6 Accessories Molded Case Circuit Breakers cExternally mounted accessories 4. Motor operators (MC) 4-1. TemBreak2 Motor driven type Spring charged type Key lock (optional) Manual charging lever Manual charging point ON/OFF+TRIPPED indicator Voltage presence LED indication Key lock (optional) Operating handle ON button Select lever TRIP button Lock plate Voltage presence LED indication Lock plate (T2MC40 / T2MC80) (T2MC12 / T2MC25) Ratings and Specifications T2MC12 Type of breaker S50-GF S100-NF S100-GF S125-NF S125-GF H100-NF L100-NF H125-NF L125-NF S100-NM S100-NN S125-NN Rated operational voltage 1 Peak AC100-110V steady-state/ AC200-220V starting current, A AC230-240V 2 DC24V DC48V DC100-110V DC200-220V Operation method Operating time, s ON at rated voltage OFF/RESET Operating switch ratings Power supply required Dielectric withstand voltage (for one minute) Weight Features T2MC25 T2MC25L E225-NF S225-NF S225-GF S225-GE S250-NF S250-GF H225-NF L225-NF E250-SF S250-SF T2MC40 T2MC80 S400-CF,S400-NF S400-GF S400-NE,S400-GE S400-PF,S400-PE S630-CF,S630-NF,S630-RF S630-NE,S630-RE S800-CF,S800-NF,S800-RF S800-NE,S800-RE H400-NE,L400-NE H630-NE,L630-NE H800-NE,L800-NE S400-NN S630-GN S800-NN ●AC100-240V ●ADC24-48V ●DC100-120V ●AC100-240V ●ADC24-48V ●DC100-120V S225-NM S250-SN ●AC100-110V ●AC200-220V ●AC230-240V ●DC24V ●DC48V ●DC100-110V ●DC200-220V 4.5/8 4/8 3.5/7 18/26 12/18 2.2/6 2.2/5.5 Motor driven (direct drive system) 0.1 ―/1.9(ON) 1.3/3.8(OFF,RESET) ―/3.3(ON) 0.9/3.8(OFF,RESET) ―/3.3(ON) 0.9/3.8(OFF,RESET) ―/9.2(ON) 4.3/9.8(OFF,RESET) ―/3.8(ON) 2.0/5.2(OFF,RESET) ―/1.3(ON) 1.2/2.9(OFF,RESET) ― Spring driven 0.1 ―/2.2(ON) 1.7/3.5(OFF,RESET) ―/2.2(ON) 1.3/3.5(OFF,RESET) ―/2.2(ON) 1.3/3.5(OFF,RESET) 0.1③④ 100V 0.1A (Open voltage/current: 44 V/4 mA)⑤ 300VA or higher 1.5③④ 100V 0.1A (Open voltage/current: 48 V/1 mA) 300VA or higher 1.5③④ 100V 0.1A (Open voltage/current: 48 V/1 mA) 300VA or higher AC1500V (AC 1000 V for DC 24/48 V) 1.4kg AC1500V (AC 1000 V for DC 24/48 V) 3.5kg AC1500V (AC 1000 V for DC 24/48 V) 3.5kg ―/2.2(ON) 1.3/3.5(OFF,RESET) ― Spring driven 0.1 Notes: ① : Permissible operating range is 85 to 110%. A power transformer is available as option for AC380V or AC400-460V. ② : The currents shown are the maximum values at the maximum rated operational voltage. ③ : The operating time is the value when the rated operational voltage is supplied. Allow a longer time for the motor operator to complete the operation. ④ : The motor operator is of a short time duty. Do not subject it to more than 10 continuous ON-OFF operations. If this occurs, allow the motor operator to cool for at least 15 minutes. ⑤ : When the rated operational voltage is DC24V the open voltage will be DC22V. 6-24 ★Installation and removal ease T2MC12/25/25L: Simply rotate two knobs allows the motor operator to be installed on or removed from the breaker. T2MC40/80: The compact and lightweight design enables easy installation and removal. ★High-speed, stable actuation The operating time as short as up to 0.1 second makes it possible to use the motor operators for synchronized closing of breakers. ★Silent operation T2MC12/25/25L use a direct drive system, providing operational silence. ★“Lock-in off” capability This capability allows the breaker to be padlocked in the OFF state. Up to thee padlocks with a 5 to 8 mm hasp diameter can be used. Padlocks are not supplied. ★Compact and lightweight T2MC40/80 is of compact design where the OCR of the breakers does not hide behind the operator, and thus does not need to be removed when changes in setting of the OCR are to be made.