the same. The only variable is the number of parts used to handle the amount of current available. Larger circuit breaker frames require more and/or larger arcing and main contact pieces. Keep in mind that the design goal is to efficiently handle arcing through the heat resistant arcing contacts so that the main contacts are protected from unnecessary damage. This approach permits the main contacts to be made from low resistance materials, such as silver or silver alloys to minimize the heat developed during normal operation. Page 19 Low Voltage Power Circuit Breakers Figure 18. Contact Assembly Mounted (Front View) Figure 19. Contact Assembly Mounted (Rear View) Finally, it was pointed out in Module 5 that some newer low voltage power circuit breaker designs take full advantage of certain natural facts of physics to assist with the opening process. You will recall that the concept centers around magnetic fields established in conductors when current is flowing in the conductors. The low voltage power circuit breaker design takes full advantage of this electromagnetic force to assist with opening and keeping the circuit breaker closed. In certain configurations, the force and also the insulator are used to help hold the contacts closed temporarily during a fault condition, which is where a power circuit breaker’s short time rating comes from. Circuit breaker designs taking advantage of this concept can be smaller and lighter and still maintain the higher withstand (short-time) capabilities associated with low voltage power circuit breakers. When it is time for the contacts to open, this same force can be used in the opposite direction to speed the opening action. Think about the concept of electromagnetic assistance with opening and closing of contacts in the following fashion (Figure 20). A door could be viewed as the movable contact. Our super-hero can be considered the rigid insulator used to push closed or pull open the door (contact). Assistance from the wind (electromagnetic force) in the proper direction would help our super-hero open or keep the door closed. Page 20 Low Voltage Power Circuit Breakers Figure 20. Electromagnetic Force Can Be Used to Help With Opening and Closing Arc Extinguishers In Module 5, a number of ways or combinations of ways to extinguish an arc was discussed. Low voltage power circuit breakers use some type of Arc Extinguishers (arc chutes or arc chambers) mounted above and around the main contacts to extinguish arcs in air (Figures 21 and 22). This leads to the name low voltage power air circuit breakers. Arc chutes, in some form, have been used to extinguish arcs for more than a half century. The primary purpose of an arc chute is to extinguish an arc each time a circuit breaker interrupts a current. This is accomplished by confining, dividing and cooling the arc. This accomplished, the arc is not able to sustain itself through current zero. Not all arc extinguishers are created equal and, therefore, some are more efficient than others. Efficiency is very important because the amount of contact damage caused by arcing is directly related to how fast or efficiently arcs are extinguished. More efficiency leads to longer contact life. Figure 21. Top Rear View Magnum DS Circuit Breaker Showing Arc Chambers and One Arc Chute Removed Figure 22. One Arc Chute Removed From a Magnum DS Circuit Breaker (Bottom View) During the arcing process, ionized gases are generated and normally vented, in some fashion, harmlessly away from the circuit breaker, breaker compartment, and any operator who might be in close proximity to the equipment. It is also Page 21 Low Voltage Power Circuit Breakers known that the high pressure created by these gases, if controlled properly, can be put to good use during interruption. To this end, the molded case low voltage power circuit breaker design, for example, utilizes this gas pressure to help with the interruption process while minimizing gas leakage back into the circuit breaker itself. This improvement is accomplished through the use of seals in the arc chamber and a close fit of pieces and parts. This can only be accomplished with molded frame designs. Obviously, the design and process is a bit more involved than just described. For now, the most important thing to remember is that the original arc extinguisher concept is still used today, but great strides have been taken to improve upon the original concept with significant improvements in overall efficiency. Operating Mechanism You learned in Module 5 that some type of a mechanism is provided with all circuit breakers for opening and closing. Low voltage power circuit breakers are no exception. A low voltage power circuit breaker operating mechanism is composed of a number of different parts, assemblies and accessories, all dedicated to ensuring that the circuit breaker opens and closes consistently. The mechanism is a two-step spring charged stored energy type providing three basic functions: • A means to charge the closing springs • A means to close/open the circuit breaker using the stored energy of the closing and opening springs • A means to perform an Open-Close-Open duty cycle Two varieties of the mechanism exist: • Manual • Electrical (Motor Operated) The manually operated circuit breaker has its closing springs charged manually through the use of some type of charging handle. The circuit breaker is closed using a manual close button which is a mechanical process. As the circuit breaker closes, a set of smaller opening springs are charged. The circuit breaker is opened using a manual trip (open) button, which is a mechanical process. Safety interlocks, accessory items and trip units can also cause the circuit breaker to trip through mechanical means. Most manually operated power circuit breakers can be equipped with an optional device to electrically release the spring’s stored energy, thus closing the circuit breaker. Previously, it was not practical or even possible to convert manually operated low voltage power circuit breakers to electrically operated circuit breakers in the field. This is no longer impossible with newer low voltage power circuit breaker designs. Such designs permit manually operated circuit breakers to be converted to electrically operated circuit breakers by field installing UL Listed electrical operators. Page 22 Low Voltage Power Circuit Breakers Figure 23. Magnum DS Power Circuit Breaker Being Manually Charged An electrically operated circuit breaker can be operated every way a manually operated circuit breaker can be operated. In addition, a small electric motor is normally used to automatically charge the closing springs, and an electrical means to close or trip (open) the circuit breaker is provided. Integral Trip Unit For a circuit breaker to do its job, a means must be provided enabling the circuit breaker to perform automatically or in response to other commands. In short, the circuit breaker is a rather dumb device without a brain (intelligence source). This source of intelligence is the trip unit. As required by ANSI Standards, low voltage power circuit breakers must be provided with an Integrally Mounted Trip Unit. This means that the trip unit must be inside of, or part of, the circuit breaker. Prior to the advent of the first solid state trip unit, electromagnetic type tripping devices, commonly called dual-overcurrent magnetic trips, were used with all low voltage power circuit breakers. In recent times, this type of tripping device on low voltage power circuit breakers has disappeared from the scene. For this reason, only microprocessor-based trip units will be discussed in this module. A typical microprocessor-based trip unit used with low voltage power circuit breakers offers the following capabilities (Figure 24): • Programming • Monitoring • Diagnostic • Communication • Testing Figure 24. Integrally Mounted Trip Units Page 23 Low Voltage Power Circuit Breakers The capabilities of a particular trip unit depends on the trip unit design itself and system requirements. Some trip units can only offer basic features, while others can offer basic features or, if required by the system, additional sophisticated and highly advanced features. The operating response of a trip unit is graphically represented by time-current characteristic curves. These curves show how and when a particular trip unit will act for given values of time and current. A characteristic curve is represented by a band created by a minimum and maximum value of time or current. The programmable or adjustable features of a trip unit permit movement of its characteristic curve or parts of the curve (Figure 25). This movement can be done in both a horizontal and vertical direction. Some trip units even allow the shape of the curve to be changed. Figure 25. Typical Trip Curve Horizontal Movement Most trip units offer protection combinations of: • (L) Long delay protection - protection against overloads and short circuits • (S) Short delay protection - protection against short circuits • (I) Instantaneous protection - protection against short circuits • (G) Ground fault protection - protection against ground faults A trip unit offering all four of these protection at one time is commonly called an LSIG Trip Unit. Other combinations are also available, such as LI, LS, LSI, LIG and LSG. The long, short and ground functions would have programmable values of current and time. Obviously, instantaneous has no associated time because the trip is instantaneous (Figure 26). Trip units have these different programmable features programmed so they coordinate with one another and with the requirements of the system being protected to provide the closest possible system coordination and protection against all eventualities. This coordination discipline is where you start hearing phrases like curve shaping and close coordination. No attempt will be made in this module to get into the details of this discipline. It is quite specialized and best left to individuals with the proper training. Page 24 Low Voltage Power Circuit Breakers Figure 26. Advanced Trip Unit Time-Current Curve Adjustments More advanced trip units are able to monitor and display currents, energy, power, power quality and power factor. They also may be able to diagnose problems and provide advance warnings of potential problems, such as harmonics. Two way communications for remote monitoring and control is also available. This affords the user a cost effective way to monitor and control expansive, multi-location facilities with a wide array of protective equipment and operational machinery. Trip and no trip tests can usually be performed on the trip unit and circuit breaker utilizing integral testing capabilities or separate test kits. Normally, the tests can be performed with the circuit breaker in service and full protection provided during the testing. This type of testing is secondary testing. Primary testing involves specialty testing equipment and a testing expertise, and is not discussed in this module. Accessory Items Accessories used with low voltage power circuit breakers are usually added to the circuit breaker to provide additional features, such as status indication and remote operation. It is possible, however, that some accessories for some circuit breaker designs might be mounted remotely from the circuit breaker. These devices might be totally mechanical, totally electrical or a combination. The intent here is to briefly discuss the function of commonly used accessory items, although all low voltage power circuit breakers do not necessarily offer all of the devices being discussed, nor is this list all inclusive. • Electrical Operator - This is an assembly of devices including a small spring charging motor that when added to a manually operated circuit breaker converts it to an electrically operated circuit breaker. This allows for remote operation (open/close) of the circuit breaker. The ability to field install this device is more common with newer low voltage power circuit breakers. Power circuit breakers normally use to be either manual or electrical by design, and could not be easily converted. • Operations Counter - An operations counter is a counting device, usually linked in some fashion to the operating mechanism. It is used to count the open and close operations of the circuit breaker, and serves as a maintenance aid. • Auxiliary Switch - An auxiliary switch consists of “normally open” (NO) and “normally closed” (NC) contacts (Figure 27). The contacts on some switches are convertible from NO to NC and vice versa. The contacts are frequently referred to as “a” or “b” contacts. The “a” being open when the circuit breaker is open and the “b” closed when the circuit breaker is open. In short, these auxiliary contacts change “state” when the circuit breaker main contacts change “state.” An auxiliary switch is normally mounted on the circuit Page 25 Low Voltage Power Circuit Breakers breaker. Contacts from these switches are frequently used for electrical operation of a circuit breaker, remote signaling, and electrical interlocking. Figure 27. Graphical Representation of a Four Contact Auxiliary Switch (2A and 2B) • Undervoltage Release (UVR) - An undervoltage release, normally a circuit breaker mounted electromechanical device, trips the circuit breaker when the voltage falls below a predetermined level. • Shunt Trip (ST) - A shunt trip is an electromechanical device which is standard on most electrically operated power circuit breakers. When added to a manually operated circuit breaker, it provides for remote controlled electrical tripping. • Spring Release (SR) - The spring release device is standard on most electrically operated power circuit breakers. When added to a manually operated circuit breaker, it permits the circuit breaker to be closed electrically from a remote location. • Bell Alarm (OTS) - The bell alarm, frequently called an overcurrent trip switch (OTS) on a power circuit breaker, is normally circuit breaker mounted. Its function is to provide a signal to indicate that the circuit breaker has tripped open automatically (trip unit command). It will not operate if the circuit breaker is tripped open by other means, such as the use of a manual trip button, an electrical control switch, or the operation of an undervoltage release device. • Locking Devices - Low voltage power circuit breakers normally have a wide array of mechanical locking devices to prevent unauthorized circuit breaker operation (Figure 28). Figure 28. Padlock Shown Mounted on Front of Molded Frame Type Power Breaker Preventing Unauthorized Use of Open and Close Buttons • Mechanical Interlocks - These devices provide a way to mechanically interlock two circuit breakers. A typical use for such a device is to prevent one circuit breaker from closing while another circuit breaker is already closed. • Capacitor Trip Device - A capacitor trip device is normally mounted externally from the circuit breaker. It uses a small storage capacitor for AC control Page 26 Low Voltage Power Circuit Breakers of the circuit breaker to ensure reliable tripping power during fault conditions. • Lifting Device - Because some low voltage power circuit breakers can be sizable and heavy, a variety of devices is usually available to lift and move the circuit breaker once it is out of its compartment (Figure 29). Figure 29. Rail Mounted Lifting Device Being Used to Lift a Magnum DS Power Circuit Breaker From Its Compartment Extension Rails • Truck Operated Cell Switch (TOC) - A TOC switch is usually mounted in the circuit breaker compartment and is activated by movement of a drawout circuit breaker into and out of the “Connected” position. As the circuit breaker moves, the contacts are activated providing a means for remote indication of the circuit breaker’s position. Page 27 Low Voltage Power Circuit Breakers Review 2 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. For many years low voltage power circuit breakers were open type metalframe circuit breakers. Today, newer low voltage power circuit breaker designs are _________________ frame type designs. 2. When a low voltage power circuit breaker opens, its arcing contacts part before the main contacts part to draw any arcs formed away from the main contacts. TRUE FALSE 3. Low voltage power circuit breakers are considered air circuit breakers and use _______________ _______________ to eliminate the arc by confining, dividing and cooling it. 4. The operating mechanism springs of both manually operated and electrically operated low voltage power circuit breakers can be charged manually. TRUE FALSE 5. A low voltage power circuit breaker’s source of intelligence is its _______________ _______________. 6. Current transformers used in a low voltage power circuit breaker to monitor and reduce the current to useful levels are also known as _______________. 7. Time-current characteristic curves graphically represent the operating response of the _______________ ______________. 8. Circle the type or types of protection from the four types listed below that offer some degree of protection against short circuits. (a) Long Delay Protection (b) Instantaneous Protection (c) Short Delay Protection (d) Ground Fault Protection 9. An auxiliary switch is graphically represented below. On the graphic, label each of the four contacts as either “a” or “b” type contacts. 10. A _______________ _______________ is an electromechanical device used to provide for remote controlled tripping of a manually operated low voltage power circuit breaker. 11. A bell alarm on a low voltage power circuit breaker, also referred to as an overcurrent trip switch, provides a signal to indicate when a circuit breaker has tripped open for any reason. TRUE FALSE 12. A TOC switch is activated by movement of a circuit breaker into and out of the “Connected” position. Indicate next to each letter below what word the letters represent. T _______________ O _______________C _______________ Switch Page 28 Low Voltage Power Circuit Breakers Mounting Methods As briefly discussed earlier, low voltage power circuit breakers are usually available in the two following mounting configurations: • Fixed • Drawout Total usage of low voltage power circuit breakers today is dominated by the drawout configuration because it provides for easier maintenance and continuity of service. Most circuit breaker manufacturers, however, offer both types. Fixed Circuit Breaker Fixed low voltage power circuit breakers usually have fixed primary conductor stabs protruding from the rear of the circuit breaker. The circuit breaker is bolted in position within its assembly compartment, and the rear conductor stabs are bolted to primary bus connections (Figure 30). Secondary connections are also made manually. Power must be turned off to the assembly to connect a fixed circuit breaker into the system or to remove it from the system. Figure 30. Fixed Type DSII Circuit Breaker Drawout Circuit Breaker Drawout low voltage power circuit breakers have a levering device to move the circuit breaker from one compartment position to the next. Usually part of the levering mechanism is on the circuit breaker with a corresponding part is in its compartment. Working together, they provide the mechanical means required to move the circuit breaker. Drawout circuit breakers are designed to be removed and connected without cutting power to the entire assembly under load conditions because the circuit breaker, by design, automatically opens before racking can take place. This means that power to the assembly does not have to be turned off when a circuit breaker is removed from or inserted into the assembly, thus ensuring continuity of service. Drawout circuit breaker compartments are provided with extension rails which, when not in use, are stored inside the compartment (Figure 31). The extension rails provide a means by which a drawout circuit breaker can be easily removed from its compartment for inspection, maintenance or movement to another area. Figure 31. Drawout Molded Case Circuit Breaker Shown on Compartment Extension Rails Page 29 Low Voltage Power Circuit Breakers Primary electrical connections between the circuit breaker and the primary bus are automatically made or broken as the circuit breaker is moved into or out of the “Connected” position within the circuit breaker compartment. Primary connectors mounted to the back of the circuit breaker slide onto the primary bus connectors. These primary connectors, often called finger clusters or disconnect contacts, are frequently composed of a number of spring loaded fingers (contacts) (Figure 32). The number of fingers (contacts) used is dictated by the amount of current they will carry. Fingers (contacts) are made of an excellent conducting material or material combination, such as silver plated copper. Figure 32. Rear View of Magnum DS Power Circuit Breaker Showing Six Primary Finger Clusters Secondary electrical connections are usually automatically made or broken as the circuit breaker is moved into and out of its compartment. As the circuit breaker is moved into the “Test” position from the “Disconnect” position, the secondary connections are made providing the required secondary power for testing or operating the breaker, but no primary power. The secondaries remain connected as the breaker moves into the “Connected” position. When the circuit breaker is moved out of the “Connected” position, the secondaries remain connected and stay connected until the circuit breaker is moved farther out of its compartment past the “Test” position. The graphics of the four positions presented earlier in the module demonstrate the movement and connections. Governing Standards You will recall from Module 5 that circuit breakers are designed, built and tested in accordance with one or more specific sets of standards. In this module, you will be introduced to the standards specific to low voltage power circuit breakers. The intent here is not to present and study the different applicable standards word for word. That type of undertaking would be a course unto itself. Our goal is to understand a little about low voltage power circuit breaker related standards, where they were, and where they are today. Figure 33. Many Standards Page 30 Low Voltage Power Circuit Breakers You will hear many people repeat specific standards designations. Many of those same people do not have an intimate knowledge of what the standards actually say, nor are we saying they should. The actual product selection based on standards compliance should be left to the experts. It is helpful, however, to know what specific standards your products comply with and what general topic a specific standard addresses. Keep in mind that a standard exists for almost everything. There are specific standards for circuit breakers and others for the structural assembly. Compliance with these exacting standards ensures customers of the very best possible product selection with a high degree of comfort. There is no room for compromise when performance, quality and safety are involved. A number of years ago, low voltage power circuit breakers and most other types of equipment were designed and built primarily with only domestic standards in mind. This approach also was taken by foreign suppliers. A manufacturer would offer a circuit breaker designed, tested and manufactured in keeping with applicable standards for that part of the world or even particular country. Trying to play a significant role in other world markets was, at best, extremely difficult. If manufacturers today expect to be global participants, they must offer products that comply with the standards applicable to a variety of different markets around the world. This will require that you become familiar with both domestic and international nomenclature, ratings, procedures and governing standards. The task is greater, but so is the reward. Some of the lines separating different types of low voltage circuit breakers were at times blurred in the past. Low voltage metal-frame power circuit breakers were built and tested to certain ANSI and UL specifications, while some low voltage encased circuit breakers were tested to UL specifications specific to molded case circuit breakers. The newest low voltage power circuit breakers today, like Magnum DS, are tested to specific low voltage power circuit breaker standards, like ANSI. They are also tested to standards that cover a much broader product scope, like IEC. The primary testing standards associated with low voltage power circuit breakers today are: ANSI The American National Standards Institute’s ANSI C37.50 is a specific North American testing standard entitled “Low Voltage AC Power Circuit Breakers Used In Enclosures.” This standard specifies rigorous tests for product performance. There are additional C37 standards which govern power circuit breaker and trip unit construction, such as C37.13 and C37.17 respectively. UL Underwriter’s Laboratories Incorporated’s UL1066, for the most part, calls for testing to demonstrate compliance with ANSI C37.50 just mentioned. A UL Label is affixed to the breaker to indicate successful compliance. IEC The International Electrotechnical Commission IEC 947-2 is a more general international testing standard covering a variety of devices, including circuit breakers of all types, and is entitled “Low Voltage Switchgear and Controlgear.” Closing Comments on Standards Before concluding this section, it might help to minimize confusion if you remember that there is often a great deal of referencing to other standards that takes place within a specific standard. Successful testing with respect to one standard often includes automatic compliance with other standards. Example 1 - ANSI C37.13 details the physical attributes, such as stored energy, that a low voltage AC power circuit breaker must have, while ANSI C37.50 references C37.13 and details how the described breaker should be tested. The key Page 31 Low Voltage Power Circuit Breakers here is that successful testing in keeping with ANSI C37.50 brings with it compliance to C37.13. Example 2 - In a similar fashion, IEC 947-2 references IEC 947-1 (General Rules). Compliance with IEC 947-2, therefore, brings with it IEC 947-1 compliance. Testing The testing required and the standards that must be met by a low voltage power circuit breaker depend on the area of the world where the circuit breaker is applied. To play a major international role, low voltage power circuit breakers should be able to meet the requirements of ANSI, UL and IEC (Figure 34). Figure 34. Dominant Worldwide Standards As you continue through this module, you will become well aware that the required testing is the key factor in defining the type of circuit breaker. In a very general and simplistic way, low voltage power circuit breakers undergo a sequence of four rigorous tests. 1. The first sequence consists of a temperature rise, an overload, and a shortcircuit test. 2. The second sequence is a series of short-circuit tests. 3. The third sequence is an endurance test. 4. The fourth is a momentary rating test. Molded case circuit breakers, for example, are subjected to tests similar to numbers 1, 2 and 3. The fourth test sequence, momentary rating test, is specific to power circuit breakers and to some IEC molded case circuit breakers. Specific testing details will not be covered in this module. It should be pointed out, however, that the momentary rating test just mentioned (test sequence 4) subjects the circuit breaker to tremendous physical forces and severe heating effects. Very simply speaking, the circuit breaker is subjected to its full short time current rating for two (2) time periods up to 30 cycles each. The short time rating indicates what magnitude of current the circuit breaker can stand with its contacts closed for a short period without being damaged. The circuit breaker’s short time rating is often equal to its 600 volt interrupting capacity. A low voltage power circuit breaker must be strong enough to survive this test and function properly after completion. Page 32 Low Voltage Power Circuit Breakers Helping the Customer Selection of the proper low voltage power circuit breaker for a specific application is not a difficult process. There are some important questions, however, you must be able to answer. Fortunately, the most difficult part of the job has already been done by other qualified individuals when they determined the requirements of the system. This includes determining things like: • Circuit Breaker type required • Application voltage • Maximum fault current system could see • Continuous current for the system and each branch • System frequency • Types of trip unit capabilities • Programmable functions • Accessory needs • Mounting configuration • Special requirements Your job is to make sure these types of questions are answered. The more familiar you are with what a particular circuit breaker line has to offer, the easier the task. Let’s start by looking at what circuit breaker manufacturers do to help. Manufacturers normally provide a great deal of assistance in the way of printed material, computer accessible information and direct contact. This does not mean, however, you should not put forth that extra effort to know personally what is available. Learn to use all the information provided. Most selection factors fall into one of two categories: Standard Selection Factors • Standard selection factors • Special selection factors Standard selection factors normally are associated with the circuit breaker’s ratings/standards, operation method, accessory items, and how the breaker will be mounted. The most common points to consider will be discussed. 1. Standards - Applicable standards were discussed in this module and earlier modules. You should be told or it will appear in a written specification what standards the circuit breakers must meet. Newer low voltage power circuit breakers meet a wide array of standards which will make them acceptable in most parts of the world. In addition, make sure you are aware of any special local requirements and/or standards. 2. Ratings - This is a critical part of the selection process. You should already know what is required. Now you must determine what specific circuit breakers will meet the rating requirements. Manufacturers normally provide easy to read tables outlining the ratings of every circuit breaker frame. Keep in mind there could be more than one table. This is especially true for newer circuit breaker designs that meet both ANSI and IEC requirements. A manufacturer might choose to present it as one combined table or two tables. If you know what is required, you will be able to make a selection from the tables under normal circumstances. Page 33 Low Voltage Power Circuit Breakers ANSI Example Let’s take a look at a typical type ANSI table for a low voltage power circuit breaker and see what it has to offer (Figure 35). The table used in this example will not cover every circuit breaker rating for a particular design. Enough of the table is presented to give you a good working knowledge on how to proceed. Each area of the table that is discussed is identified by a circled letter to simplify the discussion. One last important point should be made before beginning. Always read footnote references carefully. They provide important information and could be critical to the proper selection. Figure 35. Example ANSI Ratings Table A: The “Breaker Type” is usually the name given to the circuit breaker by the manufacturer along with some general information about the ratings of that specific circuit breaker type. In the example ratings table shown, XYZ-508 is the first circuit breaker listed. The XYZ is the circuit breaker’s name. The first number “5” gives you a general idea what the interrupting rating is of the XYZ-508 circuit breaker at a voltage of 480 volts. This is a common presentation method because the widest used application voltage domestically is 480 volts. The last two numbers, “08” in this case, usually tell you the maximum continuous current rating of the circuit breaker. XYZ-508 can, therefore, carry 800 amperes continuously, and interrupt 50,000 amperes at 480 volts. B: This column outlines specifically the maximum continuous current the circuit breaker will carry. Notice that circuit breaker type XYZ-616 in the example table will carry a maximum continuous current of 1600 amperes. Notice also that the last two numbers of the circuit breaker type XYZ-616 (“16”) give you the same information, with 16 meaning 1600. Take the time to make this same comparison with circuit breaker type XYZ-632. C: Notice that the rest of this table is devoted to the interrupting capabilities in amperes of the different circuit breaker types at different application voltages. Also notice that the application voltages listed are: • 208-240 volts • 480 volts • 600 volts The nominal voltage range for the ANSI market is 208 to 600 Volts AC at a frequency of 50 or 60 hertz. Get comfortable with seeing these voltages when talking about ANSI rated low voltage power circuit breakers. D: You will notice that these two columns are labeled differently. The first column entitled “With Instantaneous Trip” outlines the interrupting capabilities of each circuit breaker frame at the different application voltages. These ratings are applicable when the circuit breaker’s trip unit provides instantaneous protection. Page 34 Low Voltage Power Circuit Breakers In other words, the circuit breaker can be applied to safely handle faults of the magnitudes shown. You will also notice in the column entitled “Without Instantaneous Trip” that some of the interrupting ratings are somewhat lower than the left column under 208-240 volts. These ratings are the magnitudes that the circuit breaker can tolerate safely for a short delay period of time (30 cycles) before opening at the short delay current ratings shown. This might sound like a contradiction. It really is not for a number of reasons. Consider the following points. 1. You will recall from material presented earlier that a low voltage power circuit breaker’s short time rating is normally the same as its interrupting rating. The key word here is normally. The partial ratings table being considered here already indicates that there are some very limited times when a low voltage power circuit breaker could have a higher interrupting rating if it has instantaneous protection versus just short time protection and no instantaneous. This was probably the result of a conscious decision to meet some very specific application requirement for a particular customer or industry, knowing the fact that a circuit breaker had to have instantaneous to be applied at these somewhat higher ratings. 2. The fact still remains that low voltage power circuit breakers must be and are only applied in keeping with their nameplate rating. This, in almost all cases, shows the interrupting rating and the short time rating to be the same. When electrical systems are being considered, fault calculations are done to determine the maximum fault current a system can experience. Low voltage power circuit breakers are then selected with ratings that are able to deal successfully and safely with the worst case fault scenario calculated. In other words, if a low voltage power circuit breaker with an adequate short delay current rating is applied, it will stay closed for the appropriate short time no matter what. This is true because it will not see (experience) more that it was designed to safely handle. End of that part of the story. 3. On the other hand, a low voltage power circuit breaker, which is already in the open position, will trip open instantaneously if an attempt is made to close the breaker on an existing fault. This safety feature prevents damage that could result from closing on a fault. Today, this feature is normally accomplished through circuitry which is part of the trip unit. This self protecting circuitry is often called a discriminator circuit or may be called a making current release in newer designs like Magnum DS. Its purpose has nothing to do with a circuit breaker that is already closed and functioning. For now, how this feature is technically accomplished will not be discussed. Just be aware that such a feature exists with low voltage power circuit breakers. Future training material specific to a particular low voltage power circuit breaker design will discuss just how it is accomplished. Remember: • Low voltage power circuit breakers are applied at their nameplate ratings. • Low voltage power circuit breakers are sized and selected for application to handle the maximum fault that could be encountered where they are applied. • Low voltage power circuit breakers are provided with a means to trip (open) instantaneously if they are closed in on an existing fault. E: Let’s just briefly take a look at the footnote. It tells you that these ratings are also the short time ratings of the circuit breaker. The material in D was discussed Page 35 Low Voltage Power Circuit Breakers as though we already knew these were short time ratings, and we did. Suppose we did not know that fact and failed to read the footnote. We would not be as informed as we should be for the proper circuit breaker selection. It could be like making the selection blindfolded. Be sure to read the footnotes. IEC Example ANSI and IEC Example IEC Example - An IEC example similar to the one just presented will not be offered here. Ratings tables and their appearance as to how data is presented can change from country to country and even manufacturer to manufacturer. The information presented, however, is usually similar. You should be aware of some of the noticeable differences in the presented data, and start now to become familiar with IEC rated breakers. For now, consider the following to get started: • The voltage range for the international market is 380 through 690 Volts AC at a frequency of 50 or 60 hertz. • The general continuous current range for low voltage power circuit breakers is 800 through 6300 amperes. • The voltage and current abbreviations and names are different, such as: Ue – application voltage, such as 380 or 690 volts. In – rated current such as 800 or 6300 amperes. Ics – rated service short circuit breaking capacity. Icu – rated ultimate short-circuit breaking capacity. Icw – rated short time withstand current (similar to the ANSI short time rating and the circuit breaker is expected to function properly again after having dealt with the Icw). Let’s make a quick comparison from a presentation standpoint. Keep in mind, the important things are: 1. Will the circuit breaker being considered do the job? 2. Will the circuit breaker being considered meet the standards in effect where the circuit breaker is to be used? It is not possible to simply take a product designed and tested to one standard (ANSI or IEC) and certify it to the other standard. A manufacturer must undertake a concerted design effort to satisfy both standards individually. Breaker Frame (A) Rated Voltage (V) Interrupting (kA) IEC 800 - 2000 415 690 480 600 40 or 65 or 130 40 or 65 or 85 42 or 100 or 200 42 or 100 or 200 ANSI 800 - 1600 This is by far not an all inclusive example. It is only intended to draw some simple ANSI and IEC comparisons between some of the most common selection points that must be considered when selecting low voltage power circuit breakers. You can see that although not exactly the same, it is primarily a matter of familiarization. 3. Operation Method - As discussed earlier, low voltage power circuit breakers are either manually or electrically operated. You must always specify the method of operation. At some point, you will need to know the secondary control voltage being used for an electrically operated circuit breaker. Even if the circuit breakers are manually operated, it is a good idea to find out the sec- Page 36 Low Voltage Power Circuit Breakers ondary control voltage. The control voltage is necessary for the final selection of a number of items, not just electrically operated circuit breakers. 4. Accessory Items - Many of the common accessory items associated with low voltage power circuit breakers were discussed earlier. You have to be alert for these items in a specification or ask the customer if any are required. A determination can then be made if a compatible accessory is available to meet the need. Make a list of the required accessories and the specific requirements that are appropriate for them, such as control voltage, number and types of contacts and overall function. 5. Mounting Method - You will need to know whether the breakers will be fixed mounted or drawout. Always check to see if there are any special requirements for either configuration. Special Selection Factors There may not be special conditions to consider, although this should be determined as soon as possible. You may be able to deal with certain special conditions and others might call for assistance from the manufacturer. Do not hesitate to ask for help. Some conditions or requirements to look for that might not be considered standard are: • High or low ambient temperatures • Moist or corrosive atmospheres • Altitude • High shock conditions • Unusual circuit breaker mounting conditions Page 37 Low Voltage Power Circuit Breakers Review 3 Answer the following questions without referring to the material just presented. 1. Of the two most common low voltage power circuit breaker mounting methods, the fixed configuration is most commonly used because it is less expensive. TRUE FALSE 2. When a drawout type low voltage power circuit breaker is in the “Connected” position, both _______________ and _______________ electrical connections are made. 3. If you were called upon to select a low voltage power circuit breaker, name at least five selection factors, standard or special factors, you might consider during the selection process. ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ 4. In a low voltage power circuit breaker ratings table, the “Frame Size” indicates the circuit breaker’s interrupting rating in amperes. TRUE FALSE 5. The nominal voltage range for low voltage power circuit breakers in the domestic market governed by ANSI Standards is _______________ to 600 Volts AC. 6. In terms of the international market governed by IEC Standards, Ue stands for the _______________ _______________, such as 415 volts. 7. In today’s global market, standards are usually so similar that a low voltage power circuit breaker designed and tested to IEC Standards can simply be certified to ANSI Standards and vice versa, without the need for additional testing. TRUE FALSE 8. A low voltage power circuit breaker is always provided with instantaneous protection against closing in on a fault current. TRUE FALSE 9. Low voltage power circuit breakers are sized, selected, and applied to safely handle the _______________ fault current it could possibly be exposed to. 10. Circle the letter next to the testing standard that most influences the design and testing of low voltage power circuit breakers used in the United States. (a) ANSI C50.51 (b) UL1866 (c) IEC 947-2 (d) ANSI C37.50 Page 38 Low Voltage Power Circuit Breakers Advanced Low Voltage Power Circuit Breakers The Magnum DS Family of low voltage power circuit breakers is not an extension of any other low voltage design (Figure 36). It is at the forefront of technology and development. For this reason, it is an excellent design to discuss when certain specific examples are required in this module. Keep in mind, however, all low voltage power circuit breakers do not necessarily offer as many features or use the same advanced technology as Magnum DS. Even though this might be the case, it does not mean that another design does not qualify as a low voltage power circuit breaker, or that there are not other capable low voltage power circuit breakers. Figure 36. Magnum DS Family of Low Voltage Power Circuit Breakers 2 Frame Sizes 800 Through 5000 Amperes) Magnum DS is a low voltage power circuit breaker. It is built and tested to all applicable ANSI Standards for low voltage AC power circuit breakers and Underwriter’s Laboratories Listed. Because of its flexible design, an International Electrotechnical Commission rated version of Magnum DS is also available to address international requirements. This IEC version is called Magnum. Everything that is expected of an ANSI rated low voltage power circuit breaker is delivered by Magnum DS, and then some. If you think this sounds a bit biased, it is. Eaton Electrical is justifiably proud of Magnum DS, and as you learn more and more detailed information about low voltage power circuit breakers, you will most certainly agree. You will recall a discussion of the areas that might set a low voltage power circuit breaker apart from other types of low voltage circuit breakers. Namely: • Method used to make and break circuits • Ratings • Construction/Maintainability • Integrally Mounted Trip Units • Operating Mechanisms • Testing You were initially introduced to the primary factors that make the low voltage power circuit breaker unique. Other factors and methods that were rather common with low voltage power circuit breakers but not necessarily unique were also discussed. You will revisit a number of the areas just mentioned. Each topic discussed, however, will be presented in more detail with special emphasis placed on those factors that set the low voltage power circuit breaker apart from other types of low voltage circuit breakers, such as molded case and insulated case circuit breakers. The general topics to be discussed are: • Standards and Testing • Construction Methods Page 39 Low Voltage Power Circuit Breakers • Ratings and Performance • Operational Techniques • Integral Trip Unit • Applications • Low Voltage Power Circuit Breaker Summary The last section reiterates many of the facts learned with special attention given to the unique factors associated with low voltage power circuit breakers. This summary can serve as a review and a future quick reference. Standards and Testing The standards that are applicable to low voltage power circuit breakers and the testing involved to prove compliance by a specific low voltage power circuit breaker design are in Module 5 and previously in this module. You learned from those discussions that standards and testing go to the heart of the matter. This is true from three very important standpoints: 1. This is the industry’s determination as to whether or not a particular circuit breaker design is capable of meeting a wide range of published operational and physical requirements. 2. The proven and stated compliance to specific standards tells potential users that the equipment from the manufacturers under consideration all meet certain basic standards, which makes the user’s evaluation process much simpler. Once this determination is made, a particular manufacturer can still gain an evaluated advantage by offering additional unique features and/or an operational design approach preferred by the user. 3. It is a solid way of defining specific types of circuit breakers within a larger general grouping. For example: The larger general grouping is “Low Voltage Circuit Breakers.” Specific types within the Low Voltage Circuit Breaker grouping would be “Low Voltage Power, Insulated Case, Molded Case and Miniature.” As you can see, when a specific type circuit breaker is specified, such as a low voltage power circuit breaker, the specifier already knows what the base expectations are from each manufacturer. You will recall, from both Module 5 and previous sections, a map of the world showing the standards most influential in different parts of the world (Figure 37). It bears revisiting the map again to emphasize the importance, in today’s global economy, of having flexible designs capable of complying with all major standards around the world. In this module the emphasis will be primarily on ANSI and IEC Standards. You should never lose sight of the fact, however, that there are a number of other standards that can play a critical role in determining what equipment is acceptable for application in a given area of the world. Even local and/or individual city codes and requirements may have to be considered. Page 40 Low Voltage Power Circuit Breakers Figure 37. Most Influential Standards Worldwide In previous modules, references other than ANSI and IEC were made with respect to standards and testing, such as UL, IEEE. There is a strong relationship between ANSI, UL and IEEE. As a matter of fact, you will notice in manufacturer’s publications for low voltage power circuit breakers and even low voltage metal enclosed switchgear references made to all. The following two samples are typical statements you might encounter when reading publications for both the power circuit breaker and the metal enclosed switchgear: Typical Low Voltage Power Circuit Breaker Statement: “Type XYZ low voltage power circuit breakers are UL listed, and built and tested to applicable NEMA, ANSI, IEEE and UL standards (ANSI C37.50, C37.13, UL 1066).” Typical Low Voltage Metal Enclosed Switchgear Statement: “Type XYZ low voltage metal enclosed switchgear conforms to NEMA SG3, NEMA SG5, ANSI C37.20.1, ANSI C37.51 and UL1558.” It may seem to you like a confusing web at this point. Once the relationship is understood, it will be clear as to why these references are made. There will be no detailed discussion of the standards relating to low voltage metal enclosed in this module, only those relevant to the power circuit breaker. Keep in mind, however, it works the same way. The standards state different requirements for the different pieces of equipment, but the intent is the same - an uncompromised piece of equipment with proven performance capabilities. For the purpose of this section, let’s identify the key players as a minimum and elaborate on a couple. This should not be considered as a substitute for the standards themselves. For a full explanation of any standard, consult the standard itself for details and proper conformance instructions. IEEE (Institute of Electrical and Electronic Engineers) • IEEE is an objective technical organization made up of manufacturers, users, and other general interest parties. • IEEE defines technical definitions, technical requirements, temperature limits, altitude correction, insulation limits, and service conditions. For electrical equipment, including switchgear, it supplies the test requirements for the low voltage power circuit breaker construction and test standards, namely ANSI C37.13 and ANSI C37.50. NEMA (National Electrical Manufacturers Association) • NEMA is an electrical equipment manufacturer only organization, such as Eaton Electrical, General Electric, and Square D. NEMA defines preferred ratings, related requirements, and application recommendations. • NEMA Standards normally cover additional information about a product of specific interest to the manufacturing community, which the American Page 41 Low Voltage Power Circuit Breakers National Standards Committee does not include in its scope. NEMA votes on the suitability of standards for ANSI designation and adopts, by reference, the appropriate American National Standards. • The applicable low voltage power circuit breaker NEMA Standard is SG-3, and it adopts ANSI C37.16 in its entirety. • UL is an independent, non profit, third party testing and certification company headquartered in Northbrook, Illinois. It functions to develop standards and to insure that equipment meets relevant published standards. • UL also adopts otherwise recognized standards, and, in some instances, develops their own independent certification tests. In the case of low voltage power circuit breakers, the UL Standard is UL1066, which was previously mentioned. UL1066, entitled “Standard for Low Voltage AC and DC Power Circuit Breakers Used in Enclosures,” calls for testing to demonstrate compliance with ANSI/IEEE C37.13 without change. A UL Label is affixed to the circuit breaker to indicate successful compliance. CSA (Canadian Standards Association) • The Canadian Standards Association is in the category of a major international standard. Its design and testing requirements are essentially the same as required by UL. In fact, harmonization programs between UL and CSA are ongoing to close the gap and/or eliminate differences. The Canadian Standards Association standard most associated with low voltage power circuit breakers is CSA 22.2-31 for Switchgear Assemblies. ANSI (American National Standards Institute) You were briefly introduced to ANSI. Now let’s take the time to get to know ANSI much better because ANSI is the key to low voltage power circuit breakers. It is the recognized North American Authority on equipment standards. UL (Underwriters Laboratories Inc.) ANSI’s Purpose - ANSI is a nonprofit, privately-funded membership organization that coordinates the development of U.S. voluntary national standards, called American National Standards. It is also the U.S. member body to the non-treaty international standards bodies, such as the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC). ANSI serves both the private and public sectors’ need for voluntary standardization. ANSI’s History - The institute was founded in 1918. It was prompted by the need for an umbrella organization to coordinate the activities of the U.S. voluntary standards system and eliminate conflict and/or duplication in the development process. The institute serves a diverse membership of over 1300 companies, 250 professional, technical, trade, labor and consumer organizations, and some 30 government agencies. A simple yet very typical example of why ANSI came into existence can be related to the low voltage power circuit breaker. In the early days of low voltage power circuit breaker development, manufacturers and users were building and applying equipment with little thought given to uniform performance or design standardization. The C37 standard was developed and implemented to establish minimum performance standards for the circuit breaker and its physical design features. The standard was meant to address even the smallest detail. A close button, for example, might not say close on it or it varied in color from one manufacturer to the next. These inconsistencies in design made products confusing for use by customers. This might seem to be one trivial point, but you can imagine how big the problem would be when compounded with every aspect of a low voltage power circuit breaker. ANSI’s Functions - ANSI functions to: Page 42 Low Voltage Power Circuit Breakers • Coordinate the self-regulating, due process consensus voluntary standards system • Administer the development of standards and approve them as American National Standards • Provide the means for the U.S. to influence development of international and regional standards • Disseminate timely and important information on national, international and regional standards activities to U.S. industry These standards are intended to provide guidance, direction, and requirements. Compliance to these standards does not, nor is it meant to limit manufacturers in construction, materials, or the technology used. Specifically relating to power circuit breakers, ANSI standards are written by either the IEEE Switchgear Committee or NEMA. The electrical standards written by both of these organizations are reviewed and clarified by the Accredited Standards Committee (ASC) for power switchgear and power circuit breakers. The ASC standards group is entitled C37. ANSI Defined Standards for Low Voltage Power Circuit Breakers - Although there are a multitude of ANSI standards relating to many different types of equipment, only those standards relating to low voltage power circuit breakers are outlined here. The intent is just to make you aware of just how many are applicable to just one category of electrical equipment. You will notice that each standard is followed by a specific year. As additions or changes are made to a standard, the year is altered to indicate the latest version. Obviously, staying on top of the latest version is an ongoing process. You should also note that each standard is given a broad word definition. 1. ANSI/IEEE C37.13-1990, “Low Voltage AC Power Circuit Breakers Used in Enclosures” 2. ANSI C37.16-1997, “Preferred Ratings Related Requirements and Application Recommendations for Low Voltage Power Circuit Breakers and AC Power Circuit Protectors” 3. ANSI C37.17-1997, “Trip Devices for AC and General Purpose DC Low Voltage Power Circuit Breakers” 4. ANSI C37.50-1989, “Test Procedures for Low Voltage AC Power Circuit Breakers Used in Enclosures” 5. IEEE Standard C37.100-1992, “IEEE Standard Definitions for Power Switchgear” 6. IEEE C37.20.1-1993, “Standard for Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear” 7. ANSI C37.51-1989, “Standard for Switchgear - Metal-Enclosed Low Voltage AC Power Circuit Breaker Switchgear Assemblies - Conformance Test Procedures” 8. NEMA SG-3-1981, “Low Voltage Power Circuit Breakers” 9. UL1066-1993, “Standard for Low Voltage AC and DC Power Circuit Breakers Used in Enclosures” This lengthy list gives you some indication why it is a matter of practicality when a manufacturer states that a piece of equipment is built and tested to all applicable Page 43 Low Voltage Power Circuit Breakers NEMA, ANSI, IEEE and UL standards. It was also mentioned that a great deal of referencing to other standards takes place within the body of a specific standard. Successful testing and compliance with respect to one standard often includes automatic compliance with other standards. It is worth repeating one of the examples given. Example: ANSI C37.13 details the physical attributes, such as Stored Energy, that a low voltage AC power circuit breaker must have to comply. At the same time, ANSI C37.50 references C37.13 and details how the described circuit breaker should be tested. The key here is that successful testing in keeping with ANSI C37.50 brings with it compliance to C37.13. There is no need to mention C37.13, when it is stated that the circuit breaker complies with C37.50. IEC (International Electrotechnical Commission) IEC presides over the standardization of equipment for a number of other parts of the world. In view of today’s global markets, there is a significant amount of interaction between the organizations just discussed and IEC. IEC 947-2 is a multi-part international testing standard covering a variety of devices, including circuit breakers of all types. It is entitled “Low Voltage Switchgear and Controlgear.” As far as IEC is concerned, every device tested to IEC 947-2 must be subjected to several test sequences in order to be approved. Because IEC 947-2 covers both low voltage power circuit breakers and low voltage molded case circuit breakers, the exact test sequences performed are not necessarily the same. They depend on the category of the device. Category A Device - In general, this is a device without a short time Withstand Rating, such as a molded case circuit breaker. Category B Device - This is a device with a short time withstand rating, such as a power circuit breaker and certain molded case circuit breakers. Typically, these devices are referred to as Air Circuit Breakers or just ACBs. IEC 947-2 was developed with assistance from members of the U.S. National Committee. Still, a number of significant differences exist between IEC 947-2 and applicable ANSI standards. In particular, the various ratings of a circuit breaker can differ when tested to each standard. Therefore, any product comparisons made between products tested to these different standards (domestic versus international) should only be made with a thorough understanding of the differences. Standards Conclusion This might seem to be a monumental amount of information about standards. It is only the tip of the iceberg. This is not to imply that you must be an expert on standards to deal with power circuit breakers. You can, however, begin to appreciate just how much effort, investment, and plain hard work goes into being able to legitimately print in a document a statement such as: “Magnum DS Low Voltage Power Circuit Breakers are UL Listed and built and tested to all applicable ANSI Standards.” Keep in mind that all these standards establish minimum requirements. There is nothing prohibiting a manufacturer from exceeding standards by offering additional features and/or using newer and improved operational techniques for more efficient and higher levels of performance. Magnum DS does just that in a number of areas. The majority of the remaining discussions in this module will be presented as they relate to applicable ANSI Standards. Remember, however, that other standards do exist in other parts of the world. They must be complied with to participate in the international segment (Figure 38). Page 44 Low Voltage Power Circuit Breakers Figure 38. Circuit Breaker Identification Low Voltage Power Circuit Breaker C37.50 Testing Testing of a low voltage power circuit breaker in keeping with required ANSI Standards provides the first glimpse at what makes a low voltage power circuit breaker unique. Remember, low voltage power circuit breakers are applied at or below their nameplate ratings. That nameplate rating is a result of having successfully completed a series of rigorous tests. This is referred to as a 100% rating. Although every detail of the testing will not be covered here, you will have an appreciation for just how demanding these ANSI defined tests are for low voltage power circuit breakers. The tests will be described as four test sequences. It should be pointed out here that all tests are performed using a Drawout circuit breaker in its enclosure for each frame size. The first three test sequences are similar in many ways to the tests performed on other types of low voltage circuit breakers, such as a molded case circuit breaker. It is the fourth test sequence performed on a low voltage power circuit breaker that differentiates the power circuit breaker from other types of circuit breakers. Note that all the following test sequences, except for Test Sequence 4 in which the circuit breaker has no Trip Unit, are preceded and followed by a calibration test and dielectric check. Test Sequence 1 - This test sequence consists of a temperature rise test, an overload switching test, and then a short circuit test. The circuit breaker is equipped with an instantaneous trip. 1. The circuit breaker is loaded to 100% of the maximum rating of the frame size (in normal enclosure) until the temperature is constant. The standard lists the maximum permissible temperature rises at various parts of the circuit breaker. 2. The circuit breaker is then subjected to number of opening operations on over-load switching. 3. The circuit breaker is then given a 3-phase short circuit test at its maximum voltage rating, which is 635 volts for this 600 volt rated circuit breaker. The short circuit current in this case can be no less than the 600 volt interrupting capacity of the circuit breaker being tested. The three maximum voltages used during testing and typically listed on the nameplate are listed below along with their corresponding application voltages: Maximum Voltage Application Voltage 635 volts 508 volts 254 volts 600 volts 480 volts 240 volts 4. The short circuit test consists of initiating current through the closed circuit breaker, causing it to trip. After 15 seconds, the circuit breaker is re-closed on the fault, and then allowed to trip open to clear the fault. This is known as an O-CO (open-close open) test. 5. The short circuit test is followed by a calibration check and a dielectric test. Test Sequence 2 - This test sequence consists of a series of short circuit tests on a circuit breaker equipped with selective tripping (no instantaneous). Page 45 Low Voltage Power Circuit Breakers 1. Once again, all short circuit tests are preceded by a dielectric test and a calibration test. After the interruptions, the circuit breaker is given another dielectric test and the calibration is again checked. 2. Each short circuit test is an O-CO test meaning that the circuit breaker interrupts the full fault current twice. 3. After the 3-phase short circuit tests are completed at different prescribed voltages, single phase tests are performed. A new circuit breaker may be used for each test, or each test may be done on different poles of the same circuit breaker. 4. One single-phase test is done at each of the same three maximum voltage ratings used for the three-phase tests (635, 508 and 254 volts) at the appropriate Interrupting Rating for that voltage. Test Sequence 3 - This test sequence includes tests of mechanical and electrical endurance. 1. A circuit breaker is calibrated, given a dielectric test, and subjected to a large number of operations. Some of the operations are at no load and some at full load. 2. The required number of operations varies by circuit breaker frame size. 3. After the endurance test, the same circuit breaker is given a full 3-phase OCO short circuit test at 635 volts and a dielectric withstand test. The required number of operations for the endurance test just described is about the same for larger frame power circuit breakers and somewhat higher for smaller frame power circuit breakers compared to molded case circuit breaker endurance tests. For the sake of comparison, refer to the two endurance ratings tables, one for power circuit breakers and one for molded case circuit breakers (Figures 39 and 40). Figure 39. Low Voltage Power Circuit Breaker Endurance Ratings (Per C37.50) Figure 40. Low Voltage Molded Case and Insulated Case Circuit Breaker Endurance Ratings (Per UL 489) Test Sequence 4 - This test sequence includes a short time current (withstand) test. Molded case and insulated case circuit breakers are not usually subjected to this type of test and, therefore, have no full 30 cycle Short Time Rating. This is one of the key differences. 1. For this test, the circuit breaker does not have a trip unit or the trip unit is disconnected. During the short-circuit testing, the circuit breaker can be tripped instantaneously by a shunt trip. Page 46 Low Voltage Power Circuit Breakers 2. The circuit breaker is closed and then energized at its full short time current rating. The short time rating is usually equal to the 600 volt short circuit current rating. 3. The current is left on for 30 cycles (1/2 second), then off for 15 seconds, then back on for another 30 cycles. The circuit breaker remains closed during this test sequence. 4. After the short time current (withstand) tests, the same circuit breaker is given a 3-phase short circuit test sequence at full short circuit current rating and 635 volts. The circuit breaker is opened as quickly as possible by the shunt trip, which is energized at the same instant the power is applied. The intent is to force the circuit breaker to open during the worst case conditions (full current asymmetry). This is where the short time rating for the circuit breaker comes from. 5. After the final test, the circuit breaker calibration is checked and given a dielectric withstand test. During Test Sequence 4, the circuit breaker is subjected to tremendous physical forces from the magnetic fields and to severe heating effects from the current. Think about it. Both the magnetic forces and the heating vary with the square of the current (Figure 41). For example, a 4000 ampere frame low voltage power circuit breaker at 85,000 amperes is subjected to forces and heating more than 450 times normal for each 30 cycle test. It is quite awesome. Figure 41. Magnetic Force Versus Current Page 47 Low Voltage Power Circuit Breakers Review 4 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. ANSI is the recognized North American Authority on equipment standards. TRUE FALSE 2. Cutler-Hammer’s Magnum DS low voltage power circuit breakers are built and tested to all applicable ANSI Standards. The IEC Standards version of this Cutler-Hammer low voltage power circuit breaker is called ___________________. 3. Magnum DS low voltage power circuit breakers carry a UL Label which indicates the circuit breaker’s successful compliance with UL Standard Number ___________________. 4. The primary North American testing procedures for low voltage power circuit breakers used in an enclosure are stated in ANSI Standard C37._____ _____. 5. All low voltage circuit breakers have full 30 cycle short time rating because all of them must pass a momentary rating test. TRUE FALSE Page 48 Low Voltage Power Circuit Breakers Construction Method You learned that low voltage power circuit breakers are essentially an assembly of parts on a metal frame or in an encased housing of insulating material. Because the makeup of both approaches was adequately discussed, the details will not be repeated. One point, however, that should be repeated centers around what applicable standards are required relative to the construction method. The frame construction used must hold all the circuit breaker parts in place and be capable of withstanding the tremendous physical forces and severe heating effects a power circuit breaker could be subjected to while performing its function. Standards do not specify the exact nature of the construction or the construction material. Those decisions are left to the circuit breaker manufacturer. Obviously, the construction method and materials used must result in a strong, rigid design. For many years, the preferred approach was the open type metalframe which had a number of pieces welded and/or bolted together. With the significant technological strides made in the areas of insulating material and molding processes, versatile rigid frame housings of high strength engineered thermoset composite resins have become available. Not only does the rigid frame housing type low voltage power circuit breaker meet the stringent requirements of ANSI, it exceeds them in a number of instances. The Magnum DS circuit breaker uses a 3-piece construction (Figure 42): A 2-piece engineered thermoset composite resin case completely encloses the current paths and arc chambers. The operating mechanism sits on the front of the case and is electrically isolated from the current contact structures. It is in turn covered by an insulating front cover. Figure 42. Magnum DS Low Voltage Power Circuit Breaker Rigid Frame Construction (Right Side View) The rigid frame construction results in a more compact, lighter weight low voltage power circuit breaker. Previous circuit breaker designs with many parts that were once produced and attached individually to the frame can now be molded as an integral part of the rigid frame. The overall strength and rigidity of the engineered thermoset composite resin design can even contribute to higher performance capabilities by the power circuit breaker. This was the result with Magnum DS which has higher short time ratings (withstand) than previously available power circuit breakers, along with higher interrupting capabilities. In the way of review, remember that the short time rating consists of the following two components: • Short delay current component (kA) Page 49 Low Voltage Power Circuit Breakers • Short delay time component (cycles) In addition to the improved performance characteristics just mentioned, the rigid frame housing type low voltage power circuit breaker has individual arc chambers that (Figure 43): • Insulate and isolate Arcing from other poles, the rest of the circuit breaker, and personnel • Provide support for the current path pole assembly Figure 43. Top Rear View Magnum DS Power Circuit Breaker Showing Arc Chambers with One Arc Chute Removed Ratings and Performance The rigid frame housing also provides for the rigid mounting of circuit breaker components which: • Improves the mechanism’s life by eliminating frame deflection • Provides for the consistent operation of mechanism • Eliminates the need for mechanism adjustments Some of the most useful information about a low voltage power circuit breaker can be found in its ratings table. Ratings tables were briefly covered during the Circuit Breaker Selection discussion. The ratings published in these tables are backed up by testing as outlined in applicable standards. These ratings tell quite a story. They indicate how a particular circuit breaker will perform during a given set of application circumstances. In a similar regard, the ratings indicate what circuit breaker should be selected for a specific application. Although ratings tables from different manufacturers often look similar and even reflect many of the same ratings, it is not a good idea to assume that all low voltage power circuit breakers have the same ratings. Get into the habit of reviewing different tables and comparing the published ratings. There is no room for unexpected surprises in circuit breaker selection. Figure 44. Example ANSI Ratings Table Page 50 Low Voltage Power Circuit Breakers To demonstrate the value of making these comparisons, let’s once again look at a partial ANSI ratings table, contrasting the ratings for one type low voltage power circuit breaker (Type XYZ) with those of the Magnum DS low voltage power circuit breaker (Figure 44). Once you have taken the time to look the table over a bit, several comparison examples will be discussed. Keep in mind that this table only presents excerpts and is not intended to show the ratings of all available circuit breakers for an entire line. It can be assumed that both circuit breakers used in the examples meet all applicable ANSI standards for low voltage power circuit breakers. The comparisons to be discussed are identified in the table by a circled letter, for example. A - Notice first that the ratings given for the Magnum DS power circuit breaker apply for all system voltages. Ratings for other power circuit breakers can vary by voltage. Uniform ratings across all application voltages for the 3200 ampere frame circuit breakers and below simplifies the selection process. Interrupting ratings higher than 100,000 amperes are available with Magnum DS frame sizes above 3200 amperes for certain application voltages. Therefore, the uniformity is not totally maintained on the larger frame circuit breakers. B - The short time rating (withstand) for Magnum DS once again applies across the entire range of application voltages, while the other is only applicable to 480 volts. In addition, notice that Magnum DS has higher short time current ratings than does the other power circuit breaker. A broader range and higher short time ratings allow Magnum DS to be applied in systems with higher available short circuit currents while maintaining full selectivity. C - An interrupting rating of 100,000 amperes is available with 3200 ampere frame and below Magnum DS circuit breakers at all application voltages. This rating is not at all available with the other power circuit breaker. Notice further that the short time rating is 85,000 amperes (3200 amperes and below). What does this accomplish? 1. These ratings mean that this particular Magnum DS rating has a hefty short time (withstand) capability and can withstand a short circuit of 85,000 amperes for the full 30 cycles required by ANSI. 2. It also means that this Magnum DS rating can be applied on a system that could experience a short circuit as high as 100,000 amperes. The circuit breaker would be selective up to 85,000 amperes, and would open instantaneously from 85000 to 100,000 amperes. D - One more area on a ratings table to be alert to is with and without instantaneous trip. It is possible for some circuit breakers to have higher interrupting ratings if they can trip instantaneously. In those instances, the interrupting rating might be lower if the circuit breaker is required to provide short time protection. This is not the case, however, with Magnum DS at interrupting ratings of 85,000 amperes and below. As a general rule, the ratings for most ANSI rated low voltage power circuit breakers are similar where system requirements are less stringent. When the application requirements become more stringent and/or special, the capabilities of different power circuit breakers begin to differ. Look at ratings tables closely. They have a story to tell. Extended Interrupting Ratings: Interrupting ratings can be extended up to 200,000 amperes by providing a combination of a low voltage power circuit Page 51 Low Voltage Power Circuit Breakers breaker connected in series with current limiting fuses (current limiters). This combination is provided on systems where the overload and switching functions of the circuit breaker are required, and available fault currents could exceed the interrupting rating of the circuit breaker by itself. For smaller frame circuit breakers, the current limiters usually are integrally mounted in the circuit breaker (Figure 45). For larger frame circuit breakers, the current limiters are usually mounted in a separate drawout truck and positioned adjacent to the circuit breaker. Figure 45. DSL II Fused Type Circuit Breaker (Side View) Altitude and Ratings: Low voltage power circuit breakers are applicable at their full voltage and current ratings up to a maximum altitude of 6600 feet (2000 meters) above sea level. When a circuit breaker is installed at higher altitudes, the ratings are subject to correction factors in accordance with ANSI Standards. Fortunately, you are not often faced with this situation. Even if you are, it probably has already been taken into account by the specifier. It is good, however, to be aware of such application exceptions. Current Waveforms and Ratings: The subject of current waveforms and their effect on circuit breaker ratings will not be discussed in great detail in this module. Once again this consideration is usually made by the specifier and taken into account when a particular circuit breaker is specified. You should be somewhat familiar with the concepts. If for no other reason, it could help to explain why a certain circuit breaker rating selection was made for a particular application. It will also be good background information later in this module when applications are discussed. You noticed in the ratings table just discussed that interrupting ratings and short time ratings were expressed in symmetrical amperes. For most discussions and selections involving low voltage power circuit breakers, this will be the case. Without getting into too much detail, it is important to know that there are two common ways to rate protective devices in amperes. These ratings are symmetrical and asymmetrical. The symmetrical and asymmetrical ampere ratings can be quite different for the same device. To clarify the significance of the two terms, let’s briefly discuss each individually. The graphic shown of a Symmetrical AC Current represents a fault current flowing in a circuit (Figure 46). The fault current has a sine wave shape and is symmetrical with respect to the horizontal axis. That is, the current rises and falls equally above and below the horizontal axis, so the shapes are symmetrical. The graphic shown of an Asymmetrical Current becoming Symmetrical represents an offset fault current wave (Figure 47). It rises above the horizontal axis considerably more than it goes below for the first few cycles. This wave is said to be offset from or asymmetrical with respect to the horizontal axis. This condition occurs in circuits containing reactance which are short-circuited at some time Page 52 Low Voltage Power Circuit Breakers other than when the current is passing through the zero point on the cycle. It occurs in all 3-phase circuits in one or more phases. When this happens, a DC current is superimposed on top of the AC current causing asymmetry. The DC component actually decays to zero within a short time after the fault occurs. The final decay of the DC component signifies a change from asymmetrical to symmetrical. How fast this actually happens depends upon the quantity relationship of reactance and resistance in the circuit, the X/R ratio. The more resistance in the circuit, the faster the DC component decays, or the larger the X/R ratio, the longer the decay time. Figure 46. Symmetrical AC Current Figure 47. Asymmetrical Current Becoming Symmetrical as DC Components Decay Continuing this discussion of current waveforms, let’s take a look at some background information. Low voltage power circuit breakers typically part their Contacts after several cycles of fault current, assuming there is no intentional time delay. In short, contact parting only begins once time delays are expired. The circuit breaker can be called upon to interrupt more than the symmetrical value of fault current, as calculated from the impedance of the circuit. This is because of the presence of the DC component just discussed. We will not discuss here why the degree of asymmetry can be different, just know that the degree can vary. What is of real importance is the rate at which the DC component decays and the change to symmetrical takes place. This rate, and hence the current value, can be related directly back to the ratio of circuit reactance to circuit resistance or the X/R ratio. For this reason, the X/R ratio is a significant and specified factor for standards testing. It is also an important ratio to know when selecting circuit breakers for application on a system. As long as the X/R ratio for the system does not exceed the tested X/R for the circuit breakers, you are home free. If the system X/R ratio exceeds the tested X/R for the circuit breakers, the circuit breakers would have to have their published interrupting capacity and short delay current capability de-rated. A circuit breaker with a higher interrupting capacity and higher short delay current rating might be needed to accommodated the de-rating factor. Page 53 Low Voltage Power Circuit Breakers As previously mentioned, these types of system determinations are normally made well ahead of time by the specifier or consultant, which is when the equivalent system short circuit rating is normally specified. For your information, the ANSI tested X/R ratio for power circuit breakers is 6.6. This 6.6 ratio was not always the case. As a matter of fact, power circuit breakers were not always rated in symmetrical terms. That is history and we will not discuss why a change was made from asymmetrical to symmetrical. At some point, the industry made the change and determined that an X/R ratio of 6.6 for power circuit breakers was typical, and would be a good base to work with for testing and application. At least all the manufacturers were working with the same standardized starting point. Now, when the calculated short circuit current X/ R ratio for a particular system is higher than the standard 6.6 X/R ratio for low voltage power circuit breakers, a table can be consulted to determine what de-rating factor should be applied to the circuit breaker’s interrupting rating to insure proper circuit breaker sizing and selection. To give you an idea of what these de-rating factors look like, refer to the partial table of low voltage power circuit breaker de-rating factors (Figure 48). Keep in mind that these considerations and decisions must be made for all types of circuit breakers, not just low voltage power circuit breakers. Before this discussion is concluded, let’s take a look a one simple example. Figure 48. Interrupting Rating De-Rating Factors for All Low Voltage Power Circuit Breakers Table Example: The total available fault current from all sources that this low voltage power circuit breaker could see was calculated to be 48,000 amperes symmetrical. For this example, we are only considering what circuit breaker could be used to deal instantaneously with a potential fault of this magnitude. From some selection chart you might select a circuit breaker with a 50,000 ampere interrupting capability. In this example that would not be a good selection because it has also been determined that the system X/R ratio is 9.94. You can see from the de-rating table that a 9.94 ratio equates to a de-rating factor of 0.937. This factor used on the circuit breaker’s interrupting capability of 50,000 amperes reduces it to 46,850 amperes, not sufficient to deal with the potential fault current of 48,000 amperes [50,000 x 0.937 = 46,850]. Obviously, a circuit breaker with a higher interrupting capability must be selected for this application. If a circuit breaker with an interrupting capability of 65,000 amperes is selected, you can see from the calculation that it would do the job [65,000 x 0.937 = 60,905]. Page 54 Low Voltage Power Circuit Breakers Review 5 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. The frame or housing of a low voltage power circuit breaker is not required by applicable standards to be manufactured from any specific type of material. The manufacturer of the circuit breaker makes that decision. TRUE FALSE 2. The short time rating of a low voltage power circuit breaker is also known as the ___________________ rating. 3. Two different components combine to make a low voltage power circuit breaker’s short time rating. One is the short delay time component and the other is the __________________ __________________ __________________ component. 4. All low voltage power circuit breakers meeting the same applicable ANSI Standards must offer all the same ratings. TRUE FALSE 5. Magnum DS low voltage power circuit breaker interrupting ratings are the same for all application voltages on 3200 ampere frame circuit breakers and below. TRUE FALSE 6. The highest interrupting rating available from any unfused 3200 ampere frame and below low voltage power circuit breaker is offered by Magnum DS. That interrupting rating is ___________________ amperes. 7. Two parts of the graphic below are labeled. One component has an arrow pointing to it but is not labeled. Label the unlabeled component next to the arrow pointer. 8. Use the information provided here to determine what would be the minimum interrupting capacity a low voltage power circuit breaker should have to safely deal with a maximum available fault current of 63 kA on an instantaneous basis. The system in which this circuit breaker will be applied has an X/R ratio of 6.59. Circle the correct multiple choice answer, (a), (b), (c) or (d). (a) 42,000 amperes interrupting capacity (b) 65,000 amperes interrupting capacity (c) 85,000 amperes interrupting capacity (d) Enough information is not provided to determine the answer Page 55 Low Voltage Power Circuit Breakers Operational Techniques Generally, all low voltage power circuit breakers use the same functional parts to accomplish their task. You learned earlier that all of them have: • a set of main and arcing contacts to isolate or connect circuits • a two-step stored energy mechanism to open or close the contacts • a mechanical and/or electrical mechanism to charge the springs • arc chambers (chutes) to extinguish any arcs formed during opening • the intelligence to operate automatically or respond to commands Does this mean that all low voltage power circuit breakers are virtually the same? No. You will recall that ANSI Standards provide for the minimum requirements to be classified as a low voltage power circuit breaker. In addition, the standards do not state how something must be accomplished, only what must be accomplished. It was already pointed out earlier in this module that ANSI Standards do not dictate the construction method. If there is a better way to accomplish the same results, do it. What differentiates one low voltage power circuit breaker from another are the design techniques used to accomplish the task. Techniques that can result in: • improved operational efficiency • better performance characteristics • higher ratings • additional features • smaller and lighter devices In short, the customer ends up benefiting by being able to do more and/or do it better by comparing and then using one circuit breaker over another. Let’s take a look at some of the design techniques in a little more detail. Primary Opening and Closing Contacts Low voltage power circuit breakers generally have separate arcing and main current carrying contacts. This does not necessarily mean, however, the arcing and main contacts are physically two separate pieces. On some designs, they are two distinct parts of the same assembly. On other designs, the arcing and main contacts are just different contact areas on the same contact. The arcing and main contacts are designed mechanically so that on closing, the arcing contacts make before the main contacts. On opening, the main contacts part before the arcing contacts. This type of construction ensures that arcing takes place on the more heat resistant arcing contacts. Because the damaging arcing takes place on the arcing contacts, the main contacts are protected and can be made of pure silver or a silver alloy. This main contact composition is much lower in resistance and minimizes the heat developed during operation. Contacts are usually maintainable and/or replaceable, a key feature for a low voltage power circuit breaker. A complete primary contact assembly generally consists of three primary parts (Figures 49 and 50): • Moving Contact Assembly • Stationary Contact Assembly • Operating Arm Page 56 Low Voltage Power Circuit Breakers Figure 49. DSII Type Primary Contact Assembly Mounted (Front View) Figure 50. DSII Type Primary Contact Assembly Mounted (Rear View) Moving Contact Assembly The moving contact assembly is hinged or pivoted in some manner within the circuit breaker permitting it to open and close as required. It is made up of a main contact and an arcing contact. 1. The moving main contact is connected to the load conductor through either a hinged or flexible connection. It also varies in size depending upon the amount of current. When it closes, it butts up against the stationary portion of the contact completing the circuit. It opens the circuit when it pivots in the opposite direction and breaks contact with the fixed portion. 2. The moving arcing contact makes first with its fixed counterpart upon closing, and separates last upon opening. It can be a Butt type design or a Finger (wedge) type design. Stationary Contact Assembly The stationary contact assembly is in a fixed (stationary) position within the circuit breaker. It is made up of a main contact and a fixed arcing contact or some part that acts as a fixed arcing contact. 1. The stationary main contact is rigidly connected to the line conductor. The contact itself is often a butt type contact, and varies in size depending upon the amount of current it is designed to carry. By butt contact, it is meant that a connection is made when the moving part of the contact butts solidly up against the stationary part of the contact. Page 57 Low Voltage Power Circuit Breakers 2. The stationary arcing contact can be a wedge type contact or a butt type contact. By wedge type contact, it is meant that the moving part wedges in between two fixed parallel arcing fingers (contacts). Operating Arm (Link) A rigid operating arm (link), usually made of an insulating material, is the connection between the moving contact assembly and the circuit breaker’s operating mechanism. It operates the moving contact assembly during the opening and closing process in conjunction with the operating mechanism. The operating link is sometimes considered to be part of the operating mechanism. Now that primary opening and closing contacts have been reviewed in a general way, let’s take a closer look at how all of this works together. We will review the innovative Magnum DS approach. Keep in mind, however, that all designs are not the same and some are more effective than others. Magnum DS Primary Contact System All low voltage power circuit breaker designs try, with varying degrees of success, to maximize the combination of two important design aspects: • Contact Finger Design and Movement • Natural Electromagnetic Laws The Magnum DS primary contact system features a very effective and efficient combination of these two design aspects. 1. The Magnum DS movable contact design centers around a single contact finger that performs both the main contact and arcing contact functions. These two functions are performed on different parts of the same contact finger. A highly conductive alloy pad is part of the copper contact finger and functions as the moving main contact. The upper portion of the same copper contact finger functions as the moving arcing contact. A complete movable contact assembly is merely a combination of a number of single contact fingers. The exact number of contact fingers required depends upon the frame size and interrupting rating of the circuit breaker (Figures 51 and 52). Figure 51. Graphic of Single Magnum DS Contact Finger Page 58 Low Voltage Power Circuit Breakers Figure 52. Graphic of Magnum DS Multi-Finger Configuration You learned that design efficiencies often separate one circuit breaker from another. The contact design used from one circuit breaker to another is a great example of just such a difference in efficiency. If a visual comparison is made between the Magnum DS moving contact assembly and its counterpart on a number of other low voltage power circuit breakers, one thing will be obvious - the difference in the total mass (Figure 53). This is especially true in the area of arcing contacts. The finger and wedge type arcing contact design, used on DS II for example, is not nearly as efficient at controlling an arc as the butt type arcing contact used by Magnum DS. Consequently, the finger and wedge design makes up for this shortcoming with additional mass. On the other hand, Magnum DS can reduce mass and weight because of its more efficient arc control. Figure 53. Magnum DS (Left) and DS II (Right) Moving Contact Assembly Comparison To simplify this discussion, let’s talk in terms of a single contact finger. Once you grasp the concept in terms of one contact finger, it will not matter how many fingers are needed to carry the current. The design concept remains constant. Improved overall reliability is the result of this simple design. The opening and closing action of the single contact finger can best be described as a “Heel-Toe” motion (Figure 54). The main contact portion can be viewed as the “Heel” and the arcing contact portion the “Toe.” If you rock your foot forward and backward from heel to toe and toe to heel, you demonstrate the movement of the contact design. Notice as your foot rocks, there are times when only the toes touch, times when only the heel touches, and a brief time when they touch simultaneously. Page 59 Low Voltage Power Circuit Breakers Figure 54. “Heel-Toe” Movement When the circuit breaker is closed, the “Heel” (main contact portion) is in contact with the stationary contact and carrying current (Figure 55). At the same time, the “Toe” (arcing contact portion) is separated from the stationary arcing contact (arc runner). At this point, it is similar to your foot resting on its heel with your toes off the floor. Under short circuit conditions, the force on the “Heel” (main contact portion) to keep the main contact closed is enhanced by the positioning of the fulcrum point, which is located in close proximity to the contact, and electromagnetic force on the moving conductor. As the circuit breaker is called upon to open, the “Toe” touches down before the “Heel” lifts off. During the brief time that both the “Heel” and “Toe” are in contact with their fixed counterparts, the current that is present commutates (changes its path) from the main contact portion of the contact finger to the arcing portion. When the “Heel” (main contact portion) lifts off, any remaining current is driven to the ‘Toe” (arcing contact portion) by the arc voltage produced. Remember, the voltage drives the current. The path the current travels is very short and the transfer is made quickly. The result is very little arcing damage to the ‘Heel” (main contact portion). This protection of the main contacts is a primary reason why the main contacts have a longer life, and can be made of higher conductive materials. This use of purer conductive materials results in better thermal performance. Once the main separation is made, it is followed by separation of the “Toe” (arcing contact portion) where the main arc is created. How the circuit breaker deals with the arcing that takes place will be discussed when Arc Chutes are discussed. Page 60 Low Voltage Power Circuit Breakers Figure 55. Magnum DS Heel-Toe Contact Action Cross Sectional View of Part of Circuit Breaker Only) Fully Closed Position (Gap at Toe) All Toe (Arcing) Contacts Touch Only Center Toe (Arcing) Contacts Touch Simultaneously Touching of All Contacts (Heel and Toe) Full Open Position (No Contacts Touching) When the circuit breaker is called upon to close, the “Heel-Toe” action functions to first touch down the “Toe” followed by the “Heel.” Most of the impact on the contacts during closing is absorbed by the “Toe” portion. Once again the main contacts are protected resulting in a longer life. As was the case during the opening operation, the “Heel” and “Toe” are simultaneously closed for a short period of time to ensure that any arcing is handled by the “Toe” (arcing contact portion). Closing is completed as the contact finger rocks back on its “Heel” and the “Toe” lifts off the fixed arcing contact area (arc runner). In general, the movable contact can be attached to the load conductor through a hinged connection or attached with a flexible connector. Because of its complex opening and closing action, Magnum DS utilizes two braided connectors (flexible shunts) to attach each contact finger. Not only do the flexible braided connectors eliminate extra bolted joints which are natural hot spots, they help to reduce the mounting space required for the primary contacts. The flexible connectors (shunts) also allow the finger to have the motion necessary for the “Heel-Toe” (rocking) motion. 2. Naturally generated electromagnetic forces are cleverly used by Magnum DS to assist with the withstand and opening process (Figure 56). A compact C Loop current path design permits electromagnetic forces, primarily produced as a natural result of a fault current, to supplement the contact forces provided by the operating mechanism. The contact fingers are pivoted in such a way that the magnetically induced forces create a force which Levers the main contact onto the stationary contact (blow-on force), temporarily increas- Page 61 Low Voltage Power Circuit Breakers ing the closing contact pressure during a fault current. This accomplishes two things significant to Magnum DS: • The operating mechanism does not have to be as large or heavy. • Higher short time ratings (withstand) are achievable. Figure 56. Compact C Loop Design (Physics of Blow-On Forces) Furthermore, when the circuit breaker is tripped, the fulcrum (pivot point) is released and the electromagnetic forces on the contact fingers are converted to an opening force to speed up the opening action. You might consider these uses of electromagnetics as design magic, actually they are design ingenuity. These natural laws of physics were around before the circuit breaker. It is now that designs are making good use of electromagnetic forces to help keep the contacts closed when necessary, and to help to open them quickly. Operating Mechanism Low voltage power circuit breakers operate through spring stored energy mechanisms to perform the opening and closing functions. Both manually operated and electrically operated mechanisms are available. The closing springs can be manually or electrically charged with an electrically operated mechanism, and manually charged only with the manually operated mechanism (Figure 57). Manual charging is accomplished through the use of some type of manual charging handle on the front of the circuit breaker. The mechanism is such that when the circuit breaker is closed, the opening springs are simultaneously charged. The spring mechanisms are two-step stored energy mechanisms. That is, the closing springs are charged and remain charged with the circuit breaker open until a close button or electrical solenoid releases them, closing the circuit breaker. Figure 57. Magnum DS Closing Springs Being Manually Charged Circuit breaker closing, once the spring is charged, is rapid and occurs within five cycles. The spring charging time is typically several seconds. Page 62 Low Voltage Power Circuit Breakers A number of different devices associated with the mechanism are accessible from the front of the circuit breaker (Figure 58). As a minimum, these devices are: • Manual On (Close) Button • Manual OFF (Trip) Button • Spring Charged Indicator • Main Contacts Position (Open/Close) Indicator Figure 58. Magnum DS Circuit Breaker Front Cover The operating mechanism consists of two major parts: • Stored energy or spring charging mechanism • Mechanism for closing and opening the circuit breaker These two basic parts are normally combined into one overall operating mechanism. There are two varieties as previously mentioned: manually operated and electrically operated. In the past, low voltage power circuit breakers were either manually operated or electrically operated, and could not be converted from one to the other in the field. Today, a number of manufacturers offer circuit breakers that can be converted from manual to electrical in the field by the addition of an electrical operator. If a circuit breaker is manually operated, it can be: • Electrically tripped with an electrical shunt trip device • Electrically closed with an electrical spring release device Once again, all operating mechanisms are not designed or constructed the same, although they perform the same general function. Some are larger and heavier than others, while some are more efficient than others. Let’s take a brief look at some features of the Magnum DS operating mechanism. Magnum DS Operating Mechanism The Magnum DS operating mechanism is based on the well proven DSII power circuit breaker design, which has a recognized reputation for reliability. It is compact and light in weight for a number of reasons. Two of the most important are: 1. The clever use of naturally generated electromagnetic forces to create a blow-on force to assist the mechanism with keeping the primary contacts closed. This design technique led to a lighter more compact mechanism. 2. The rigid frame (housing) provides for very rigid mounting conditions for the operating mechanism. This leads to a longer mechanism life and improved operations with lighter and fewer mechanism parts. Page 63 Low Voltage Power Circuit Breakers The Magnum DS operating mechanism is the type that can be converted in the field from manually operated to electrically operated with the addition of an electrical operator (Figure 59). The electrical operator mounts inside the front cover of the circuit breaker. All Magnum DS circuit breakers are pre-wired to accept the addition of electrical operators simply and quickly. Figure 59. Field Installable Electrical Operator Shown Mounted with Front Cover Removed Arc Chamber (Chutes) Whether you call the arc extinguishing part of the circuit breaker an arc chamber or arc chutes, all low voltage power circuit breakers utilize somewhat similar means to extinguish arcs that are generated when contacts part. Once again, however, some methods are more effective than others. The purpose is to extinguish the arc as soon as possible. This is accomplished by combining a number of well proven techniques, such as: • De-ionizing the arc gases • Stretching the arc • Breaking the arc into pieces • Cooling the arc For a long time, low voltage power circuit breakers have had an individual arc chute mounted on the top of each circuit breaker pole. The arc chute is designed such that it fits well down over the circuit breaker’s arcing contacts. This arc chute positioning confines the arc inside the arc chute at all times. The arc chute housing is made of a strong insulating material. This housing holds a number of pieces called splitters, usually in a vertically stacked arrangement. The splitters are often made of steel in a special shape and/or configuration to aid arc interruption. When a fault occurs and the contacts separate, the splitters attract the arc further up into the arc chute where the arc is stretched, cooled, deionized and extinguished. In open metal-frame low voltage power circuit breakers, individual insulating barriers are mounted as required between the different circuit breaker poles, which also separates individual arc chutes (Figure 60). This is often necessary to help maintain the proper electrical clearances. Figure 60. DSII Metal-Frame Circuit Breaker with One Arc Chute Shown Removed Page 64 Low Voltage Power Circuit Breakers Magnum DS Arc Extinguishing The Magnum DS low voltage power circuit breaker takes full advantage of the fact that its rigid frame housing is molded from high strength thermoset engineered composite resins. The arc chamber is actually an integral part of the circuit breaker frame. The arc chamber insulates and isolates each pole from one another, from the rest of the circuit breaker, and from operating personnel. It also provides the space required to mount and enclose individual arc chutes over each set of contacts. It is a well known fact that a high pressure in the arc chamber contributes to improved interruption. The top of the arc chutes (arc chute exits) are baffled with a cover to create the back pressures. Magnum DS also uses an arc chamber seal to: • Prevent undesirable back flow of gas generated during arcing into the rest of the circuit breaker • Confine gas to maintain pressure for improved interruption. By designing the contact carrier assembly to be a close fit with the molded enclosure, and by including the arc chamber seal, the reverse flow of gas is minimized. The arc chamber seal design not only permits Magnum DS to increase the interruption performance, it is also a safety feature to protect the mechanism and operators from potentially harmful gases. This precise fit type design is able to be accomplished because of Magnum DS’s engineered frame design. Metal-frame construction, by nature, cannot be constructed to such close tolerances. You will recall during the discussion of Magnum DS contact operation that a compact C Loop current path is used during normal operation. This design permits the circuit breaker to take advantage of electromagnetic forces to keep the contacts closed - the blow-on effect. When the circuit breaker is called upon to open and deal with the interruption of a fault current and the generated arc, the same blow-on force is converted to an opening force to help speed the opening action. After the main contacts part, any remaining current is transferred to the arcing contacts by the arcing voltage (Figure 61). Magnetic action is enhanced and the arc is drawn to the arc chute. As the arcing contacts separate, the moving arcing contact discharges into the arc chute plates while the integral arc runner helps to draw the arc up into the arc chute. Remember, the integral arc runner serves a dual purpose. It functions as the fixed arcing contact and is also a critical part of the arc chute itself. Figure 61. Magnum DS Arc Running System Page 65 Low Voltage Power Circuit Breakers Finally, the alternating V shape of the arc chute plates (splitters) is very effective at dividing and cooling the arc (Figure 62). The result is a fast and efficient arc extinguishing process. Figure 62. Bottom View Magnum DS Arc Chute Showing Alternating V Shaped Plates Integral Trip Unit All low voltage power circuit breakers must have the intelligence to operate automatically or to respond to specific commands. This intelligence package is the trip unit. You will recall that ANSI Standards require that trip units used with low voltage power circuit breakers be part of (integral to) the circuit breaker (Figure 63). We discussed a low voltage power circuit breaker’s tripping system. The system included a trip actuator, a current sensor (transformer) for each phase, and the trip unit (brains of the system). You also know that trip units come in a wide variety of shapes and sizes with an even wider array of capabilities. Most low voltage power circuit breaker trip units used today are RMS sensing microprocessor-based designs. Usually they are selected based on the system requirements for protection and other needs, such as communications capabilities. Figure 63. Magnum DS Microprocessor-Based Trip Unit Shown Mounted on Left and Unmounted on Right The discussion here will focus on what types of features, protective and otherwise, are available today with digital microprocessor-based trip units. Keep in mind, some of the most sophisticated electrical systems might utilize every feature a family of trip units has to offer. Other system applications might just need the most basic protection package. In short, these tripping systems can be tailored to meet very precise system requirements. Generally, sophisticated microprocessor-based trip units are capable of providing combinations of a number of capabilities, such as: • Programmable protection and coordination • Advanced warnings and alarms • System diagnostics and testing Page 66 Low Voltage Power Circuit Breakers Programmable Protection and Coordination • System monitoring • Power quality monitoring • Energy monitoring and management • Communications Precise system coordination can be achieved when an expansive number of timecurrent curve shaping adjustments are part of the trip unit’s capabilities. This means that a large number of incremental set points must be available for both current pickup and time settings. To offer the most flexibility, the slope of a timecurrent curve should be adjustable along with the current and time settings. To optimize the coordination effort, programmable adjustments should include the following: • Long delay pickup (current) • Long delay time and slope adjustments • Short delay pickup (current) • Short delay time and slope adjustments • Instantaneous pickup (current) • Ground fault pickup (current) • Ground fault time and slope adjustments Current (pickup) settings, delay time settings and slope selections determine the resultant characteristic curve. Let’s take the time here to review several of these issues. We will briefly look at the different types of protection available with special attention given to short delay protection (withstand capabilities), a premier feature of low voltage power circuit breakers. Circuit Breaker Coordination The word Coordination is used quite often in these training modules and out in industry. All of us have an idea what the process involves. It is a big responsibility to consider all the variables in a distribution system, do the analysis and make the ultimate equipment decisions. Equipment decisions that must place safety first followed by a number of other considerations, like equipment protection, power outages, cost, space limitations, and unusual application conditions. Coordination is the process of selecting and applying circuit breakers in an electrical distribution system to localize a fault condition and restrict power outages to the equipment affected. The goal of coordination is improved selectivity. Proper coordination requires a comparison of the operating characteristics of the circuit breakers in the system. Time-current characteristic curves are used to determine if coordination will exist when choosing the size of the circuit breakers or just analyzing an existing system. By overlaying the time-current curves of two circuit breakers or comparing them in some other manner, you can determine whether selectivity exists. If the curves of the two circuit breakers intersect, for example, the intersection area indicates conditions under which both circuit breakers may trip. If such a pair of circuit breakers were used in an electrical distribution system, those conditions could result in both circuit breakers tripping. This would be a needless interruption of power to some portions of the system. On the other hand, if the curves of the circuit breakers are distinctly separate and do not intersect, the circuit breakers are said to be coordinated. Page 67 Low Voltage Power Circuit Breakers Preparing for and doing a coordination study can be quite an effort, especially with a large, diverse system. Accurate system one-line diagrams must be prepared. All pertinent data including types and ratings for all circuit breakers, available short circuit currents and any special requirements must be determined and shown on the diagrams. This brief discussion will give you some idea as to what went on behind the scenes before you were asked for a particular circuit breaker with specific ratings and operating characteristics. Obviously, this subject is far more involved than this, but at least you will have a better appreciation for the process. Circuit Breaker Coordination Example Refer to Figure 64 for this example. A system one-line diagram is prepared first showing pertinent data, like types and ratings of circuit breakers and available short circuit currents. For convenience, the one-line diagram for this example is shown superimposed on the coordination curve. A coordination study begins with the circuit breaker nearest the load and works toward the source. For this example, a small motor is the load. The time-current characteristics for the motor during starting and normal running might look like the curve superimposed on the coordination curve. The downstream 50 ampere molded case circuit breaker one (MCCB1) is selected first with its corresponding curve put in place. This is followed in a similar manner by the curve for the 200 ampere molded case circuit breaker two (MCCB2), and the upstream 800 ampere power circuit breaker 1 (PCB1) curve. Notice that all three circuit breaker curves are distinctly separate, which means coordination exists between the circuit breakers. Because the curve representing the motor’s startup and normal running does not intersect the curve for MCCB1, MCCB1 should not trip under normal conditions. Should the motor’s rotor become locked and continuously draw some potentially harmful level of current, MCCB1 would be the first in line to deal with the problem. MCCB2 and PCB1 are positioned to deal with higher, more potentially destructive current levels. Although this is a very minor example, it demonstrates the procedure. The more involved the system, the more involved and time consuming the coordination process. Page 68 Low Voltage Power Circuit Breakers Figure 64. Selectively Coordinated System Example Page 69 Low Voltage Power Circuit Breakers Review 6 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. When a low voltage power circuit breaker closes, its arcing contacts make before its main contacts. The arcing contacts also break before the main contacts when the same circuit breaker opens. TRUE FALSE 2. The Magnum DS movable contact design centers around a single contact finger as shown graphically below. Two parts of a contact finger are being pointed to by arrows. Identify those two parts by filling in the blank spaces next to the arrows. A—_____________ ____________ contact B—_____________ ____________ contact 3. A “Heel-Toe” contact structure is utilized by Magnum DS power circuit breakers. When all the “Heels” of all the contact fingers are touching and all the “Toes” are not, the circuit breaker is in what position? Circle the best answer from the choices below. (a) the circuit breaker is ready to close (b) the circuit breaker is open (c) the circuit breaker is closed (d) None of the above 4. The naturally generated force used by Magnum DS power circuit breakers to temporarily increase the closing contact pressure is called the ________________-________________ force. 5. Magnum DS power circuit breakers also use a similar naturally generated force to speed up the circuit breaker’s opening action. TRUE FALSE 6. The stored energy spring mechanism of both manually operated and electrically operated low voltage power circuit breakers can be charges manually. TRUE FALSE 7. The arc chamber of a Magnum DS power circuit breaker _____________ and ______________ each circuit breaker pole from one another, from the rest of the circuit breaker, and from operating personnel. 8. Because Magnum DS power circuit breakers use arc chambers, they do not use arc chutes like older power circuit breaker designs. TRUE FALSE 9. Most modern low voltage power circuit breaker trip units are true _________________ sensing microprocessor-based designs. Page 70 Low Voltage Power Circuit Breakers 10. ANSI Standards require low voltage power circuit breakers to have an integrally mounted trip unit. TRUE FALSE Page 71 Low Voltage Power Circuit Breakers Protective Systems All electrical power distribution systems are intended to provide power to equipment with the utmost in safety. System protection, with the primary goal of safety, is designed to balance the remaining goals of conductor/equipment protection and service continuity at the most reasonable cost. To meet these goals, protective equipment, under fault or overload conditions, must isolate the affected section of the power system to maintain service to other sections, minimize equipment damage, and limit the duration of any outage. Depending on the design, these functions are performed by protective systems with varying degrees of effectiveness. There are three basic approaches for designing a power system protection package. The system can be: • Series-Combination Rated • Fully Rated • Selectively Coordinated Each approach safely protects the system. The degree, however, to which service continuity is preserved on unfaulted portions of the system and the initial cost of the system differs by the system design selected. Low voltage power circuit breakers are capable of functioning on any system selected. Because of their short time ratings, however, low voltage power circuit breakers are ideally suited for selectively coordinated systems. Only the selectively coordinated system will be discussed. The Selectively Coordinated Protective System maximizes service continuity. All circuit breakers are fully rated to interrupt the maximum fault current available at their point of application on the system. With selective coordination, only the circuit breaker nearest the fault operates to isolate the faulted circuit from the power source. A selectively coordinated system requires that each upstream circuit breaker have short time protection. The upstream circuit breakers must be capable of withstanding the thermal and magnetic stresses delivered by the fault current for the period of time it takes the circuit breaker nearest the fault to interrupt the fault. This type of duty requires the withstand capabilities only available with a low voltage power circuit breaker. In most instances, the initial cost of a selectively coordinated system is higher than the other systems mentioned. The continuity of service, however, cannot be matched. The selectivity of a system can be based on any one of the following alternatives: • Magnitude of the fault current (current selectivity) • Duration of time during which system experiences fault current (time selectivity) • Combination of current and time (complete selectivity) Let’s take a look at a simple system example to illustrate each of the just mentioned alternatives. Selectively Coordinated System Example: Take a look at the graphic of a simple power system using all low voltage power circuit breakers (Figure 65). The large X marked “C” represents where a fault occurs. Circuit breaker “B” is the downstream circuit breaker and “A” the upstream circuit breaker. Page 72 Low Voltage Power Circuit Breakers For a completely selective system, upstream circuit breaker “A” requires greater trip time than does downstream circuit breaker “B” for all values of current; hence complete selectivity. Complete selectivity requires that the time-current characteristic curves of the two circuit breakers should not overlap at any point. The curves would maintain a sufficient time interval (spacing on the coordination plot shown) to allow for normal operating time of the downstream circuit breaker (B) before a “trip” operation would be initiated for the upstream circuit breaker (A). Current selectivity occurs between circuit breakers “A” and “B” when downstream circuit breaker “B” has a lower Continuous Current Rating and a lower instantaneous trip setting than upstream circuit breaker “A”. Current selectivity increases with increased differences in the continuous and instantaneous settings of the upstream and downstream circuit breakers. Time selectivity occurs between upstream circuit breaker “A” and downstream circuit breaker “B” when, for the same value of current, the upstream circuit breaker utilizes a longer time delay than the downstream circuit breaker. Time delay selectivity is best achieved with circuit breakers having trip units equipped with significant short time delay capabilities. The upstream circuit breaker must be sufficiently delayed in initiating a trip operation to allow the downstream circuit breaker enough time to clear the fault completely. This means that the upstream circuit breaker must be capable of withstanding the thermal and magnetic stresses introduced by the fault current during the time delay. Historically, this type of selectivity has been and continues to be achieved with power circuit breakers having short time capabilities along with significant withstand ratings. Figure 65. Selectively Coordinated System Example Power system maximum fault current through breakers A and B is 65 kA to fault at C. Breaker A is completely selectively coordinated for all values of fault current; breaker B isolates all faults at C. Breaker A is current selectively coordinated for all fault conditions of less than 50kA; both A and B trip for faults above 50kA at C. Breakers A and B relatively close in continuous current rating; breaker A is time selectively coordinated for Fault Currents to C above 30 kA. Long Delay Protection (L) Long Delay Protection reacts to overload conditions and certain short circuit conditions. The protection consists of a long delay current setting, a long delay time setting, and quite often a curve slope adjustment for the time setting. Short Delay Protection (S) Short Delay Protection reacts to short circuit conditions (Figure 66). It is similar to long delay protection in that it has a current setting, a time setting, and quite often a curve slope adjustment for the time setting. Good system coordination depends heavily on the flexibility of the trip unit’s short delay protection and the withstand capabilities of the circuit breaker. Low voltage power circuit breaker time adjustments are adjustable up to 0.5 seconds or 30 cycles. Low voltage power circuit breakers are designed, built and tested to withstand faults in the system in which they are applied for this extensive amount of time. Page 73 Low Voltage Power Circuit Breakers Figure 66. Typical Short Delay Protection Adjustments Typical Short Delay Current (Pickup) Adjustment Typical Short Delay Time Adjustment Typical Short Delay Time Adjustment With Flat Slope With (I2T) Slope Instantaneous Protection (I) Instantaneous Protection reacts to high level fault conditions. The instantaneous setting establishes the current level at which the trip unit’s instantaneous tripping function will trip the circuit breaker with no intentional time delay. Ground Fault Protection (G) Ground Fault Protection reacts to ground fault conditions. The protection also consists of a ground fault current setting, a ground fault time setting, and quite often a curve slope adjustment for time. Overcurrent Protection Combinations The overcurrent protection provided to a system can be provided in a number of combinations of the long (L), short (S), instantaneous (I) and ground fault (G) protection functions just covered. It is common to hear trip units described in terms of the protective functions offered using only the first letters (L,S,I,G) as the description. The following descriptions are just two examples of how trip units or circuit breakers are often described: 1. LS Trip Unit - This tells you that this particular trip unit offers long (L) and short (S) protection. It does not provide any other of the specifics or capabilities associated with that protection. 2. LI Circuit Breaker - This means that the circuit breaker is equipped with a trip unit that offers long (L) and instantaneous (I) protection. Once again, specifics are not provided. The common protective function combinations you will encounter are: • LI (long and instantaneous) • LS (long and short) • LSI (long, short and instantaneous) • LIG (long, instantaneous and ground) • LSG (long, short and ground) Page 74 Low Voltage Power Circuit Breakers • Characteristic Curve Review LSIG (long, short, instantaneous and ground) The operating response of a trip unit is graphically represented by time-current characteristic curves. These curves show how and when a particular trip unit will act for given values of current. The more versatile the trip unit, the easier it is to accomplish close coordination and achieve optimum protection. The programmable or adjustable parts of a trip unit permit movement of its characteristic curve or parts of the curve. The movement can be done both horizontally and vertically on the time-current grid (Figure 67). Figure 67. Advanced Trip Unit Time-Current Curve Adjustments Advance Warnings and Alarms The more capable microprocessor-based trip units using various methods offer early warnings of a specific condition or alarms of detected conditions. Many of these features can be indicated directly by the trip unit, indicated by an accessory device, or indicated on the screen of a remote computer. What is available and how it is accomplished is a function of the specific trip unit. Some typical examples of these advance warnings and alarms are: 1. High Load Alarm - The high load alarm is activated when the load current exceeds a selected current level to give an advanced warning of the condition. 2. Long Delay Trip Alarm - The long delay trip alarm operates after the circuit breaker trips due to an overload condition. 3. Short Circuit Trip Alarm - The short circuit trip alarm operates after the circuit breaker trips due to conditions, such as an instantaneous trip or a short delay trip. 4. Ground Fault Trip Alarm - The ground fault trip alarm operates after the circuit breaker trips due to conditions that exceed the ground fault settings. System Diagnostics and Testing Depending upon the sophistication of the trip unit, microprocessor-based trip units can store information in memory for use during diagnostic activities. In a number of instances, the reason for certain situations or operations can be directly determined from the trip unit. Integral testing capabilities are also part of most microprocessor-based trip units (Figure 68). The circuit breaker can usually be tested so the circuit breaker will actually trip (Trip Test Mode) or tested without the actual operation of the circuit breaker (No Trip Test Mode). Most circuit breaker designs usually continue to provide protection during the testing process Page 75 Low Voltage Power Circuit Breakers Figure 68. Close-Up of One Type of Magnum DS Trip Unit’s Front Accessible Testing Port System Monitoring Power Quality Monitoring Energy Monitoring and Management Communications Advanced microprocessor-based trip units are capable of monitoring much or all of the following data: • Steady-state value of phase, neutral and ground currents • Minimum and maximum current values • Average demand current • Cause of trip • Magnitude of fault current causing trip operation The most sophisticated trip units are capable of calculating and displaying in some manner power quality information. Typical displayed information would be: • Percentage of harmonic content • Total harmonic distortion (THD) Once again, the more sophisticated trip units can monitor and display in some manner power and energy values, such as: • Power in kilowatts • Peak demand in kilowatts • Total energy in kilowatt-hours • Forward and reverse energy in kilowatt-hours Most microprocessor-based trip units are capable of communicating in some manner. Two way communications is possible via a network twisted pair for remote monitoring and control. The circuit breaker, through the trip unit, is able to respond to open and close commands via the communications network. Many Eaton Electrical devices, including trip units, are IMPACC compatible devices. Eaton’s Cutler-Hammer IMPACC network is a unique system that centralizes multiple monitoring, protection, and control devices in a building’s electrical distribution system. Compatible devices can be remotely monitored, controlled and even programmed. The IMPACC Communications Network called INCOM is a noise immune communications network. INCOM interconnects microprocessor based electrical distribution and control products with remote personal computers into an information and control communications network. Applications You learned that low voltage power circuit breakers have a number of unique features and/or capabilities. Some of the features make them the ideal or, in some instances, the only choice in circuit breakers. Most of this centers around short time capabilities. The more and/or closer the required system coordination, the more valuable a low voltage power circuit breaker becomes. Because a number of topics have been discussed, let’s take a look at several application examples. This will help to pull a number of these capabilities together in a real way. Page 76 Low Voltage Power Circuit Breakers Zone Selective Interlocking Today’s modern microprocessor-based trip units are usually available with zone selective interlocking. Zone selective interlocking is provided for the short delay and ground fault delay tripping functions for improved system protection. The zone selective interlocking feature is a means of communications over a pair of wires between two or more compatible trip units. Zone selective interlocking makes it possible for programmed trip unit settings to be altered automatically to respond to different fault conditions and locations. This results in the effects of the interruption being localized and provides positive coordination between circuit breakers provided. A typical ground fault protection scheme using zone selective interlocking is graphically illustrated (Figure 69). For circuit breakers outside the zone of protection, the trip unit on the circuit breaker nearest the fault sends an interlocking signal to the trip unit of the upstream circuit breakers. This interlocking signal restrains immediate tripping of the upstream circuit breakers until their programmed coordination times are reached. Thus correctly applied zone selective interlocking can reduce damage due to short circuit or ground fault conditions. Figure 69. Ground Fault Protection Scheme Using Zone Selective Interlocking Magnum DS Application Example: You learned that Magnum DS low voltage power circuit breakers have: • Higher short time ratings (withstand capabilities) • Even higher interrupting ratings These facts, when applied to a real world application, result in interesting results. Let’s take a look at an industrial user with a large transformer feeding a facility. This user has multiple service entrances utilizing an outdoor liquid filled 3750 kVA transformer. Each of the connections from the transformer enter the facility and each feed separate 3000 ampere main circuit breakers (M1 and M2). Each main circuit breaker in turn feeds a number of 800 ampere feeder circuit breakers (F1 through F6). This might be a good time to review the one-line diagram for this example (Figure 70). The diagram represents an example using insulated case circuit breakers first and then Magnum DS power circuit breaker. Page 77 Low Voltage Power Circuit Breakers Figure 70. Insulated Case and Magnum DS Application Example One-Line Diagram Prior to Magnum DS low voltage power circuit breakers, the user utilized insulated case circuit breakers in order to obtain a high enough interrupting capacity for the application. It was calculated that this system had a potential fault capability of 93,500 amperes when everything that could contribute was considered. From the calculation, it was obvious that the system required circuit breakers with an interrupting rating of 100,000 amperes. The user would not consider the expense of fused power circuit breakers and did not have enough floor space anyway. The only acceptable solution at that time was using insulated case circuit breakers with an interrupting capacity of 100,000 amperes. There was a drawback to this solution. The insulated case circuit breakers only had a short delay current rating of 25,000 amperes for the feeder circuit breakers and 35,000 amperes for the main circuit breakers. Thus, for a fault greater than 35,000 amperes on the load side of the starters within any of the motor control centers, total coordination would be lost. A 50,000 ampere fault, for example, at point “A” on a branch circuit of motor control center 1 (MCC1) would take the entire motor control center 1 (MCC1) out of service because of circuit breaker (F1) opening. In addition, all the other motor control centers connected to Bus #1 would be lost because of main circuit breaker (M1) opening. With the availability of Magnum DS low voltage power circuit breakers, the picture and the results would be quite different. If Magnum DS circuit breakers with a short delay rating of 85,000 amperes and an interrupting rating of 100,000 amperes were used, the coordination achieved would be much better with far less equipment out of service. In addition, Magnum DS circuit breakers would require less floor space. Let’s conclude this application example by tabulating a comparison between the insulated case circuit breaker, the Magnum DS power circuit breaker and a DSLII (integrally fused DSII) power circuit breaker. For the sake of comparison and this tabulation, let’s assume that floor space is not limited and that fused power circuit breakers could be applied. By comparing the data presented in Figure 71, it is clear that the DSLII power circuit breaker could handle the 50,000 ampere fault condition just described. There are, however, three drawbacks associated with using the DSLII power circuit breaker in lieu of the Magnum DS power circuit breaker. They are: 1. The initial installation cost for DSLII would be the highest of the three circuit breakers. Page 78 Low Voltage Power Circuit Breakers 2. DSLII circuit breakers would require significantly more floor space than the other two circuit breakers. 3. The DSLII does not have a short time rating. Therefore, it cannot selectively coordinate with downstream devices. Figure 71. Application Tabulation Table Page 79 Low Voltage Power Circuit Breakers Review 7 Answer the following questions without referring to the material just presented. Begin the next section when you are confident that you understand what you’ve already read. 1. Of the three approaches to system protection listed below, circle the one that offers the best service continuity. (a) Series-Combination Rated (b) Selectively Coordinated (c) Fully Rated 2. The short delay time adjustment of a low voltage power circuit breaker is adjustable up to ___________________ seconds or ___________________ cycles. 3. The area represented by dotted lines on the time-current graphic below represents a typical short delay ___________________ adjustment. 4. What types of protection would an LSG type trip unit offer? ______________________________ ______________________________ ______________________________ 5. If a trip unit offers a slope adjustment on ground fault protection, it means that the portion of the curve representing the ground fault current adjustment can have its slope changed. TRUE FALSE 6. Zone selective interlocking permits two or more compatible devices, such as trip units, to communicate over a ___________________ of __________________. Page 80 Low Voltage Power Circuit Breakers Meaning of Nameplate Ratings Low voltage power circuit breakers are applied at their nameplate ratings. This is a good time to elaborate a bit on the subject, especially because we just covered a real application situation with Magnum DS circuit breakers. Let’s take a closer look at a Magnum DS nameplate and see what can be learned. Nameplates are prominently displayed on the front of the circuit breaker. Some of the information presented is general in nature, but most of it is specific to that circuit breaker. Refer to the Magnum DS nameplate graphic, and let’s briefly cover the referenced areas (Figure 72). Figure 72. Typical Magnum DS Nameplate A—Magnum DS, this is the name of the family of low voltage power circuit breakers. B—This is the identification number for this particular low voltage power circuit breaker. Refer to the Magnum DS Identification System Graphic to interpret this number (Figure 38). Identification numbers present a significant amount of information. In addition, identification numbers are frequently used in industry when discussing and/or ordering circuit breakers. This is a good time to start getting used to the concept of a product numbering system, whether it is called a catalog number or an identification number. The Magnum DS Identification System Table is rather self explanatory. Let’s just consider and interpret the identification number on the nameplate, MDS-C32. Figure 73. Magnum DS Identification System 1. The “M” stands for Magnum. 2. The “DS” identifies that this circuit breaker is tested to and for application in keeping with ANSI Standards. Page 81 Low Voltage Power Circuit Breakers 3. The “C” indicates that this circuit breaker has an interrupting capacity of 100,000 amperes. 4. The “32” indicates the frame size in amperes, which is 3200 amperes for this circuit breaker. C—Additional ratings specific information is presented here, some of which you already know by understanding the identification number. D—This is a very key area of the nameplate. The majority of information on how this particular circuit breaker can be safely applied is presented in this area. Each line starts off by indicating the maximum voltage at which the ratings that follow apply. You will notice that the ratings are the same for every voltage on the Magnum DS nameplate. This is an area where assumptions cannot be made. The same ratings apply for a specific Magnum DS frame size for all three maximum voltages. This is not the case with every type of low voltage power circuit breaker. Some have reduced ratings at certain voltages. Be observant! The 100,000 indicates that this circuit breaker will safely interrupt a fault current as high as high as 100,000 amperes instantaneously. The 85,000 indicates that this circuit breaker has this withstand capabilities to safely deal with a fault current as high as 85,000 amperes on a short time basis up to 0.5 seconds or 30 cycles. E—This is another area of the nameplate where information specific to this particular circuit breaker is indicated. The voltage rating of the circuit breaker’s factory installed accessories are shown here. In addition, specific manufacturing information pertaining to this circuit breaker can be found in this area, like the General Order Number (G.O. #). F—This area of the nameplate outlines a reference which specifies enclosure construction details to maintain published ratings. Low Voltage Power Circuit Breaker Summary In this training module, many points were made about Low Voltage Power Circuit Breakers. Issues were presented that applied to all low voltage power circuit breakers, and to specific low voltage power circuit breakers. In this summary, we will briefly review many of the points made. Some of the issues are unique to low voltage power circuit breakers while others are common, but not necessarily unique. A general summary is presented first followed by a Magnum DS summary. This summary is not intended to be all inclusive, especially as it relates to Magnum DS. It will, however, be an excellent review and act as a good future reference. Standards and Testing Summary 1. ANSI and IEC are the two most dominant standards relating to low voltage power circuit breakers worldwide. 2. ANSI Standards are the recognized North American Authority on low voltage power circuit breaker design. 3. ANSI C37.50 is the primary standard for testing low voltage power circuit breakers. 4. ANSI C37.50 testing is composed of four test sequences. The fourth test sequence is unique to low voltage power circuit breakers. Other types of low voltage circuit breakers are not subjected to this test sequence. This fourth test sequence determines whether or not a low voltage power circuit breaker has withstand capabilities to receive a 30 cycle short time rating. During the actual testing, the circuit breaker is subjected to two 30 cycle tests. Page 82 Low Voltage Power Circuit Breakers 5. ANSI Low voltage power circuit breakers are always rated for continuous operation at 100% of their current ratings in their enclosure. 6. ANSI Standards do not specify the nature of construction or construction material for low voltage power circuit breakers. 7. ANSI Standards require low voltage power circuit breakers to provide an open-close-open duty cycle. This is accomplished with a two-step spring stored energy mechanism. 8. ANSI Standards require low voltage power circuit breakers to have integral trip units. General Features Summary 1. Precise system coordination with unmatched short time ratings and withstand capabilities 2. Applied in a system at nameplate ratings 3. 5 cycle closing maximum 4. Strong, rigid frames to deal with the physical stresses associated with short time ratings (withstand capabilities) 5. Two-step stored energy spring operating mechanism 6. Both manual and electrical operation 7. Integral trip units 8. Typically supplied as four position drawout circuit breakers 9. Through the door or behind the door drawout 10. Fixed mount configurations 11. Fused configuration for 200,000 ampere interrupting 12. Maintainable design Magnum DS Summary 1. Meets or exceeds ANSI/UL Standards for low voltage power circuit breakers 2. 3 cycle closing 3. Rigid frame housing of engineered composite resins 4. Rugged, maintainable construction 5. Compact and lightweight 6. Through the door drawout or Fixed 7. Higher short time ratings (withstand) than DSII 8. Higher interrupting ratings than DSII 9. Field convertible manual to electrical operation 10. Field installable UL listed accessories 11. Front viewable and mounted electrical accessories 12. Only two frame sizes, 800 through 5000 amperes (smallest 3200 ampere frame in industry) 13. Heel-toe contact structure 14. Improved contact material 15. Compact “C” loop current path Page 83 Low Voltage Power Circuit Breakers 16. Braided current path connections 17. Sealed arc chamber for isolation and insulation 18. Programmable, RMS sensing microprocessor-based trip units 19. Moving contact wear indicator 20. Zone selective interlocking 21. IMPACC compatible communications Page 84 Low Voltage Power Circuit Breakers Review 8 Answer the following questions without referring to the material just presented. 1. A Magnum DS power circuit breaker identified as MDS-616 is a ___________________ ampere frame circuit breaker. 2. What is the interrupting capacity of a Magnum DS power circuit breaker with an identification number of MDS-C32? ___________________ kA interrupting 3. The Magnum DS family of power circuit breakers uses only two different frame sizes to cover _________________ through _________________ amperes. 4. All low voltage circuit breakers are rated for continuous operation at 100% of their current ratings in their enclosure. TRUE FALSE 5. The two-step spring store energy mechanism used in a low voltage power circuit breaker makes it possible for the circuit breaker to perform an openclose-open duty cycle, which is required by ANSI Standards. TRUE FALSE 6. A drawout Magnum DS power circuit breaker can be levered into or out of three different positions within its enclosure without ever opening the enclosure’s front door. Name these three positions. (a) ______________________________ position (b) ______________________________ position (c) ______________________________ position 7. Magnum DS power circuit breakers have field installable electrical accessories which can be viewed from the front of the circuit breaker. They must, however, be installed at the factory to be UL listed. TRUE FALSE 8. Magnum DS power circuit breakers offer higher short time ratings as well as higher _____________________ ratings. Page 85 Low Voltage Power Circuit Breakers Glossary Air Circuit Breaker A circuit breaker that makes and breaks power circuits in air using arc chutes. Arcing The effect generated when electrical current bridges the air gap between two conductors that are not touching. Arc Chute A component of the arc extinguisher in a low voltage circuit breaker. It elongates and cools an arc. Arc Extinguisher A common method used to extinguish an arc. In general, it confines, divides and cools the arc. ANSI American National Standards Institute. Butt A design type for making contacts in a circuit breaker. Circuit Breaker A reusable overcurrent protection device. After tripping to break the circuit, it can be reset to protect the circuit again. Connected Position The position in which the circuit breaker is fully connected and functional. Contacts Method to open and close the circuit as the contacts come together or separate. Continuous Current Rating The amount of current the breaker can carry continuously at 60 cycles without exceeding the temperature rise limit, according to ANSI charts. Control Voltage Voltage used to operate secondary devices. Coordination The process of selecting and applying circuit breakers in an electrical distribution system to localize a fault condition and restrict power outages to the equipment affected CSA Canadian Standards Association Disconnect Position The position in which neither the primary nor secondary electrical connections of the circuit breaker are made. This position is often used as a storage position for the circuit breaker within its enclosure. Drawout A type of circuit breaker that can be moved into or out of its structure without unbolting, often on a racking mechanism. Faceplate Shield A device to protect the operator from dangerous voltages while the breaker door is open. Finger A design type for making contacts in a circuit breaker. Finger Clusters Automatic main disconnect devices for a circuit breaker. Fixed A type of circuit breaker that is bolted into a fixed position with bus or cable mechanically bolted to breaker terminations. Ground Fault Protection A form of protection which reacts to ground fault conditions. IEEE Institute of Electrical and Electronic Engineers. An objective technical organization made up of manufacturers, users, and other general interest parties Page 86 Low Voltage Power Circuit Breakers Integrally Mounted Trip Unit The trip unit is inside of, or part of, the circuit breaker. International Electrotechnical Commission Abbreviated IEC. This organization is associated with equipment used internationally. Interrupting Rating Also “Ampere Interrupting Capacity (AIC).” A rating of the amount of current that a protective device, such as a fuse or circuit breaker, can safely interrupt. Instantaneous Protection A form of protection which reacts to high level fault conditions. Lever The act of moving the breaker from one position to another. Long Delay Protection A form of protection which reacts to overload conditions and certain short circuit conditions. NEMA National Electrical Manufacturers Association. SF6 An arc extinguishing technology involving the use of sulfur hexafluoride gas. Short Delay Protection A form of protection which reacts to short circuit conditions. Short Time Rating A rating for how fast a circuit breaker will open, expressed in cycles. Stored Energy A mechanism used to overcome inherent forces opposed to the breaker closing process, which stores energy until it is needed to help open the breaker. Test Position The position in which the circuit breaker’s primary connections are disconnected. Secondary connections are not disconnected and testing can be safely performed because the circuit breaker is not energized. Trip Free Breaker cannot be prevented from tripping, even when holding the handle in the ON position. Trip Unit Device that trips the operating mechanism in case of a short circuit or overload condition. Underwriter’s Laboratories UL. An independent laboratory that tests equipment to determine whether it meets certain safety standards when properly used. Vacuum An arc extinguishing technology. Features a pair of separable contacts enclosed in a vacuum-tight envelope. Because the environment inside the interrupter envelope is a vacuum, an arc cannot be sustained easily. Withdrawn Position In this position, the circuit breaker has no electrical connections. It is far enough out of its enclosure to permit inspection and maintenance. Withstand Rating See “Short Time Rating.” Page 87 Low Voltage Power Circuit Breakers Review 1 Answers 1. False 2. b. Test, c. Disconnect 3. True 4. Continuous current 5. True 6. Short time 7. True 8. Open Close Open Review 2 Answers 1. Molded 2. False 3. Arc chutes, arc extinguishers 4. True 5. Trip unit 6. Sensors 7. Trip unit 8. Circles around a, b, and c 9. Left to right: b, b, a 10. Shunt trip 11. False 12. Truck, Operated, Cell Review 3 Answers 1. False 2. Primary, secondary 3. Any 5 of the following: Standards Ratings Operation Method Accessory Items Mounting Method High or Low Ambient Temperatures Moist or Corrosive Atmospheres Altitude High Shock Conditions Unusual Circuit Breaker Mounting Conditions 4. False 5. 208 6. Application Voltage 7. False 8. True 9. Maximum 10. D Page 88 Low Voltage Power Circuit Breakers Review 4 Answers 1. True 2. Magnum 3. UL1066 4. C37.50 5. False Review 5 Answers 1. True 2. Withstand 3. Short delay current 4. False 5. True 6. 100,000 7. DC Component 8. B Review 6 Answers 1. False 2. upper right blank: Moving Arcing lower left blank: Moving Main 3. C 4. Blow-on 5. True 6. True 7. Insulates, Isolates 8. False 9. RMS 10. True Review 7 Answers 1. B 2. 0.5, 30 3. Short Delay Current 4. Long Delay Protection, Short Delay Protection, Ground Fault Protection 5. False 6. Pair, Wires Review 8 Answers 1. 1600 2. 100 kA 3. 800, 5000 4. False 5. True 6. a: connected b: test c: disconnect 7. False 8. Interrupting Page 89