QUICKTRONIC® PROStart® T8 QUICKSTEP® Bi

advertisement
www.sylvania.com
QUICKTRONIC® PROStart® T8
QUICKSTEP® Bi-Level Dimming Systems
Lamp Striation Control
Low Ballast Factor
Q HES T 8 PSL BI-LEVEL
High Efficiency Series
Lamp / Ballast Guide
Primary Systems
32W T8 - OCTRON® lamps
1 or 2 lamp
QHES2x32T8/UNV PSL-SC
Also operates:
FBO32, FBO31, FO25, FBO24, FO17,
FBO16 & energy saving equivalents
Key System Features
• Q
UICKSTEP Stepped Switching,
bi-level dimming (0.77 BF to
0.25 BF)
• High Efficiency Systems –
over 90% efficient
• NEMA Premium Electronic Ballast
Program compliant
• California Title 24 compliant
• PROStart Programmed Rapid Start
• Extends lamp life
• LSC (Lamp Striation Control)
• Universal input voltage (120-277V)
• RoHS Compliant
• Lead-free solder and manufacturing
process
Application Information
SYLVANIA QUICKTRONIC
PROStart T8 QUICKSTEP
ballasts are ideally suited for:
•
•
•
•
•
•
•
•
Office
Schools
Commercial
Retail
Occupancy sensor usage
Building control systems
Institutional
Load shedding
ECS263R2 - 8/2012
SYLVANIA QUICKTRONIC High Efficiency
PROStart T8 QUICKSTEP Bi-Level
Dimming ballasts are programmed
rapid start electronic ballasts that will
easily switch from 100% to 50% power
with standard wall switches. The ballast
operates linear and U-bend equivalent
T8 lamps at high efficiency. QUICKSTEP
bi-level step dimming ballasts are specifically designed to meet California’s Energy
Efficiency Standards (Title 24*) for multilevel lighting controls (Section 131). The
combined lamp and ballast system offers
a high efficiency system for T8 luminaires
along with high performance features
that are standard on SYLVANIA High
Efficiency Series ballasts.
The QUICKTRONIC PROStart QUICKSTEP
ballasts are RoHS Compliant featuring
lead-free solder and manufacturing
process and meet the requirements for
the NEMA Premium Electronic Ballast
System Information
SYLVANIA QUICKTRONIC PROStart
QUICKSTEP High Efficiency (QHES) ballasts
operate from 120V through 277V, eliminating
“wrong voltage” wiring errors and reducing
the number of models in inventory by 50%.
QUICKTRONIC QHE PROStart ballast
delivers an optimized programmed rapid
start technology which extends T8 lamp
life and allows over 100,000 switching
cycles for occupancy sensor and building
control systems applications. These ballasts
have two AC line inputs in addition to the
neutral wire. These AC line inputs must
be connected to the same phase of the
line voltage. The two line inputs can be
configured to provide a bi-level light output
system by wiring with two switches. When
both switches are on, the lamps operate at
full light output. When either switch is off,
the lamps operate in a dimmed mode and
the ballast wattage is reduced by 50%.
Alternatively, the ballasts can be controlled
by occupancy sensors allowing for
customized zone controls and various
energy saving configurations.
For additional information on this program
go to: www.cee1.org or www.nema.org.
program. The NEMA Premium program
promotes the use of high efficiency
T8 electronic ballasts by meeting
or exceeding the Ballast Efficiency
Factors, (BEF) established by the CEE,
(Consortium for Energy Efficiency).
*California’s Energy Efficiency Standards 2008
Title 24 Section 131.
%
Relative Lamp
Input Mean Mean % % Life
Lamp &
Power Initial System
Light System Energy @3hrs/
Ballast Type
BF
(W) LPW
Lumens Output Power Savings Start
2-FO32/700 QTP2x32 ISL
0.78 51 86 3930 100%100% 0% 100%
2-FO32/XPS
QHES2x32 PSL 0.77
Full Power
48
99
4490
114%
94%
6%
150%
2-FO32/XPS
QHES2x32 PSL 0.25
50% Power
24
65
1455
37%
47%
53%
150%
180%
% Relative Light Output
% System Wattage
% Lamp Life
160%
6%
Energy
Savings
140%
114%
120%
100%
150%
150%
100% 100% 100%
94%
53%
Energy
Savings
80%
60%
47%
37%
40%
20%
2-FO32/700
QTP2x32 ISL
2-FO32/XPS
QHES2x32 PSL
Full Power
2-FO32/XPS
QHES2x32 PSL
50% Power
Low Ballast Factor
SPECIFICATION DATA
Catalog #
Date
Project
Prepared by
T8 QUICKSTEP
Type
®
High Efficiency
Comments
Performance Guide
Input
Rated BallastInitial Mean
Input System1
Item
OSRAM SYLVANIA Current
Lamp Lumens No. of Factor System System Power (W) Efficacy
Number
Description (AMPS)
Type
(lm) Lamps (BF) Lumens Lumens 120V 277V (lm/W)
4775
1550
4390
1425
4195
1365
3810
1240
3390
1100
2155
730
2420
775
2225
715
2125
680
1930
620
1715
550
1090
365
4490
1455
4125
1340
3945
1280
3585
1165
3185
1035
2025
685
2275
730
2090
670
2000
640
1815
580
1615
515
1025
340
48
24
46
23
42
22
38
21
37
20
24
16
25
15
24
15
22
14
20
13
20
14
14
12
BEF 2
48
99
1.60
24
65
1.04
46
95
1.67
23
62
1.09
42 1001.83
22 621.14
38 1002.03
21 591.19
37 922.08
20 551.25
24 903.21
16 461.63
25 973.12
15 521.67
24 933.25
15 481.67
22 973.55
14 491.79
20 973.90
13 481.92
20 863.90
14 391.79
14 785.57
12 302.17
2: BEF (Ballast Efficiency Factor) shown = (Ballast Factor x 100) divided by Input Power (Note: calculation based on lowest input power)
Installation Notes
• Install in accordance with National & Local Electric Code
• Ground Ballast Case
• The AC line inputs must be connected to the same phase of the line voltage
• DO NOT CONNECT two separate phases of line voltage to the input of QUICKSTEP ballasts, the ballast will be damaged and not covered by warranty
LAMP
LAMP
LAMP
Yellow
Yellow
Neutral
S1
S2
Black
Black
White
Yellow
Yellow
Blue
Blue
BALLAST
Line
Red
Red
Neutral
1-Lamp QHES (QUICKSTEP)
Full light output (full power)
S1 & S2 closed (on)
Bi-level mode (50% power)
S1 or S2 open (off)
S1
S2
Black
Black
White
Blue
Blue
BALLAST
Red
Red
2-Lamp QHES (QUICKSTEP)
Full light output (full power)
S1 & S2 closed (on)
Bi-level mode (50% power)
S1 or S2 open (off)
Special Note: This ballast has LSC (Lamp Striation Control) which minimizes or eliminates striating lamps. Under certain conditions however, T8 lamps may
still striate. This condition will not affect the life or light output of the lamp and will not affect the ballast. Consult lamp manufacturers for additional details.
Dimensions:
Overall: 9.5" L x 1.68" W x 1.18" H
Mounting: 8.90"
Product Weight:
1.6 lbs each (approx)
Item Number
QUICKTRONIC High Efficiency
Step Dim, QUICKSTEP (bi-level)
Number of Lamps (2)
Height
8.70 mm
Slot
Width
Mounting
Length
Wiring:
LAMP
Leads only
(no connectors provided)
Length
S1
49158 QHES 2 x 32T8 / UNV PSL
Line- SC
S2
Neutral
Yellow
Yellow
Blue
Blue
Black
BALLAST
Enclosure
Size: Small Can Red
Black
Starting Type/PROStart/LowRed
Ballast Factor
White
Line Voltage (120-277V)
Primary Lamp Wattage & Type
SYLVANIA, OCTRON, QUICKSTEP, PROStart, SUPERSAVER,
the system solution and QUICK60+ are registered trademarks of OSRAM SYLVANIA Inc.
QUICKTRONIC is a registered trademark of OSRAM AG. NEMA Premium is a registered trademark of National Electrical Manufacturers Association.
Specifications
Data based on F32T8
Starting Method: Programmed Rapid Start
Ballast Factor: 0.77/0.25 (see table)
Circuit Type: Series
Lamp Frequency: >40 kHz
Lamp CCF: Less than 1.7
Starting Temp:3
0 °F/-18°C for OCTRON T8 lamps;
32°F/0°C in dimmed mode;
60°F/16°C for SUPERSAVER® T8 lamps
Input Frequency: 50/60 Hz
THD: <10% (full power)
<20% (@50% power)
Power Factor: >97% (full power)
Voltage Range: ±10%
Q HES T 8 PSL BI-LEVE L
QHES 2x32T8/UNV PSL-SC (@100%) 0.40/0.18 FO32XPS 3100
2
0.77
49158 Banded Pack
(@50%) 0.20/0.09 FO32XPS 3100
2
0.25
(@100%) 0.39/0.17 FO30SS 2850
2
0.77
(@50%) 0.20/0.09 FO30SS 2850
2
0.25
(@100%)0.36/0.16 FO28SS 2725 2
0.77
(@50%)0.19/0.09 FO28SS 2725 2
0.25
(@100%)0.32/0.14 FO25SS 2475 2
0.77
(@50%)0.18/0.08 FO25SS 2475 2
0.25
(@100%)0.31/0.14 FO25XPS 2200 2
0.77
(@50%)0.17/0.08 FO25XPS 2200 2
0.25
(@100%) 0.20/0.10 FO17XPS 1400
2
0.77
(@50%) 0.13/0.07 FO17XPS 1400
2
0.26
(@100%)0.21/0.10 FO32XPS 3100 1
0.78
(@50%)0.12/0.06 FO32XPS 3100 1
0.25
(@100%)0.20/0.09 FO30SS 2850 1
0.78
(@50%) 0.12/0.06 FO30SS 2850
1
0.25
(@100%)0.18/0.09 FO28SS 2725 1
0.78
LAMP
(@50%)0.12/0.06 FO28SS 2725 1
0.25
LAMP
(@100%)0.17/0.07 FO25SS 2475 1
0.78
(@50%)0.11/0.05 FO25SS 2475 1
0.25
Yellow
(@100%)0.16/0.08
0.78
Blue FO25XPS 2200 1
Yellow
(@50%)0.12/0.06
0.25
Blue FO25XPS 2200 1
S1
(@100%) 0.11/0.06 FO17XPS 1400
1
0.78
Black
BALLAST
Line
Red
Black
S2
(@50%) 0.09/0.05 FO17XPS 1400
1
0.26
Red
Whiteeach, (add “-B” to description). 1: System Efficacy is based on the lowest Input Power
Neutral
Banded
Pack contains 10 pieces
Data based upon SYLVANIA OCTRON® lamps
shown. QUICKTRONIC® QHE QUICKSTEP
PROStart ballasts are also compatible with
other lamp manufacturers equivalent lamp
types that meet ANSI specifications.
UL Listed Class P, Type 1 Outdoor
CSA Certified
70°C Max. Case Temp. (5 yr. warranty)
FCC 47CFR Part 18 Non-Consumer
Class A Sound Rating
RoHS Compliant 4
ANSI C62.41 Cat A. Transient Protection
Remote Mounting (Max. wire length from
ballast case to lampholder): up to 7 feet for
all lamps except 4 feet for energy saving
T8 lamps (keep blue wires short, ie. lamp(s)
attached to the blue leads to remain in the
fixture that houses the ballast).
Lamp Seasoning: For optimal performance,
fluorescent lamps may require seasoning
for up to 12 hours prior to low temperature
starting & low level dimming. Refer to NEMA
LSD 23-2002 Lighting Systems Division:
Recommended Practice — Lamp Seasoning
for Fluorescent Dimming Systems
3 Operation below 50°F/10°C may affect light
output or lamp operation – see
“Low Temp. Starting” definition.
4 Complies with European Union Restriction of
Hazardous Substances Directive.
System Life / Warranty
QUICKTRONIC products are covered by the
QUICK 60+® warranty, a comprehensive
lamp and ballast system warranty.
For additional details, refer to the
QUICK 60+ warranty bulletin.
OSRAM SYLVANIA
National Customer
Service and Sales Center
1-800-LIGHTBULB
(1-800-544-4828)
www.sylvania.com
Specifications subject to change without notice.
©2012 OSRAM SYLVANIA
High Efficiency QUICKSTEP® (Bi-Level) T8 Dimming Systems (120-277V)
Line
PSL
Download